1-TLH CBIS Expansion - IFB - PLANS.pdf

PDF 6 MB Posted

Attached to
REBID - TLH Checked Bagged Inspection System Expansion
Solicitation number
IFB-090-25-CW
Issued by
Leon County, Florida

About this file

These documents are design and engineering plans for the Tallahassee International Airport's Checked Baggage Inspection System (CBIS) Expansion project, prepared by RS&H Associates, Inc. and BNP Associates, Inc. The project involves upgrading and expanding the existing baggage handling system (BHS) at the airport, specifically focusing on the first-floor CBIS area. The design is dated September 16, 2024, with the project located at 3330 Capital Circle SW in Tallahassee, Florida. The plans include detailed schematics for telecommunications, electrical systems, and baggage handling equipment, with a comprehensive set of drawings covering existing conditions, proposed modifications, sequencing, and installation details.

The documents provide technical specifications for replacing and upgrading equipment, including new uninterruptible power supplies (UPS), network switches, workstation computers, and screening equipment. The project involves installing a new CT80DR+XL Explosives Detection System (EDS) machine, reconfiguring conveyor systems, and updating control stations and safety signage. The design accounts for electrical load calculations, grounding requirements, and telecommunications infrastructure, with specific attention to integrating new equipment with existing systems. The plans indicate careful consideration of operational continuity, with staged removal and replacement of components to minimize disruption to airport operations.

View the file

Other files

Show all 16

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

NORTH

NORTH

MEXICO

OF

GULF

KEY

WEST

TALLAHASSEE

FERNANDINA

BEACH

ORLANDO

TAMPA

FORT

PALM

FT.

MIAMI

MYERS

WEST

BEACH

LAUDERDALE

JACKSONVILLE

ATLANTIC

OCEAN

S-373

CITY OF

TALLAHASSEE

S-261A

TALLAHASSEE

INTERNATIONAL AIRPORT

904-256-2500 Fax 904-256-2503

10748 Deerwood Park Blvd. South

Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956 *

5620 * LCC000210 * GB238ASSOCIATES, INC.

LOCATION MAP

N.T.S.

VICINITY MAP

N.T.S.

TALLAHASSEE INTERNATIONAL AIRPORT

CBIS EXPANSION

TALLAHASSEE, FLORIDA

SEPTEMBER 16, 2024

RS&H PROJECT NO. 20012001.007

ISSUED FOR BID

T701 TELECOMMUNICATIONS RISER DIAGRAM

T101 ENLARGED PLAN - CBRA RM A101

T100 TELECOMMUNICATIONS FIRST FLOOR PLAN

T001 TELECOMMUNICATIONS GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

TELECOMMUNICATIONS

EP602 ELECTRICAL POWER SCHEDULES

E101 ELECTRICAL FLOOR PLAN

E001 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS

ELECTRICAL

B.702 TYPICAL DETAILS - SAFETY SIGNAGE

B.701 TYPICAL DETAILS - SAFETY SIGNAGE

B.700 TYPICAL DETAILS - LOADING

B.600 SEQUENCE 1 & 2 AND STEP 1 & 2

B.501 E-STOP AND CONTROLS STATION PLAN

B.500 TYPICAL CONTROLS STATION DETAILS

B.401 EDS MAINTENANCE ZONE

B.400 PARTIAL PLAN - EDS REMOVAL PATH

B.201 PARTIAL PLAN - PROPOSED CONDITIONS

B.200 GENERAL ARRANGEMENT - PROPOSED CONDITIONS

B.102 PARTIAL PLAN - DEMOLITION CONDITIONS

B.101 GENERAL ARRANGEMENT - EXISTING CONDITIONS

B.003 KEY PLAN

B.002 CONVEYOR MANIFEST

B.001 SYMBOLS, LEGENDS, ABBREVIATIONS AND SHEET LIST

BAGGAGE HANDLING

SHEET NUMBER SHEET NAME

SHEET INDEX

CHECK AND FIELD VERIFY ALL BHS RELATED DIMENSIONS ON THE JOB SITE

BEFORE PROCEEDING WITH WORK AND BE RESPONSIBLE FOR THEIR ACCURACY.

IF DISCREPANCIES ARE FOUND BETWEEN THE BHS DRAWINGS, SPECIFICATIONS

AND FIELD CONDITIONS, REPORT THEM TO THE OWNER.

THE FOLLOWING REQUIREMENTS, TOGETHER WITH THE PROJECT SPECIFICATIONS AND

BHS DRAWINGS SHALL APPLY.

FINISHED FLOOR ELEVATIONS PROVIDED FOR INFORMATION ONLY.

ALL FINISHED FLOOR DIMENSIONS ARE TAKEN FROM THE HIGH POINT OF THE

FINISHED FLOOR.

NO DIMENSIONS SHALL BE SCALED. DRAWING DIMENSIONS SHOWN SHALL BE

USED.

BHS CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING BHS RIGHT-OF-WAY ISSUES

AND REPORTING THEM TO THE OWNER.

BHS CONTRACTOR TO COORDINATE WITH OTHER TRADES TO MAINTAIN BAGGAGE

SYSTEM RIGHTS-OF-WAY.

ALL DIMENSIONS ARE FROM GRID TO OUTER EXTENT OF CONVEYOR SIDEGUARD,

UNLESS NOTED.

FOR ADDITIONAL BHS RIGHT-OF-WAY CLEARANCES, CROSS SECTIONS, AND

ATTACHMENT DETAILS REFERENCE THE SERIES DRAWINGS.

ALL OTHER TRADES SHALL MAINTAIN CLEAR RIGHT-OF-WAY (UNLESS NOTED)

FROM TOP OF BELT TO NEAREST OBSTRUCTION. HANGING ANY EQUIPMENT

COMPONENTS (E.G. MECHANICAL, ELECTRICAL, PLUMBING, HVAC). FROM THE

CONVEYOR, CATWALK OR ASSOCIATED SUPPORTS IS NOT ACCEPTABLE.

MODIFY EXISTING CONVEYOR DRIVE ASSEMBLIES, AS REQUIRED, TO

ACCOMMODATE SPECIFIED BHS ALTERATIONS (E.G. RECONFIGURE DRIVE FROM

LEFT HAND TO RIGHT HAND OR VICE VERSA).

ALL BHS RIGHTS-OF-WAY SHALL TAKE PRECEDENCE OVER ALL OTHER BUILDING

SERVICES (E.G. MECHANICAL, DUCT WORK AND PIPES, CONDUIT, FIRE

PROTECTION, PLUMBING).

SUPPLY SAFETY DEVICES PER CONTRACT SPECIFICATIONS.

REFERENCE

ARCHITECTURAL DRAWINGS FOR ALL FLOOR ELEVATIONS AND BUILDING

INFORMATION.

3' 0"

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

STANDARD

CONVEYOR

TOP OF

BELT

C

LR

3'

R O

W

4'

CONV

3' - 6"

ROW

5' - 6"

MINIMUM 12" CLEARANCE

AROUND ALL BHS

ELEMENTS UNLESS

OTHERWISE NOTED

XXY-ZZ

NEW OR REWORKED CONVEYOR ID

SEQUENTIAL NUMBER OF COMPONENTS IN TRAIN

SEQUENTIAL NUMBER OF SUBSYSTEMS OF THIS TYPE

SUBSYSTEM DESCRIPTION IDENTIFIER

SUBSYSTEM DESCRIPTION IDENTIFIERS

CL - CLEAR LINE

OG - OUT OF GAUGE

SF - SECURITY FEED LINE

SS - SECURITY SCREENING

SHEET NUMBER DESIGNATIONS

B.210

SEQUENCE DRAWING #

SHEET TYPE

DISCIPLINE DESIGNATOR

BHS FLOW DIRECTION

TOP OF BELT ELEVATION

UNLESS NOTED

EXISTING BHS EQUIPMENT

DEMOLISHED BHS EQUIPMENT

NEW BHS EQUIPMENT

CONTROL PANEL

ITEM NUMBER

EXISTING EQUIPMENT

ITEM NUMBER

NEW EQUIPMENT

ITEM NUMBER

RENUMBERED EQUIPMENT

ITEM NUMBER

CONTROL EQUIPMENT

CONVEYOR CROSS SECTION

CONVEYOR WITH DRIVE

CROSS SECTION

XXY-ZZ

XXY-ZZ

XXY-ZZ

XXY-ZZ

45° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

DECLINE CONVEYOR

END ROLLER

QUEUE CONVEYOR

24" MINI-CENTER DRIVE

60" CENTER DRIVE

24" MINI UNDERSLUNG DRIVE

60" STANDARD UNDERSLUNG DRIVE

45° MERGE CONVEYOR

45° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

90° POWER TURN

(OPTIONAL DRIVE LOCATIONS SHOWN)

END ROLLER

QUEUE CONVEYOR

24" MINI-CENTER DRIVE

60" CENTER DRIVE

24" MINI UNDERSLUNG DRIVE

60" STANDARD UNDERSLUNG DRIVE

45° MERGE CONVEYOR

DECLINE CONVEYOR

FIRE/SECURITY DOOR FIRE/SECURITY DOOR

HIGH SPEED PADDLE DIVERTERHIGH SPEED PADDLE DIVERTER

REVERSE MERGE CONVEYOR REVERSE MERGE CONVEYOR

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.001

SYMBOLS, LEGENDS,

ABBREVIATIONS, AND

SHEET LIST

AFF ABOVE FINISHED FLOOR

ARCH PROJECT ARCHITECT

BDD BAGGAGE DIMENSIONING DEVICE

BF BETWEEN FRAME

BHS BAGGAGE HANDLING SYSTEM

BHSC BAGGAGE HANDLING SYSTEM CONTRACTOR

BIP BAGGAGE INSERTION POINT

BIS BAGGAGE INSPECTION STATION

BIT BAGGAGE INSPECTION TABLE

BLDG BUILDING

BRP BAGGAGE REMOVAL POINT

BSD BAGGAGE STATUS DISPLAY

BSO BAGGAGE SERVICE OFFICE

BVS BAGGAGE VIEWING STATION

CBIS CHECKED BAGGAGE INSPECTION SYSTEM

CBRA CHECKED BAGGAGE RESOLUTION AREA

CI CONTROL INTERFACE

CL CENTERLINE

CLR CLEAR

CONC CONCRETE

CONT CONTINUOUS

CONV CONVEYOR

DID DIRECTIONAL INPUT DEVICE

DWG DRAWING

EL ELEVATION

EOR ENGINEER OF RECORD

EQUIP EQUIPMENT

ETD EXPLOSIVE TRACE DETECTION

EXST EXISTING

FD FIRE DOOR

FF FINISHED FLOOR

FIN FINISH

FLA FULL LOAD AMPERAGE

FLR FLOOR

FPM FEET PER MINUTE

FSD FIRE-SECURITY DOOR

GC GENERAL CONTRACTOR

HORIZ HORIZONTAL

HSPD HIGH SPEED PADDLE DIVERTER

HVAC HEATING VENTILATION AND AIRCONDITIONING

ID IDENTIFICATION

INTL INTERNATIONAL

LVL LEVEL

MAINT MAINTENANCE

MAX MAXIMUM

MCP MOTOR CONTROL PANEL

MDS MAINTENANCE DIAGNOSTIC SYSTEM

MEP MECHANICAL ELECTRICAL PLUMBING

MFG MANUFACTURER

MIN MINIMUM

MIS MAINTENANCE INFORMATION SYSTEM

MPP MOTOR POWER PANEL

MTR MOTOR

NATL NATIONAL

NEC NATIONAL ELECTRIC CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NTS NOT TO SCALE

O&M OPERATIONS AND MAINTENANCE

OC ON CENTER

OOG OUT OF GAUGE

OPNG OPENING

OPS OPERATIONS

OSHA OCCUPATIONAL SAFETY AND HEALTH

ADMINISTRATION

OSR ON SCREEN RESOLUTION

OTK OPERATIONAL TEST KIT

PAX PASSENGERS

PDP POWER DISTRIBUITION PANEL

PLC PROGRAMABLE LOGIC CONTROLLER

PSI POUNDS PER SQUARE INCH

PVS PRIMARY VIEWING STATION

REF REFERENCE

REQD REQUIRED

ROW RIGHT OF WAY

SD SECURITY DOOR

SIM SIMILAR

SS STAINLESS STEEL

STR STRUCTURE

SVS SECONDARY VIEWING STATION

TEMP TEMPORARY

TOB TOP OF BELT

TSA TRANSPORTATION SECURITY ADMINISTRATION

TSO TRANSPORTATION SECURITY OFFICER

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

SHEET NO DESCRIPTION

B.001 SYMBOLS, LEGENDS, ABBREVIATIONS, AND SHEET LIST

B.002 CONVEYOR MANIFEST

B.003 KEY PLAN

B.101 GENERAL ARRANGEMENT - EXISTING CONDITIONS

B.102 PARTIAL PLAN - DEMOLITION CONDITIONS

B.200 GENERAL ARRANGEMENT - PROPOSED CONDITIONS

B.201 PARTIAL PLAN - PROPOSED CONDITIONS

B.400 PARTIAL PLAN - EDS REMOVAL PATH

B.401 EDS MAINTENANCE ZONE

B.500 TYPICAL CONTROL STATION DETAILS

B.501 E-STOP AND CONTROL STATION PLAN

B.600 SEQUENCING

B.700 TYPICAL DETAILS - LOADING

B.701 TYPICAL DETAILS - SAFETY SIGNAGE

B.702 TYPICAL DETAILS - SAFETY SIGNAGE

SHEET LIST

GENERAL NOTES

CONVEYOR RIGHT OF WAY

IDENTIFICATION NOMLCATURE

ABBREVIATIONSGENERAL SYMBOL LEGENDCONVEYOR LEGEND FOR ELEVATIONSCONVEYOR LEGEND FOR PLAN

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

CONSTRUCTION

9/16/2024

CONVEYOR MANIFEST

CONVEYOR ID Family

CONVEYOR

LENGTH BELT SPEED HP

SS1-01 Diverter - HSPD 3.8 hp

SS1-02 Conveyor - Transport 5' - 3 1/2" 120 ft/min 2.0 hp

SS1-03 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp

SS1-04 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp

SS1-06 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp

SS1-07 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp

SS1-08 Conveyor - Transport 4' - 0" 120 ft/min 2.0 hp

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.002

CONVEYOR MANIFEST

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

F.D.

8 9 10

M

L

N

5 6 743.81.5 2.4 3.201'2'

B.101

Sim

B.200

Sim

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.003

KEY PLAN

1" = 30'-0"1

KEY PLAN EXISTING

NORTH

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

M

L

N

5 6 743.81.5 2.4 3.201'

B.102

Sim

CL1 SUBSYSTEM

SF1 SUBSYSTEM

OG1 SUBSYSTEM

SS2 SUBSYSTEM

OS1 SUBSYTEM

TC1 SUBSYSTEMTC2 SUBSYSTEMTC3 SUBSYSTEM

REMOVABLE

SUBSYSTEMS

EXISTING

SUBSYSTEMS

MODIFIED

SUBSYSTEMS

LEGEND

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.101

GENERAL

ARRANGEMENT -

EXISTING CONDITIONS

1/16" = 1'-0"1

GENERAL ARRANGEMENT - EXISTING

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

REMOVABLE

SUBSYSTEMS

EXISTING

SUBSYSTEMS

MODIFIED

SUBSYSTEMS

LEGEND

8 9 10

M

L

N

5 6 74

30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"

CL1-01

6' - 0"

4'

EL 2' - 7" AFF

MCP-SF1

MCP-TC1

MCP-SS2

MCP-TC2/TC3

MCP-SS1

MCP-OG1

MCP-TC1

MCP-SS2

MCP-SS1

MCP-TC2/TC3

SF1-07

SS1-02

THRU

SS1-09

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.102

PARTIAL PLAN -

DEMOLITION

CONDITIONS

1/8" = 1'-0"1

EXISTING BHS - GROUND LEVEL DEMOLITION PLAN

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

NEW

SUBSYSTEMS

EXISTING

SUBSYSTEMS

LEGEND

MODIFIED

SUBSYSTEMS

8 9 10

M

L

N

5 6 743.81.5 2.4 3.201'

B.201

Sim

EL 2' - 6" AFF 4'

6' - 0"

MCP-SF1

MCP-TC1

MCP-SS2

MCP-SS1

MCP-TC2/TC3

MCP-OG1

MCP-TC1

MCP-SS2

MCP-SS1

MCP-TC2/TC3

B.401

Sim

CL1 SUBSYSTEM

SF1 SUBSYSTEM

OG1 SUBSYSTEM

SS2 SUBSYSTEM

OS1 SUBSYTEM

TC1 SUBSYSTEM

TC2 SUBSYSTEM

TC3 SUBSYSTEM

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.200

GENERAL

ARRANGEMENT -

PROPOSED

CONDITIONS

1/16" = 1'-0"1

PROPOSED BHS - GROUND LEVEL GENERAL ARRANGEMENTS

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

EXISTING

SUBSYSTEMS

LEGEND

8 9 10

M

L

N

5 6 74

30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"

SS1-02

SS1-03

SS1-04

SS1-06

SS1-07

SS1-08

PROVIDE DID

TO MATCH EXISTING

PROVIDE OVERHEIGHT

PHOTOCELL AND

KNOCKDOWN BAR

BVS, PROVIDED BY

THE TSA CONTRACTOR

FDRS DESK, PROVIDED BY

THE TSA CONTRACTOR

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:3

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.201

PARTIAL PLAN -

PROPOSED

CONDITIONS

1/8" = 1'-0"1

PROPOSED BHS - GROUND LEVEL PARTIAL PLAN

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

REMOVABLE

SUBSYSTEMS

EDS REMOVAL

PATH

TSA LEGEND

TSA ACCESS

PATH

IQT TEST

LOCATIONS

FAILSAFE

LOCATION

8 9 10

M

L

N

5 6 74

8' - 0"

EXISTING TSA

AGENT/ROBOT

PATH

M

SF1-07SS1-02SS1-03SS1-04

SS1-06

SS1-07SS1-08CL1-01

CT80DR+XL

EL 2' - 10" AFFEL 2' - 6" AFFEL 2' - 6" AFFEL 2' - 4" AFF

SS1-EDS 8' - 6" 4' - 9"

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.400

PARTIAL PLAN - EDS

REMOVAL PATH

1/8" = 1'-0"1

CBIS TSA PARTIAL PLAN

1/4" = 1'-0"2

SECTION FOR SS1 LINE

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

2' - 0"3' - 5"2' - 0"

9' - 7"

2'

8'

2'

3'

4'

0"

1'

9'

2' - 8"2' - 8" 8' - 0"

1'

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.401

EDS MAINTENANCE

ZONE

1/4" = 1'-0"1

EDS MAINTENANCE ZONE PLAN

1/4" = 1'-0"2

EDS MAINTENANCE ZONE SECTION

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

INSERT / NORMAL

CS/XXX

RESET/RESTART

G

JAM

A

EMERGENCY STOP

R

EDS ENTRANCE

SELECTOR-SWITCH

CONTROL PANEL LEGEND

ILLUMINATED PUSH BUTTON

ILLUMINATED INDICATOR LIGHT

PUSH BUTTON

MUSHROOM HEAD EMERGENCY STOP

ILLUMINATED PUSH AND PULL

RELEASE WITH LOCKABLE COVER

START ALARM

CONTROL PANEL OPERATOR

ABBREVIATIONS

R - RED, A - AMBER, G - GREEN,

Y - YELLOW, W - WHITE, B -

BLACK, BL - BLUE, GY - GRAY

NOTES:

1. BHS EQUIPMENT CONTRACTOR SHALL PROVIDE ANY ADDITIONAL

EMERGENCY STOP CONTROL STATIONS THAT MAY BE REQUIRED TO MEET

CODE AND TO PROVIDE A SAFE WORKING ENVIRONMENT.

2. AS A MINIMUM, PROVIDE ONE EMERGENCY STOP CONTROL STATION ON

EACH SEGMENT OF CATWALK.

3. ALL CONTROL STATIONS SHALL BE LOCATED ON THE CATWALK SIDE OF THE

CONVEYORS.

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.500

TYPICAL CONTROL

STATION DETAILS

12" = 1'-0"2

BHS CONTROL STATION TYPE 14

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

M

L

N

5 6 74

NEW

CS/TYPE 14

CS/TYPE 14

CS/TYPE 14A

CS/TYPE 10

CS/TYPE 10

30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"

EXISTING

EXISTING

EXISTING

EXISTING

ZONE C

ZONE BZONE B

ZONE AZONE A

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.501

E-STOP AND CONTROL

STATION PLAN

1/8" = 1'-0"1

E-STOP AND CONTROL STATION PLAN

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

DEMO

EXISTING

SUBSYSTEMS

NEW

SUBSYSTEMS

REMOVABLE

SUBSYSTEMS

SEQUENCING LEGEND

8 9 10

M

L

N

5 6 74

SF1-08 REMOVE SEGMENT

TO GAIN ACCESS

FOR NEW MACHINE,

AND BRING THE EDS

INTO CBIS STAGING

AREA NEAR SF1-08

8 9 10

M

L

N

5 6 74

RECONNECT SEGMENT

SF1, LINE IN OPERATION AND

EDS STAGED FOR INSTALLATION

SF1-08

8 9 10

M

L

N

5 6 74

SS1-05

SS1-06

REMOVE SS1-05/06 REMOVABLE CONVEYORS

AND LOCATE NORTH ON PAGE, AND AWAY FROM

INSTALLATION PATH OF EDS. AFTER EDS IS IN PLACE,

REMOVE REMOVABLE CONVEYORS OUT OF CBIS AREA.

8 9 10

M

L

N

5 6 74

SS1-06

SS1-04

SS1-03 SAT EDS, AND ISAT.

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.600

SEQUENCING

1/16" = 1'-0"1

SEQUENCE 1

1/16" = 1'-0"2

SEQUENCE 2

1/16" = 1'-0"3

SEQUENCE 3

1/16" = 1'-0"4

SEQUENCE 4

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

FLOOR LOADING:

CT-80DR+ w /CONV. ATTACHED = 4,450lbs FLOOR AREA = (159.2 X 55.1) / 144 = 60.92 sq ft FLOOR LOAD = 4,450 / 60.92 = 73.04 lbs / sq ft

SYSTEM WEIGHT:

CT-80 DR+ XL = 3,700lbs EXTENSIONS = 750lbs TOTAL = 4,450lbs

11' - 8"

2' - 0" 6' - 9"

4'

3'

0' - 6"0' - 10"0' - 10"0' - 4"0' - 6" 3' - 10"0' - 4"0' - 10"

1'

1'

END OF CONVEYOR END OF CONVEYOR

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.700

TYPICAL DETAILS -

LOADING

1/4" = 1'-0"1

CT80DR+XL EDS POINT LOADS

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.701

TYPICAL DETAILS -

SAFETY SIGNAGE

6" = 1'-0"1

BHS OPERATIONAL WARNING SIGN #1

6" = 1'-0"2

BHS OPERATIONAL WARNING SIGN #2

6" = 1'-0"3

BHS OPERATIONAL WARNING SIGN #3

6" = 1'-0"4

BHS OPERATIONAL WARNING SIGN #4

6" = 1'-0"5

BHS OPERATIONAL WARNING SIGN #5

6" = 1'-0"6

BHS OPERATIONAL WARNING SIGN #6

6" = 1'-0"7

BHS OPERATIONAL WARNING SIGN #7

6" = 1'-0"8

BHS OPERATIONAL WARNING SIGN #8

6" = 1'-0"9

BHS OPERATIONAL WARNING SIGN #9

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

ISSUED FOR BID

NOT FOR CONSTRUCTON

/9

/2

:0

:4

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n .r v t

Jacob Coutant

Steve Walker

TLH CBIS Expansion

City Hall 300 S. Adams St.

Tallahassee FL 32301

2024027

9/16/24

Jacob Coutant

B.702

TYPICAL DETAILS -

SAFETY SIGNAGE

6" = 1'-0"1

BHS OPERATIONAL WARNING SIGN #10

6" = 1'-0"2

BHS OPERATIONAL WARNING SIGN #11

6" = 1'-0"3

BHS OPERATIONAL WARNING SIGN #12

6" = 1'-0"4

BHS OPERATIONAL WARNING SIGN #13

6" = 1'-0"5

BHS OPERATIONAL WARNING SIGN #14

6" = 1'-0"6

BHS OPERATIONAL WARNING SIGN #15

6" = 1'-0"7

BHS OPERATIONAL WARNING SIGN #16

6" = 1'-0"8

BHS OPERATIONAL WARNING SIGN #17

6" = 1'-0"9

BHS OPERATIONAL WARNING SIGN #18

NO. DESCRIPTION DATE

1 ISSUED FOR BID NOT FOR

CLNG

J

ELECTRICAL ABBREVIATIONS GENERAL NOTESELECTRICAL SYMBOLS

1. ALL ELECTRICAL WORK MUST COMPLY WITH NATIONAL ELECTRICAL CODE, NFPA 70, THE NATIONAL FIRE CODES, THE AMERICANS WITH DISABILITIES ACT, AND FLORIDA

BUILDING CODES.

2. THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK MUST MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES MUST BE BROUGHT

TO THE ENGINEER'S ATTENTION.

3. OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP DRAWINGS AND ADDENDA TO COORDINATE THE RELATED WORK AND SCHEDULING.

4. THE ELECTRICAL SERVICE TO AND FOR MECHANICAL AND OTHER EQUIPMENT IS BASED ON EQUIPMENT DESIGN DATA. THE ACTUAL VALUES MAY DIFFER DEPENDING UPON THE EQUIPMENT TO BE FURNISHED. ANY MODIFICATION TO THE ELECTRICAL INSTALLATION, BASED UPON ACTUAL EQUIPMENT SELECTION, MUST RESULT IN NO ADDITIONAL

COST TO THE OWNER.

5. THOROUGHLY REVIEW THE MECHANICAL PLANS TO ASSURE THAT ELECTRICAL SERVICE FOR ALL ITEMS AND/OR EQUIPMENT REQUIRING ELECTRICAL SERVICE IS INCLUDED.

ANY ITEM AND/OR EQUIPMENT NOT FURNISH AND INSTALLED WITH ELECTRICAL SERVICE, REQUIRING ELECTRICAL SERVICE, MUST BE BROUGHT TO THE ENGINEER'S

ATTENTION.

6. MECHANICAL, FIRE PROTECTION AND ELECTRICAL EQUIPMENT HAVE BEEN LOCATED AND ARRANGED TO MINIMIZE THE INTERFERENCES OF EQUIPMENT AND STRUCTURE.

THOROUGHLY FAMILIARIZE ONESELF WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES THAT RESULTS IN ADDITIONAL WORK AND MATERIAL, MUST BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT MUST BE

DECIDED BY THE ENGINEER.

7. ALL PANELBOARDS MUST BE FURNISH AND INSTALLED WITH A TYPEWRITTEN SCHEDULE SHOWING CIRCUIT NUMBERS AND A COMPLETE DESCRIPTION OF EACH CIRCUIT, INCLUDING OFFICIAL ROOM NUMBER.

8. ALL LIGHT SWITCHES AND DUPLEX RECEPTACLES MUST BE RATED FOR 20 AMPERES AT 120/277 VOLTS AC. WIRING DEVICES MUST BE SPECIFICATION GRADE.

9. ALL ELECTRICAL WIRING DEVICES INDICATED TO BE INSTALLED IN MASONRY WALLS OR FLOORS MUST BE FLUSH MOUNTED, INCLUDING BRANCH CIRCUIT PANELBOARDS, UON.

THE CONDUITS TO ASSOCIATED ELECTRICAL EQUIPMENT MUST BE CONCEALED IN WALLS OR FLOOR.

10. ALL CONDUIT RUNS MUST BE CONCEALED, UON.

11. ALL SPECIAL PURPOSE OUTLETS MUST BE FURNISHED AND INSTALLED TO MATCH EQUIPMENT TO BE SUPPLIED.

12. ALL CONDUITS MUST INCLUDE A SEPARATE GREEN EQUIPMENT GROUNDING CONDUCTOR.

13. ANY EXISTING UTILITIES LOCATED IN THE AREA OF CONSTRUCTION THAT REQUIRE RELOCATION OR TIE-IN MUST BE COORDINATED WITH THE OWNER'S REPRESENTATIVE.

PROVIDE 72 HOUR ADVANCE NOTICE.

14. ALL DISCONNECT SWITCHES MUST BE THE HEAVY DUTY TYPE, FUSED DISCONNECTS MUST HAVE LITTLEFUSE TIME DELAY, CLASS RK5 AND INDICATING CLASS RK5.

15. CHECK THEOWNER FOR EXACT LOCATION AND/OR DIMENSIONS FOR INSTALLATION OF ALL ELECTRICAL ITEMS. ALL QUESTIONABLE LOCATIONS MUST BE APPROVED BY

OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION.

16. ALL EMPTY CONDUITS MUST CONTAIN JET LINE #232 POLYOLEFIN 200 LB. TEST PULL STRING.

17. ALL WORK SHOWN ON THE ELECTRICAL PLANS MUST BE PERFORMED BY THE CONTRACTOR, UON.

18. ALL EXIT FIXTURES MUST BE CONNECTED TO THE BUILDING LIFE SAFETY PANEL AND/OR HAVE INTEGRAL EMERGENCY BATTERY.

19. ALL SURGE PROTECTED OUTLETS MUST BE EQUAL TO HUBBELL #5352.

20. EQUIPMENT INSTALLED WITHIN CONCEALED SPACES MUST HAVE REASONABLE ACCESS PANELS FURNISHED AND INSTALLED NEARBY FOR INSPECTION, TESTING, AND

SERVICE CONSIDERATIONS. LOCATION OF ACCESS PANELS PER APPROVAL OF ARCHITECT.

21. SECURITY WIRING MUST BE IN CONDUIT AND MUST BE A SEPARATE, COMPLETE, AND FULLY FUNCTIONAL SYSTEM.

22. WHERE CABLES OR CONDUITS ARE REQUIRED TO PASS THROUGH A FIRE RATED WALL, FLOOR, OR CEILING THEY MUST BE SEALED WITH FIRESTOP. THE APPROVED FIRESTOP METHOD MUST COMPLY WITH ARTICLES 300.21 OF NEC AND MUST BE UL LISTED UNDER "THROUGH-PENETRATION FIRESTOP SYSTEM (XHEZ)" IN UL FIRE RESISTANCE DIRECTORY. ALL UNSPRINKLERED FACILITIES MUST BE CONSIDERED TO HAVE INTERIOR CORRIDORS WITH FIRE RATED WALLS, UON. ANY PENETRATION THROUGH THESE WALLS AND OTHER FIRE RATED WALLS MUST BE SEALED WITH FIRESTOP. FURNISH AND INSTALL MINIMUM 1" EMT THROUGH WALL PENETRATIONS.

23. SPARE CONDUITS, WIREWAYS, AND CABLE TRAYS MUST BE SUPPORTED FROM BUILDING STRUCTURE AND NOT FROM OTHER PIPES, DUCTS, OR EXISTING RACKS, UON.

24. EXTERIOR BURIED CONDUIT RUNS MUST BE MINIMUM 24" BELOW FINISHED GRADE. FURNISH AND INSTALL CAUTION TAPE 12" BELOW GRADE. FURNISH AND INSTALL (1) SPARE WITH EACH UNDERGROUND RUN. DUCT BANKS MUST BE CONCRETE ENCASED WITH LOCATION PLAQUES PLACED EVERY 50' AND BEFORE AND AFTER EVERY TURN, UON.

SUBMIT SHOP DRAWINGS BEFORE DIGGING.

25. FURNISH AND INSTALL GROUND STRAP ACROSS ALL CABLE TRAY JOINTS. GROUND CABLE TRAY TO SERVICE GROUND WITH #1/0 AWG BARE COPPER.

26. RACEWAYS INSTALLED IN OUTDOOR LOCATIONS MUST BE HOT DIPPED GALVANIZED, AT MINIMUM, FOR CORROSION RESISTANCE. FOR HIGHLY CORROSIVE ENVIRONMENTS, SUCH AS COASTAL AREAS, ALUMINUM, STAINLESS STEEL, OR PVC COATED RACEWAYS MUST BE REQUIRED.

27. POWER CHANGE EXPENSES RESULTING FROM EQUIPMENT SUBSTITUTIONS THAT DIFFER FROM ITEMS CALLED FOR IN DRAWINGS OR SPECIFICATIONS MUST BE BORNE BY THE CONTRACTOR OR THEIR SUB. THESE MUST INCLUDE CHANGES IN VOLTAGE OR FULL LOAD AMPS RESULTING IN LARGER FEEDERS AND OR CIRCUIT BREAKERS.

28. ALL EXISTING ELECTRICAL DEVICES THAT ARE NOT SHOWN ARE EXISTING TO REMAIN, UON.

29. COORDINATE WITH DIVISION 23 FOR DISCONNECT REQUIREMENTS ON MECHANICAL EQUIPMENT. REFER TO MECHANICAL EQUIPMENT SCHEDULES FOR INFORMATION.

FURNISH AND INSTALL DISCONNECTS FOR THOSE DEVICES THAT DO NOT COME WITH FACTORY INSTALLED DISCONNECTS.

30. BEFORE INITIATING ANY UNDERGROUND WORK, LOCATE ALL UTILITIES.

MOUNTING HEIGHTS

WALL LUMINAIRES SEE LUMINAIRE SCHEDULE OR KEYNOTE

EXTERIOR SPEAKERS 10'-0" TO CENTER OF BOX, UON

FIRE ALARM HORNS/SPEAKERS HIGH BAY

FIRE ALARM HORNS/SPEAKERS

80" TO BOTTOM OF BOX

80" TO BOTTOM OF BOX

FIRE ALARM STROBES HIGH BAY 80" TO CENTER OF DEVICE

FIRE ALARM STROBES 80" TO CENTER OF DEVICE

FIRE ALARM PULL STATIONS HIGH BAY 48" TO CENTER OF DEVICE

FIRE ALARM PULL STATIONS 48" TO CENTER OF DEVICE

TV OUTLETS & TV RECEPTACLE 72" TO BOTTOM OF BOX, UON

RECEPTACLES IN INDUSTRIAL AREAS 48" AFF TO CENTER LINE, UON

RECEPTACLES 18" AFF TO CENTER LINE, UON

SWITCHES 48" AFF TO CENTER OF BOX, UON

GROUND BAR 18" AFF TO BOTTOM OF BAR OR BOX, UON

EMERGENCY PHONE 54" AFF TO CENTER LINE, UON

CARD READER 48" AFF TO CENTER LINE, UON

EPO SWITCHES 54" AFF TO CENTER LINE, UON

CEILING MOUNTED DEVICES EQUAL HEIGHT TO ROOM LUMINAIRES

4" TO BOTTOM WITH BACKSPLASH

ABOVE COUNTER DEVICES 6" TO BOTTOM WITHOUT BACKSPLASH

18" TO C.L RECEPTACLE, DUPLEX, NEMA 5-20R, WALL MOUNTED

18" TO C.L RECEPTACLE, DOUBLE DUPLEX, NEMA 5-20R, WALL MOUNTED

RECEPTACLE, DUPLEX, NEMA 5-20R, MOUNTED ON STUB UP (OR CEILING)

PANELBOARD, 120/208 VOLT

JUNCTION BOX, 4" SQ. X 1 1/2" DEEP (MOUNTED), WALL MOUNTED

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

/6

/2

:3

:0

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n D e s ig n E

R

.r v t

WM

KN

TLH CBIS EXPANSION DESIGN

3330 CAPITAL CIRCLE SW

TALLAHASSEE, FL 32310

20012001007

09/16/2024

AA

E001

ELECTRICAL GENERAL

NOTES, SYMBOLS,

AND ABBREVIATIONS

A AMPERES

AC ABOVE COUNTER

AF AMP FUSE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AL ALUMINUM

AMP AMPERE

AP ACCESS PANEL

ATS AUTOMATIC TRANSFER SWITCH

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BFG BELOW FINISHED GRADE

BHS BAGGAGE HANDLING SYSTEM

BID BAGGAGE INFORMATION DISPLAY

C CONDUIT

CAT6 CATEGORY 6 ETHERNET CABLE

CATV COMMUNITY ANTENNA TELEVISION

CB CIRCUIT BREAKER

CH CHILLER

CKT CIRCUIT

COMM COMMUNICATION

CONC CONCRETE

CR CARD READER

CRU COMPUTER ROOM UNIT

CT COOLING TOWER

CU COPPER

DC DIRECT CURRENT

DISC DISCONNECT

DWG DRAWING

E EXISTING

E EAST

EF EXHAUST FAN

EL EMERGENCY LIGHT

ELEC ELECTRIC/ELECTRICAL

EM EMERGENCY

EMT ELECTRICAL METALLIC TUBING

EOR ENGINEER OF RECORD

EQ EQUAL

ER EXISTING TO BE REMOVED

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EX EXISTING TO REMAIN

EXR EXISTING TO BE RELOCATED

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FID FLIGHT INFORMATION DISPLAY

FLA FULL LOAD AMPS

FLR FLOOR

FO FIBER OPTIC

FPB FAN POWERED TERMINAL BOX

FS FLOW SWITCH

G GROUND

GC GENERAL CONTRACTOR

GF GROUND FAULT

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GID GATE INFORMATION DISPLAY

GPU GROUND POWER UNIT

GRC GALVANIZED RIGID CONDUIT

HH HANDHOLE

HP HORSE POWER

HVAC HEATING, VENTILATING & AIR CONDITIONING

IC INTERCOM

IR INFRARED

J JUNCTION

JB JUNCTION BOX

KAIC (THOUSAND) AMPERE INTERRUPTING CAPACITY

Kcmil THOUSANDS OF CIRCULAR MILS

KVA KILOVOLT-AMPERES

KW KILOWATT

LED LIGHT EMITTING DIODE

LSI LONG TIME, SHORT TIME, INSTANTANEOUS

LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND

FAULT

LTG LIGHTING

MAX MAXIMUM

MCA MINIMUM CIRCUIT AMPACITY

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MTD MOUNTED

MUFID MULTI-USER FLIGHT INFORMATION DISPLAY

N NEUTRAL

N NORTH

N/A NOT APPLICABLE

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOC

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NO NUMBER

NTS NOT TO SCALE

O.C. ON CENTER

OAE OR APPROVED EQUAL

OH OVERHEAD

OS OCCUPANCY SENSOR

PBB PASSENGER BOARDING BRIDGE

PNL PANELBOARD

PNL PANEL

POE POWER OVER ETHERNET

PVC POLYVINYLCHLORIDE

RECP RECEPTACLE

REF REFRIGERATOR

RGS RIGID GALVANIZED STEEL

RM ROOM

RMC RIGID METAL CONDUIT

RTU ROOF TOP UNIT

S SOUTH

SCCR SHORT CIRCUIT CURRENT RATING

SEC SECURITY

SF SUPPLY FAN

SIM SIMILAR

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE SINGLE THROW

SQ SQUARE

SS STAINLESS STEEL

SW SWITCH

SWBD SWITCHBOARD

SWGR SWITCHGEAR

T TRANSFORMER

TEL TELEPHONE

TGB TELECOMMUNICATIONS GROUNDING BUS BAR

TV TELEVISION

TYP TYPICAL

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UT UTILITY

V VOLTS

VAV VARIABLE AIR VOLUME (HVAC)

VFD VARIABLE FREQUENCY DRIVE

W WATTS

W WEST

WP WEATHERPROOF

Y WYE (CONNECTED)

Z ZONE

NO. DESCRIPTION DATE

ISSUED FOR BID

NOT FOR CONSTRUCTION

ANIMAL

SCREEN RM.

A104

SCREENING

ROOM

A103

BAGGAGE HANDLING

ROOM

A100

BAG SCREENING

ROOM

A101

EDS PARTS

STORAGE

A102

BHS

STORAGE

A105

LOBBY

A107

ELEVATOR

NO.1

ELEVATOR

EQUIP.

CLNG

CLNG

CLNG

CLNG

CLNGCLNG CLNG

EX PANEL BHS3

EX

EX

BHS3-16

EXEXEX

EX

EX

EX

EX

EX

EX EX EX EX

EX

EX

EX

EX

EXEXEXEX

EX

EX

EX

EX

EX

EXEX EX

EX

EX EX

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

/6

/2

:3

:0

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n D e s ig n E

R

.r v t

WM

KN

TLH CBIS EXPANSION DESIGN

3330 CAPITAL CIRCLE SW

TALLAHASSEE, FL 32310

20012001007

09/16/2024

AA

E101

ELECTRICAL FIRST

FLOOR PLAN

NO. DESCRIPTION DATE

0 2' 4'1'

3/16" = 1'-0"

FIRST FLOOR CBIS

KEY NOTES

1. EXISTING CEILING MOUNTED RECEPTACLE OULETS FOR EDS POWER.

2. EXISTING FLOOR TO CEILING STRUCTURE MOUNTED UNISTRUT. LOCATED ADJACENT

TO NEW CT80XL (EDS MACHINE).

3. NEW UNISTRUT MOUNTED QUAD RECEPTACLE. MATCH EXISITNG INSTALLATION,

REFER TO PHOTO E101A.

PHOTO E101A

COLUMN REC / CHP-1

PANELBOARD: BHS3

LOCATION: A100

MOUNTING: SURFACE

FULLY RATED AIC: 10,000

MAX VOLTAGE: 208

ENCL: NEMA 1

SYSTEM VOLTS:

MAIN C.B.:

BUS SIZE:

208 Y/120 V, 3 PH, 4W

100 AMP

100 AMP

NO

29 20

20 4

NOTE RECEP.

VA

OTHER P AMP NO

CIRCUITDESCRIPTIONVOLT AMP

PH A PH B PH C

DESCRIPTIONVACIRCUIT

AMP P NOTE RECEP. OTHER

CT80-DRXL MACHINE (VIA UPS)

CT80 - DRXL A/C UNIT

REC. - A106

REC - A106

SPARE

SPARE

CT80 UPS

SPARE

IT - 1 CBIS CABINET

SIEMENS TRANSFORMER

PLC

AIR COMPRESSOR

CABINET - IT - 8

KNEE WALL PLUGS

KNEE WALL PLUGS

KNEE WALL PLUGS

REC. - RM 100, 103, 104, EWC - RM A107

EF - 2, EF - 3

SPARE

RECEPTACLE (NEW)

EF #14 (1/10 HP)

ELEV. EQUIP. RM REC

SPARE

SPARE

W/H-1 RM A202

SPARE

SPARE

NOTES:

1. ALL EQUIPMENT EXISTING UON.

2. ALL NEW BRANCH CIRCUITS SHALL BE 2#12, 1#12 GND - 3/4"C UON.

201 42

20 1

20 1

20 1

20 1

20 1

20 1

SPARE

SPARE

SPARE

SPARE

WORKSTATION TWIST LOCK #2

WORKSTATION TWIST LOCK #1 ELEV PIT LTS/SUMP PUMP

SPARE

SPARE

SPARE

SPARE

SPARE

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

/6

/2

:3

:0

P M

A u to d e s k D o c s /2

T L

H C

B

IS

E x p a n s io n D e s ig n /2

T L H

C

B

IS

E x p a n s io n D e s ig n E

R

.r v t

WM

KN

TLH CBIS EXPANSION DESIGN

3330 CAPITAL CIRCLE SW

TALLAHASSEE, FL 32310

20012001007

09/16/2024

AA

EP602

ELECTRICAL POWER

SCHEDULES

F. ALL CONDUCTOR SIZES ARE BASED ON COPPER.

E. CONDUCTORS FEEDING K-RATED TRANSFORMERS REQUIRE 200% NEUTRAL CONDUCTORS WITH CONDUIT SIZED PER NEC.

D. CONTRACTOR SHALL INCREASE FEEDER SIZES WHEN THEY ARE LONGER THEN 165' FOR 208 V AND 185' FOR 480 V.

SECONDARY GROUND CONDUCTORS ARE ACCEPTABLE AND SHALL BE SIZED PER NEC TABLE 250.102.

C. SECONDARY GROUND (SUPPLY SIDE BONDING JUMPER) CONDUCTOR SIZE IS PER NEC 250.102(C)(1). SECONDARY GROUND CONDUCTOR SIZE ASSUMES A SINGLE CONDUCTOR FOR SINGLE OR PARALLEL SETS, MULTIPLE

B. PRIMARY GROUND (EQUIPMENT GROUND) CONDUCTOR SIZE IS PER NEC TABLE 250.122.

A. GROUNDING ELECTRODE CONDUCTOR SIZE IS PER NEC TABLE 250.66.

GENERAL NOTES:

750 480 3 1600 4 3 600 KCMIL #4/0 EACH SET IN 3 1/2" #1/0 208 3 3000 8 4 500 KCMIL 500 KCMIL EACH SET IN 3 1/2"

500 480 3 1000 4 3 250 KCMIL #2/0 EACH SET IN 2 1/2" #2 208 3 2000 5 4 600 KCMIL 400 KCMIL EACH SET IN 4"

300 480 3 600 2 3 300 KCMIL #1 EACH SET IN 2 1/2" #2 208 3 1200 4 4 350 KCMIL #4/0 EACH SET IN 3"

225 480 3 400 1 3 500 KCMIL #3 3" #1/0 208 3 800 2 4 600 KCMIL #3/0 EACH SET IN 4"

150 480 3 300 1 3 300 KCMIL #4 2 1/2" #2 208 3 600 2 4 350 KCMIL #2/0 EACH SET IN 3"

112.5 480 3 200 1 3 #3/0 #6 2" #4 208 3 400 2 4 #3/0 #2 EACH SET IN 2 1/2"

75 480 3 150 1 3 #1/0 #6 2" #6 208 3 225 1 4 #4/0 #2 2 1/2"

45 480 3 90 1 3 #3 #8 1 1/4" #8 208 3 150 1 4 #1/0 #6 2"

30 480 3 60 1 3 #6 #10 1" #8 208 3 100 1 4 #1 #6 2"

15 480 3 30 1 3 #10 #10 3/4" #8 208 3 60 1 4 #4 #8 1 1/4"

SETS QUANTITY GUAGE SETS QUANTITY GUAGE

VOLTS PHASE

BREAKER TRIP

(AMPS)

CONDUCTOR GROUND

GUAGE

CONDUIT SIZE VOLTS PHASE

BREAKER TRIP

(AMPS)

CONDUCTOR GROUND

GUAGE

CONDUIT SIZE

XFMR SIZE

(KVA)

PRIMARY GROUNDING

ELECTRODE

CONDUCTOR

SECONDARY

TRANSFORMER SCHEDULE

4. CONDUIT SIZING IS BASED ON CONDUCTORS WITH THHW INSULATION.

3. ADJUST CONDUCTOR & GEC SIZE FOR LONG RUNS AND TEMPERATURE ABOVE DESIGN AMBIENT TEMPERATURE.

2. MAXIMUM 2% VOLTAGE DROP FOR FEEDERS; 3% VOLTAGE DROP FOR BRANCH CIRCUITS.

1. ALL FEEDER TYPES SCHEDULED MAY NOT APPLY TO THIS PROJECT.

GENERAL NOTES:

U REFER TO "ELECTRICAL UTILITY MATRIX" FOR ADDITIONAL INFORMATION.

T REFER TO "TRANSFORMER SCHEDULE" FOR CONDUCTOR SIZE.

G REFER TO "GROUNDING RISER DETAIL" FOR CONDUCTOR SIZE.

Y 4

Δ 3

400 KCMIL

SE

500 KCMIL

#3/0

EACH SET IN 4"

Y 4

Δ 3

350 KCMIL

SE

600 KCMIL

#3/0

EACH SET IN 4"

Y 4

Δ 3

250 KCMIL

SE

600 KCMIL

#3/0

EACH SET IN 4"

Y 4

Δ 3 #4/0

SE

600 KCMIL

#3/0

EACH SET IN 4"

Y 4

Δ 31200

SE

350 KCMIL #3/0 EACH SET IN 3"

Y 4

Δ 31000

SE

250 KCMIL #2/0 EACH SET IN 2 1/2"

Y 4

Δ 3 #1/0

SE

500 KCMIL

#2/0

EACH SET IN 3 1/2"

Y 4

Δ 3 #1

SE

300 KCMIL

#1/0

EACH SET IN 3"

Y 4

Δ

#4/0 #2 EACH SET IN 2 1/2"

Y 4

Δ 3 #3

SE

500 KCMIL

#1/0

3 1/2"

Y 4

Δ

350 KCMIL #3 3"

Y 4

Δ

300 KCMIL #4 3"

Y 4 3"

Δ

250 KCMIL #4

2 1/2"

Y 4

Δ 3 #4

SE

#4/0

#2

2 1/2"

Y 4 2 1/2"

Δ 3 #6

SE

#3/0

#4 2"

Y 4

Δ

#2/0 #6 2"

Y 4

Δ 3 #6

SE

#1/0

#6

2"

Y 4 2"

Δ 3 #6

SE

#1

#6 1 1/2"

Y 4 1 1/2"

Δ

#2 #6

1 1/4"

Y 4

Δ 3 #8

SE

#2

#1/0

1 1/4"

Y 4

Δ

#3 #8 1 1/4"

Y 4

Δ

#4 #8 1 1/4"

Y 4

Δ

#6 #10 1"

Y 4

Δ

#6 #10 1"

Y 4 1"

Δ

#8 #10

3/4"

Y 4

Δ

#10 #10 3/4"

SETS QUANTITY GAUGE MIN. EGC (Δ/Y)

BREAKER TRIP

(AMPS)

TYPE

CONDUCTOR MIN. GEC (SE)

MINIMUM CONDUIT SIZE

FEEDER SCHEDULE

1. SEE DRAWINGS FOR WIRE SIZING.

KEYNOTE:

LESS CURRENT-CARRYING CONDUCTORS IN RACEWAY.

INSULATION, 100% POWER FACTOR, BALANCED LOAD, NEGLIGIBLE REACTANCE, AND 6 OR

4. BASIS OF VOLTAGE DROP CALCULATIONS IS 3% DROP, 80% CIRCUIT LOAD, THHN/THWN

3. PROVIDE CONDUIT SIZE PER NEC.

PROTECTION.

2. DISTANCE IS WIRE LENGTH TO FIRST OUTLET/DEVICE/EQUIPMENT FROM OVERCURRENT

1. SEE DRAWINGS FOR WIRE SIZING WHEN DISTANCE EXCEEDS VALUES SHOWN.

GENERAL NOTES:

2 225' 520'

KEYNOTE 1

180' 415'

2 250' 578'

KEYNOTE 1

200' 462'

3 225' 520'

KEYNOTE 1

182' 421'

3 257' 594'

KEYNOTE 1

208' 479'

4 121' 280' 243' 559'

6 76' 176' 152' 353'

4 145' 335' 291' 670'

6 92' 212' 184' 424'

4 161' 372' 323' 745'

6 102' 235' 204' 471'

6 115' 265' 230' 530'

8 72' 166' 144' 333'

6 131' 303' 263' 605'

8 82' 190' 165' 381'

8 96' 222' 192' 444'

10 62' 144' 125' 289'

10 94' 216' 187' 443'

12 56' 130' 113' 260'

15 12 75' 173' 150' 346'

120 V 277 V 208 V 480 V

1Ø 3ØBREAKER TRIP

(AMPS)

COPPER WIRE

(75°C)

MAXIMUM DISTANCE (FEET)

BRANCH CIRCUIT SCHEDULE

NO. DESCRIPTION DATE

TELECOMMUNICATIONS ABBREVIATIONS TELECOMMUNICATIONS SYMBOLS

1. REFER TO CONSTRUCTION MANUAL OR SPECIFICATIONS FOR MATERIALS TO BE INCORPORATED.

2. CONTRACTOR MUST FIELD VERIFY ALL NEW DEVICE AND EQUIPMENT LOCATIONS PRIOR TO THE START OF INSTALLATION. ANY CONFLICTS MUST BE IMMEDIATELY

BROUGHT TO THE ATTENTION OF THE OWNER.

3. MINIMUM CONDUIT SIZE MUST BE 1". ALL CONDUITS MUST BE EMT. EXCEPTIONS INCLUDE:

A. GRS FOR EXTERIOR AREAS.

B. RS FOR AREAS ACCESSIBLE TO THE PUBLIC.

C. PVC FOR BURIED OR CAST-IN-PLACE CONDUITS.

D. FLEXIBLE CONDUIT FOR CONCEALED DROPS TO DEVICES AND WHERE APPROVED BY THE OWNER.

4. CONDUIT MUST NOT EXCEED 40% FILL FACTOR. INSTALLATION OF CONDUIT AND WIRING MUST BE IN COMPLIANCE WITH NATIONAL ELECTRICAL CODE (NEC). ALL WIRING MUST BE HOMERUN, UNLESS OTHERWISE NOTED. ANY SPLICES MUST BE APPROVED BY THE DESIGNER.

5. CONTRACTOR MUST COORDINATE THE ROUTING AND LOCATION OF NEW COMMUNICATIONS CONDUITS WITH THE ELECTRICAL CONTRACTOR AND OTHER TRADES.

6. CONTRACTOR MUST BE RESPONSIBLE FOR ENSURING THAT LINE VOLTAGE (120V AND ABOVE) POWER CONDUCTORS ARE NOT ROUTED WITHIN 12 INCHES OF

COMMUNICATIONS WIRING.

7. ALL CONDUCTORS MUST BE COLOR CODED AND TAGGED AS DESCRIBED IN THE WRITTEN SPECIFICATIONS AND APPROVED BY THE OWNER.

8. COORDINATE WORK WITH OTHER TRADES AND CONFIRM FINAL MOUNTING LOCATION FOR NEW AND RELOCATED EQUIPMENT WITH THE OWNER PRIOR TO INSTALLATION.

9. CONTRACTOR MUST FOLLOW MANUFACTURER'S RECOMMENDED INSTALLATION PROCEDURES FOR ALL EQUIPMENT. UNLESS OTHERWISE NOTED, ALL MATERIALS MUST

BE NEW AND UNUSED.

10. ALL RACEWAY, CONDUIT AND JUNCTION BOXES MUST BE NEW AND INSTALLED WITH PULL STRING. REUSE OF EXISTING CONDUITS MUST BE APPROVED BY THE OWNER.

WHEN INSTALLING CABLING IN EXISTING CABLE TRAY, CONTRACTOR MUST TAKE CARE NOT TO DISTURB OR DAMAGE EXISTING CABLING.

11. PROVIDE CONDUIT SLEEVES FOR ALL PENETRATIONS, WHETHER SHOWN ON DRAWING OR NOT. PROVIDE INSULATING BUSHINGS ON BOTH ENDS OF ALL.

12. NON-SECURITY DATA/COMM OUTLETS PROVIDE 1"C FROM OUTLET TO THE ACCESSIBLE CEILING SPACE. CABLE ROUTING WILL BE VIA CABLE TRAY SYSTEM TO INDICATED COMMUNICATIONS ROOM OR CABINET. PROVIDE RACEWAY SYSTEM OVER THE INACCESSIBLE CEILING SPACE AS INDICATED ON PLANS. TELE/DATA CONDUITS ARE TO BE LONG RADIUS TYPE AND SHALL CONTAIN PULL WIRES. PROVIDE PLATES FOR ALL OUTLETS. SECURITY DEVICE DATA/COMM OUTLETS PROVIDE

COMDUIT ENTIRE RUN.

GENERAL NOTES

(4) 8P8C IDC (CAT 6) JACKS WITH CAT6 TO EXISTING CBIS DATA CABINET, SEE NOTE 12

(8) 8P8C IDC (CAT 6) JACKS WITH CAT6 TO EXISTING CBIS DATA CABINET, SEE NOTE 12

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

/9

/2

:2

:1

P M

A u to d e s k D o c s /2

T

L H

C B

IS

E x p a n s io n D e s ig n /2

T L

H

C B

IS

E x p a n s io n D e s ig n T

R

.r v t

ISSUED FOR BID

NOT FOR CONSTRUCTION

WM

KN

TLH CBIS EXPANSION DESIGN

3300 CAPITAL CIR SW,

TALLAHASSE, FL 32310

20012001007

09/16/2024

AA

T001

BUILDING ID

TELECOMMUNICATIONS

GENERAL NOTES,

SYMBOLS AND

ABBREVIATIONS

AC ABOVE COUNTER

ACS ACCESS CONTROL SYSTEM

ACT ACOUSTIC CEILING TILE

AFF ABOVE FINISHED FLOOR

AHJ AUTHORITY HAVING JURISDICTION

AL ALUMINUM

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

BHS BAGGAGE HANDLING SYSTEM

C CONDUIT

CAT6 CATEGORY 6 ETHERNET CABLE

CATV CABLE TELEVISION

CBIS CHECKED BAG INSPECTION SYSTEM

CBP CUSTOMS AND BORDER PROTECTION

COMM COMMUNICATION

CR CARD READER

DC DIRECT CURRENT

DIV DIVISION

DWG DRAWING

E EXISTING

EDS EXPLOSIVES DETECTION SYSTEM

EL ELEVATION

ELEC ELECTRIC/ELECTRICAL

EM EMERGENCY

EOR ENGINEER OF RECORD

EQ EQUAL

EX EXISTING TO REMAIN

FID FLIGHT INFORMATION DISPLAY

FLR FLOOR

FO FIBER OPTIC

G GROUND

GC GENERAL CONTRACTOR

GRS GALVANIZED RIGID STEEL

HDMI HIGH DEFINITION MULTIMEDIA INTERFACE

IC INTERCOM

IDC INSULATION DISPLACEMENT CONNECTION

IDF INTERMEDIATE DISTRIBUTION FRAME

IP INTERNET PROTOCOL

ISP INTERNET SERVICE PROVIDER

J JUNCTION

JB JUNCTION BOX

KAIC (THOUSAND) AMPERE INTERRUPTING CAPACITY

Kcmil THOUSANDS OF CIRCULAR MILS

KO KNOCK OUT

LAN LOCAL AREA NETWORK

LCD LIQUID CRYSTAL DISPLAY

MAX MAXIMUM

MDF MAIN DISTRIBUTION FRAME

MIC MICROPHONE

MM MULTI-MODE

N NEUTRAL

NEC NATIONAL ELECTRICAL CODE

NTS NOT TO SCALE

OAE OR APPROVED EQUAL

OC ON CENTER

OH OVERHEAD

PNL PANEL

POE POWER OVER ETHERNET

POS POINT OF SALE

PTZ PAN-TILT-ZOOM

PVC POLYVINYL CHLORIDE

QTY QUANTITY

REX REQUEST TO EXIT

RF RADIO FREQUENCY

RM ROOM

RS RIGID STEEL

SEC SECURITY

SIDA SECURITY IDENTIFICATION DISPLAY AREA

SIM SIMILAR

SM SINGLE MODE

SPD SURGE PROTECTIVE DEVICE

SYM SYMMETRICAL

TBD TO BE DETERMINED

TEL TELEPHONE

TSA TRANSPORTATION SECURITY ADMINISTRATION

TV TELEVISION

TYP TYPICAL

UL UNDERWRITERS LABORATORIES

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER SUPPLY

UTP UNSHIELDED TWISTED PAIR

VMS VIDEO MANAGEMENT SYSTEM

WAP WIRELESS ACCESS POINT

NO. DESCRIPTION DATE

ANIMAL

SCREEN RM.

A104

SCREENING

ROOM

A103

BAGGAGE HANDLING

ROOM

A100

BAG SCREENING

ROOM

A101

EDS PARTS

STORAGE

A102

BHS

STORAGE

A105

LOBBY

A107 exhaust fan pipes up to structure and turn into ceiling

F.E.C.

ELEVATOR

NO.1

ELEVATOR

EQUIP.

CBIS CBIS CBIS CBIS CBIS

CBIS

CBISCBIS

CBIS

EX EX

EX EX EX EX EX

EX

EX

CBIS

EX EX

EX EX EX

EX

EX EX

KEY NOTES

1. PROVIDE NEW UPS WITH NETWORK MONITORING AND NEW NETWORK

SWITCH. UPS SHALL BE APC SMART-UPS (ON-LINE 1kVA, TOWER, 120V, 6x

5-15R NEMA OUTLETS, SMARTSLOT, EXTENDED RUNTIME, WITHOUT RAIL KIT)

OR APPROVED EQUAL. NETWORK MONITORING CARD SHALL BE APC PART

NUMBER AP9641 OR APPROVED EQUAL. NETWORK SWITCH SHALL BE CISCO

CATALYST IE3100 (18 PORT AND 2 GE DUAL-MEDIA UPLINK PORTS) OR

APPROVED EQUAL. REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE

AIRPORT.

2. PROVIDE NEW UPS WITH NETWORK MONITORING. UPS SHALL BE APC SMART-

UPS (ON-LINE 3kVA, TOWER, 120v, 8x 5-20R+1x L5-30R NEMA OUTLETS, SMARTSLOT, EXTENDED RUNTIME, WITHOUT RAIL KIT) OR APPROVED EQUAL.

NETWORK MONITORING CARD SHALL BE APC PART NUMBER AP9641 OR

APPROVED EQUAL. REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE

AIRPORT.

3. REPLACE EXISTING WORKSTATION COMPUTER EQUIPMENT INCLUSIVE OF PC

AND MONITORS. NEW WORKSTATION EQUIPMENT TO MEET REQUIREMENTS

OF SPECIFICATION SECTION 347739.

Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.

904-256-2500 Fax 904-256-2503

A

B

C

D

54321

10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com

FL Cert. Nos. AAC001886 * IB26000956

*5620 * LCC000210 * GB238

REVISIONS

DATE ISSUED:

REVIEWED BY:

DRAWN BY:

DESIGNED BY:

PROJECT NUMBER:

© 2021 RS&H, INC.

PROJECT STATUS:

SHEET ID:

SHEET TITLE:

PROJECT ADDRESS:

PROJECT TITLE:

/6

/2

:3

:1

P M

A u to d e s k D o c s /2

T

L H

C B

IS

E x p a n s io n D e s ig n /2

T L

H

C B

IS

E x p a n s io n D e s ig n T

R

.r v t

ISSUED FOR BID

NOT FOR CONSTRUCTION

WM

KN

TLH CBIS EXPANSION DESIGN

3300 CAPITAL CIR SW,

TALLAHASSE, FL 32310

20012001007

09/16/2024

AM

T100

TELECOMMUNICATIONS

FIRST FLOOR PLAN

NO. DESCRIPTION DATE

0 2' 4'1'

3/16" = 1'-0"

FIRST FLOOR CBIS

NEW UPS LOCATION

EXISTING PLC CABINET

BAG SCREENING

ROOM

A101

EDS PARTS

STORAGE

A102

CBIS CBIS CBIS CBIS CBIS

CBIS

CBIS

EX EX EX EX EX

EX

EX

CBIS

EX EX EX

EX EX EX EX

EX

EX EX

EX

3 4

KEY NOTES

1. EXISTING FLOOR TO CEILING STRUCTURE MOUNTED UNISTRUT. LOCATED

ADJACENT TO…