1-TLH CBIS Expansion - IFB - PLANS.pdf
PDF 6 MB Posted
- Solicitation number
- IFB-090-25-CW
- Issued by
- Leon County, Florida
About this file
These documents are design and engineering plans for the Tallahassee International Airport's Checked Baggage Inspection System (CBIS) Expansion project, prepared by RS&H Associates, Inc. and BNP Associates, Inc. The project involves upgrading and expanding the existing baggage handling system (BHS) at the airport, specifically focusing on the first-floor CBIS area. The design is dated September 16, 2024, with the project located at 3330 Capital Circle SW in Tallahassee, Florida. The plans include detailed schematics for telecommunications, electrical systems, and baggage handling equipment, with a comprehensive set of drawings covering existing conditions, proposed modifications, sequencing, and installation details.
The documents provide technical specifications for replacing and upgrading equipment, including new uninterruptible power supplies (UPS), network switches, workstation computers, and screening equipment. The project involves installing a new CT80DR+XL Explosives Detection System (EDS) machine, reconfiguring conveyor systems, and updating control stations and safety signage. The design accounts for electrical load calculations, grounding requirements, and telecommunications infrastructure, with specific attention to integrating new equipment with existing systems. The plans indicate careful consideration of operational continuity, with staged removal and replacement of components to minimize disruption to airport operations.
View the file
Other files
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NORTH
NORTH
MEXICO
OF
GULF
KEY
WEST
TALLAHASSEE
FERNANDINA
BEACH
ORLANDO
TAMPA
FORT
PALM
FT.
MIAMI
MYERS
WEST
BEACH
LAUDERDALE
JACKSONVILLE
ATLANTIC
OCEAN
S-373
CITY OF
TALLAHASSEE
S-261A
TALLAHASSEE
INTERNATIONAL AIRPORT
904-256-2500 Fax 904-256-2503
10748 Deerwood Park Blvd. South
Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956 *
5620 * LCC000210 * GB238ASSOCIATES, INC.
LOCATION MAP
N.T.S.
VICINITY MAP
N.T.S.
TALLAHASSEE INTERNATIONAL AIRPORT
CBIS EXPANSION
TALLAHASSEE, FLORIDA
SEPTEMBER 16, 2024
RS&H PROJECT NO. 20012001.007
ISSUED FOR BID
T701 TELECOMMUNICATIONS RISER DIAGRAM
T101 ENLARGED PLAN - CBRA RM A101
T100 TELECOMMUNICATIONS FIRST FLOOR PLAN
T001 TELECOMMUNICATIONS GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
TELECOMMUNICATIONS
EP602 ELECTRICAL POWER SCHEDULES
E101 ELECTRICAL FLOOR PLAN
E001 ELECTRICAL GENERAL NOTES, SYMBOLS AND ABBREVIATIONS
ELECTRICAL
B.702 TYPICAL DETAILS - SAFETY SIGNAGE
B.701 TYPICAL DETAILS - SAFETY SIGNAGE
B.700 TYPICAL DETAILS - LOADING
B.600 SEQUENCE 1 & 2 AND STEP 1 & 2
B.501 E-STOP AND CONTROLS STATION PLAN
B.500 TYPICAL CONTROLS STATION DETAILS
B.401 EDS MAINTENANCE ZONE
B.400 PARTIAL PLAN - EDS REMOVAL PATH
B.201 PARTIAL PLAN - PROPOSED CONDITIONS
B.200 GENERAL ARRANGEMENT - PROPOSED CONDITIONS
B.102 PARTIAL PLAN - DEMOLITION CONDITIONS
B.101 GENERAL ARRANGEMENT - EXISTING CONDITIONS
B.003 KEY PLAN
B.002 CONVEYOR MANIFEST
B.001 SYMBOLS, LEGENDS, ABBREVIATIONS AND SHEET LIST
BAGGAGE HANDLING
SHEET NUMBER SHEET NAME
SHEET INDEX
CHECK AND FIELD VERIFY ALL BHS RELATED DIMENSIONS ON THE JOB SITE
BEFORE PROCEEDING WITH WORK AND BE RESPONSIBLE FOR THEIR ACCURACY.
IF DISCREPANCIES ARE FOUND BETWEEN THE BHS DRAWINGS, SPECIFICATIONS
AND FIELD CONDITIONS, REPORT THEM TO THE OWNER.
THE FOLLOWING REQUIREMENTS, TOGETHER WITH THE PROJECT SPECIFICATIONS AND
BHS DRAWINGS SHALL APPLY.
FINISHED FLOOR ELEVATIONS PROVIDED FOR INFORMATION ONLY.
ALL FINISHED FLOOR DIMENSIONS ARE TAKEN FROM THE HIGH POINT OF THE
FINISHED FLOOR.
NO DIMENSIONS SHALL BE SCALED. DRAWING DIMENSIONS SHOWN SHALL BE
USED.
BHS CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING BHS RIGHT-OF-WAY ISSUES
AND REPORTING THEM TO THE OWNER.
BHS CONTRACTOR TO COORDINATE WITH OTHER TRADES TO MAINTAIN BAGGAGE
SYSTEM RIGHTS-OF-WAY.
ALL DIMENSIONS ARE FROM GRID TO OUTER EXTENT OF CONVEYOR SIDEGUARD,
UNLESS NOTED.
FOR ADDITIONAL BHS RIGHT-OF-WAY CLEARANCES, CROSS SECTIONS, AND
ATTACHMENT DETAILS REFERENCE THE SERIES DRAWINGS.
ALL OTHER TRADES SHALL MAINTAIN CLEAR RIGHT-OF-WAY (UNLESS NOTED)
FROM TOP OF BELT TO NEAREST OBSTRUCTION. HANGING ANY EQUIPMENT
COMPONENTS (E.G. MECHANICAL, ELECTRICAL, PLUMBING, HVAC). FROM THE
CONVEYOR, CATWALK OR ASSOCIATED SUPPORTS IS NOT ACCEPTABLE.
MODIFY EXISTING CONVEYOR DRIVE ASSEMBLIES, AS REQUIRED, TO
ACCOMMODATE SPECIFIED BHS ALTERATIONS (E.G. RECONFIGURE DRIVE FROM
LEFT HAND TO RIGHT HAND OR VICE VERSA).
ALL BHS RIGHTS-OF-WAY SHALL TAKE PRECEDENCE OVER ALL OTHER BUILDING
SERVICES (E.G. MECHANICAL, DUCT WORK AND PIPES, CONDUIT, FIRE
PROTECTION, PLUMBING).
SUPPLY SAFETY DEVICES PER CONTRACT SPECIFICATIONS.
REFERENCE
ARCHITECTURAL DRAWINGS FOR ALL FLOOR ELEVATIONS AND BUILDING
INFORMATION.
3' 0"
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
STANDARD
CONVEYOR
TOP OF
BELT
C
LR
3'
R O
W
4'
CONV
3' - 6"
ROW
5' - 6"
MINIMUM 12" CLEARANCE
AROUND ALL BHS
ELEMENTS UNLESS
OTHERWISE NOTED
XXY-ZZ
NEW OR REWORKED CONVEYOR ID
SEQUENTIAL NUMBER OF COMPONENTS IN TRAIN
SEQUENTIAL NUMBER OF SUBSYSTEMS OF THIS TYPE
SUBSYSTEM DESCRIPTION IDENTIFIER
SUBSYSTEM DESCRIPTION IDENTIFIERS
CL - CLEAR LINE
OG - OUT OF GAUGE
SF - SECURITY FEED LINE
SS - SECURITY SCREENING
SHEET NUMBER DESIGNATIONS
B.210
SEQUENCE DRAWING #
SHEET TYPE
DISCIPLINE DESIGNATOR
BHS FLOW DIRECTION
TOP OF BELT ELEVATION
UNLESS NOTED
EXISTING BHS EQUIPMENT
DEMOLISHED BHS EQUIPMENT
NEW BHS EQUIPMENT
CONTROL PANEL
ITEM NUMBER
EXISTING EQUIPMENT
ITEM NUMBER
NEW EQUIPMENT
ITEM NUMBER
RENUMBERED EQUIPMENT
ITEM NUMBER
CONTROL EQUIPMENT
CONVEYOR CROSS SECTION
CONVEYOR WITH DRIVE
CROSS SECTION
XXY-ZZ
XXY-ZZ
XXY-ZZ
XXY-ZZ
45° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
DECLINE CONVEYOR
END ROLLER
QUEUE CONVEYOR
24" MINI-CENTER DRIVE
60" CENTER DRIVE
24" MINI UNDERSLUNG DRIVE
60" STANDARD UNDERSLUNG DRIVE
45° MERGE CONVEYOR
45° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
90° POWER TURN
(OPTIONAL DRIVE LOCATIONS SHOWN)
END ROLLER
QUEUE CONVEYOR
24" MINI-CENTER DRIVE
60" CENTER DRIVE
24" MINI UNDERSLUNG DRIVE
60" STANDARD UNDERSLUNG DRIVE
45° MERGE CONVEYOR
DECLINE CONVEYOR
FIRE/SECURITY DOOR FIRE/SECURITY DOOR
HIGH SPEED PADDLE DIVERTERHIGH SPEED PADDLE DIVERTER
REVERSE MERGE CONVEYOR REVERSE MERGE CONVEYOR
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.001
SYMBOLS, LEGENDS,
ABBREVIATIONS, AND
SHEET LIST
AFF ABOVE FINISHED FLOOR
ARCH PROJECT ARCHITECT
BDD BAGGAGE DIMENSIONING DEVICE
BF BETWEEN FRAME
BHS BAGGAGE HANDLING SYSTEM
BHSC BAGGAGE HANDLING SYSTEM CONTRACTOR
BIP BAGGAGE INSERTION POINT
BIS BAGGAGE INSPECTION STATION
BIT BAGGAGE INSPECTION TABLE
BLDG BUILDING
BRP BAGGAGE REMOVAL POINT
BSD BAGGAGE STATUS DISPLAY
BSO BAGGAGE SERVICE OFFICE
BVS BAGGAGE VIEWING STATION
CBIS CHECKED BAGGAGE INSPECTION SYSTEM
CBRA CHECKED BAGGAGE RESOLUTION AREA
CI CONTROL INTERFACE
CL CENTERLINE
CLR CLEAR
CONC CONCRETE
CONT CONTINUOUS
CONV CONVEYOR
DID DIRECTIONAL INPUT DEVICE
DWG DRAWING
EL ELEVATION
EOR ENGINEER OF RECORD
EQUIP EQUIPMENT
ETD EXPLOSIVE TRACE DETECTION
EXST EXISTING
FD FIRE DOOR
FF FINISHED FLOOR
FIN FINISH
FLA FULL LOAD AMPERAGE
FLR FLOOR
FPM FEET PER MINUTE
FSD FIRE-SECURITY DOOR
GC GENERAL CONTRACTOR
HORIZ HORIZONTAL
HSPD HIGH SPEED PADDLE DIVERTER
HVAC HEATING VENTILATION AND AIRCONDITIONING
ID IDENTIFICATION
INTL INTERNATIONAL
LVL LEVEL
MAINT MAINTENANCE
MAX MAXIMUM
MCP MOTOR CONTROL PANEL
MDS MAINTENANCE DIAGNOSTIC SYSTEM
MEP MECHANICAL ELECTRICAL PLUMBING
MFG MANUFACTURER
MIN MINIMUM
MIS MAINTENANCE INFORMATION SYSTEM
MPP MOTOR POWER PANEL
MTR MOTOR
NATL NATIONAL
NEC NATIONAL ELECTRIC CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS CODE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
O&M OPERATIONS AND MAINTENANCE
OC ON CENTER
OOG OUT OF GAUGE
OPNG OPENING
OPS OPERATIONS
OSHA OCCUPATIONAL SAFETY AND HEALTH
ADMINISTRATION
OSR ON SCREEN RESOLUTION
OTK OPERATIONAL TEST KIT
PAX PASSENGERS
PDP POWER DISTRIBUITION PANEL
PLC PROGRAMABLE LOGIC CONTROLLER
PSI POUNDS PER SQUARE INCH
PVS PRIMARY VIEWING STATION
REF REFERENCE
REQD REQUIRED
ROW RIGHT OF WAY
SD SECURITY DOOR
SIM SIMILAR
SS STAINLESS STEEL
STR STRUCTURE
SVS SECONDARY VIEWING STATION
TEMP TEMPORARY
TOB TOP OF BELT
TSA TRANSPORTATION SECURITY ADMINISTRATION
TSO TRANSPORTATION SECURITY OFFICER
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
SHEET NO DESCRIPTION
B.001 SYMBOLS, LEGENDS, ABBREVIATIONS, AND SHEET LIST
B.002 CONVEYOR MANIFEST
B.003 KEY PLAN
B.101 GENERAL ARRANGEMENT - EXISTING CONDITIONS
B.102 PARTIAL PLAN - DEMOLITION CONDITIONS
B.200 GENERAL ARRANGEMENT - PROPOSED CONDITIONS
B.201 PARTIAL PLAN - PROPOSED CONDITIONS
B.400 PARTIAL PLAN - EDS REMOVAL PATH
B.401 EDS MAINTENANCE ZONE
B.500 TYPICAL CONTROL STATION DETAILS
B.501 E-STOP AND CONTROL STATION PLAN
B.600 SEQUENCING
B.700 TYPICAL DETAILS - LOADING
B.701 TYPICAL DETAILS - SAFETY SIGNAGE
B.702 TYPICAL DETAILS - SAFETY SIGNAGE
SHEET LIST
GENERAL NOTES
CONVEYOR RIGHT OF WAY
IDENTIFICATION NOMLCATURE
ABBREVIATIONSGENERAL SYMBOL LEGENDCONVEYOR LEGEND FOR ELEVATIONSCONVEYOR LEGEND FOR PLAN
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
CONSTRUCTION
9/16/2024
CONVEYOR MANIFEST
CONVEYOR ID Family
CONVEYOR
LENGTH BELT SPEED HP
SS1-01 Diverter - HSPD 3.8 hp
SS1-02 Conveyor - Transport 5' - 3 1/2" 120 ft/min 2.0 hp
SS1-03 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp
SS1-04 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp
SS1-06 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp
SS1-07 Conveyor - Transport 4' - 0" 90 ft/min 2.0 hp
SS1-08 Conveyor - Transport 4' - 0" 120 ft/min 2.0 hp
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.002
CONVEYOR MANIFEST
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
F.D.
8 9 10
M
L
N
5 6 743.81.5 2.4 3.201'2'
B.101
Sim
B.200
Sim
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.003
KEY PLAN
1" = 30'-0"1
KEY PLAN EXISTING
NORTH
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
M
L
N
5 6 743.81.5 2.4 3.201'
B.102
Sim
CL1 SUBSYSTEM
SF1 SUBSYSTEM
OG1 SUBSYSTEM
SS2 SUBSYSTEM
OS1 SUBSYTEM
TC1 SUBSYSTEMTC2 SUBSYSTEMTC3 SUBSYSTEM
REMOVABLE
SUBSYSTEMS
EXISTING
SUBSYSTEMS
MODIFIED
SUBSYSTEMS
LEGEND
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.101
GENERAL
ARRANGEMENT -
EXISTING CONDITIONS
1/16" = 1'-0"1
GENERAL ARRANGEMENT - EXISTING
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
REMOVABLE
SUBSYSTEMS
EXISTING
SUBSYSTEMS
MODIFIED
SUBSYSTEMS
LEGEND
8 9 10
M
L
N
5 6 74
30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"
CL1-01
6' - 0"
4'
EL 2' - 7" AFF
MCP-SF1
MCP-TC1
MCP-SS2
MCP-TC2/TC3
MCP-SS1
MCP-OG1
MCP-TC1
MCP-SS2
MCP-SS1
MCP-TC2/TC3
SF1-07
SS1-02
THRU
SS1-09
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.102
PARTIAL PLAN -
DEMOLITION
CONDITIONS
1/8" = 1'-0"1
EXISTING BHS - GROUND LEVEL DEMOLITION PLAN
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
NEW
SUBSYSTEMS
EXISTING
SUBSYSTEMS
LEGEND
MODIFIED
SUBSYSTEMS
8 9 10
M
L
N
5 6 743.81.5 2.4 3.201'
B.201
Sim
EL 2' - 6" AFF 4'
6' - 0"
MCP-SF1
MCP-TC1
MCP-SS2
MCP-SS1
MCP-TC2/TC3
MCP-OG1
MCP-TC1
MCP-SS2
MCP-SS1
MCP-TC2/TC3
B.401
Sim
CL1 SUBSYSTEM
SF1 SUBSYSTEM
OG1 SUBSYSTEM
SS2 SUBSYSTEM
OS1 SUBSYTEM
TC1 SUBSYSTEM
TC2 SUBSYSTEM
TC3 SUBSYSTEM
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.200
GENERAL
ARRANGEMENT -
PROPOSED
CONDITIONS
1/16" = 1'-0"1
PROPOSED BHS - GROUND LEVEL GENERAL ARRANGEMENTS
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
EXISTING
SUBSYSTEMS
LEGEND
8 9 10
M
L
N
5 6 74
30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"
SS1-02
SS1-03
SS1-04
SS1-06
SS1-07
SS1-08
PROVIDE DID
TO MATCH EXISTING
PROVIDE OVERHEIGHT
PHOTOCELL AND
KNOCKDOWN BAR
BVS, PROVIDED BY
THE TSA CONTRACTOR
FDRS DESK, PROVIDED BY
THE TSA CONTRACTOR
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:3
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.201
PARTIAL PLAN -
PROPOSED
CONDITIONS
1/8" = 1'-0"1
PROPOSED BHS - GROUND LEVEL PARTIAL PLAN
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
REMOVABLE
SUBSYSTEMS
EDS REMOVAL
PATH
TSA LEGEND
TSA ACCESS
PATH
IQT TEST
LOCATIONS
FAILSAFE
LOCATION
8 9 10
M
L
N
5 6 74
8' - 0"
EXISTING TSA
AGENT/ROBOT
PATH
M
SF1-07SS1-02SS1-03SS1-04
SS1-06
SS1-07SS1-08CL1-01
CT80DR+XL
EL 2' - 10" AFFEL 2' - 6" AFFEL 2' - 6" AFFEL 2' - 4" AFF
SS1-EDS 8' - 6" 4' - 9"
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.400
PARTIAL PLAN - EDS
REMOVAL PATH
1/8" = 1'-0"1
CBIS TSA PARTIAL PLAN
1/4" = 1'-0"2
SECTION FOR SS1 LINE
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
2' - 0"3' - 5"2' - 0"
9' - 7"
2'
8'
2'
3'
4'
0"
1'
9'
2' - 8"2' - 8" 8' - 0"
1'
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.401
EDS MAINTENANCE
ZONE
1/4" = 1'-0"1
EDS MAINTENANCE ZONE PLAN
1/4" = 1'-0"2
EDS MAINTENANCE ZONE SECTION
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
INSERT / NORMAL
CS/XXX
RESET/RESTART
G
JAM
A
EMERGENCY STOP
R
EDS ENTRANCE
SELECTOR-SWITCH
CONTROL PANEL LEGEND
ILLUMINATED PUSH BUTTON
ILLUMINATED INDICATOR LIGHT
PUSH BUTTON
MUSHROOM HEAD EMERGENCY STOP
ILLUMINATED PUSH AND PULL
RELEASE WITH LOCKABLE COVER
START ALARM
CONTROL PANEL OPERATOR
ABBREVIATIONS
R - RED, A - AMBER, G - GREEN,
Y - YELLOW, W - WHITE, B -
BLACK, BL - BLUE, GY - GRAY
NOTES:
1. BHS EQUIPMENT CONTRACTOR SHALL PROVIDE ANY ADDITIONAL
EMERGENCY STOP CONTROL STATIONS THAT MAY BE REQUIRED TO MEET
CODE AND TO PROVIDE A SAFE WORKING ENVIRONMENT.
2. AS A MINIMUM, PROVIDE ONE EMERGENCY STOP CONTROL STATION ON
EACH SEGMENT OF CATWALK.
3. ALL CONTROL STATIONS SHALL BE LOCATED ON THE CATWALK SIDE OF THE
CONVEYORS.
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.500
TYPICAL CONTROL
STATION DETAILS
12" = 1'-0"2
BHS CONTROL STATION TYPE 14
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
M
L
N
5 6 74
NEW
CS/TYPE 14
CS/TYPE 14
CS/TYPE 14A
CS/TYPE 10
CS/TYPE 10
30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0" 30' - 0"
EXISTING
EXISTING
EXISTING
EXISTING
ZONE C
ZONE BZONE B
ZONE AZONE A
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.501
E-STOP AND CONTROL
STATION PLAN
1/8" = 1'-0"1
E-STOP AND CONTROL STATION PLAN
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
DEMO
EXISTING
SUBSYSTEMS
NEW
SUBSYSTEMS
REMOVABLE
SUBSYSTEMS
SEQUENCING LEGEND
8 9 10
M
L
N
5 6 74
SF1-08 REMOVE SEGMENT
TO GAIN ACCESS
FOR NEW MACHINE,
AND BRING THE EDS
INTO CBIS STAGING
AREA NEAR SF1-08
8 9 10
M
L
N
5 6 74
RECONNECT SEGMENT
SF1, LINE IN OPERATION AND
EDS STAGED FOR INSTALLATION
SF1-08
8 9 10
M
L
N
5 6 74
SS1-05
SS1-06
REMOVE SS1-05/06 REMOVABLE CONVEYORS
AND LOCATE NORTH ON PAGE, AND AWAY FROM
INSTALLATION PATH OF EDS. AFTER EDS IS IN PLACE,
REMOVE REMOVABLE CONVEYORS OUT OF CBIS AREA.
8 9 10
M
L
N
5 6 74
SS1-06
SS1-04
SS1-03 SAT EDS, AND ISAT.
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.600
SEQUENCING
1/16" = 1'-0"1
SEQUENCE 1
1/16" = 1'-0"2
SEQUENCE 2
1/16" = 1'-0"3
SEQUENCE 3
1/16" = 1'-0"4
SEQUENCE 4
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
FLOOR LOADING:
CT-80DR+ w /CONV. ATTACHED = 4,450lbs FLOOR AREA = (159.2 X 55.1) / 144 = 60.92 sq ft FLOOR LOAD = 4,450 / 60.92 = 73.04 lbs / sq ft
SYSTEM WEIGHT:
CT-80 DR+ XL = 3,700lbs EXTENSIONS = 750lbs TOTAL = 4,450lbs
11' - 8"
2' - 0" 6' - 9"
4'
3'
0' - 6"0' - 10"0' - 10"0' - 4"0' - 6" 3' - 10"0' - 4"0' - 10"
1'
1'
END OF CONVEYOR END OF CONVEYOR
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.700
TYPICAL DETAILS -
LOADING
1/4" = 1'-0"1
CT80DR+XL EDS POINT LOADS
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.701
TYPICAL DETAILS -
SAFETY SIGNAGE
6" = 1'-0"1
BHS OPERATIONAL WARNING SIGN #1
6" = 1'-0"2
BHS OPERATIONAL WARNING SIGN #2
6" = 1'-0"3
BHS OPERATIONAL WARNING SIGN #3
6" = 1'-0"4
BHS OPERATIONAL WARNING SIGN #4
6" = 1'-0"5
BHS OPERATIONAL WARNING SIGN #5
6" = 1'-0"6
BHS OPERATIONAL WARNING SIGN #6
6" = 1'-0"7
BHS OPERATIONAL WARNING SIGN #7
6" = 1'-0"8
BHS OPERATIONAL WARNING SIGN #8
6" = 1'-0"9
BHS OPERATIONAL WARNING SIGN #9
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
ISSUED FOR BID
NOT FOR CONSTRUCTON
/9
/2
:0
:4
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n .r v t
Jacob Coutant
Steve Walker
TLH CBIS Expansion
City Hall 300 S. Adams St.
Tallahassee FL 32301
2024027
9/16/24
Jacob Coutant
B.702
TYPICAL DETAILS -
SAFETY SIGNAGE
6" = 1'-0"1
BHS OPERATIONAL WARNING SIGN #10
6" = 1'-0"2
BHS OPERATIONAL WARNING SIGN #11
6" = 1'-0"3
BHS OPERATIONAL WARNING SIGN #12
6" = 1'-0"4
BHS OPERATIONAL WARNING SIGN #13
6" = 1'-0"5
BHS OPERATIONAL WARNING SIGN #14
6" = 1'-0"6
BHS OPERATIONAL WARNING SIGN #15
6" = 1'-0"7
BHS OPERATIONAL WARNING SIGN #16
6" = 1'-0"8
BHS OPERATIONAL WARNING SIGN #17
6" = 1'-0"9
BHS OPERATIONAL WARNING SIGN #18
NO. DESCRIPTION DATE
1 ISSUED FOR BID NOT FOR
CLNG
J
ELECTRICAL ABBREVIATIONS GENERAL NOTESELECTRICAL SYMBOLS
1. ALL ELECTRICAL WORK MUST COMPLY WITH NATIONAL ELECTRICAL CODE, NFPA 70, THE NATIONAL FIRE CODES, THE AMERICANS WITH DISABILITIES ACT, AND FLORIDA
BUILDING CODES.
2. THOROUGHLY REVIEW THE PROJECT TO ENSURE THAT ALL WORK MUST MEET OR EXCEED THE ABOVE REQUIREMENTS. ANY ALLEGED DISCREPANCIES MUST BE BROUGHT
TO THE ENGINEER'S ATTENTION.
3. OBTAIN COPIES OF ALL RELATED PLANS, SPECIFICATIONS, SHOP DRAWINGS AND ADDENDA TO COORDINATE THE RELATED WORK AND SCHEDULING.
4. THE ELECTRICAL SERVICE TO AND FOR MECHANICAL AND OTHER EQUIPMENT IS BASED ON EQUIPMENT DESIGN DATA. THE ACTUAL VALUES MAY DIFFER DEPENDING UPON THE EQUIPMENT TO BE FURNISHED. ANY MODIFICATION TO THE ELECTRICAL INSTALLATION, BASED UPON ACTUAL EQUIPMENT SELECTION, MUST RESULT IN NO ADDITIONAL
COST TO THE OWNER.
5. THOROUGHLY REVIEW THE MECHANICAL PLANS TO ASSURE THAT ELECTRICAL SERVICE FOR ALL ITEMS AND/OR EQUIPMENT REQUIRING ELECTRICAL SERVICE IS INCLUDED.
ANY ITEM AND/OR EQUIPMENT NOT FURNISH AND INSTALLED WITH ELECTRICAL SERVICE, REQUIRING ELECTRICAL SERVICE, MUST BE BROUGHT TO THE ENGINEER'S
ATTENTION.
6. MECHANICAL, FIRE PROTECTION AND ELECTRICAL EQUIPMENT HAVE BEEN LOCATED AND ARRANGED TO MINIMIZE THE INTERFERENCES OF EQUIPMENT AND STRUCTURE.
THOROUGHLY FAMILIARIZE ONESELF WITH THE WORK TO BE PERFORMED BY OTHER TRADES AND THE PHYSICAL CHARACTERISTICS OF THE STRUCTURE IN ORDER TO SCHEDULE AND INSTALL EQUIPMENT AND TO MINIMIZE POSSIBLE INTERFERENCE. FAILURE TO PROPERLY COMMUNICATE AND SCHEDULE WORK WITH OTHER TRADES THAT RESULTS IN ADDITIONAL WORK AND MATERIAL, MUST BE THE RESPONSIBILITY OF THE CONTRACTOR. THE MODIFICATIONS REQUIRED TO RESOLVE THE CONFLICT MUST BE
DECIDED BY THE ENGINEER.
7. ALL PANELBOARDS MUST BE FURNISH AND INSTALLED WITH A TYPEWRITTEN SCHEDULE SHOWING CIRCUIT NUMBERS AND A COMPLETE DESCRIPTION OF EACH CIRCUIT, INCLUDING OFFICIAL ROOM NUMBER.
8. ALL LIGHT SWITCHES AND DUPLEX RECEPTACLES MUST BE RATED FOR 20 AMPERES AT 120/277 VOLTS AC. WIRING DEVICES MUST BE SPECIFICATION GRADE.
9. ALL ELECTRICAL WIRING DEVICES INDICATED TO BE INSTALLED IN MASONRY WALLS OR FLOORS MUST BE FLUSH MOUNTED, INCLUDING BRANCH CIRCUIT PANELBOARDS, UON.
THE CONDUITS TO ASSOCIATED ELECTRICAL EQUIPMENT MUST BE CONCEALED IN WALLS OR FLOOR.
10. ALL CONDUIT RUNS MUST BE CONCEALED, UON.
11. ALL SPECIAL PURPOSE OUTLETS MUST BE FURNISHED AND INSTALLED TO MATCH EQUIPMENT TO BE SUPPLIED.
12. ALL CONDUITS MUST INCLUDE A SEPARATE GREEN EQUIPMENT GROUNDING CONDUCTOR.
13. ANY EXISTING UTILITIES LOCATED IN THE AREA OF CONSTRUCTION THAT REQUIRE RELOCATION OR TIE-IN MUST BE COORDINATED WITH THE OWNER'S REPRESENTATIVE.
PROVIDE 72 HOUR ADVANCE NOTICE.
14. ALL DISCONNECT SWITCHES MUST BE THE HEAVY DUTY TYPE, FUSED DISCONNECTS MUST HAVE LITTLEFUSE TIME DELAY, CLASS RK5 AND INDICATING CLASS RK5.
15. CHECK THEOWNER FOR EXACT LOCATION AND/OR DIMENSIONS FOR INSTALLATION OF ALL ELECTRICAL ITEMS. ALL QUESTIONABLE LOCATIONS MUST BE APPROVED BY
OWNER'S REPRESENTATIVE PRIOR TO INSTALLATION.
16. ALL EMPTY CONDUITS MUST CONTAIN JET LINE #232 POLYOLEFIN 200 LB. TEST PULL STRING.
17. ALL WORK SHOWN ON THE ELECTRICAL PLANS MUST BE PERFORMED BY THE CONTRACTOR, UON.
18. ALL EXIT FIXTURES MUST BE CONNECTED TO THE BUILDING LIFE SAFETY PANEL AND/OR HAVE INTEGRAL EMERGENCY BATTERY.
19. ALL SURGE PROTECTED OUTLETS MUST BE EQUAL TO HUBBELL #5352.
20. EQUIPMENT INSTALLED WITHIN CONCEALED SPACES MUST HAVE REASONABLE ACCESS PANELS FURNISHED AND INSTALLED NEARBY FOR INSPECTION, TESTING, AND
SERVICE CONSIDERATIONS. LOCATION OF ACCESS PANELS PER APPROVAL OF ARCHITECT.
21. SECURITY WIRING MUST BE IN CONDUIT AND MUST BE A SEPARATE, COMPLETE, AND FULLY FUNCTIONAL SYSTEM.
22. WHERE CABLES OR CONDUITS ARE REQUIRED TO PASS THROUGH A FIRE RATED WALL, FLOOR, OR CEILING THEY MUST BE SEALED WITH FIRESTOP. THE APPROVED FIRESTOP METHOD MUST COMPLY WITH ARTICLES 300.21 OF NEC AND MUST BE UL LISTED UNDER "THROUGH-PENETRATION FIRESTOP SYSTEM (XHEZ)" IN UL FIRE RESISTANCE DIRECTORY. ALL UNSPRINKLERED FACILITIES MUST BE CONSIDERED TO HAVE INTERIOR CORRIDORS WITH FIRE RATED WALLS, UON. ANY PENETRATION THROUGH THESE WALLS AND OTHER FIRE RATED WALLS MUST BE SEALED WITH FIRESTOP. FURNISH AND INSTALL MINIMUM 1" EMT THROUGH WALL PENETRATIONS.
23. SPARE CONDUITS, WIREWAYS, AND CABLE TRAYS MUST BE SUPPORTED FROM BUILDING STRUCTURE AND NOT FROM OTHER PIPES, DUCTS, OR EXISTING RACKS, UON.
24. EXTERIOR BURIED CONDUIT RUNS MUST BE MINIMUM 24" BELOW FINISHED GRADE. FURNISH AND INSTALL CAUTION TAPE 12" BELOW GRADE. FURNISH AND INSTALL (1) SPARE WITH EACH UNDERGROUND RUN. DUCT BANKS MUST BE CONCRETE ENCASED WITH LOCATION PLAQUES PLACED EVERY 50' AND BEFORE AND AFTER EVERY TURN, UON.
SUBMIT SHOP DRAWINGS BEFORE DIGGING.
25. FURNISH AND INSTALL GROUND STRAP ACROSS ALL CABLE TRAY JOINTS. GROUND CABLE TRAY TO SERVICE GROUND WITH #1/0 AWG BARE COPPER.
26. RACEWAYS INSTALLED IN OUTDOOR LOCATIONS MUST BE HOT DIPPED GALVANIZED, AT MINIMUM, FOR CORROSION RESISTANCE. FOR HIGHLY CORROSIVE ENVIRONMENTS, SUCH AS COASTAL AREAS, ALUMINUM, STAINLESS STEEL, OR PVC COATED RACEWAYS MUST BE REQUIRED.
27. POWER CHANGE EXPENSES RESULTING FROM EQUIPMENT SUBSTITUTIONS THAT DIFFER FROM ITEMS CALLED FOR IN DRAWINGS OR SPECIFICATIONS MUST BE BORNE BY THE CONTRACTOR OR THEIR SUB. THESE MUST INCLUDE CHANGES IN VOLTAGE OR FULL LOAD AMPS RESULTING IN LARGER FEEDERS AND OR CIRCUIT BREAKERS.
28. ALL EXISTING ELECTRICAL DEVICES THAT ARE NOT SHOWN ARE EXISTING TO REMAIN, UON.
29. COORDINATE WITH DIVISION 23 FOR DISCONNECT REQUIREMENTS ON MECHANICAL EQUIPMENT. REFER TO MECHANICAL EQUIPMENT SCHEDULES FOR INFORMATION.
FURNISH AND INSTALL DISCONNECTS FOR THOSE DEVICES THAT DO NOT COME WITH FACTORY INSTALLED DISCONNECTS.
30. BEFORE INITIATING ANY UNDERGROUND WORK, LOCATE ALL UTILITIES.
MOUNTING HEIGHTS
WALL LUMINAIRES SEE LUMINAIRE SCHEDULE OR KEYNOTE
EXTERIOR SPEAKERS 10'-0" TO CENTER OF BOX, UON
FIRE ALARM HORNS/SPEAKERS HIGH BAY
FIRE ALARM HORNS/SPEAKERS
80" TO BOTTOM OF BOX
80" TO BOTTOM OF BOX
FIRE ALARM STROBES HIGH BAY 80" TO CENTER OF DEVICE
FIRE ALARM STROBES 80" TO CENTER OF DEVICE
FIRE ALARM PULL STATIONS HIGH BAY 48" TO CENTER OF DEVICE
FIRE ALARM PULL STATIONS 48" TO CENTER OF DEVICE
TV OUTLETS & TV RECEPTACLE 72" TO BOTTOM OF BOX, UON
RECEPTACLES IN INDUSTRIAL AREAS 48" AFF TO CENTER LINE, UON
RECEPTACLES 18" AFF TO CENTER LINE, UON
SWITCHES 48" AFF TO CENTER OF BOX, UON
GROUND BAR 18" AFF TO BOTTOM OF BAR OR BOX, UON
EMERGENCY PHONE 54" AFF TO CENTER LINE, UON
CARD READER 48" AFF TO CENTER LINE, UON
EPO SWITCHES 54" AFF TO CENTER LINE, UON
CEILING MOUNTED DEVICES EQUAL HEIGHT TO ROOM LUMINAIRES
4" TO BOTTOM WITH BACKSPLASH
ABOVE COUNTER DEVICES 6" TO BOTTOM WITHOUT BACKSPLASH
18" TO C.L RECEPTACLE, DUPLEX, NEMA 5-20R, WALL MOUNTED
18" TO C.L RECEPTACLE, DOUBLE DUPLEX, NEMA 5-20R, WALL MOUNTED
RECEPTACLE, DUPLEX, NEMA 5-20R, MOUNTED ON STUB UP (OR CEILING)
PANELBOARD, 120/208 VOLT
JUNCTION BOX, 4" SQ. X 1 1/2" DEEP (MOUNTED), WALL MOUNTED
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
/6
/2
:3
:0
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n D e s ig n E
R
.r v t
WM
KN
TLH CBIS EXPANSION DESIGN
3330 CAPITAL CIRCLE SW
TALLAHASSEE, FL 32310
20012001007
09/16/2024
AA
E001
ELECTRICAL GENERAL
NOTES, SYMBOLS,
AND ABBREVIATIONS
A AMPERES
AC ABOVE COUNTER
AF AMP FUSE
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AL ALUMINUM
AMP AMPERE
AP ACCESS PANEL
ATS AUTOMATIC TRANSFER SWITCH
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BFG BELOW FINISHED GRADE
BHS BAGGAGE HANDLING SYSTEM
BID BAGGAGE INFORMATION DISPLAY
C CONDUIT
CAT6 CATEGORY 6 ETHERNET CABLE
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CH CHILLER
CKT CIRCUIT
COMM COMMUNICATION
CONC CONCRETE
CR CARD READER
CRU COMPUTER ROOM UNIT
CT COOLING TOWER
CU COPPER
DC DIRECT CURRENT
DISC DISCONNECT
DWG DRAWING
E EXISTING
E EAST
EF EXHAUST FAN
EL EMERGENCY LIGHT
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
EOR ENGINEER OF RECORD
EQ EQUAL
ER EXISTING TO BE REMOVED
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EX EXISTING TO REMAIN
EXR EXISTING TO BE RELOCATED
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FID FLIGHT INFORMATION DISPLAY
FLA FULL LOAD AMPS
FLR FLOOR
FO FIBER OPTIC
FPB FAN POWERED TERMINAL BOX
FS FLOW SWITCH
G GROUND
GC GENERAL CONTRACTOR
GF GROUND FAULT
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GID GATE INFORMATION DISPLAY
GPU GROUND POWER UNIT
GRC GALVANIZED RIGID CONDUIT
HH HANDHOLE
HP HORSE POWER
HVAC HEATING, VENTILATING & AIR CONDITIONING
IC INTERCOM
IR INFRARED
J JUNCTION
JB JUNCTION BOX
KAIC (THOUSAND) AMPERE INTERRUPTING CAPACITY
Kcmil THOUSANDS OF CIRCULAR MILS
KVA KILOVOLT-AMPERES
KW KILOWATT
LED LIGHT EMITTING DIODE
LSI LONG TIME, SHORT TIME, INSTANTANEOUS
LSIG LONG TIME, SHORT TIME, INSTANTANEOUS, GROUND
FAULT
LTG LIGHTING
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MTD MOUNTED
MUFID MULTI-USER FLIGHT INFORMATION DISPLAY
N NEUTRAL
N NORTH
N/A NOT APPLICABLE
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOC
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NO NUMBER
NTS NOT TO SCALE
O.C. ON CENTER
OAE OR APPROVED EQUAL
OH OVERHEAD
OS OCCUPANCY SENSOR
PBB PASSENGER BOARDING BRIDGE
PNL PANELBOARD
PNL PANEL
POE POWER OVER ETHERNET
PVC POLYVINYLCHLORIDE
RECP RECEPTACLE
REF REFRIGERATOR
RGS RIGID GALVANIZED STEEL
RM ROOM
RMC RIGID METAL CONDUIT
RTU ROOF TOP UNIT
S SOUTH
SCCR SHORT CIRCUIT CURRENT RATING
SEC SECURITY
SF SUPPLY FAN
SIM SIMILAR
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE SINGLE THROW
SQ SQUARE
SS STAINLESS STEEL
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
T TRANSFORMER
TEL TELEPHONE
TGB TELECOMMUNICATIONS GROUNDING BUS BAR
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UT UTILITY
V VOLTS
VAV VARIABLE AIR VOLUME (HVAC)
VFD VARIABLE FREQUENCY DRIVE
W WATTS
W WEST
WP WEATHERPROOF
Y WYE (CONNECTED)
Z ZONE
NO. DESCRIPTION DATE
ISSUED FOR BID
NOT FOR CONSTRUCTION
ANIMAL
SCREEN RM.
A104
SCREENING
ROOM
A103
BAGGAGE HANDLING
ROOM
A100
BAG SCREENING
ROOM
A101
EDS PARTS
STORAGE
A102
BHS
STORAGE
A105
LOBBY
A107
ELEVATOR
NO.1
ELEVATOR
EQUIP.
CLNG
CLNG
CLNG
CLNG
CLNGCLNG CLNG
EX PANEL BHS3
EX
EX
BHS3-16
EXEXEX
EX
EX
EX
EX
EX
EX EX EX EX
EX
EX
EX
EX
EXEXEXEX
EX
EX
EX
EX
EX
EXEX EX
EX
EX EX
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
/6
/2
:3
:0
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n D e s ig n E
R
.r v t
WM
KN
TLH CBIS EXPANSION DESIGN
3330 CAPITAL CIRCLE SW
TALLAHASSEE, FL 32310
20012001007
09/16/2024
AA
E101
ELECTRICAL FIRST
FLOOR PLAN
NO. DESCRIPTION DATE
0 2' 4'1'
3/16" = 1'-0"
FIRST FLOOR CBIS
KEY NOTES
1. EXISTING CEILING MOUNTED RECEPTACLE OULETS FOR EDS POWER.
2. EXISTING FLOOR TO CEILING STRUCTURE MOUNTED UNISTRUT. LOCATED ADJACENT
TO NEW CT80XL (EDS MACHINE).
3. NEW UNISTRUT MOUNTED QUAD RECEPTACLE. MATCH EXISITNG INSTALLATION,
REFER TO PHOTO E101A.
PHOTO E101A
COLUMN REC / CHP-1
PANELBOARD: BHS3
LOCATION: A100
MOUNTING: SURFACE
FULLY RATED AIC: 10,000
MAX VOLTAGE: 208
ENCL: NEMA 1
SYSTEM VOLTS:
MAIN C.B.:
BUS SIZE:
208 Y/120 V, 3 PH, 4W
100 AMP
100 AMP
NO
29 20
20 4
NOTE RECEP.
VA
OTHER P AMP NO
CIRCUITDESCRIPTIONVOLT AMP
PH A PH B PH C
DESCRIPTIONVACIRCUIT
AMP P NOTE RECEP. OTHER
CT80-DRXL MACHINE (VIA UPS)
CT80 - DRXL A/C UNIT
REC. - A106
REC - A106
SPARE
SPARE
CT80 UPS
SPARE
IT - 1 CBIS CABINET
SIEMENS TRANSFORMER
PLC
AIR COMPRESSOR
CABINET - IT - 8
KNEE WALL PLUGS
KNEE WALL PLUGS
KNEE WALL PLUGS
REC. - RM 100, 103, 104, EWC - RM A107
EF - 2, EF - 3
SPARE
RECEPTACLE (NEW)
EF #14 (1/10 HP)
ELEV. EQUIP. RM REC
SPARE
SPARE
W/H-1 RM A202
SPARE
SPARE
NOTES:
1. ALL EQUIPMENT EXISTING UON.
2. ALL NEW BRANCH CIRCUITS SHALL BE 2#12, 1#12 GND - 3/4"C UON.
201 42
20 1
20 1
20 1
20 1
20 1
20 1
SPARE
SPARE
SPARE
SPARE
WORKSTATION TWIST LOCK #2
WORKSTATION TWIST LOCK #1 ELEV PIT LTS/SUMP PUMP
SPARE
SPARE
SPARE
SPARE
SPARE
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
/6
/2
:3
:0
P M
A u to d e s k D o c s /2
T L
H C
B
IS
E x p a n s io n D e s ig n /2
T L H
C
B
IS
E x p a n s io n D e s ig n E
R
.r v t
WM
KN
TLH CBIS EXPANSION DESIGN
3330 CAPITAL CIRCLE SW
TALLAHASSEE, FL 32310
20012001007
09/16/2024
AA
EP602
ELECTRICAL POWER
SCHEDULES
F. ALL CONDUCTOR SIZES ARE BASED ON COPPER.
E. CONDUCTORS FEEDING K-RATED TRANSFORMERS REQUIRE 200% NEUTRAL CONDUCTORS WITH CONDUIT SIZED PER NEC.
D. CONTRACTOR SHALL INCREASE FEEDER SIZES WHEN THEY ARE LONGER THEN 165' FOR 208 V AND 185' FOR 480 V.
SECONDARY GROUND CONDUCTORS ARE ACCEPTABLE AND SHALL BE SIZED PER NEC TABLE 250.102.
C. SECONDARY GROUND (SUPPLY SIDE BONDING JUMPER) CONDUCTOR SIZE IS PER NEC 250.102(C)(1). SECONDARY GROUND CONDUCTOR SIZE ASSUMES A SINGLE CONDUCTOR FOR SINGLE OR PARALLEL SETS, MULTIPLE
B. PRIMARY GROUND (EQUIPMENT GROUND) CONDUCTOR SIZE IS PER NEC TABLE 250.122.
A. GROUNDING ELECTRODE CONDUCTOR SIZE IS PER NEC TABLE 250.66.
GENERAL NOTES:
750 480 3 1600 4 3 600 KCMIL #4/0 EACH SET IN 3 1/2" #1/0 208 3 3000 8 4 500 KCMIL 500 KCMIL EACH SET IN 3 1/2"
500 480 3 1000 4 3 250 KCMIL #2/0 EACH SET IN 2 1/2" #2 208 3 2000 5 4 600 KCMIL 400 KCMIL EACH SET IN 4"
300 480 3 600 2 3 300 KCMIL #1 EACH SET IN 2 1/2" #2 208 3 1200 4 4 350 KCMIL #4/0 EACH SET IN 3"
225 480 3 400 1 3 500 KCMIL #3 3" #1/0 208 3 800 2 4 600 KCMIL #3/0 EACH SET IN 4"
150 480 3 300 1 3 300 KCMIL #4 2 1/2" #2 208 3 600 2 4 350 KCMIL #2/0 EACH SET IN 3"
112.5 480 3 200 1 3 #3/0 #6 2" #4 208 3 400 2 4 #3/0 #2 EACH SET IN 2 1/2"
75 480 3 150 1 3 #1/0 #6 2" #6 208 3 225 1 4 #4/0 #2 2 1/2"
45 480 3 90 1 3 #3 #8 1 1/4" #8 208 3 150 1 4 #1/0 #6 2"
30 480 3 60 1 3 #6 #10 1" #8 208 3 100 1 4 #1 #6 2"
15 480 3 30 1 3 #10 #10 3/4" #8 208 3 60 1 4 #4 #8 1 1/4"
SETS QUANTITY GUAGE SETS QUANTITY GUAGE
VOLTS PHASE
BREAKER TRIP
(AMPS)
CONDUCTOR GROUND
GUAGE
CONDUIT SIZE VOLTS PHASE
BREAKER TRIP
(AMPS)
CONDUCTOR GROUND
GUAGE
CONDUIT SIZE
XFMR SIZE
(KVA)
PRIMARY GROUNDING
ELECTRODE
CONDUCTOR
SECONDARY
TRANSFORMER SCHEDULE
4. CONDUIT SIZING IS BASED ON CONDUCTORS WITH THHW INSULATION.
3. ADJUST CONDUCTOR & GEC SIZE FOR LONG RUNS AND TEMPERATURE ABOVE DESIGN AMBIENT TEMPERATURE.
2. MAXIMUM 2% VOLTAGE DROP FOR FEEDERS; 3% VOLTAGE DROP FOR BRANCH CIRCUITS.
1. ALL FEEDER TYPES SCHEDULED MAY NOT APPLY TO THIS PROJECT.
GENERAL NOTES:
U REFER TO "ELECTRICAL UTILITY MATRIX" FOR ADDITIONAL INFORMATION.
T REFER TO "TRANSFORMER SCHEDULE" FOR CONDUCTOR SIZE.
G REFER TO "GROUNDING RISER DETAIL" FOR CONDUCTOR SIZE.
Y 4
Δ 3
400 KCMIL
SE
500 KCMIL
#3/0
EACH SET IN 4"
Y 4
Δ 3
350 KCMIL
SE
600 KCMIL
#3/0
EACH SET IN 4"
Y 4
Δ 3
250 KCMIL
SE
600 KCMIL
#3/0
EACH SET IN 4"
Y 4
Δ 3 #4/0
SE
600 KCMIL
#3/0
EACH SET IN 4"
Y 4
Δ 31200
SE
350 KCMIL #3/0 EACH SET IN 3"
Y 4
Δ 31000
SE
250 KCMIL #2/0 EACH SET IN 2 1/2"
Y 4
Δ 3 #1/0
SE
500 KCMIL
#2/0
EACH SET IN 3 1/2"
Y 4
Δ 3 #1
SE
300 KCMIL
#1/0
EACH SET IN 3"
Y 4
Δ
#4/0 #2 EACH SET IN 2 1/2"
Y 4
Δ 3 #3
SE
500 KCMIL
#1/0
3 1/2"
Y 4
Δ
350 KCMIL #3 3"
Y 4
Δ
300 KCMIL #4 3"
Y 4 3"
Δ
250 KCMIL #4
2 1/2"
Y 4
Δ 3 #4
SE
#4/0
#2
2 1/2"
Y 4 2 1/2"
Δ 3 #6
SE
#3/0
#4 2"
Y 4
Δ
#2/0 #6 2"
Y 4
Δ 3 #6
SE
#1/0
#6
2"
Y 4 2"
Δ 3 #6
SE
#1
#6 1 1/2"
Y 4 1 1/2"
Δ
#2 #6
1 1/4"
Y 4
Δ 3 #8
SE
#2
#1/0
1 1/4"
Y 4
Δ
#3 #8 1 1/4"
Y 4
Δ
#4 #8 1 1/4"
Y 4
Δ
#6 #10 1"
Y 4
Δ
#6 #10 1"
Y 4 1"
Δ
#8 #10
3/4"
Y 4
Δ
#10 #10 3/4"
SETS QUANTITY GAUGE MIN. EGC (Δ/Y)
BREAKER TRIP
(AMPS)
TYPE
CONDUCTOR MIN. GEC (SE)
MINIMUM CONDUIT SIZE
FEEDER SCHEDULE
1. SEE DRAWINGS FOR WIRE SIZING.
KEYNOTE:
LESS CURRENT-CARRYING CONDUCTORS IN RACEWAY.
INSULATION, 100% POWER FACTOR, BALANCED LOAD, NEGLIGIBLE REACTANCE, AND 6 OR
4. BASIS OF VOLTAGE DROP CALCULATIONS IS 3% DROP, 80% CIRCUIT LOAD, THHN/THWN
3. PROVIDE CONDUIT SIZE PER NEC.
PROTECTION.
2. DISTANCE IS WIRE LENGTH TO FIRST OUTLET/DEVICE/EQUIPMENT FROM OVERCURRENT
1. SEE DRAWINGS FOR WIRE SIZING WHEN DISTANCE EXCEEDS VALUES SHOWN.
GENERAL NOTES:
2 225' 520'
KEYNOTE 1
180' 415'
2 250' 578'
KEYNOTE 1
200' 462'
3 225' 520'
KEYNOTE 1
182' 421'
3 257' 594'
KEYNOTE 1
208' 479'
4 121' 280' 243' 559'
6 76' 176' 152' 353'
4 145' 335' 291' 670'
6 92' 212' 184' 424'
4 161' 372' 323' 745'
6 102' 235' 204' 471'
6 115' 265' 230' 530'
8 72' 166' 144' 333'
6 131' 303' 263' 605'
8 82' 190' 165' 381'
8 96' 222' 192' 444'
10 62' 144' 125' 289'
10 94' 216' 187' 443'
12 56' 130' 113' 260'
15 12 75' 173' 150' 346'
120 V 277 V 208 V 480 V
1Ø 3ØBREAKER TRIP
(AMPS)
COPPER WIRE
(75°C)
MAXIMUM DISTANCE (FEET)
BRANCH CIRCUIT SCHEDULE
NO. DESCRIPTION DATE
TELECOMMUNICATIONS ABBREVIATIONS TELECOMMUNICATIONS SYMBOLS
1. REFER TO CONSTRUCTION MANUAL OR SPECIFICATIONS FOR MATERIALS TO BE INCORPORATED.
2. CONTRACTOR MUST FIELD VERIFY ALL NEW DEVICE AND EQUIPMENT LOCATIONS PRIOR TO THE START OF INSTALLATION. ANY CONFLICTS MUST BE IMMEDIATELY
BROUGHT TO THE ATTENTION OF THE OWNER.
3. MINIMUM CONDUIT SIZE MUST BE 1". ALL CONDUITS MUST BE EMT. EXCEPTIONS INCLUDE:
A. GRS FOR EXTERIOR AREAS.
B. RS FOR AREAS ACCESSIBLE TO THE PUBLIC.
C. PVC FOR BURIED OR CAST-IN-PLACE CONDUITS.
D. FLEXIBLE CONDUIT FOR CONCEALED DROPS TO DEVICES AND WHERE APPROVED BY THE OWNER.
4. CONDUIT MUST NOT EXCEED 40% FILL FACTOR. INSTALLATION OF CONDUIT AND WIRING MUST BE IN COMPLIANCE WITH NATIONAL ELECTRICAL CODE (NEC). ALL WIRING MUST BE HOMERUN, UNLESS OTHERWISE NOTED. ANY SPLICES MUST BE APPROVED BY THE DESIGNER.
5. CONTRACTOR MUST COORDINATE THE ROUTING AND LOCATION OF NEW COMMUNICATIONS CONDUITS WITH THE ELECTRICAL CONTRACTOR AND OTHER TRADES.
6. CONTRACTOR MUST BE RESPONSIBLE FOR ENSURING THAT LINE VOLTAGE (120V AND ABOVE) POWER CONDUCTORS ARE NOT ROUTED WITHIN 12 INCHES OF
COMMUNICATIONS WIRING.
7. ALL CONDUCTORS MUST BE COLOR CODED AND TAGGED AS DESCRIBED IN THE WRITTEN SPECIFICATIONS AND APPROVED BY THE OWNER.
8. COORDINATE WORK WITH OTHER TRADES AND CONFIRM FINAL MOUNTING LOCATION FOR NEW AND RELOCATED EQUIPMENT WITH THE OWNER PRIOR TO INSTALLATION.
9. CONTRACTOR MUST FOLLOW MANUFACTURER'S RECOMMENDED INSTALLATION PROCEDURES FOR ALL EQUIPMENT. UNLESS OTHERWISE NOTED, ALL MATERIALS MUST
BE NEW AND UNUSED.
10. ALL RACEWAY, CONDUIT AND JUNCTION BOXES MUST BE NEW AND INSTALLED WITH PULL STRING. REUSE OF EXISTING CONDUITS MUST BE APPROVED BY THE OWNER.
WHEN INSTALLING CABLING IN EXISTING CABLE TRAY, CONTRACTOR MUST TAKE CARE NOT TO DISTURB OR DAMAGE EXISTING CABLING.
11. PROVIDE CONDUIT SLEEVES FOR ALL PENETRATIONS, WHETHER SHOWN ON DRAWING OR NOT. PROVIDE INSULATING BUSHINGS ON BOTH ENDS OF ALL.
12. NON-SECURITY DATA/COMM OUTLETS PROVIDE 1"C FROM OUTLET TO THE ACCESSIBLE CEILING SPACE. CABLE ROUTING WILL BE VIA CABLE TRAY SYSTEM TO INDICATED COMMUNICATIONS ROOM OR CABINET. PROVIDE RACEWAY SYSTEM OVER THE INACCESSIBLE CEILING SPACE AS INDICATED ON PLANS. TELE/DATA CONDUITS ARE TO BE LONG RADIUS TYPE AND SHALL CONTAIN PULL WIRES. PROVIDE PLATES FOR ALL OUTLETS. SECURITY DEVICE DATA/COMM OUTLETS PROVIDE
COMDUIT ENTIRE RUN.
GENERAL NOTES
(4) 8P8C IDC (CAT 6) JACKS WITH CAT6 TO EXISTING CBIS DATA CABINET, SEE NOTE 12
(8) 8P8C IDC (CAT 6) JACKS WITH CAT6 TO EXISTING CBIS DATA CABINET, SEE NOTE 12
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
/9
/2
:2
:1
P M
A u to d e s k D o c s /2
T
L H
C B
IS
E x p a n s io n D e s ig n /2
T L
H
C B
IS
E x p a n s io n D e s ig n T
R
.r v t
ISSUED FOR BID
NOT FOR CONSTRUCTION
WM
KN
TLH CBIS EXPANSION DESIGN
3300 CAPITAL CIR SW,
TALLAHASSE, FL 32310
20012001007
09/16/2024
AA
T001
BUILDING ID
TELECOMMUNICATIONS
GENERAL NOTES,
SYMBOLS AND
ABBREVIATIONS
AC ABOVE COUNTER
ACS ACCESS CONTROL SYSTEM
ACT ACOUSTIC CEILING TILE
AFF ABOVE FINISHED FLOOR
AHJ AUTHORITY HAVING JURISDICTION
AL ALUMINUM
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BHS BAGGAGE HANDLING SYSTEM
C CONDUIT
CAT6 CATEGORY 6 ETHERNET CABLE
CATV CABLE TELEVISION
CBIS CHECKED BAG INSPECTION SYSTEM
CBP CUSTOMS AND BORDER PROTECTION
COMM COMMUNICATION
CR CARD READER
DC DIRECT CURRENT
DIV DIVISION
DWG DRAWING
E EXISTING
EDS EXPLOSIVES DETECTION SYSTEM
EL ELEVATION
ELEC ELECTRIC/ELECTRICAL
EM EMERGENCY
EOR ENGINEER OF RECORD
EQ EQUAL
EX EXISTING TO REMAIN
FID FLIGHT INFORMATION DISPLAY
FLR FLOOR
FO FIBER OPTIC
G GROUND
GC GENERAL CONTRACTOR
GRS GALVANIZED RIGID STEEL
HDMI HIGH DEFINITION MULTIMEDIA INTERFACE
IC INTERCOM
IDC INSULATION DISPLACEMENT CONNECTION
IDF INTERMEDIATE DISTRIBUTION FRAME
IP INTERNET PROTOCOL
ISP INTERNET SERVICE PROVIDER
J JUNCTION
JB JUNCTION BOX
KAIC (THOUSAND) AMPERE INTERRUPTING CAPACITY
Kcmil THOUSANDS OF CIRCULAR MILS
KO KNOCK OUT
LAN LOCAL AREA NETWORK
LCD LIQUID CRYSTAL DISPLAY
MAX MAXIMUM
MDF MAIN DISTRIBUTION FRAME
MIC MICROPHONE
MM MULTI-MODE
N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NTS NOT TO SCALE
OAE OR APPROVED EQUAL
OC ON CENTER
OH OVERHEAD
PNL PANEL
POE POWER OVER ETHERNET
POS POINT OF SALE
PTZ PAN-TILT-ZOOM
PVC POLYVINYL CHLORIDE
QTY QUANTITY
REX REQUEST TO EXIT
RF RADIO FREQUENCY
RM ROOM
RS RIGID STEEL
SEC SECURITY
SIDA SECURITY IDENTIFICATION DISPLAY AREA
SIM SIMILAR
SM SINGLE MODE
SPD SURGE PROTECTIVE DEVICE
SYM SYMMETRICAL
TBD TO BE DETERMINED
TEL TELEPHONE
TSA TRANSPORTATION SECURITY ADMINISTRATION
TV TELEVISION
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
UTP UNSHIELDED TWISTED PAIR
VMS VIDEO MANAGEMENT SYSTEM
WAP WIRELESS ACCESS POINT
NO. DESCRIPTION DATE
ANIMAL
SCREEN RM.
A104
SCREENING
ROOM
A103
BAGGAGE HANDLING
ROOM
A100
BAG SCREENING
ROOM
A101
EDS PARTS
STORAGE
A102
BHS
STORAGE
A105
LOBBY
A107 exhaust fan pipes up to structure and turn into ceiling
F.E.C.
ELEVATOR
NO.1
ELEVATOR
EQUIP.
CBIS CBIS CBIS CBIS CBIS
CBIS
CBISCBIS
CBIS
EX EX
EX EX EX EX EX
EX
EX
CBIS
EX EX
EX EX EX
EX
EX EX
KEY NOTES
1. PROVIDE NEW UPS WITH NETWORK MONITORING AND NEW NETWORK
SWITCH. UPS SHALL BE APC SMART-UPS (ON-LINE 1kVA, TOWER, 120V, 6x
5-15R NEMA OUTLETS, SMARTSLOT, EXTENDED RUNTIME, WITHOUT RAIL KIT)
OR APPROVED EQUAL. NETWORK MONITORING CARD SHALL BE APC PART
NUMBER AP9641 OR APPROVED EQUAL. NETWORK SWITCH SHALL BE CISCO
CATALYST IE3100 (18 PORT AND 2 GE DUAL-MEDIA UPLINK PORTS) OR
APPROVED EQUAL. REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE
AIRPORT.
2. PROVIDE NEW UPS WITH NETWORK MONITORING. UPS SHALL BE APC SMART-
UPS (ON-LINE 3kVA, TOWER, 120v, 8x 5-20R+1x L5-30R NEMA OUTLETS, SMARTSLOT, EXTENDED RUNTIME, WITHOUT RAIL KIT) OR APPROVED EQUAL.
NETWORK MONITORING CARD SHALL BE APC PART NUMBER AP9641 OR
APPROVED EQUAL. REMOVED EQUIPMENT SHALL BE TURNED OVER TO THE
AIRPORT.
3. REPLACE EXISTING WORKSTATION COMPUTER EQUIPMENT INCLUSIVE OF PC
AND MONITORS. NEW WORKSTATION EQUIPMENT TO MEET REQUIREMENTS
OF SPECIFICATION SECTION 347739.
Copyright © 2019. This drawing is an instrument of service and property of RS&H, Inc. Any use or reproduction without the expressed written consent of this corporation is prohibited. All rights reserved.
904-256-2500 Fax 904-256-2503
A
B
C
D
54321
10748 Deerwood Park Blvd. South Jacksonville, Florida 32256-0597 www.rsandh.com
FL Cert. Nos. AAC001886 * IB26000956
*5620 * LCC000210 * GB238
REVISIONS
DATE ISSUED:
REVIEWED BY:
DRAWN BY:
DESIGNED BY:
PROJECT NUMBER:
© 2021 RS&H, INC.
PROJECT STATUS:
SHEET ID:
SHEET TITLE:
PROJECT ADDRESS:
PROJECT TITLE:
/6
/2
:3
:1
P M
A u to d e s k D o c s /2
T
L H
C B
IS
E x p a n s io n D e s ig n /2
T L
H
C B
IS
E x p a n s io n D e s ig n T
R
.r v t
ISSUED FOR BID
NOT FOR CONSTRUCTION
WM
KN
TLH CBIS EXPANSION DESIGN
3300 CAPITAL CIR SW,
TALLAHASSE, FL 32310
20012001007
09/16/2024
AM
T100
TELECOMMUNICATIONS
FIRST FLOOR PLAN
NO. DESCRIPTION DATE
0 2' 4'1'
3/16" = 1'-0"
FIRST FLOOR CBIS
NEW UPS LOCATION
EXISTING PLC CABINET
BAG SCREENING
ROOM
A101
EDS PARTS
STORAGE
A102
CBIS CBIS CBIS CBIS CBIS
CBIS
CBIS
EX EX EX EX EX
EX
EX
CBIS
EX EX EX
EX EX EX EX
EX
EX EX
EX
3 4
KEY NOTES
1. EXISTING FLOOR TO CEILING STRUCTURE MOUNTED UNISTRUT. LOCATED
ADJACENT TO…