084-954.lca

259 KB Posted

Attached to
Spun Concrete Transmission Poles for The New World Substation 230kV Transmission Line
Solicitation number
1412223278
Issued by
Duval County, Florida

About this file

This Load Case Analysis (LCA) file from Burns & McDonnell contains structural engineering calculations for a 250B utility transmission pole designed using PLS-POLE Version 21.01 software. The analysis evaluates the pole's performance under multiple loading conditions including wind, transverse, and longitudinal forces in accordance with NESC (National Electrical Safety Code) standards. The file presents 24 distinct load cases across various scenarios including NESC 250B, 250C, and 250D standards, each with different strength factors and wind pressure parameters. Load cases are identified by transmission line configuration designations (ITRN1AH through ITRN3BK, ISWAH through ISWBK, and TRNJ1 through TRNJ3), with calculations showing vertical, transverse, and longitudinal force vectors on Falcon ACSR 2000# conductors and 3-number-6 Alumoweld guy wire systems. The pole structure, specified at 185-186 feet in length with various azimuth angles ranging from -67.3 to 60.2 degrees, experiences conductor tensions varying from approximately 800 to 4,600 pounds across different load cases. Analysis includes deflection scenarios with wind and creep, zero tension conditions, first crack assessments, and stringing deadend load configurations both ahead and behind the pole structure.

The LCA file demonstrates comprehensive structural validation across all design load cases with detailed output for each configuration's vertical, transverse, and longitudinal responses. Wind load parameters range from zero wind conditions in creep and deadend scenarios to maximum wind pressures of 60 mph in NESC 250C conditions, with specialized analysis including directional wind calculations (wind towards 225 degrees). Concrete pole strength factors, material properties, and deflection criteria are systematically evaluated, with the file indicating compliance verification through multiple load case iterations. Conductor tensions, pole deflection angles, and azimuth positions are recorded with precision to support engineering design decisions. The analysis supports the Jacksonville Electric Authority's New World 230kV Transmission Line project, where the pole specifications must satisfy ultimate strength design methodology and withstand field loads as specified in the associated technical requirements for spun concrete transmission poles.

Text of this file

TYPE='LCA FILE' VERSION='17' UNITS='US' SOURCE='PLS-POLE Version 21.01' USER='Burns & McDonnell' FILENAME='' 70 ; num_load_cases 24 ; num_load_points 1 1 1 1 0.1 33 0 0.000000 1 0 1 1 0 0 1 0 0 1.600000 0 0 1 80.549900 32808.400000 3 NESC 250B Initial RS NA+,I NA+ 0 ; include insulator wind/weight

1.000000 0.650000 0.900000 0.000000 0.000000 0.650000 0.650000 0.650000 0.000000 1.000000 1.000000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.5000000000 ; Structure weight load factor

22.5000000000 0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 30.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

477.4499100000 1808.2851600000 -2840.8790900000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=2.90 uv=3.07 lbs/ft ten=3263 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

302.4079600000 2036.0954200000 -2707.4236800000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3272 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

132.1907400000 2234.1670200000 -2522.9178100000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=2.90 uv=3.07 lbs/ft ten=3242 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

317.7615400000 2006.6088000000 2736.5709800000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3282 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

317.4616400000 2007.3724500000 2738.3740800000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3284 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

317.1604700000 2007.1783300000 2738.5018600000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3284 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

55.5035100000 564.1696000000 -620.8268600000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.65 uv=0.27 lbs/ft ten=822 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

52.0358700000 395.5174200000 -734.7069500000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.65 uv=0.27 lbs/ft ten=822 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

36.5476500000 475.5644000000 688.8612000000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.65 uv=0.27 lbs/ft ten=823 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250B Initial RS NA-,I NA- 0 ; include insulator wind/weight

1.000000 0.650000 0.900000 0.000000 0.000000 0.650000 0.650000 0.650000 0.000000 1.000000 1.000000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.5000000000 ; Structure weight load factor -22.5000000000 -0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 30.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

477.4499100000 961.3630700000 -3069.0713400000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=2.90 uv=3.07 lbs/ft ten=3263 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

302.4079600000 1212.2883000000 -2972.6703200000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3272 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

132.1907400000 1431.7762300000 -2826.1097600000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=2.90 uv=3.07 lbs/ft ten=3242 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

317.7615400000 1253.1568100000 2961.6523000000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3282 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

317.4616400000 1254.4250300000 2963.1756400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3284 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

317.1604700000 1254.7347800000 2963.0240500000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3284 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

55.5035100000 421.5039600000 -694.0407200000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.65 uv=0.27 lbs/ft ten=822 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

52.0358700000 237.9164500000 -781.7414000000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.65 uv=0.27 lbs/ft ten=822 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

36.5476500000 341.6477100000 739.7253700000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.65 uv=0.27 lbs/ft ten=823 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250B Load FE NA+,U NA+ 0 ; include insulator wind/weight

1.000000 0.650000 0.900000 0.000000 0.000000 0.650000 0.650000 0.650000 0.000000 1.000000 1.000000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.5000000000 ; Structure weight load factor

22.5000000000 0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 30.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

444.0128200000 1766.4013500000 -2825.8264100000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=2.90 uv=3.07 lbs/ft ten=3232 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

270.5532200000 1993.8152500000 -2696.7417200000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3241 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

101.4905800000 2194.3437200000 -2520.0241300000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=2.90 uv=3.07 lbs/ft ten=3217 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

286.8503500000 1970.3766200000 2732.1397300000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3261 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

286.5502400000 1970.9824900000 2733.6674300000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3262 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

286.2501300000 1971.5364100000 2735.1038000000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3264 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

54.8265800000 551.7148800000 -605.3162700000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.65 uv=0.27 lbs/ft ten=802 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.4437600000 387.2806500000 -716.7197900000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.65 uv=0.27 lbs/ft ten=802 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

36.2562000000 462.8591400000 667.9980800000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.65 uv=0.27 lbs/ft ten=798 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250B Load FE NA-,U NA- 0 ; include insulator wind/weight

1.000000 0.650000 0.900000 0.000000 0.000000 0.650000 0.650000 0.650000 0.000000 1.000000 1.000000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.5000000000 ; Structure weight load factor -22.5000000000 -0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 30.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

444.0713900000 981.4354600000 -3037.1744200000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=2.90 uv=3.07 lbs/ft ten=3243 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

270.1747100000 1229.0661100000 -2938.3524900000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3250 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

101.0581300000 1446.5472000000 -2792.0420700000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=2.90 uv=3.07 lbs/ft ten=3222 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

286.2780700000 1268.1680800000 2928.1459100000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3261 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

285.9781900000 1269.2779900000 2929.3937400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3262 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

285.6782900000 1270.3358200000 2930.5502700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.90 uv=3.07 lbs/ft ten=3264 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

54.8273200000 410.2215000000 -677.8813700000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.65 uv=0.27 lbs/ft ten=802 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.4438800000 230.9588700000 -763.3480800000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.65 uv=0.27 lbs/ft ten=802 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

36.2530100000 330.1096400000 718.1979600000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.65 uv=0.27 lbs/ft ten=798 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250B Load FE Max (wind towards 225),U Max 0 ; include insulator wind/weight

1.000000 0.650000 0.900000 0.000000 0.000000 0.650000 0.650000 0.650000 0.000000 1.000000 1.000000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.5000000000 ; Structure weight load factor

21.7100000000 -5.9150000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 30.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

430.5571800000 1544.9259800000 -2602.6046900000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=1.68 uv=3.07 lbs/ft ten=2938 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

277.0073600000 1742.1057900000 -2506.7906200000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=1.45 uv=3.07 lbs/ft ten=2955 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

126.6243400000 1920.4051900000 -2373.9685500000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=1.21 uv=3.07 lbs/ft ten=2946 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

286.6508700000 1937.0336200000 2710.1294700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.71 uv=3.07 lbs/ft ten=3228 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

286.3508100000 1937.6676400000 2711.6742000000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.71 uv=3.07 lbs/ft ten=3230 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

286.0507500000 1938.2514600000 2713.1306600000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=2.71 uv=3.07 lbs/ft ten=3231 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

49.4639300000 388.9250000000 -451.8751400000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.25 uv=0.27 lbs/ft ten=582 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

48.5988400000 309.9382300000 -592.5785100000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.41 uv=0.27 lbs/ft ten=658 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

36.2270900000 448.1217800000 650.0287900000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.61 uv=0.27 lbs/ft ten=776 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250C Initial RS NA+,I NA+ 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor

44.2800000000 0.0000000000 54 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 60.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

427.6254400000 2753.8135400000 -3779.1429200000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=5.39 uv=2.25 lbs/ft ten=4408 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

186.5505500000 3006.9853900000 -3542.3356900000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=5.30 uv=2.25 lbs/ft ten=4361 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

-43.1413000000 3209.3297800000 -3241.0059400000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=5.21 uv=2.25 lbs/ft ten=4260 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

234.9390100000 2970.6465600000 3572.1496100000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.51 uv=2.25 lbs/ft ten=4362 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

234.6202400000 2891.3184700000 3485.2226700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.33 uv=2.25 lbs/ft ten=4254 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

234.2862400000 2800.3896400000 3384.5009400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.13 uv=2.25 lbs/ft ten=4128 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

57.6651600000 918.2622300000 -954.6755300000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=1.26 uv=0.20 lbs/ft ten=1281 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.3381600000 657.2907900000 -1136.1162500000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=1.26 uv=0.20 lbs/ft ten=1280 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

27.4441300000 746.8639900000 1006.2028400000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=1.29 uv=0.20 lbs/ft ten=1217 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250C Initial RS NA-,I NA- 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor -44.2800000000 -0.0000000000 54 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 60.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

427.6254400000 987.2924100000 -4203.7303200000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=5.39 uv=2.25 lbs/ft ten=4408 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

186.5505500000 1322.5167000000 -4028.1919800000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=5.30 uv=2.25 lbs/ft ten=4361 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

-43.1413000000 1607.1123200000 -3786.7301300000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=5.21 uv=2.25 lbs/ft ten=4260 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

234.9390100000 1361.5348100000 4000.7067700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.51 uv=2.25 lbs/ft ten=4362 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

234.6202400000 1333.2762900000 3899.2753700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.33 uv=2.25 lbs/ft ten=4254 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

234.2862400000 1299.8276200000 3782.3039800000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.13 uv=2.25 lbs/ft ten=4128 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

57.6651600000 619.0160600000 -1096.0210200000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=1.26 uv=0.20 lbs/ft ten=1281 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.3381600000 329.7241500000 -1226.8094700000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=1.26 uv=0.20 lbs/ft ten=1280 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

27.4441300000 461.4964400000 1106.1587600000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=1.29 uv=0.20 lbs/ft ten=1217 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250C Load FE NA+,U NA+ 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor

44.2800000000 0.0000000000 54 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 60.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

409.9790300000 2764.8493700000 -3949.0226800000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=5.42 uv=2.25 lbs/ft ten=4565 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

160.3685400000 3024.5140000000 -3694.8450200000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=5.33 uv=2.25 lbs/ft ten=4501 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

-77.2674500000 3240.6446800000 -3390.5368300000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=5.23 uv=2.25 lbs/ft ten=4400 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

212.9029100000 3137.5342900000 3968.9499600000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.55 uv=2.25 lbs/ft ten=4790 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

212.5657000000 3052.1836100000 3868.2549300000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.37 uv=2.25 lbs/ft ten=4666 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

212.2180400000 2955.1929100000 3753.3502600000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.16 uv=2.25 lbs/ft ten=4526 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

57.4463000000 917.5070700000 -956.0401800000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=1.26 uv=0.20 lbs/ft ten=1282 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.1217700000 656.3625700000 -1137.6339900000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=1.26 uv=0.20 lbs/ft ten=1281 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

27.2434600000 749.5249800000 1013.4520000000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=1.29 uv=0.20 lbs/ft ten=1224 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250C Load FE NA-,U NA- 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor -44.2800000000 -0.0000000000 54 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 60.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

410.7226800000 1129.8998600000 -4358.5660100000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=5.42 uv=2.25 lbs/ft ten=4607 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

159.3243500000 1466.8393600000 -4155.6795800000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=5.33 uv=2.25 lbs/ft ten=4542 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

-79.6129200000 1757.4485000000 -3899.3769000000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=5.23 uv=2.25 lbs/ft ten=4437 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

211.8562500000 1621.9902100000 4344.5025900000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.55 uv=2.25 lbs/ft ten=4790 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

211.5333000000 1584.8285800000 4230.9314400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.37 uv=2.25 lbs/ft ten=4666 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

211.1890300000 1542.1165000000 4101.5869700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.16 uv=2.25 lbs/ft ten=4526 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

57.4522500000 620.9090400000 -1096.1426600000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=1.26 uv=0.20 lbs/ft ten=1283 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

51.1246100000 331.6219300000 -1227.5813800000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=1.26 uv=0.20 lbs/ft ten=1282 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

27.2375500000 466.4286600000 1112.1138200000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=1.29 uv=0.20 lbs/ft ten=1224 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250C Load FE Max (wind towards 225),U Max 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor

42.7200000000 -11.6400000000 54 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 1 8.000000 60.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

347.3889000000 1955.4607700000 -2691.4375900000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=3.15 uv=2.25 lbs/ft ten=3090 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

192.7732700000 2017.8067300000 -2397.1453700000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=2.66 uv=2.25 lbs/ft ten=2882 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

60.9029600000 2059.1008400000 -2126.6469800000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=2.19 uv=2.25 lbs/ft ten=2698 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

212.4434300000 3037.1489500000 3869.3461100000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.20 uv=2.25 lbs/ft ten=4661 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

212.1187300000 2954.8882700000 3771.5832900000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=5.03 uv=2.25 lbs/ft ten=4541 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

211.7797900000 2861.9283000000 3660.9354000000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=4.84 uv=2.25 lbs/ft ten=4406 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

41.2647300000 452.9520500000 -459.7732600000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.48 uv=0.20 lbs/ft ten=608 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

43.3593200000 461.8636600000 -790.5202400000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.79 uv=0.20 lbs/ft ten=887 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

27.1692900000 714.1871400000 967.6885100000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=1.21 uv=0.20 lbs/ft ten=1168 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250D Initial RS NA+,I NA+ 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor

2.5300000000 0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 0 0.000000 15.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

343.2015600000 803.6849700000 -1600.4961800000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=0.33 uv=2.25 lbs/ft ten=1782 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

224.9343100000 933.7405600000 -1536.8435100000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1788 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

110.1666900000 1045.7175400000 -1442.9725400000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=0.33 uv=2.25 lbs/ft ten=1770 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

232.8608200000 948.6259400000 1571.5485400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1825 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

232.6418500000 949.7851500000 1573.5775400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1827 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

232.4209400000 949.7883900000 1573.5855500000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1827 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

37.6287400000 196.6647800000 -247.5321800000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.07 uv=0.20 lbs/ft ten=315 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

35.7669100000 130.0824700000 -287.5650200000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.07 uv=0.20 lbs/ft ten=315 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

26.7003400000 176.6821200000 292.8431100000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.07 uv=0.20 lbs/ft ten=341 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250D Initial RS NA-,I NA- 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor -2.5300000000 -0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 0 0.000000 15.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

343.2015600000 708.4570300000 -1626.1533800000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=0.33 uv=2.25 lbs/ft ten=1782 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

224.9343100000 841.1203300000 -1566.6619800000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1788 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

110.1666900000 955.5135100000 -1477.0508400000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=0.33 uv=2.25 lbs/ft ten=1770 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

232.8608200000 863.9122200000 1596.8532400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1825 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

232.6418500000 865.1282000000 1598.8507700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1827 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

232.4209400000 865.1880700000 1598.8273700000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1827 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

37.6287400000 180.6243600000 -255.7635100000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.07 uv=0.20 lbs/ft ten=315 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

35.7669100000 112.3632200000 -292.8529000000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.07 uv=0.20 lbs/ft ten=315 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

26.7003400000 161.6262300000 298.5611900000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.07 uv=0.20 lbs/ft ten=341 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250D Load FE NA+,U NA+ 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor

2.5300000000 0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 0 0.000000 15.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

317.8712800000 785.2921100000 -1569.9390000000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=0.33 uv=2.25 lbs/ft ten=1746 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

201.8833200000 913.2331800000 -1508.3808600000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1753 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

89.1188000000 1024.6520100000 -1418.6889100000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=0.33 uv=2.25 lbs/ft ten=1738 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

210.0202900000 915.0595700000 1519.5174400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1763 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul weight

ITRN2BK

209.8003800000 915.6999900000 1520.6416500000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1765 lbs vtl=24.0,0.8,1.4 ft 12:1' ; V T and L loads including insul weight

ITRN2BK

0.0000000000 0.0000000000 0.0000000000 '12:1' ; V T and L loads including insul weight

ITRN3BK

209.5802300000 916.2012300000 1521.5223400000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1766 lbs vtl=35.0,0.8,1.4 ft 13:1' ; V T and L loads including insul weight

ITRN3BK

0.0000000000 0.0000000000 0.0000000000 '13:1' ; V T and L loads including insul weight

ISWAH

0.0000000000 0.0000000000 0.0000000000 '21:1' ; V T and L loads including insul weight

ISWAH

37.0024500000 187.3903600000 -235.2848800000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-53.1 deg uh=0.07 uv=0.20 lbs/ft ten=299 lbs vtl=0.8,0.7,-1.2 ft 21:1' ; V T and L loads including insul weight

ISWAH2

0.0000000000 0.0000000000 0.0000000000 '22:1' ; V T and L loads including insul weight

ISWAH2

35.2315200000 124.1002800000 -273.4394500000 '3no_6_alumoweld_500#@250BIRS.wir 186 ft azi=-67.3 deg uh=0.07 uv=0.20 lbs/ft ten=299 lbs vtl=1.8,0.7,-1.2 ft 22:1' ; V T and L loads including insul weight

ISWBK

26.4791900000 165.5733200000 273.5727200000 '3no_6_alumoweld_500#@250BIRS.wir 156 ft azi=60.2 deg uh=0.07 uv=0.20 lbs/ft ten=318 lbs vtl=1.0,0.7,1.2 ft 23:1' ; V T and L loads including insul weight

ISWBK

0.0000000000 0.0000000000 0.0000000000 '23:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ1

0.0000000000 0.0000000000 0.0000000000 '31:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ2

0.0000000000 0.0000000000 0.0000000000 '32:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight

TRNJ3

0.0000000000 0.0000000000 0.0000000000 '33:1' ; V T and L loads including insul weight NESC 250D Load FE NA-,U NA- 0 ; include insulator wind/weight

1.000000 0.750000 0.900000 0.000000 0.000000 0.650000 0.750000 0.750000 0.000000 1.000000 0.800000 0.000000; Strength factors: steel, wood, ult. conc, first conc, zero conc, guy, arm, brace, insulator, foundation

1.1000000000 ; Structure weight load factor -2.5300000000 -0.0000000000 0 ; Factored structure transverse and longitudinal wind pressures

1.000000 0.000000 0.000000 0 0.000000 15.000000

ITRN1AH

0.0000000000 0.0000000000 0.0000000000 '1:1' ; V T and L loads including insul weight

ITRN1AH

317.8781800000 697.4677300000 -1593.9974900000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-64.9 deg uh=0.33 uv=2.25 lbs/ft ten=1748 lbs vtl=12.7,0.7,-1.3 ft 1:1' ; V T and L loads including insul weight

ITRN2AH

0.0000000000 0.0000000000 0.0000000000 '2:1' ; V T and L loads including insul weight

ITRN2AH

201.8087400000 827.6077100000 -1535.6210000000 'falcon_acsr_2000#@250BIRS.wir 184 ft azi=-60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1754 lbs vtl=23.8,0.8,-1.4 ft 2:1' ; V T and L loads including insul weight

ITRN3AH

0.0000000000 0.0000000000 0.0000000000 '3:1' ; V T and L loads including insul weight

ITRN3AH

89.0530400000 940.7721300000 -1449.0716000000 'falcon_acsr_2000#@250BIRS.wir 185 ft azi=-55.6 deg uh=0.33 uv=2.25 lbs/ft ten=1739 lbs vtl=34.8,0.8,-1.4 ft 3:1' ; V T and L loads including insul weight

ITRN1BK

209.9017100000 836.1054000000 1541.5669600000 'falcon_acsr_2000#@250BIRS.wir 156 ft azi=60.2 deg uh=0.33 uv=2.25 lbs/ft ten=1763 lbs vtl=13.0,0.7,1.3 ft 11:1' ; V T and L loads including insul weight

ITRN1BK

0.0000000000 0.0000000000 0.0000000000 '11:1' ; V T and L loads including insul…

This is the start of the file's text. The full file is on GovTribe.

Other files

File Type Posted
066A-954.lca —
065-960.bak BAK file
1412223278 Addendum 4.pdf PDF
066-960.bak BAK file
050 - 960.lca —
048 - 960.bak BAK file
084 - 954.bak BAK file
C1261.lca —
083-954.lca —
068-954.lca —
083 - 954.bak BAK file
065-960.lca —
066A-954.bak BAK file
079 - 954.bak BAK file
C1261.bak BAK file
1412223278 Addendum 3.pdf PDF
067-954.lca —
068-954.bak BAK file
066B-960.lca —
079-954.lca —
050 - 960.bak BAK file
067-954.bak BAK file
1412223278 Addendum 2.pdf PDF
048 - 960.lca —
1412223278 Appendix B - Bid Forms.pdf PDF
1412223278 Solicitation.pdf PDF
Project Specific Tech Specs for the New World Substation 230kV (Spun Concrete Poles) 07.30.26.pdf PDF
GENERAL TECH SPECS SPUN CONCRETE (rev 1.3).pdf PDF
1412223278 Addendum 1.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

File details come from the government source that posted it. Updated .