About this file

This technical specification document outlines requirements for firestopping and smoke stopping products and installation services for repairing elevators in multiple buildings at a Veterans Affairs medical center in Biloxi, Mississippi. The specification requires firestopping systems tested and rated by FM, UL, or WH to maintain fire barrier integrity for wall, floor, and roof penetrations. Smoke stopping seals are also required in smoke partitions. Approved products must be asbestos-free and have low flame spread and smoke development. Installation must follow approved manufacturer instructions and details.

The related federal contract opportunity is a solicitation to provide all labor, materials, equipment, and supervision for Project 520-22-170 to repair elevators at the Biloxi VA medical center. The Department of Veterans Affairs Veterans Health Administration VISN 16 is the contracting agency. The response due date and award date are not specified.

View the file

Other files

File Type Posted
Bldg 19 - Floor Plan.pdf PDF
Bldg 30 - Crawl Space Piping Area A.pdf PDF
Bldg 17 - Basement Piping.pdf PDF
010000 GENERAL REQUIREMENTS.docx DOCX document
Bldg 2 - Crawlspace Piping.pdf PDF
Bldg 14 - 1st Floor Piping.pdf PDF
096800 CARPET and FLOORING.doc DOC document
260533 - Raceway and Boxes for Electrical Systems.doc DOC document
024100 Demolition.doc DOC document
36C25622R0089 EXHIBIT B R1.docx DOCX document
Bldg 3 - Basement Piping.pdf PDF
262726 WIRING DEVICES.doc DOC document
Bldg 2 - Floor Plan.pdf PDF
013323 Samples and Shop Drawings.doc DOC document
Bldg 25 - Sump Pump-Pit Detail.pdf PDF
Bldg 2 - Crawlspace Piping Original.pdf PDF
VHA Supplemental Contract Requirements for Combatting COVID-19.docx DOCX document
Bldg 53 - Floor Plan.pdf PDF
260511 - Requirements for Electrical Installations.doc DOC document
Bldg 14 - Sump Pump-Pit Detail.pdf PDF
Bldg 15 - Floor Plan.pdf PDF
Bldg 5 - Floor Plan.pdf PDF
36C25622R0089 Solicitation.pdf PDF
Bldg 28 - 1st Floor Piping.pdf PDF
P09 Final SOW 520-22-170 Repair Elevators Multiple Bldgs.docx DOCX document
Bldg 15 - Foundation Piping.pdf PDF
Bldg 1 - Basement Piping Area C.pdf PDF
Bldg 1 - Basement Piping Original.pdf PDF
36C25622R0089 EXHIBIT A R1.docx DOCX document
Bldg 30 - Sump Pump-Pit Detail.pdf PDF
Bldg 53 - Basement Piping.pdf PDF
Bldg 3 and 30 - Floor Plan.pdf PDF
Bldg 17 - Floor Plan.pdf PDF
Bldg 1 - Floor Plan.pdf PDF
220511 COMMON PLUMBING WORK RESULTS.doc DOC document
013526 Safety Requirements.doc DOC document
Bldg 30 - Crawl Space Piping Composite.pdf PDF
Bldg 30 - 1st Floor Piping Area A.pdf PDF
Bldg 30 - 1st Floor Piping Area B.pdf PDF
Bldg 1 - Basement Piping Area A-B.pdf PDF
260521 - Low Voltage Conductors and Cables.doc DOC document
Bldg 1 - 1st Floor Piping Area A-B.pdf PDF
Bldg 19 - 1st Floor Piping Original.pdf PDF
079200 JOINT SEALANTS.doc DOC document
Bldg 25 - 1st Floor Piping Area A.pdf PDF
Bldg 28 - Sump Pump-Pit Detail.pdf PDF
Bldg 5 - 1st Floor Piping.pdf PDF
ICRA - Contracting Only.pdf PDF
265100 INTERIOR LIGHTING.doc DOC document
Bldg 30 - 1st Floor Piping Composite.pdf PDF
Show 40 more

Latest 50 of 79 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

520-22-170

SECTION 07 84 00

FIRESTOPPING

PART 1 GENERAL

1.1 DESCRIPTION

A.

Closures of openings in walls, floors, and roof decks against penetration of flame, heat, and smoke or gases in fire resistant rated construction.

B.

Closure of openings in walls against penetration of gases or smoke in smoke partitions.

1.2 RELATED WORK

N/A

1.3 SUBMITTALS

A.

Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B.

Manufacturers literature, data, and installation instructions for types of firestopping and smoke stopping used.

C.

List of FM, UL, or WH classification number of systems installed.

D.

Certified laboratory test reports for ASTM E814 tests for systems not listed by FM, UL, or WH proposed for use.

1.4 DELIVERY AND STORAGE

A.

Deliver materials in their original unopened containers with manufacturer’s name and product identification.

B.

Store in a location providing protection from damage and exposure to the elements.

1.5 warranty

Firestopping work subject to the terms of the Article “Warranty of Construction”, FAR clause 52.246-21, except extend the warranty period to five years.

1.6 QUALITY ASSURANCE

FM, UL, or WH or other approved laboratory tested products will be acceptable.

1.7 APPLICABLE PUBLICATIONS

A.

Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.

B.

American Society for Testing and Materials (ASTM):

E84-10 Surface Burning Characteristics of Building Materials

E814-11 Fire Tests of Through-Penetration Fire Stops

C.

Factory Mutual Engineering and Research Corporation (FM):

Annual Issue Approval Guide Building Materials

D.

Underwriters Laboratories, Inc. (UL):

Annual Issue Building Materials Directory

Annual Issue Fire Resistance Directory

1479-10 Fire Tests of Through-Penetration Firestops

E.

Warnock Hersey (WH):

Annual Issue Certification Listings

PART 2 - PRODUCTS

2.1 FIRESTOP SYSTEMS

A.

Use either factory built (Firestop Devices) or field erected (through-Penetration Firestop Systems) to form a specific building system maintaining required integrity of the fire barrier and stop the passage of gases or smoke.

B.

Through-penetration firestop systems and firestop devices tested in accordance with ASTM E814 or UL 1479 using the "F" or "T" rating to maintain the same rating and integrity as the fire barrier being sealed. "T" ratings are not required for penetrations smaller than or equal to 100 mm (4 in) nominal pipe or 0.01 m2 (16 sq. in.) in overall cross sectional area.

C.

Products requiring heat activation to seal an opening by its intumescence shall exhibit a demonstrated ability to function as designed to maintain the fire barrier.

D.

Firestop sealants used for firestopping or smoke sealing shall have following properties:

1.

Contain no flammable or toxic solvents.

2.

Have no dangerous or flammable out gassing during the drying or curing of products.

3.

Water-resistant after drying or curing and unaffected by high humidity, condensation or transient water exposure.

4.

When used in exposed areas, shall be capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.

E.

Firestopping system or devices used for penetrations by glass pipe, plastic pipe or conduits, unenclosed cables, or other non-metallic materials shall have following properties:

1.

Classified for use with the particular type of penetrating material used.

2.

Penetrations containing loose electrical cables, computer data cables, and communications cables protected using firestopping systems that allow unrestricted cable changes without damage to the seal.

3.

Intumescent products which would expand to seal the opening and act as fire, smoke, toxic fumes, and, water sealant.

F.

Maximum flame spread of 25 and smoke development of 50 when tested in accordance with ASTM E84.

G.

FM, UL, or WH rated or tested by an approved laboratory in accordance with ASTM E814.

H.

Materials to be asbestos free.

2.2 SMOKE STOPPING IN SMOKE PARTITIONS

A.

Use silicone sealant in smoke partitions as specified in Section 07 92 00, JOINT SEALANTS.

B.

Use mineral fiber filler and bond breaker behind sealant.

C.

Sealants shall have a maximum flame spread of 25 and smoke developed of 50 when tested in accordance with E84.

D.

When used in exposed areas capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.

PART 3 - EXECUTION

3.1 EXAMINATION

Submit product data and installation instructions, as required by article, submittals, after an on site examination of areas to receive firestopping.

3.2 PREPARATION

A.

Remove dirt, grease, oil, loose materials, or other substances that prevent adherence and bonding or application of the firestopping or smoke stopping materials.

B.

Remove insulation on insulated pipe for a distance of 150 mm (six inches) on either side of the fire rated assembly prior to applying the firestopping materials unless the firestopping materials are tested and approved for use on insulated pipes.

3.3 INSTALLATION

A.

Do not begin work until the specified material data and installation instructions of the proposed firestopping systems have been submitted and approved.

B.

Install firestopping systems with smoke stopping in accordance with FM, UL, WH, or other approved system details and installation instructions.

C.

Install smoke stopping seals in smoke partitions.

3.4 CLEAN-UP AND ACCEPTANCE OF WORK

A.

As work on each floor is completed, remove materials, litter, and debris.

B.

Do not move materials and equipment to the next-scheduled work area until completed work is inspected and accepted by the Resident Engineer.

C.

Clean up spills of liquid type materials.

- - - E N D - - -