This document contains a specification section for roof accessories on a parking garage project and the corresponding federal contract solicitation. The specification section requires roof hatches, steel ladders, and other roof accessories compliant with referenced industry standards. Materials must meet specifications for aluminum, insulation, wood nailers, and coatings. The contract solicitation is for construction of a new parking structure to accommodate approximately 435 vehicles on the VA campus in Wilkes-Barre, Pennsylvania. The project budget is between $10-20 million and has a NAICS code of 236220. This is a set-aside for verified service-disabled veteran-owned small businesses utilizing tiered evaluation down to the large business level. The contractor must comply with all applicable wage and hour laws. Pricing shall be in whole dollars only and the solicitation may be canceled before award if in the government's best interest. The Department of Veterans Affairs Veterans Health Administration VISN 4 is the issuing agency.
View the file
Other files for this federal contract opportunity
Show all 50
Y1LZ--693-222 | Parking Structure Solicitation Amendment 2 has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Parking Garage Project Number 693-222 Department of Veterans Affairs Wilkes-Barre, Pennsylvania
077200 - 1
SECTION 077200 ROOF ACCESSORIES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Roof hatches.
B. Related Sections include the following:
1. Division 6 Section "Rough Carpentry" for wood cants, and wood nailers.
2. Division 7 Section "Sheet Metal Flashing and Trim" for shop- and field-fabricated metal flashing and counterflashing, fasciae, and miscellaneous sheet metal trim and accessories.
3. Division 7 Section "EPDM Single-Ply Membrane System."
1.3 SUBMITTALS
A. Product Data: For each type of roof accessory indicated. Include construction details, materials, dimensions of individual components and profiles, and finishes.
B. Shop Drawings: Show fabrication and installation details. Indicate dimensions, weights, loadings, required clearances, method of field assembly, and components.
Include plans, elevations, sections, details, and attachments to other work.
C. Coordination Drawings: Roof plans, drawn to scale, and coordinating penetrations and roof-mounted items. Show the following:
1. Size and location of roof accessories specified in this Section.
2. Method of attaching roof accessories to roof or building structure.
D. Samples: For each type of exposed finish.
1.4 QUALITY ASSURANCE
A. Standards: Comply with the following:
1. SMACNA's "Architectural Sheet Metal Manual" details for fabrication of units, including flanges and cap flashing to coordinate with type of roofing indicated.
077200 - 2
2. NRCA’s “Roofing and Waterproofing Manual” details for installing units.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated into the Work include, but are not limited to, the following:
1. Bilco Company
2. Babcock-Davis Hatchways, Inc.
3. J. L. Industries, Inc.
4. Metallic Products Corporation.
5. Milcor, Inc.
6. Wasco Products, Inc.
2.2 MATERIALS, GENERAL
A. Aluminum Sheet: ASTM B 209 for alclad alloy 3003H14 or alloy and temper required to suit forming operations, with mill finish, unless otherwise indicated.
B. Insulation: Manufacturer’s standard rigid or semirigid glass-fiber board.
C. Wood Nailers: Softwood lumber, pressure treated with waterborne preservatives for aboveground use, complying with AWPA C2; not less than 1-1/2 inches thick.
D. Fasteners: Same metal as metals being fastened, or nonmagnetic stainless steel or other noncorrosive metal as recommended by manufacturer. Match finish of exposed fasteners with finish of material being fastened.
1. Where removing exterior exposed fasteners affords access to building, provide nonremovable fastener heads.
E. Gaskets: Manufacturer's standard tubular or fingered design of neoprene, EPDM, or PVC; or flat design of foam rubber, sponge neoprene, or cork.
F. Bituminous Coating: SSPC-Paint 12, solvent-type bituminous mastic, nominally free of sulfur and containing no asbestos fibers, compounded for 15-mil dry film thickness per coating.
G. Mastic Sealant: Polyisobutylene; nonhardening, nonskinning, nondrying, nonmigratiing sealant.
H. Elastomeric Sealant: Generic type recommended by unit manufacturer that is compatible with joint surfaces; ASTM C 920, Type S, Grade NS, Class 25, and Uses NT, G, A, and, as applicable to joint substrates indicated, O.
077200 - 3
I. Roofing Cement: ASTM D 4586, nonasbestos, fibrated asphalt cement designed for trowel application or other adhesive compatible with roofing system.
2.3 ROOF HATCHES
A. General: Fabricate units to withstand 40-lbf/sq. ft. external and 20-lbf/sq. ft. internal loading pressure. Frame with minimum 9-inch high, integral-curb, double-wall construction with 1-1/2-inch insulation, formed cants and cap flashing (roofing counterflashing), with welded or sealed mechanical corner joints. Provide double-wall cover (lid) construction with 1-inch thick insulation core. Provide gasketing and equip with corrosion-resistant or hot-dip galvanized hardware including pintle hinges, hold-open devices, interior padlock hasps, and both interior and exterior latch handles.
1. Type: Single-leaf personnel access, 36 by 36 inches.
B. Ladder Safety Post: Manufacturer’s standard ladder safety post. Post to lock in place on full extension. Provide release mechanism to return post to closed position.
C. Material: Aluminum, sheets and extrusions.
1. Finish: Mill aluminum.
2.4 STEEL LADDERS
A. General:
1. Comply with ANSI A14.3 unless otherwise indicated.
2. For elevator pit ladders, comply with ASME A17.1.
B. Steel Ladders:
1. Space siderails 16 inches apart unless otherwise indicated.
2. Siderails: Continuous, 1/2-by-3-inch steel flat bars, with eased edges.
3. Rungs: 1-inch diameter steel bars.
4. Fit rungs in centerline of siderails; plug-weld and grind smooth on outer rail faces.
5. Provide nonslip surfaces on top of each rung, either by coating rung with aluminum-oxide granules set in epoxy-resin adhesive or by using a type of manufactured rung filled with aluminum-oxide grout.
6. Support each ladder at top and bottom and not more than 60 inches o.c. with welded or bolted steel brackets.
7. Galvanize exterior ladders, including brackets and fasteners.
8. Prime exterior ladders, including brackets and fasteners, with zinc-rich primer.
077200 - 4
PART 3 - EXECUTION
3.1 INSTALLATION
A. General: Comply with manufacturer’s written instructions. Coordinate installation of roof accessories with installation of roof deck, roof insulation, flashing, roofing membranes, penetrations, equipment, and other construction involving roof accessories to ensure that each element of the Work performs properly and that combined elements are waterproof and weathertight. Anchor roof accessories securely to supporting structural substrates so they are capable of withstanding lateral and thermal stresses, and inward and outward loading pressures.
B. Install roof accessory items according to construction details of NRCA’s “Roofing and Waterproofing Manual,” unless otherwise indicated.
C. Separation: Separate metal from incompatible metal or corrosive substrates, including wood, by coating concealed surfaces, at locations of contact, with bituminous coating or providing other permanent separation.
D. Flange Seals: Unless otherwise indicated, set flanges of accessory units in a thick bed of roofing cement to form a seal.
E. Cap Flashing: Where required as component of accessory, install cap flashing to provide waterproof overlap with roofing or roof flashing (as counterflashing). Seal overlap with thick bead of mastic sealant.
F. Operational Units: Test-operate units with operable components. Clean and lubricate joints and hardware. Adjust for proper operation.
3.2 CLEANING AND PROTECTION
A. Clean exposed surfaces according to manufacturer's written instructions. Touch up damaged metal coatings.
END OF SECTION 077200