This electrical blueprint package is part of Bid Package #1 for the New ECAT Facility Project in Pensacola, Florida, prepared by KEDbluestone architects in coordination with Escambia County and QSC Services, LLC. The document provides electrical site plans and specifications for underground utility infrastructure installation to support the construction of an Administration Building, Bus Wash Station, Fuel Depot, and Maintenance Building along Clarinda Lane. The electrical scope includes the installation of thirteen conduit systems (labeled C1 through C13) ranging from 1 inch to 5 inches in diameter, serving multiple buildings and systems including utility primary connections, emergency power, telecommunications, spare capacity, and specialized systems such as vacuum and generator connections. The project requires four types of handholes (HH-1 through HH-4) with varying dimensions, from 13" x 24" x 18" deep to 48" x 48" x 36" deep stackable assemblies. All installations must comply with the National Electrical Code (NEC), International Building Code (IBC), ADA Accessibility Guidelines, and International Energy Conservation Code (IECC), with final approval from the Authority Having Jurisdiction.

The electrical contractor must coordinate all site conduit locations and installations with future Bid Package #2 documents and verify final conduit origins, terminations, and connection points prior to installation. Utility conduit routing must be coordinated with Florida Power and Light prior to installation, and a utility conduit routing plan must be submitted to the engineer for review. The temporary generator connection, including cabinet, transfer switch, fuel pump emergency off switch, and Code Blue Safety Light, will be located at a designated site and installed under Bid Package #2. All materials must be new, free of defects, and listed by a nationally recognized testing laboratory unless otherwise noted. Conduit runs shall not include bends greater than 90 degrees, and emergency system conduits must remain completely independent of all other conduits and raceways. Branch circuit wiring shall be #12 AWG minimum unless noted otherwise, with 10 AWG required for longer runs exceeding specified distances.

View the file

Other files

Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

J J

EPO

DPM

PP

T

CD CR

D#

I#

U#

PC

FAP

NEP

FAA

PIV

PS

TS

FS

SD

SD

B#

SD

DSD

RI

H

J

F

SD

A

S

S

A

S

S

AM

AR

HD

SD

ZAM

CO

VCC

DCD

F

H

S

ASD

FSD

1P 1 POLE (2P, 3P, 4P, ETC.)

A 6" ABOVE COUNTER OR BACKSPLASH

TO CENTERLINE OF DEVICE

A, AMP AMPERE

AC ABOVE COUNTER, AIR CONDITIONING UNIT

ACLG ABOVE CEILING

AF AMP FRAME

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFCI ARC FAULT CIRCUIT

INTERRUPTER

AHU AIR HANDLING UNIT

AL ALUMINUM

ALT ALTERNATE

AMP AMPERE

AMPL AMPLIFIER

ANNUN ANNUNCIATOR

APPROX APPROXIMATELY

AQ-STAT AQUASTAT

ARCH ARCHITECT, ARCHITECTURAL

AS AMP SWITCH

AT AMP TRIP

ATC AUTOMATIC TEMPERATURE CONTROLS

CONTRACTOR

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AUX AUXILIARY

AV AUDIO VISUAL

AWG AMERICAN WIRE GAUGE

B BLACK DEVICE COLOR WITH BLACK

UNBREAKABLE THERMOPLASTIC COVER

PLATE

BAS BUILDING AUTOMATION SYSTEM

BATT BATTERY

BD BOARD

BLDG BUILDING

BMS BUILDING MANAGEMENT SYSTEM

C CONDUIT

CAB CABINET

CAT CATALOG

CATV CABLE TELEVISION

CB CIRCUIT BREAKER

CCTV CLOSED CIRCUIT TELEVISION

CKT CIRCUIT

CLG CEILING

CM CONSTRUCTION MANAGER

COMB COMBINATION

CMPR COMPRESSOR

CONN CONNECTION

CONST CONSTRUCTION

CONT CONTINUATION OR CONTINUOUS

CONTR CONTRACTOR

CP CIRCULATING PUMP

CRT CATHODE-RAY TUBE

CT CURRENT TRANSFORMER

CTR CENTER

CU COPPER

DEPT DEPARTMENT

DET DETAIL

DIA DIAMETER

DISC DISCONNECT

DIST DISTRIBUTION

DN DOWN

DO AUTOMATIC DOOR OPENER

DPR DAMPER

DS SAFETY DISCONNECT SWITCH

DT DOUBLE THROW

DWG DRAWING

EC ELECTRICAL CONTRACTOR

ECB ENCLOSED CIRCUIT BREAKER

ELEC ELECTRIC, ELECTRICAL

ELEV ELEVATOR

ELU EMERGENCY LIGHTING UNIT

EM EMERGENCY

EMS ENERGY MANAGEMENT SYSTEM

EMT ELECTRICAL METALLIC TUBING

EP ELECTRIC PNEUMATIC

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXIST EXISTING

EXH EXHAUST

EXP EXPLOSION PROOF

FA FIRE ALARM

FABP FIRE ALARM BOOSTER POWER

SUPPLY PANEL

FACP FIRE ALARM CONTROL PANEL

FCU FAN COIL UNIT

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FPC FIRE PROTECTION CONTRACTOR

FU FUSE

FUDS FUSED SAFETY DISCONNECT SWITCH

GA GAUGE

GAL GALLON

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERATOR

GFI GROUND FAULT CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTOR

GND GROUND

GYP BD GYPSUM BOARD

HWC-# DOMESTIC WATER CIRCULATING PUMP

HOA HANDS-OFF-AUTOMATIC SWITCH

H INSTALL DEVICE HORIZONTALLY

HH HANDHOLE

HP HORSEPOWER

HPF HIGH POWER FACTOR

HT HEIGHT

HTG HEATING

HTR HEATER

HV HIGH VOLTAGE

HVAC HEATING, VENTILATING AND AIR

CONDITIONING

IC INTERRUPTING CAPACITY

IG ISOLATED GROUND

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

I/W INTERLOCK WITH

J-BOX JUNCTION BOX

K.E.C. KITCHEN EQUIPMENT CONTRACTOR

KV KILOVOLT

KVA KILOVOLT-AMPERE

KVAR KILOVOLT-AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

LT LIGHT

LTG LIGHTING

ELECTRICAL ABBREVIATIONS

LTNG LIGHTNING

LV LOW VOLTAGE

M INSTALL DEVICE IN MILLWORK

MAX MAXIMUM

MAG.S MAGNETIC STARTER

M/C MOMENTARY CONTACT

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDC MAIN DISTRIBUTION CENTER

MDP MAIN DISTRIBUTION PANEL

MFR MANUFACTURER

MFS MAIN FUSED DISCONNECT SWITCH

MH MANHOLE

MIC MICROPHONE

MIN MINIMUM

MISC MISCELLANEOUS

MLO MAIN LUGS ONLY

MMS MANUAL MOTOR STARTER

MOA MULTIOUTLET ASSEMBLY

MSP MOTOR STARTER PANELBOARD

MSBD MAIN SWITCHBOARD

N/A NOT APPLICABLE

NFDS NON-FUSED SAFETY DISCONNECT

SWITCH

NIC NOT IN CONTRACT

NL NIGHT LIGHT

N.O. NORMALLY OPEN

NPF NORMAL POWER FACTOR

NTS NOT TO SCALE

OC ON CENTER

OH OVERHEAD

OL OVERLOADS

PA PUBLIC ADDRESS

PB PULL BOX OR PUSHBUTTON

PC PLUMBING CONTRACTOR

PE PNEUMATIC ELECTRIC

PED PEDESTAL

PF POWER FACTOR

PH PHASE

PIV POST INDICATING VALVE

PNL PANEL

PP POWER POLE

PR PAIR

PRI PRIMARY

PROJ PROJECTION

PRV POWER ROOF VENTILATOR

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (CONDUIT)

PWR POWER

QTY QUANTITY

RAC RIGID ALUMINUM CONDUIT

RCPT RECEPTACLE

REQD REQUIRED

RM ROOM

RMC RIGID METALLIC CONDUIT

RTU ROOF TOP UNIT

SC SURFACE CONDUIT

SEC SECONDARY

SHT SHEET

SIM SIMILAR

SLD SINGLE-LINE DIAGRAM

S/N SOLID NEUTRAL

SPEC SPECIFICATION

SPKR SPEAKER

SP SPARE

SPP SINGLE-POINT POWER

SR SURFACE RACEWAY

SS STAINLESS STEEL

SSW SELECTOR SWITCH

S/S STOP/START PUSHBUTTONS

STA STATION

STD STANDARD

SURF SURFACE MOUNTED

SW SWITCH

SWBD SWITCHBOARD

SYM SYMMETRICAL

SYS SYSTEM

TEL TELEPHONE

TERM TERMINAL

T TAMPER RESISTANT

TL TWIST LOCK

T-STAT THERMOSTAT

TTC TELEPHONE TERMINAL CABINET

TV TELEVISION

TVTC TELEVISION TERMINAL CABINET

TYP TYPICAL

UC UNDER COUNTER

UE UNDERGROUND ELECTRICAL

UG UNDERGROUND

UH UNIT HEATER

UT UNDERGROUND TELEPHONE

UTIL UTILITY

UV ULTRAVIOLET

V VOLT

VA VOLT-AMPERES

VDT VIDEO DISPLAY TERMINAL

VERT VERTICAL

VFD VARIABLE FREQUENCY DRIVE

VOL VOLUME

W WATT

W/ WITH

WG WIRE GUARD

WH WATER HEATER

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

XFR TRANSFER

#" LOCATION-SPECIFIC MOUNTING

HEIGHT ABOVE FINISHED FLOOR

TO CENTERLINE OF DEVICE

∠ ANGLE

@ AT

▲ DELTA

' FEET

" INCHES

# NUMBER

Ø PHASE

C CENTER LINE

P PLATE

1. ALL INSTALLATIONS SHALL COMPLY WITH ALL APPLICABLE FEDERAL, STATE, AND LOCAL CODES INCLUDING, BUT NOT LIMITED TO, THE NATIONAL ELECTRICAL CODE (NEC), INTERNATIONAL BUILDING CODE (IBC), AMERICANS WITH DISABILITIES ACT (ADA) ACCESSIBILITY GUIDELINES, AND THE INTERNATIONAL ENERGY CONSERVATION CODE (IECC). THE AUTHORITY HAVING JURISDICTION (AHJ) SHALL HAVE FINAL APPROVAL OF ALL INSTALLATIONS

AND PRACTICES.

2. ALL MATERIALS FURNISHED SHALL BE NEW, FREE OF DEFECTS, AND LISTED BY A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) UNLESS NOTED

OTHERWISE.

3. INSTALLATION OF CONDUITS AND HANDHOLES SHALL COMPLY WITH CURRENT STANDARDS AND SPECIFICATIONS APPROVED BY THE AHJ.

4. CONDUITS SHOWN ON DRAWINGS ARE SCHEMATIC ONLY. CONDUIT RUNS SHALL NOT INCLUDE BENDS GREATER THAN 90 DEGREES.

5. EMERGENCY SYSTEM SHALL BE SEPARATE CONDUITS OR RACEWAYS AND SHALL REMAIN COMPLETELY INDEPENDENT OF ALL OTHER CONDUITS AND

HANDHOLES.

6. RACEWAYS SHALL NOT BE INSTALLED BELOW FLOOR SLABS UNLESS SPECIFICALLY NOTED.

EQUIPMENT GROUNDING CONDUCTOR

PHASE CONDUCTOR (SHORT LINE)

NEUTRAL CONDUCTOR (LONG LINE)

EQUIPMENT/DEVICE HOME RUN KEY

1. BRANCH CIRCUIT WIRING SHALL BE #12AWG UNLESS NOTED OTHERWISE ON THE PLAN OR IN THE SCHEDULES.

2. AS A MINIMUM, USE 10 AWG CONDUCTOR FOR 20 AMPERE, 120 VOLT BRANCH CIRCUIT HOME RUNS LONGER

THAN 100 FEET AND 277 VOLT BRANCH CIRCUIT HOME RUNS LONGER THAN 200 FEET.

3. REFER TO SPECIFICATION SECTION 260519 FOR ADDITIONAL REQUIREMENTS.

GENERAL NOTES

LIGHTING CONTROL SYMBOLS

SYMBOL DESCRIPTION

WALL SWITCH

FIRE ALARM SYMBOLS

SYMBOL DESCRIPTION

CONTROL PANEL

NOTIFICATION APPLIANCE CIRCUIT

EXTENDER PANEL

REMOTE ANNUNCIATOR PANEL

POST INDICATOR VALVE AND TAMPER

SWITCH

AIR PRESSURE SWITCH

VALVE TAMPER SWITCH

WATER FLOW SWITCH

LINEAR BEAM SMOKE DETECTOR

DUCT SMOKE DETECTOR

DUCT SMOKE DETECTOR REMOTE

INDICATOR STATION

HEAT DETECTOR ADDRESSABLE

LINEAR HEAT DETECTION CABLE

ADDRESSABLE FIRE ALARM MANUAL

PULL STATION

SMOKE DETECTOR

AUDIO/VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

SPEAKER NOTIFICATION APPLIANCE,

CEILING MOUNTED

SPEAKER/VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED

HORN NOTIFICATION APPLIANCE, WALL

MOUNTED

AUDIO/VISUAL NOTIFICATION APPLIANCE,

WALL MOUNTED

SPEAKER NOTIFICATION APPLIANCE,

WALL MOUNTED

SPEAKER/VISUAL NOTIFICATION

APPLIANCE, WALL SWITCH

VISUAL NOTIFICATION APPLIANCE, WALL

MOUNTED

ADDRESSABLE MONITOR MODULE

ADDRESSABLE RELAY MODULE

HVAC ELEVATOR HOISTWAY DAMPER

HVAC SMOKE DAMPER

MAGNETIC DOOR HOLDER

ZONE ADAPTER MODULES

CEILING MOUNT SENSOR, DUAL

TECHNOLOGY

CEILING MOUNT SENSOR, INFRARED

TECHNOLOGY

CEILING MOUNT SENSOR, ULTRASONIC

TECHNOLOGY

GENERAL ELECTRICAL SYMBOLS

LINEAR BEAM SMOKE DETECTOR

BEAM SMOKE REFLECTOR

CO DETECTOR

ELECTRICAL CONNECTION

EMERGENCY STOP PUSH BUTTON

DIGITAL POWER METER

UTILITY TRANSFORMER

SWITCHBOARD

PANELBOARD

TRANSFORMER

DISCONNECT SWITCH

UTILITY POWER METER

VOICE COMMAND CENTER

DUCT CO DETECTOR

BELL

HIGH FIDELITY SPEAKER - CEILING MOUNT

AIR SAMPLING SMOKE DETECTOR

HIGH FIDELITY SPEAKER - WALL MOUNT

COMBINATION STARTER

ELECTRICAL EQUIPMENT

(DASHED LINES INDICATE CODE REQUIRED CLEARANCES)

BREAKER FUNCTION SCHEDULE

SYMBOL DESCRIPTION

A ARC FAULT INTERUPTER (AFCI)

AR ARC ENERGY REDUCTION MAINTENANCE SWITCH

E EXISTING BREAKER TO REMAIN

EM PROVIDE IDENTIFICATION PER NEC 700.12(I)(2)(4)

EN EXISTING BREAKER SERVING NEW CIRCUIT

G GROUND FAULT CIRCUIT INTERUPTER (GFCI) PROTECTION (5mA) GE GROUND FAULT CIRCUIT INTERUPTER FOR EQUIPMENT (30mA)

GF ADJUSTABLE GROUND FAULT PROTECTION FOR EQUIPMENT

HL HANDLE LOCK TO LOCK BREAKER IN CLOSED POSITION

K# KEY INTERLOCK (# REPRESENTS GROUPED KEYING)

LSI LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT

LSIG LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ADJUSTMENT

LSIA LONG-TIME, SHORT-TIME, INSTANTANEOUS ADJUSTMENT, AND GROUND FAULT ALARM

N NEW BREAKER IN EXISTING PANEL

NE NEW BREAKER SERVING EXISTING CIRCUIT

SD DENOTE SERVICE DISCONNECT

ST SHUNT TRIP (120V OPERATED UNLESS NOTED OTHERWISE)

GENERAL PLAN SYMBOLS

NEW WORK BY THE EC (DARK SOLID LINE)

WORK BY OTHERS AND/OR EXISTING (LIGHT SOLID LINE)

DEMO WORK BY THE EC (DARK DASHED LINE)

NEW UNDERGROUND WORK BY THE EC (DARK DASHED LINE)

MATCHLINE

KEYED NOTE

LIGHTING CONTROL CALLOUT SYMBOL (DIAMOND)

1 ELECTRICAL EQUIPMENT SYMBOL (OCTAGON)

SECTION VIEW, TOP REPRESENTS DETAIL NUMBER, BOTTOM REPRESENTS SHEET NUMBER

ENLARGED VIEW, TOP REPRESENTS VIEW NUMBER, BOTTOM REPRESENTS SHEET NUMBER

POWER SYMBOLS

SYMBOL DESCRIPTION

DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R

CORD REEL / CORD DROP

SIMPLEX RECEPTACLE, NEMA 5-20R

SPECIAL RECEPTACLE

RECESSED FLOOR BOX OR POKE-THRU

DUPLEX / DOUBLE DUPLEX RECEPTACLE, NEMA 5-20R, EMERGENCY POWER

MARK SCHEDULED EQUIPMENT (UNDERLINED)

MARK NONSCHEDULED EQUIPMENT

(E) MARK EXISTING EQUIPMENT - (E) PREFIX (HALFTONE)

(R) MARK EXISTING RELOCATED EQUIPMENT - (R) PREFIX

AUTOMATIC DOOR PUSH PAD

CEILING MOUNTED RECEPTACLE, NEMA 5-20R

LIGHTING SYMBOLS

SYMBOL DESCRIPTION

RECESSED MOUNTED (DIAGONAL SLASH)

RECESSED DOWNLIGHT (ARROW

INDICATES WALL WASH)

EMERGENCY LIGHT

POLE MOUNTED SITE FIXTURE

SURFACE OR PENDANT FIXTURE (DOTS)

WALL MOUNTED FIXTURE (STEM OR STEMS)

SURFACE MOUNTED

CRITICAL FIXTURE (FULL SHADED)

LIFE SAFETY (HALF SHADED)

SINGLE / DOUBLE FACED EXIT SIGN

EMERGENCY REMOTE HEAD (SINGLE/DOUBLE)

COMBINATION EXIT/EMERGENCY LIGHT

CYLINDRICAL FIXTURE (ARROW INDICATES

WALL WASH)

SURFACE MOUNT MULTI-OUTLET ASSEMBLY

FIRE SMOKE DAMPER

GROUND BAR

HAND HOLEHH-#

PHOTOCELL

HORSE POWER RATED SWITCH

H

BR

LHD

X

5518 NW 88th Street

Johnston, IA 50131

515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e v is io n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

100 CLARINDA LN

PENSACOLA, FLORIDA,32505 ES000BID PACKAGE #1 ELECTRICAL COVER PAGE

KEDbluestone

5518 NW 88TH STREET,

JOHNSTON, IA 50131

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, SUITE 1170,

DALLAS, TX 75243

214.749.0333

BID PACKAGE 1

09.03.2026

KEDbluestone

BID PACKAGE #1 ELECTRICAL SHEET LIST

ES000 BID PACKAGE #1 ELECTRICAL COVER PAGE

ES100 BID PACKAGE #1 ELECTRICAL SITE PLAN

B

R I A N R . K E

I T

H

No 84763

STATE OFP

R

O

F E

S S I O N A L E N G

I N

E E

R

L I C E N S

E

F L O R I D

A

AB

UTILITY

XFMR

C3

C1

C5

C2

C4

C6

'HH-2'

'HH-2'

'HH-1'

'HH-1'

'HH-4'

'HH-1'

'HH-2'

'HH-2'

C7

'HH-2'

'HH-2'

'HH-2'

'HH-2'

C8

C9

C10

C9 C12

C9

C9

C9

C11

LORETTA STREET

W 42ND LANE

N

CLO

VER

STR

EET

C

LO

VER

STR

EET

W 40TH LANE

W 41TH LANE

H

IG

H W

AY 29

CLARINDA LANE

PAPA DON BOULEVARD

MAINTENANCE BUILDING

ADMIN BUILDING

WASH STATION

FUELING STATION

TRANSFER CENTER

MAINT. YARD

C13

'HH-3'

TEMP

GENERATOR

C9

'HH-2'

'HH-2'

C9

VACUUM

FUTURE

ELECTRICAL

ROOM

'HH-4'

'HH-3'

'HH-3' 'HH-3'

PULL SLOT

8" E

XTENSION

MOUSE HOLES - (2)

KNOCKOUTS - (8)

STAINLESS STEEL HEX

HEAD BOLT W/WASHER

SKID RESISTANT SURFACE

EXTENSIONS AS

REQUIRED BY

CONDUIT DEPTH.

SLOPE GRADE AWAY

FROM COVER 1" IN

3'

GRAVEL DRAINAGE

BED MINIMUM 6" DEPTH

CONDUITS LARGER THAN MOUSE

HOLES CAN ACCOMMODATE,

SHALL ENTER BOTTOM OF HANDHOLE

WITH LONG RADIUS SWEEPS.

1. PROVIDE HANDHOLES AS REQUIRED FOR INSTALLATION OF SITE CONDUITS AND SERVICES.

NOTES:

SYSTEM LABEL

5518 NW 88th Street

Johnston, IA 50131

515-727-0700 www.KEDbluestone.com

KED

bluestone

Architect of Record:

ADG

800 SW ADAMS STREET, SUITE 101

PEORIA, IL 61602

R e v is io n s

P - 309.672.6948

Discipline:Discipline:Discipline:

P - P - P -

Discipline:

P -

PROJECT NO.

DATE

DRAWN BY

STATUS

Discipline:Discipline: Owner Consultant

QSC SERVICES, LLC

PMB #69

545 BRENT LN. PENSACOLA, FL

P - 309.231.8272

OWNER ID:

Design and Construction Administration Division

ESCAMBIA COUNTY, FL

100 E. BLOUNT ST. PENSACOLA, FL 32501

PROJECT NUMBER: 126-030

KEDbluestone RESERVES PROPRIETARY RIGHTS, INCLUDING

COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN

THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE

PROPERTY OF KEDbluestone AND SHALL NOT BE USED OR

REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE

EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF

KEDbluestone. © 2026 KEDbluestone

ESCAMBIA COUNTY AREA TRANSIT - FACILITY:

03 - TRANSFER CENTER

100 CLARINDA LN

PENSACOLA, FLORIDA,32505 ES100BID PACKAGE #1 ELECTRICAL SITE PLAN

KEDbluestone

5518 NW 88TH STREET,

JOHNSTON, IA 50131

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

RLG CONSULTING ENGINEERS

12001 N CENTRAL,

DALLAS, TX 75243

214.739.8100 214.739.8100 515.727.0700

HODGSON DOUGLAS LANDSCAPE ARCHITECTS

12001 N. CENTRAL EXPRESSWAY, SUITE 1170,

DALLAS, TX 75243

214.749.0333

BID PACKAGE 1

09.03.2026

KEDbluestone

N

1" = 50'-0"

BID PACKAGE #1 ELECTRICAL SITE PLAN

ID CONDUIT SIZE SERVES SYSTEM SERVED ORIGIN

C1

C2

C3

MAINT. BLDG.

ADMIN. BLDG.

(2) 5" UTILITY PRIMARY UTILITY CONNECTION POINT

(4) 4"

(3) 4" MAINT. BLDG.

EM POWER

POWER

C4

TRANSFER CENTER

CONDUIT LEGEND

KEYED NOTES:

1. FUTURE UTILITY TRANSFORMER AND PAD

LOCATION. TRANSFORMER AND PAD TO BE

INSTALLED IN BID PACKAGE #2. COORDINATE

FINAL LOCATION PER FLORIDA POWER AND

LIGHT REQUIREMENTS AND TERMINATE

CONDUITS 6’-0” FROM EDGE OF CONCRETE

PAD.

2. COORDINATE FINAL CONDUIT SIZE,

QUANTITY AND ROUTING WITH UTILITY PRIOR

TO INSTALLATION. SUBMIT UTILITY CONDUIT

ROUTING PLAN TO ENGINEER FOR REVIEW.

PRIOR TO CONDUIT INSTALLATION.

3. TEMPORARY GENERATOR CONNECTION

CABINET, TRANSFER SWITCH, TEMPORARY

GENERATOR, CODE BLUE SAFETY LIGHT,

AND FUEL PUMP EMERGENCY OFF SWITCH

WILL BE LOCATED AT THIS LOCATION AND

INSTALLED IN BID PACKAGE #2.

4. FUTURE GENERATOR AND GENERATOR PAD

LOCATION. GENERATOR AND PAD TO BE

INSTALLED IN BID PACKAGE #2. TERMINATE

CONDUITS WITHIN 6’-0” OF FUTURE

CONCRETE PAD.

5. STOP CONDUIT WITHIN 10' OF BUILDING AND

RECORD LOCATION FOR FUTURE

CONNECTION.

6. BUILDING TO BE FED WITH CONDUIT AS PART

OF BID PACKAGE #2

GENERATOR

UTILITY XFMR

ADMIN. BLDG.(3) 4" EMERGENCY

ADMIN. BLDG.(2) 2" SPARES

ADMIN. BLDG.(1) 4" SPARES

POWER

EMERGENCY

SPARES

SPARES

TRANSFER CENTER

TRANSFER CENTER

TRANSFER CENTER

(2) 4"

(2) 4"

(1) 2"

(1) 4"

C5

WASH & FUEL

SPARESWASH & FUEL(1) 2"

SPARESWASH & FUEL(1) 4"

(2) 4" POWER

POWER

C6

VACCUM(2) 3"

SPARES(2) 2"

SPARES

VACCUM

VACCUM(1) 1 1/2"

N.T.S.N.T.S.

EXTERIOR HANDHOLE DETAIL

HH-1

HH-2

HANDHOLE 13" X 24" X 18" DEEP STACKABLE ASSEMBLY. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION

HANDHOLE 36" X 36" X 30" DEEP STACKABLE ASSEMBLY. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION

QUAZITE

BOX PG1324BA18

COVER PG1324CA00

OR APPROVED EQUAL

QUAZITE

BOX PG3636BA30

COVER PG3636CA00

OR APPROVED EQUAL

GENERAL ELECTRIC SCHEDULE

SYMBOL DESCRIPTION MANUFACTURER

MAINT. BLDG.(1) 1" EM CONTROLS

MAINT. BLDG. EM SPARE

MAINT. BLDG. EM SPARE

(1) 2"

(1) 1"

EM POWERMAINT. BLDG TEMP. GENERATOR(2) 4"

C7 EM CONTROLSMAINT. BLDG(2) 1"

TELECOM(2) 4"C8

(3) 4"C9

(3) 4"C10

C11 (2) 4"

TELECOM

TELECOM

TELECOM

WASH & FUEL HANDHOLE

HANDHOLE

MAINT. BLDG.

ADMIN. BLDG.

GENERAL NOTES:

1. LABEL ALL CONDUITS WHERE THEY TERMINATE

OR ENTER HANDHOLE AND JUNCTION/PULL BOXES.

SEAL ALL CONDUITS AND INSTALL PULL STRING.

2. CONDUIT LOCATION SHOWN ARE DIAGRAMMATIC.

ELECTRICAL CONTRACTOR SHALL COORDINATE ALL

SITE CONDUIT LOCATIONS AND INSTALLATIONS WITH

THE ELECTRICAL ROOMS AND EQUIPMENT INDICATED

IN FUTURE BID PACKAGE NO. 2 FINAL CONDUIT ORIGINS,

TERMINATIONS, AND POINTS OF CONNECTION SHALL BE

VERIFIED AGAINST BID PACKAGE NO. 2 DOCUMENTS AND

COORDINATED BETWEEN AFFECTED CONTRACTORS PRIOR

TO INSTALLATION.

GENERATOR

GENERATOR

GENERATOR

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

MAINT. BLDG.

WASH STATION

TEMP. GENERATOR

HANDHOLE

HANDHOLE

HANDHOLE

C12 (2) 4" TELECOMTRANSFER CENTER HANDHOLE

C13 (2) 1" SPAREVACUUM TEMP. GENERATOR

SPARESMAINT. BLDG(3) 1 - 1/4" TEMP. GENERATOR

WASH STATION

WASH STATION

HH-3 HANDHOLE 30" X 30" X 30" DEEP STACKABLE ASSEMBLY. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION

QUAZITE

BOX PG3030BA30

COVER PG3030CA00

OR APPROVED EQUAL

HH-4 HANDHOLE 48" X 48" X 36" DEEP STACKABLE ASSEMBLY. REFER TO

SPECIFICATIONS FOR ADDITIONAL INFORMATION

QUAZITE

BOX PG4040BA36

COVER PG4040CA00

OR APPROVED EQUAL