017823_07 Submittal ATS 26 36 23 (1).pdf
PDF 1 MB Posted
- Attached to
- RFP 25-329-K for Generator FEMA and GEMA Funded Project (Construction for GEMA's Hazard Mitigation
- Solicitation number
- PE-66079-NONST-2025-000000053
- Issued by
- Fulton County, Georgia
About this file
This file is an Operation & Maintenance Manual and Installation Guide submittal for an ASCO Automatic Transfer Switch (ATS) Model Series 3ATS rated at 2000 Amps, submitted by Yancey Power Systems for the City of Roswell Water Treatment Plant (WTP) project managed by Layne Heavy Civil Inc. The submittal includes comprehensive technical documentation consisting of two primary components: the ASCO 3ATS 2000 Amps Operation & Maintenance Manual and the ASCO Group G Controller User's Guide Installation Manual (document 381333-406). The automatic transfer switch is designed to seamlessly transfer electrical loads between normal and emergency power sources, with the controller managing sensing, timing, and control functions. The manual covers installation requirements including mounting on a level, rigid supporting structure with proper cable connections, functional testing procedures (manual operation, voltage checks, and electrical operation), preventive maintenance protocols, and troubleshooting guidance. The documentation specifies that an experienced licensed electrician must perform installation and that the transfer switch contains factory-wired components requiring only mounting and service cable connections.
The technical specifications and operational guidance address both automatic and non-automatic transfer configurations, with detailed descriptions of operation sequences for the 3ATS, 3ADTS, 3NTS, and 3NDTS models. The Group G Controller includes a user interface with graphic display and control buttons enabling monitoring and control with the enclosure door closed. Voltage and frequency settings are factory-configured with default values but are adjustable through a menu system requiring password entry (default 1111). The manual includes comprehensive timer settings for various transfer features, engine exerciser configurations, and optional accessories including communication modules, current sensing modules, relay expansion modules, and uninterruptible power supply modules. Preventive maintenance recommendations include annual inspections, contact condition checks, lubrication maintenance, and cable connection verification, with monthly transfer switch operation tests required. The documentation provides detailed event logging capabilities, statistics tracking, and alarm management functions, with support available through ASCO Services, Inc. at 800-800-2726.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Submittal
01 78 23.07 000
Contractor hereby certifies that (i) Contractor has complied with the requirements of Contract Documents in preparation, review and submission of designated Submittal and (ii) the Submittal is complete and in accordance with the Contract Documents and requirements of laws and regulations and governing agencies.
By:______________ Guy Goff__________________
Contractor (Authorized Signature)
O&M’s 26 36 23 Automatic Transfer Switch
Yancey Power Systems 259 Lee Industrial Blvd.
Austell, GA 30168-7406
770.941.2424 tel
770.941.2411 fax
877.278.6235 toll free www.YanceyPower.com
Operation & Maintenance Manuals
ASCO
Automatic Transfer Switch
Model Series 3ATS 2000 Amps
For:
City of Roswell WTP ATS
Customer: Yancey Job # 14-1400 Layne Heavy Civil Inc. Project Manager Ron Ball Christian Lammers 300 E. Broad Street Fairburn, GA 30213
INDEX
TAB 1: ASCO ATS Model 3ATS- 2000 Amps O & M Manual
TAB 2: ASCO Group G Controller User’s Guide
Installation Manual ASCO 3ATS, 3ADTS, 3NTS, 3NDTS
381333-406 ASCO Power Technologies Page 1
DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
Rating Label Each transfer switch contains a rating label to define the loads and fault circuit withstand/closing ratings. Refer to the label on the transfer switch for specific values.
Do not exceed the values on the rating label.
Exceeding the rating can cause person injury or serious equipment damage.
An experienced licensed electrician must install the transfer switch.
Installation These transfer switches are factory wired and tested.
Installation requires mounting, connecting service cables, and connecting engine start and auxiliary control circuits (if required.).
Supporting Foundation The supporting foundation for the enclosure must be level and straight. Refer to the applicable enclosure outline drawing included with the transfer switch for all mounting details including door opening space.
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the enclosure outline drawing for specified area and location.
Provide cable bending space and 1 inch minimum clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting Refer to the outline and mounting diagram and mount the transfer switch according to details and instructions shown on the diagram. Mount it vertically to a rigid supporting structure. Level all mounting points by using flat washers behind the holes to avoid distortion of the transfer switch.
Protect the transfer switch from construction grit and metal chips to prevent malfunction or shortened life of the transfer switch.
381333-406
Refer to the outline and wiring drawings provided with the 3ATS, 3NTS, 3ADTS, or 3NDTS for all installation and connection details and accessories.
DANGER !
WARNING !
CAUTION !
Refer to User�s Guide 381333-400 for the Goup G Controller status display messages, time delays, pickup and dropout settings, and adjustments.
3ATS, 3ADTS, 3NTS, 3NDTS
G-design 1600-3000 A Transfer Switches Installation Manual
WARNING !
NOTICE
INSTALLATION
Mounting Power Connections Engine Starting Contacts
FUNCTIONAL TEST
1- Manual Operation 2- Voltage Checks 3- Electrical Operation
TESTING & SERVICE
Transfer Test Preventive Maintenance Manual Load Transfer
TROUBLESHOOTING
INDEX
Table of Contents
ASCO 3ATS, 3ADTS, 3NTS, 3NDTS Installation Manual
Page 2 ASCO Power Technologies 381333-406
Line Connections Refer to the wiring diagram provided with the transfer switch.
All wiring must be made in accordance with the National Electrical Code and local codes.
De-energize the conductors before making any line or auxiliary circuit connections. Be sure that the Normal and Emergency line connections are in proper phase rotation. Place the engine generator starting control in the OFF position. Make sure engine generator is not in operation.
Testing Power Conductors Do not connect the power conductors to the transfer switch until they are tested. Installing power cables in conduit, cable troughs, and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor�s strands. For this reason, after the cables are pulled into position, and before they are connected, they should be tested to verify that they are not defective or have been damaged during installation.
Connecting Power Cables After the power cables have been tested, connect them to the appropriate terminal lugs on the transfer switch as shown on the wiring diagram provided with the transfer switch. Make sure that the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the transfer switch. Be careful when stripping insulation from the cables, avoid nicking or ringing the conductor. Remove surface oxides from cables by cleaning with a wire brush. When aluminum cable is used, apply joint compound to conductors. Tighten cable lugs to the torque specified on rating label.
Harnesses The transfer switch is connected to the left side of the controller by a plug-in harness (two plugs).
Auxiliary Circuits Connect auxiliary circuit wires to appropriate terminals on the transfer switch as shown on the wiring diagram.
Controller Ground A grounding wire must be connected to the controller�s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Engine Starting Contacts The engine control contact connections (if used) are located on the transfer switch for 3ATS & 3NTS or in the upper right side of the enclosure for 3ADTS & 3NDTS. Connect signal wires to appropriate terminals as specified in Table A and shown in Figure 1.
Table A. Engine Start Connections.
When normal source fails
Terminals on transfer switch contact closes TB1 and TB2 contact opens TB1 and TB3
Figure 1. Engine start and auxiliary circuit terminal block.
Figure 2. Main contact position indicators on right side.
TB
DANGER !
window indicators
OPEN or
CLOSED
Emergency contacts
Normal contacts
381333-406 ASCO Power Technologies Page 3 maintenance h dl
Clockwise DOWN closes the Normal source contacts (lower) and opens the Emergency source contacts (upper)
Counterclockwise DOWN closes the Emergency source contacts (upper) and opens the Normal source contacts (lower)
Clockwise DOWN CLOSES the contacts Pull out shaft to close Emergency source contacts (upper) Push in shaft to close Normal source contacts (lower)
Counterclockwise DOWN OPENS the contacts Pull out shaft to open Emergency source contacts (upper) Push in shaft to open Normal source contacts (lower) maintenance handle insert handle into hole in hub slide hub onto shaft and insert the pin
Functional Test The functional test consists of three checks: manual operation, voltage checks, and electrical operation.
Do these checks in the order presented to avoid damaging the transfer switch.
1 � Manual Operation A maintenance handle is provided on the transfer switch for maintenance purposes only. Manual operation of the transfer switch should be checked before it is energized (operated electrically).
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1. After deenergizing both power sources, open the enclosure door. Locate and remove the maintenance handle from the clip on the left side of the transfer switch. See Figures 3, 4, and 5. See Figure 2 for the contact position indicators.
2. Install the handle into the hole in the molded hub. Move the handle up or down as shown to manually operate the transfer switch. It should operate smoothly without any binding. If it does not, check for shipping damage or construction debris.
3. 3ADTS and 3NTS have two contact shaft hubs. See Figure 5.
4. Return the transfer switch to the Normal position.
Note: If Normal and Emergency connections are reversed this operation is also reversed.
Figure 3. Maintenance handle on 3ATS & 3NTS.
Figure 4. Maintenance handle operation on 3ATS &
3NTS.
Figure 5. Maintenance handle on 3ADTS & 3NDTS.
NOTICE
WARNING !
Page 4 ASCO Power Technologies 381333-406
Figure 6. Four indicator lights.
2 � Voltage Checks First check the nameplate on the transfer switch; rated voltage must be the same as normal and emergency line voltages.
Use extreme caution when using a meter to measure voltages in the following steps.
Do not touch power terminals; shock, burns, or death could result!
Perform steps 1 through 6 at the right. Observe the indicator lights. See Figure 6.
Black circle means the light is on.
White circle means the light is off.
* If necessary, adjust the voltage regulator on the generator according to the manufacturer�s recommendations. The transfer switch will respond only to the rated voltage specified on the transfer switch nameplate.
Also see User�s Guide 381333-400 for voltage settings in the controller.
Close the normal source circuit breaker. The normal source accepted and the load on normal lights should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch normal source terminals.
Close the emergency source circuit breaker.
(Start generator, if necessary.) The emergency source accepted light should come on.
Use an accurate voltmeter to check phase to phase and phase to neutral voltages present at the transfer switch emergency source terminals.*
Use a phase rotation meter to check phase rotation of emergency source; it must be the same at the normal source.
Shut down the engine-generator, if applicable.
The emergency source accepted light should go off. Then put the starting control selector switch (on the generator set) in the automatic position.
Close the enclosure door. 6
Continue to 3 � Electrical Operation on the next page.
DANGER !
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
381333-406 ASCO Power Technologies Page 5
Figure 7. Transfer button and indicator lights.
3 � Electrical Operation This procedure will check the electrical operation of the transfer switch.
Close the transfer switch enclosure door and tighten the screws before you test electrical operation.
Perform steps 1 through 5 at the right. Observe the status lights. See Figure 7.
Black circle means light is on.
White circle means light is off.
NOTE: For 3NTS manually start the emergency generator at the generator. Then press the transfer button for load transfer.
If the inphase transfer feature is activated, transfer may not occur immediately. Transfer will occur when the phase relationship between sources is correct. Press the transfer button again for load retransfer to normal, then manually stop the generator at the generator.
Also see User�s Guide 381333-400 for inphase transfer and time delay settings in the controller.
This completes the functional test of the transfer switch.
Leave the engine-generator starting control in the automatic position.
The normal source must be available and the generator must be ready to start. Check that the normal source accepted light is on.
For 3ATS & 3ADTS press the transfer button. The engine should start and run within 15 seconds. For 3NTS & 3NDTS the generator must be started manually at the generator.
The emergency source accepted light should come on.
For 3ATS & 3ADTS the transfer switch should transfer to the emergency position. The load on emergency light should come on and the load on normal light should go off. For 3NTS & 3NDTS press the transfer button for load transfer. For 3ADTS & 3NDTS both lights will be off during the delayed-transition transfer time delay.
If the transfer to emergency delay is used, the transfer occurs after a time delay. For immediate transfer (bypass timer) press the transfer button again.
For 3ATS & 3ADTS the transfer switch should transfer back to the normal position. The load on normal light should come on and the load on emergency light should go off. For 3NTS & 3NDTS press the transfer button for load retransfer. For 3ADTS & 3NDTS both lights will be off during the delayed-transition transfer time delay.
If the retransfer to normal delay is used the retransfer should occur after a time delay. For immediate retransfer (bypass timer) press the transfer button again.
For 3ATS & 3ADTS the unloaded running delay keeps the generator running for a cool-down period. Then the generator should stop and the emergency source accepted light should go off. For 3NTS & 3NDTS manually stop the generator at the generator (after a cool-down period).5
WARNING !
Observe these lights
Press this button
Page 6 ASCO Power Technologies 381333-406
Testing & Service Transfer Test
Operate the transfer switch at least once a month by following the Electrical Operation procedure on page 6.
Preventive Maintenance Reasonable care in preventive maintenance will insure high reliability and long life for the transfer switch. An annual preventive maintenance program is recommended.
Yearly Inspection
Hazardous voltage capable of causing shock, burns, or death is used in this transfer switch.
Deenergize both Normal & Emergency power sources before performing inspections!
Clean the enclosure. Deenergize all sources, then brush and vacuum away any excessive dust accumulation. Remove moisture with a clean cloth.
Inspect the transfer switch contacts. Deenergize all sources, then remove the transfer switch barriers and check the contact condition. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully.
Maintain transfer switch lubrication. Under normal operating conditions no further lubricating is required. Renew factory lubrication if the transfer switch is subjected to severe dust, abnormal operating conditions, or if the TS coil is replaced. Order lubrication kit 75-100.
Check all cable connections & retighten them.
Torque to values shown on the transfer switch label.
Replacement Parts When ordering replacement parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch nameplate. In the US call 800-800-2726 (ASCO) or contact customercare@asco.com.
Manual Load Transfer This procedure will manually transfer the load if the controller is disconnected.
Do not manually operate the transfer switch until both power sources are disconnected: open both circuit breakers.
1. Deenergize both the normal and emergency source (open both circuit breakers).
2. Use the maintenance handle to manually operate the transfer switch to the opposite source. See pages 3 and 4, Manual Operation.
3. Close the enclosure door. If the transfer switch is in the emergency position, manually start the generator and then close the emergency source circuit breaker.
DANGER !
WARNING!
ASCO Services, Inc. (ASI) is ASCO Power Technologies� national service organization.
ASI can be contacted at 1-800-800-2726 for information on preventive maintenance agreements.
381333-406 ASCO Power Technologies Page 7
Troubleshooting
Check in Numerical Sequence Problem
1 Operation 2 Generator 3 Voltage
For 3ATS & 3ADTS the engine-generator set does not start when the transfer test button is pressed or when the Normal source fails.
The outage must be long enough to allow for the feature 1C time delay plus engine cranking and starting time.
Starting control must be in automatic position.
Batteries must be charged and connected.
Check wiring to the engine starting contacts.
For 3ATS & 3ADTS the transfer switch does not transfer the load to the emergency source after the gen-set starts.
Wait for the feature 2B time delay. For immediate transfer, press the transfer button (bypass timer). If inphase transfer is active, wait for inphase condition.
For 3NTS & 3NDTS press the transfer button.
Is the generator accepted light on?
Generator output circuit breaker must be closed.
Generator frequency must be correct.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals EA and EC (or EL1 and EL2 for 2 pole switches). *
* There are factory settings.
For 3ATS & 3ADTS the transfer switch does not transfer the load to normal source when normal returns or after transfer test.
Wait for the feature 3A time delay. For immediate retransfer, press the transfer button (bypass timer). If inphase transfer is active, wait for inphase condition.
For 3NTS & 3NDTS press the transfer button.
Voltmeter should read at least 90% of nominal phase to phase voltage between transfer switch terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches).
For 3ATS & 3ADTS the generator does not stop after load retransfer to the normal source.
Wait for the feature 2E delay.
Starting control must be in automatic position. -
For 3ADTS & 3ADTS the load is deenergized (off). Load Disconnect Timer on display.
Wait for the delayed-transition transfer timer. See User�s Guide 381333-400.
Not in auto light is always on.
For 3NTS & 3NDTS this light is always on, indicating it is a manual transfer switch.
Alert light is on.
Read the display for more information. Refer to User�s Guide 381333-400.
Page 8 ASCO Power Technologies 381333-406
INDEX
A alert light, 7 see User�s Guide 381333-400
ASI is ASCO Services Inc.
800-800-2726(ASCO)
customercare@asco.com automatic operation, 3ATS, 5 auxiliary circuits, 2
B battery, 7
C cables, power, 2 connections, 2 controller see User�s Guide 381333-400 controller ground, 3 cooldown, generator, 5, 7
D DANGER statements, 1, 2, 4, 6
E electrical operation, 5 emergency source accepted light, 4, 5 engine starting contacts, 2
F foundation, 2 frequency, 7 functional test, 3
G generator, 3, 4, 5, 7 ground, controller, 2
H harness, 2
HELP 800-800-2726(ASCO)
customercare@asco.com
I inphase transfer feature, 5, 7 inspection, 6 installation, 2 insulator backing piece, 2
WARNING, 2
L lights, 4, 5, 7 line connections, 2 load on emergency light, 4, 5 load on normal light, 4, 5 lubrication, 6
M maintenance, 6 maintenance handle, 3, 6
WARNING, 3, 6
manual load transfer, 6
WARNING, 3, 6
manual operation, 3
WARNING, 3, 6
manual transfer, 3NTS, 5 membrane controls, 4, 5 mounting, 2
N non-automatic 3NTS, 5, 7 normal source accepted light, 4, 5 not in auto light, 7
O operation, electrical, 5
P phase rotation, 4 preventive maintenance, 6 problem, 7
R rating label, 1 replacement parts, 6 retransfer button, 5, 7
S source acceptable lights, 4, 5 starting contacts, 3 starting control, 7 starting problem, 4, 7 stopping problem, 7
T terminals, 2, 3 testing power conductors, 2 time delays, 5, 7 transfer button, 5, 7 transfer problem, 7 troubleshooting, 7
V voltage checks, 4, 7
W WARNING statements, 1, 3, 5, 6
Printed in U.S.A. © ASCO Power Technologies, L.P. 2013
User’s Guide Group G Controller for Automatic & Non-Automatic Transfer Switches
50 Hanover Rd., Florham Park, NJ 07928 USA For sales or service call 800-800-2726 (ASCO) www.ascopower.com
381333-400 A
DANGER is used in this manual to warn of a hazard situation which, if not avoided, will result in death or serious injury.
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
To avoid severe equipment damage, the engine-generator set must have automatic shutdown devices, and the electrical system must have protective devices.
Refer to the manual provided with the transfer switch for installation, functional testing, and troubleshooting.
OVERVIEW
Control Overview..........................................1-1 Status Information ........................................1-2 Source Acceptability.....................................1-2 Screen Navigation ........................................1-3 Sequence of Operation diagrams
3ATS .................................................1-4
3ADTS ...............................................1-5
3NTS .................................................1-6
3NDTS ...............................................1-7
SETTINGS
Settings Overview ........................................2-1 Change a Setting, Password........................2-1 Voltage and Frequency ................................2-2 Timers....................................................2-3, 2-4 General..................................................2-5, 2-6 Features ................................................2-7, 2-8 Engine Exercisers ...............................2-9, 2-10 View Event Log ..........................................2-11 View Statistics, View About........................2-11
SCREEN MESSAGES
Screen Messages and their Meanings..3-1, 3-2 Control Messages and their Meanings.........3-3
DESCRIPTION of OPERATION
3ATS .................................................4-1
3ADTS ...............................................4-3
3NTS .................................................4-5
3NDTS ...............................................4-7
ACCESSORIES
Acc. 11BE software bundle ..........................5-1 Current, Relay, and UPS Modules ...............5-2 Load Shed – Optional Accessory 30............5-2
APPENDIX
Cover removal, DIP switches ...................... A-1 Voltage adjustment and other settings ....... A-2 Logged Events ........................................... A-3 Event Causes and Statistics Kept .............. A-4
INDEX..............................................back pages
Table of Contents
Refer to the outline and wiring drawings provided with the transfer switch for all installation and connection details and accessories.
DANGER
WARNING
CAUTION
381333-400 A ASCO Power Technologies
Overview 1-1
The Group G Controller handles the sensing, timing, and control functions for Automatic and Non-Automtatic Transfer Switches (3ATS, 3ADTS, 3NTS, 3NDTS). This microprocessor-based controller includes a user interface. All monitoring and control functions can be done with the enclosure door closed for convenience and safety. Voltage pickup and dropout settings and time delay settings can be made through a system of menus.
Control Overview
The user interface includes a graphic display, control buttons, and indicator lights. Five buttons allow access to all monitoring, control, and settings functions. Six lights show status indication of source acceptability, transfer switch position, and alerts. The screens are arranged in three levels. Access to some screens require entering a password (indicated by a closed padlock symbol).
Up-down arrows buttons The up and down arrow buttons are used to navigate the settings. These buttons also increase and decrease a value to modify a parameter while in the settings level screens.
Enter/save settings button (see page 2-1 for Are you sure? screen) The enter/save settings button moves from the status level to the Main Menu level and other levels. It also is used to select a parameter and to enter or save a new setting.
Escape button (see page 2-1 for Are you sure? screen) The escape button ignores a change and returns to the previous status level.
Transfer button (see page 2-1 for Are you sure? screen) The transfer button has several functions. Refer to the control message (bottom line) on the control status / home screen. A closed padlock symbol indicates that a password must be entered (see page 2-1).
• transfer test function simulates a failure of the normal source.
• for a 3NTS and 3NDTS, press this button to transfer or retransfer the load. See pages 3-1, 3-2, 3-3
• bypass timer function cancels an active time delay
• abort function cancels a pending operation (inphase transfer, for example)
Four transfer switch status lights (light is on when:)
• Normal source accepted (left light)
• Emergency source accepted (right light)
• Load on normal [transfer switch in normal position]
• Load on emergency [transfer switch in emergency position]
Alert light (light is on when:)
• Alert light. Read the display for more information. Any alarm condition turns on this light.
Not in automatic light (light is on when:)
• Not in automatic mode (manual); blinking indicates transfer inhibit.
For 3NTS and 3NDTS this light is always on, indicating that it is a manual transfer switch.
message lines for control status control message
User Interface
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
Overview 1-2
ASCO Power Technologies 381333-400 A
Status Information
The controller provides the status of both power sources (normal and emergency) and the position of the transfer switch. Press the up and down arrow buttons. No password is required to navigate through these screens.
ATS Status Screen The ATS status is the home screen. It shows the present status of the ATS including: transfer sequence status, and running timers, status of connected source, and position of ATS. A control message appears below the status messages. The control message instructs the user on what action is available.
All other screens automatically return to the ATS Status screen (home screen) after five minutes of inactivity.
Metering Screen One of several metering screens is provided (a factory setting). It shows the rms voltage and frequency readings of the power sources. If the current sensing option is provided, the load current is also displayed.
Alarm Screen Active alarm message appear or no active alarms. A control message appears below the alarm message. If an active alarm must be acknowledged, the screen stays on until you press enter. Some alarms are self clearing.
Controller Screen Controller information, name, location, present date and time appears. If an optional software key (dongle) is plugged into the controller, a key symbol is shown in upper right corner of this screen. Accessory 11BE is described on page 5-1.
Source Acceptability (Feature 1C time delay is described on page 2-3.)
The controller considers a source unacceptable if any of these conditions are true:
• Any phase voltage of the source is less than the voltage dropout setting for more than the Feature 1C setting.
• Any phase voltage is greater than voltage trip setting for more than 3 seconds.
• Frequency of the source is less than the frequency dropout setting for more than Feature 1C setting.
• Frequency is greater than over-frequency trip setting for more than 3 seconds.
The controller considers a source acceptable again when all these conditions are true:
• Each phase voltage is greater than the voltage pickup setting.
• Each phase voltage is less than over-voltage trip setting by more than 2% of nominal.
• The frequency of the source is greater than the frequency pickup setting.
• Frequency is less than the over-frequency trip setting by more than 2% of nominal.
3 message lines for ATS position other status
3 message lines for ATS position other status
Key indicates optional software key (dongle) installed (Accessory 11BE)
381333-400 A ASCO Power Technologies
Overview 1-3
Screen Navigation
Home /
Control Status
Metering
Event Log
Factory
Engine
Exerciser
Communication
General
Date & Time
Features
Alarms
Controller
Information
Statistics
Settings
About
Timers
Pick Up / Drop Out
Display
Other
Parameters
Common Alarms
Name & Location
Settings
Button Legend
Enter/Save
Escape
Up – Down Arrows
Password Required
Factory
Password Required
P
FP
P
P
P
P
P
P
P
P
P
P
FP
page 1-2 page 2-11 pages 2-9
2-10 page 2-11 page 2-11 pages 2-3 2-4 pages 2-5 2-6 pages 2-7 2-8 page 2-2
Overview
General
Main Menu
Overview 1-4
ASCO Power Technologies 381333-400 A
3ATS Sequence of Operation – Normal Source Failure
Normal source unacceptable (see page 1-2)
Normal source acceptable
Load on Normal.
Observe the indicator lights
Automatic start of emergency generator
Emergency acceptable
Electrical loads switched to generator
Load switched back to Normal source.
Generator stops status messages
Waiting for Normal source to return
Emergency generator starting
Emergency accepted light comes on
Load on emergency light comes on Normal source accepted light comes on
Load on Normal light comes on
* To bypass Feature 31G if Emergency fails, set it to yes in Features settings.
** To bypass Feature 31F if Normal fails, set it to yes in Features settings.
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
See page 2-3 for Feature 1C, 2B, 2E, 3A, 31F, 31G time delays Legend light is on light is off time delay
Feature 3A time delay, if used
Feature 31G time delay, if used*
All lights off
Generator runs unloaded for Feature 2E time delay
Normal source acceptable
Feature 2B time delay, if used
Feature 31F time delay, if used.**
381333-400 A ASCO Power Technologies
Overview 1-5
3ADTS Sequence of Operation – Normal Source Failure switch lights are off during the delayed transition transfer time delay
Emergency generator starting
Waiting for Normal source to return
Normal source acceptable
Load on Normal.
Automatic start of the emergency generator
Normal source unacceptable (see page 1-2)
Emergency acceptable
Electrical loads switched to generator
Load switched back to Normal source
Generator stops status messages switch lights are off during the delayed transition transfer time delay
Emergency accepted light comes on
Normal source accepted light comes on
*To bypass Feature 31G if Emergency fails, set it to yes in Features settings.
**To bypass Feature 31F if Normal fails, set it to yes in Features settings.
Observe the indicator lights
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
Load on emergency light comes on
Load on Normal light comes on
See page 2-3 for Feature 1C, 2B, 2E, 3A, 31F, 31G time delays Legend light is off
Feature 3A time delay, if used
Feature 31G time delay, if used*
All lights off
Generator runs unloaded for Feature 2E time delay
Feature 2B time delay, if used
Feature 31F time delay, if used.**
Normal source acceptable
Overview 1-6
ASCO Power Technologies 381333-400 A
3NTS Sequence of Operation – Normal Source Failure
Load on Normal.
Manually start the generator (at generator)
Normal source unacceptable (see page 1-2).
Emergency acceptable
Normal source acceptable
Let the generator run unloaded for cooldown*
Stop the generator status messages
Emergency generator starting transfer button
* Follow the generator manufacturer’s recommendations.
Observe the indicator lights
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
Emergency accepted light comes on
Normal source accepted light comes on
Load on emergency light comes on
Waiting for Normal source to return
Press transfer button to transfer load to gen.
Load on Normal light comes on
Press transfer button to transfer load to normal
See page 2-3 for time delays (usually set to zero for 3NTS) Legend light is off time delay press transfer button
All lights off
Feature 2B time delay, if used
Feature 3A time delay, if used
381333-400 A ASCO Power Technologies
Overview 1-7
3NDTS Sequence of Operation – Normal Source Failure
Load on Normal.
Emergency acceptable
Let the generator run unloaded for cooldown*
Stop the generator status messages
Emergency generator starting switch lights are off during the delayed transition transfer time delay switch lights are off during the delayed transition transfer time delay
* Follow the generator manufacturer’s recommendations.
Normal source accepted light comes on Load on emergency light comes on
Oberve the indicator lights
Load on Normal
Load on Emergency
Normal Source Accepted
Emergency Source Accepted
Load on Normal light comes on
See page 2-3 for time delays (usually set to zero for 3NDTS) Legend light is on light is off time delay press transfer button transfer button
Manually start the generator (at generator)
Press transfer button to transfer load to gen.
Press transfer button to transfer load to normal
Feature 2B
Normal source unacceptable (see page 1-2).
All lights off
Feature 3A
Waiting for Normal source to return
Emergency accepted light comes on
ASCO Power Technologies 381333-400 A
Settings 2-1
Settings Overview (Main Menu Settings)
Any indiscriminate change in these settings may affect the normal operation of the transfer switch. This change could allow the load circuits to remain connected to an inadequate source.
The settings can be displayed and changed from the user interface. Some settings may required a password.
1. On the ATS Status screen, press the enter/save button to display to the Main Menu screen.
2. On the Main Menu screen, press the up or down arrow buttons to select Settings, then press the enter/save button.
3. On the Settings screen, press the up or down arrow buttons to select a parameter, then press the enter/save button.
Change a Setting
To change a setting in the controller:
1. Navigate to the settings screen that you want to change.
2. Press the enter/save settings button to start the first field blinking. If required, enter the password.
3. Press the up and down arrow buttons to change the flashing digit(s) or word, and press the enter/save settings button to move to the next field.
4. Repeat step 3 until all the fields have been entered.
NOTE If a field is blinking, information must be entered. The escape button will end the editing session.
Password The default password is 1111 (see pages 2-5, 2-6).
If Enter Password displays, you must enter the correct password first.
Use the up and down arrow buttons to change the flashing digit of the password. Press the enter/save settings button to move to the next digit (left to right). The password is accepted when all four digits have been entered correctly and the enter/save settings button is pressed.
If Login Error Invalid Password displays, press the enter/save settings button to reenter the password.
You can now change the settings on the selected screen.
NOTE Once the password is entered, it will stay unlocked for 5 minutes so that you do not have to keep entering
it. To save time, plan to make all your settings at one time.
If no password is desired, set the password to 0000. This password unlocks the controller so that anyone can change the settings and transfer the load without entering a password. Instead, the Are you sure? screen appears.
Are you sure?
Once the correct password is entered, the controller stays unlocked for 5 minutes. During that time period if you press the transfer button, the Are You Sure? screen appears (instead of Enter Password).
You can:
▪ press the enter/save button to confirm (commit) load transfer, or
▪ press the escape button to cancel the load transfer operation.
Settings 2-2
381333-400 A ASCO Power Technologies
Voltage and Frequency Settings (Main Menu Settings Pick Up / Drop Out)
Unless otherwise specified on the order, the voltage and frequency settings are set at the factory to the default values. If a setting must be changed follow the procedure below. Some settings may require a password.
Any indiscriminate change in these settings may affect the normal operation of the transfer switch. This
Description Settings Default Setting % of nominal
Adjustment Range increments of 1%
Display Screen (see below)
Dropout 85% 70 to 98% N Volt DO Pickup 90% 85 to 100% N Volt PU
Normal Source Voltage Over Voltage Trip* off off, 102 to 115% N Volt OV
Dropout 75% 70 to 98% E Volt DO Pickup 90% 85 to 100 E Volt PU
Emergency Source Voltage Over Voltage Trip* off off, 102 to 115% E Volt OV
Dropout 85% 85 to 98% N Freq DO Pickup 86% 86 to 100% N Freq PU
Normal Source
Frequency Over Frequency Trip* off off, 101 to 110% N Freq OF Dropout 85% 85 to 98% E Freq DO Pickup 95% 86 to 100% E Freq PU
Emergency Source
Frequency Over Frequency Trip* off off, 101 to 110% E Freq OF
* The Over Voltage and Over Frequency reset is fixed at 2% below the trip setting.
The voltage and frequency settings can be displayed and changed from the user interface. See the table above.
Some settings may require a password.
1. On the Main Menu press the up or down arrow buttons to select Settings, then press the enter/save button to move to the Settings level of menus.
2. Press the up and down arrow buttons to highlight Pickup / Dropout, then press the enter/save settings button to move to the PU/DO display.
3. Then you can press the up and down arrow buttons to highlight the voltage and frequency settings screens.
An overview explanation of the settings is listed below.
Description Explanation
Normal Source Voltage
This screen shows dropout, pickup, and over-voltage trip settings for the normal source.
They are in percentage of the nominal voltage and volts rms.
Emergency Source Voltage
This screen shows dropout, pickup, and over-voltage trip settings for the emergency source.
They are in percentage of the nominal voltage and volts rms.
Normal Source
Frequency
This screen shows dropout, pickup, and over-frequency trip settings for the normal source.
They are in percentage of the nominal frequency and Hz.
Emergency Source
Frequency
This screen shows dropout, pickup, and over-frequency trip settings for the emergency source. They are in percentage of the nominal frequency and Hz.
ASCO Power Technologies 381333-400 A
Settings 2-3
Timer Settings (Main Menu Settings Timers)
Unless otherwise specified on the order, the timer (time delay) settings are set at the factory to the default values.
If a setting must be changed, carefully follow the procedure on the next page. Some settings may require a password.
Any indiscriminate change in these settings may affect the normal operation of the transfer switch. This
Feature Timer Default Setting Adjustment Range 1 sec. increments
Display Screen (see next page)
1C override momentary Normal source outages 3 seconds 0 to 6 sec see NOTICE below N Fail (1C)
1F override momentary Emergency source outages 4 seconds 0 to 6 sec see NOTICE below E Fail (1F) transfer to Emergency (if Normal fails) 0 0 to 60 min 59 sec N E N Fail (2B)
2B transfer to Emergency (if just a test) 0 0 to 60 min 59 sec N E Test (2B)
2E engine cooldown 5 minutes 0 to 60 min 59 sec Cool Down (2E) Retransfer to Normal
(if Normal fails) 30 minutes 0 to 60 min 59 sec E N N Fail (3A) 3A Retransfer to Normal
(if just a test) 30 seconds 0 to 9 hours 59 min 59 sec E N Test (3A)
31F Normal to Emergency pre-transfer signal 0 0 to 5 min 59 sec N E PreX (31F)
31G Emergency to Normal pre-transfer signal 0 0 to 5 min 59 sec E N PreX (31G)
31M Normal to Emergency post-transfer signal 0 0 to 5 min 59 sec N E PosX (31M)
31N Emergency to Normal post-transfer signal 0 0 to 5 min 59 sec E N PosX (31N)
Inphase inphase transfer 1.5 seconds 0 to 3 sec In-Phase Load disconnect delay transition transfer 3 seconds 0 to 5 min 59 sec LD Disconnect Fail accept maximum failure to accept Emergency source alarm 3 seconds 0 to 6 sec see NOTICE below E Accept Fail
Standard adjustment up to 6 seconds (total power outage). See NOTICE below.
To bypass Feature 31F if the Normal source fails, set bypass to yes in Features settings (page 2-7).
To bypass Feature 31G if the Emergency source fails, set bypass to yes in Features settings (page 2-7).
This timer appears only on the display for a 3ATS or 3NTS. Allows time for generator to stabilize before initiating inphase transfer.
This timer appears only on the display for a 3ADTS or 3NDTS.
To bypass load disconnect timer on source failures, set bypass to yes in Feature settings (page 2-7).
This timer is disabled on 3NTS and 3NDTS.
Feature 1C, 1F, and Fail accept maximum timers can be extended to 0 to 60 min 59 sec if an external 24 V dc power supply is included and the External Battery check box is selected (General Settings, Other Parameters, page 2-5). Accessory 1UP is available (page 5-2) if longer than 6 seconds is required.
Settings 2-4
381333-400 A ASCO Power Technologies
Timer Settings continued (Main Menu Settings Timers)
The timer (time delay) settings can be displayed and changed from the user interface. See the table on the previous page. Some settings may require a password.
1. On the Main Menu press the up and down arrow buttons to highlight Settings, then press the enter/save button to move to the Settings menus.
2. Press the up and down arrow buttons to highlight Timers, then press the enter/save settings button to move to the list of timers.
3. Then you can press the up and down arrow buttons to highlight the timer settings displays. An overview explanation of the settings is listed below.
Display Screen Explanation
N Fail (1C) Momentary Normal source failure timer. It can be bypassed by pressing the transfer / bypass button.
E Fail (1F) Momentary Emergency source failure timer.
N E N Fail (2B) Normal to Emergency transfer timer (when normal source fails). It can be bypassed by pressing the transfer / bypass button.
N E Test (2B) Normal to Emergency transfer timer (when transfer button is pressed).
Cool Down (2E) Engine cool down timer does not run if the load was not transferred. It cannot be bypassed.
E N N Fail (3A) Emergency to Normal retransfer timer (when normal source fails). It can be bypassed by pressing the transfer / bypass button.
E N Test (3A) Emergency to Normal retransfer timer (when transfer button is pressed).
N E PreX (31F)
Normal to Emergency pre-transfer signal timer for external equipment. When this timer is running, the transfer can be aborted by pressing the transfer / bypass button.
If the in-phase feature is enabled, load transfer is prevented until the condition is met. To bypass Feature 31F if the Normal source fails, set bypass to yes in the Feature settings.
E N PreX (31G)
Emergency to Normal pre-transfer signal timer for external equipment. If the in-phase feature is enabled, load transfer is prevented until the condition is met. To bypass Feature 31G if the Emergency source fails, set bypass to yes in the Feature settings.
N E PosX (31M) Normal to Emergency post-transfer signal timer for external equipment.
E N PosX (31N) Emergency to Normal post-transfer signal timer for external equipment.
In-Phase In-phase timer precedes inphase transfers, if provided. Not available for 3ADTS, 3NDTS.
LD Disconnect Load disconnect timer only for 3ADTS, 3NDTS delayed-transition transfer switch.
The load is not connected to either source.
E Accept Fail Failure to accept the Emergency source alarm timer turns on alert light when alarm expires
ASCO Power Technologies 381333-400 A
Settings 2-5
General Settings (Main Menu Settings General)
Unless otherwise specified on the order, the general settings are set at the factory to the default values.
Parameter Sub Level Default Setting Adjustment Range Display Screen
(see next page) Time hh:mm:ss 01-23:00 - 59:00-59 hh:mm:ss Date day mm/dd/yy 01-12 / 01-31 / 00-99 day mm/dd/yy
Format US
US
ISO
EU
mm/dd/yy yy/mm/dd dd/mm/yy Date & Time
Daylight Savings Time Off Off
Apr/Oct Mar/Nov
Off Apr/Oct Mar/Nov
Baud Rate 9600
115200 57600 38400 19200 Off
115200 57600 38400 19200 Off
Device Address (Dev Addr) 1 1 - 247 1 - 247
Protocol AscoBusII AscoBusII AscoBusI Modbus
AscoBusII AscoBusI Modbus
Communication
– RS485 Port
(optional Accessory 11BE)
Emulate Grp1 no yes or no or
Language English
English Korean Chinese Turkish Russian German Italian
Portuguese French Canadian
French Spanish
English Korean Chinese Turkish Russian German Italian
Portuguese French CAN
French Spanish
Contrast 15 1 to 20 1 to 20 Backlight On On, Off, 1 to 59 On, Off, 1 to 59
Volt Label Vab/bc/ca Vab/bc/ca Uab/bc/ca Uuv/vw/wu
Vab/bc/ca Uab/bc/ca Uuv/vw/wu
Display
Source 1/2 no yes or no or Password 1111 a-z, A-Z, 0-9, 4 characters * * * *
External Battery no yes or no or Current Sensing (accessory) Off Off, 1CT, 2CT, 3CT Off, 1CT, 2CT, 3CT
CT Ratio 400:5 50 - 4000:5 50 - 4000:5
Other Parameters
Clear Events (accessory) Loss E when on E no yes or no or
E accept Fail no yes or no or Common Alarms
Load Disconnected no yes or no or Name a-z, A-Z, 0-9, space, 20 char Name & Location Location a-z, A-Z, 0-9, space, 20 char
When Emulate Grp1 box is checked, baud rate is 9600 and protocol is AscoBusII.
Source 1/2 only available for English language.
Load Disconnected appears only on the display for a 3ADTS, 3NDTS.
The alert light also turns on for common alarms.
Settings 2-6
381333-400 A ASCO Power Technologies
General Settings continued (Main Menu Settings General)
The general settings can be displayed and changed from the user interface. See the table on the previous page.
If a setting must be changed follow the procedure below. Some settings may require a password.
1. From the Main Menu press the up and down arrow buttons to highlight Settings, then press the enter/save
2. Press the up and down arrow buttons to highlight General, then press the enter/save settings button to move to the list of general settings.
3. Then you can press the up and down arrow buttons to highlight the general settings displays. An overview
Parameter Explanation
Date & Time This screen allows the user to change the time, date, date format, and daylight savings time.
Communication (Accessory 11BE)
If optional Accessory 11BE was ordered, this screen allows the user to configure the RS485 communication port. The baud rate can be set off, 9600 – 115200. The address can be set 1 to 247. See the Appendix for setting DIP switches S7 and S8. S7 sets the terminating resistor; S8 sets 2 wire or 4 wire.
Display This screen selects the language for messages (English is the default language). Screen contrast can be set. Three voltage phase labels can be set. Source 1/2 (S1/S2) can be set instead of Normal and Emergency (N/E).
Other Parameters
This screen allows the user to change the password (default password is 1111).
There is a setting for an external battery (if connected) for Feature 1C or 1F extended time range.
If the optional current sensing module is installed, current sensing should be set for single phase or three phase. The current transformer (CT) ratio should be set for the ampere size of the transfer switch (refer to the label on the CT used). See current transformer WARNING below.
All events can be cleared from the controller, if desired.
This screen shows selected alarm conditions. If enabled, the alarm condition will turn on the alert indicator and deenergize the configured common alarm output relays (OP1, OP2, OP3) for external monitoring.
Loss E when on E Loss of emergency when connected to Emergency.
E Accept Fail Expiration of failure to accept timer (failure to acquire emergency source)
Common Alarms
Load Disconnect For 3ADTS and 3NDTS only.
Name & Location
This screen allows the user to enter a name and location of the Transfer Switch (maximum 20 alphanumeric characters each). If communication is used, the name and location is exported (for ASCO bus II protocol name has an 8 character limit).
The name & location parameter is not available (disabled) if English language is not selected.
Never leave an open secondary circuit of a current transformer. Dangerous voltage can cause shocks, burns, and/or death. When disconnected always install a shorting jumper between the current transformer terminals.
WARNING
ASCO Power Technologies 381333-400 A
Settings 2-7
Features Settings (Main Menu Settings Features)
Unless otherwise specified on the order, the features settings are set at the factory to the default values. If a setting must be changed follow the procedure on the next page. Some settings may require a password.
Any indiscriminate change in these settings may affect the normal operation of the transfer switch. This
Feature Default Setting Adjustment Range Display Screen (see next page)
Bypass Normal to Emergency transfer Feature 31 upon
Normal source failure no yes or no BP N E F31 N Fail
Bypass Emergency to Normal transfer Feature 31 upon Emergency source failure no yes or no BP E N F31 E Fail
Bypass delayed-transition transfer upon a source failure no yes or no BP DTTS Src Fail
Commit to transfer no yes or no Commit Transfer Inphase monitor enable no yes or no In Phase On
Load Shed Inphase enable no yes or no Load Shed In Phase Fail Accept Timer no yes or no Fail Accept Timer
External Feature 6B no yes or no Ext. Feature 6B External Feature 17 no yes or no Ext. Feature 17 yes yes or no Feature 31 no yes or no Common Alarm no yes or no NR2
Controller Output contact OP1 (select one) no yes or no Not In Auto no yes or no Feature 31 yes yes or no Common Alarm no yes or no NR2 no yes or no Not In Auto
Relay Expansion Module Output contact OP2
(select one) no yes or no 1G no yes or no Feature 31 no yes or no Common Alarm no yes or no NR2
Relay Expansion Module Output contact OP3
(select one) yes yes or no Not In Auto no yes or no Manual Manual DTTS
Load Disconnect Recovery Mode yes yes or no Auto
This feature appears only on the display for a 3ADTS.
This feature appears only on the display for a 3ATS.
This feature appears only on the display for a 3ATS or 3ADTS, not on a 3NTS or 3NDTS.
The Controller Output contact OP1 can be set to operate with a Common Alarm only if Accessory 11BE is ordered. See page 5-1.
The Relay Expansion Module is optional Accessory 18RX for 3ATS and 3NTS. It is included with a 3ADTS and
3NDTS. See page 5-2.
This feature appears only on the display for a 3NDTS.
Settings 2-8
381333-400 A ASCO Power Technologies
Features Settings continued (Main Menu Settings Features)
The features settings can be displayed and changed from the user interface. See the table on the previous page.
Some settings may require a password.
1. From the Main Menu press the up and down arrow buttons to highlight Settings, then press the enter/save
2. Press the up and down arrow buttons to highlight Features, then press the enter/save settings button to move to the list of features.
3. Then you can press the up and down arrow buttons to highlight the feature settings displays. An overview
Display Screen Explanation
BP N E F31 N Fail This display shows the setting for bypass Normal to Emergency transfer Feature 31 if the Normal source fails. If set to yes, there is no delay.
BP E N F31 E Fail This display shows the setting for bypass Emergency to Normal transfer Feature 31 if the Emergency source fails.
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .