This document is a Marine Surveyor's Barge Inspection Report for the State of Maryland, Department of Natural Resources, Engineering and Construction Division. The report details the inspection and assessment of the 60-foot steel hopper/utility barge "Baltimore", including the condition of the hull, deck, framing, spuds, and interior compartments. The inspection found significant corrosion and metal loss on the hull sides and bottom, requiring replacement of steel plates from the lower rub rail to the chine on the port and starboard sides, as well as the forward and aft rakes. Additional recommendations include replacing cables for the two hydraulic winches, repairing the spud, and coating/painting the exterior once repairs are completed.
Based on the inspection findings, the state agency has issued a contract opportunity for sand/steel, grit/wet blasting, modification, repair, and restoration services to the three steel spud utility deck barges, in alignment with the surveyor's recommendations. The contract will require the awarded vendor to perform the necessary repairs and maintenance to restore the barges to serviceable condition.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
“BALTIMORE”
Capt. Phineas T. McHenry, Ltd.
Marine Surveyor
38 Oak Hill Lane
Elkton, MD 21921
443-350-6168 www.kenhenrymarinesurvey.com khenry1492@verizon.net http://www.kenhenrymarinesurvey.com/
MARINE SURVEYOR ⬧ MARINE CONSULTANT
38 OAK HILL LANE ⬧ ELKTON, MD 21921
BARGE INSPECTION
REPORT NO. 5793 JUNE 29, 2022
TO WHOM IT MAY CONCERN: This is to certify that the undersigned surveyor at the request of Kelly Wright, State of Maryland, Department of Natural Resources, Engineering and
Construction Division, 580 Taylor Avenue, D-3, Annapolis, Maryland, 21401, attended the barge out of the water at DNR E/C Terminal, 301 Cemetery Avenue, Cambridge, Maryland, 21613, on the 21st and 29th days of June in the year 2022, and did an inspection of the deck, hull sides, bottom, and interior to determine overall condition and establish areas of repair.
DESCRIPTION
The steel barge is called “Baltimore”. The barge is a hopper/utility barge with fore and aft rakes.
The barge was built in the year 1990. The barge’s approximate measurements are as following:
LOA 60’0”, BEAM 24’0”, FROM WATERLINE TO DECK GUNWALE 4’4”, and DRAFT 2’0”.
The transverse trusses are 2” x 3” x .250” placed at 24” centers. The vertical stanchions are 3” x
5” x .250” channel. The diagonal stanchions are 2” x 2” x .250” channel. The bottom frames are
2” x 3” x .250” placed at 24” centers. The barge has soft chines. The 5/16” (.3125”) steel plates were used in the construction of the deck, hull sides and bottom. A standard of 20% metal loss is being used with ultrasound gauge error of 0.025. Any readings lower than .250” is below acceptable level.
PORT HULL SIDE - EXTERIOR
This area starts at the bow from the water line to the bottom of the vessel. I noted that on port side the weld seams have heavy stay current and significant metal loss.
Capt. Phineas McHenry, Ltd.
Marine Surveyor June 29, 2022
BARGE INSPECTION REPORT #5793 PAGE 2 of 31
PORT HULL SIDE – EXTERIOR (cont.)
There is a stainless steel washer with bolt that was used to stop a leak as shown on the left side picture. The right side picture shows very deep crevice pitting and significant metal loss. A reading of .292” was taken beside the pitted areas at the two foot mark. Note, that in the left side picture there are two ultra sound readings: one is .117” and the other is .118”, which indicates a very thin area of metal. This reading was taken at the four foot mark.
The picture on the left shows the degree of metal loss from stray current. The picture on the right shows the amount of exterior scaling.
Marine Surveyor June 29, 2022
BARGE INSPECTION REPORT #5793 PAGE 3 of 31
1) At the 6 foot mark and 12 inches from the bottom, the reading was .146” and at the 7 foot mark, there was a reading of .221”.
2) At the 12 foot mark, there is heavy scaling and pitting a with a reading of .305”. This reading was taken beside a pitted area.
3) The picture on the upper left side shows a reading of .289” approximately 5 inches from the bottom. Also note the heavy scaling.
4) At the 15 foot mark, there is a reading of .249”.
5) From 15’6” mark to the 20’ mark, there is heavy scaling and pitting.
6) At the 20’ mark, test reading down by the chine shows .306”, and just above that reading, it read .304”, as shown in the left hand lower picture.
Marine Surveyor June 29, 2022
BARGE INSPECTION REPORT #5793 PAGE 4 of 31
7) At 31’, the reading was .313”.
8) In the picture below on the left side shows a bolted on steel plate patch at 42’ with a reading of
.208”.
Marine Surveyor June 29, 2022
BARGE INSPECTION REPORT #5793 PAGE 5 of 31
9) At 44’, there is a reading of .286”. Down at the chine, there is pitting and very deep pitting near the 45’ mark.
10) Between 42’ to 46’, the hull is rusting, scaling, and pitting. At 46’, a reading of .319”.
11) At 47’ a reading of .320”, at 48’ a reading of .320”, and at 51’ a reading of .325”.
12) From 51’ to 53’, which includes the slant of the chine, show deteriorated steel and welds.
Marine Surveyor June 29, 2022
BARGE INSPECTION REPORT #5793 PAGE 6 of 31
STARBOARD HULL SIDE
On the starboard side, the weld seam has heavy metal loss as shown on the lower right hand picture.
1) A .146” reading on the starboard side by the chine. I also noted heavy pitting at the lower end of the rake.
2) The picture below on the left side shows a random reading of .112” located down at the base of the rake on the hull side .
Note; that the facing of the bow is different due to the barge being turned in order to the back aft of the inspection.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 7 of 31
STARBOARD HULL SIDE EXTERIOR (cont.)
The picture on the upper left hand side show the thickness of the hull above the upper rub rail.
The picture on the upper right hand side shows deep pitting concentration and heavy rusting, between the 7’ and 8’ markings.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 8 of 31
The two picture above run from 10’ mark to the 14’ mark with random readings of .316” at the 10’ mark and .295” 13’ mark. There is also a considerable amount of pitting and corrosion.
The above pictures are showing heavy and deep pitting from stray current.
Extreme metal loss on the chine along with heavy pitting around the 24’ mark. Running from the 26’ line up the 27’ mark, there is heavy pitting. In this area, there are readings .326” at the 25’ mark and .312” at the 27’ mark.
The pictures below shows scaling and pitting of the hull below the water line . The vertical weld seam has taken a hit from stray current as well.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 9 of 31
There was a .283” reading between the 36’ and 37’ marks. A .270” at the 38’ mark
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 10 of 31
From the 41’ mark going forward to 44’, there is heavy scaling with pitting. A reading at 41’ mark was .286”.
At the 48’ to 50’, .312” and .293”. A .267” at the 49’6”.
The underside of the starboard lower rub rail has stray current damage. Test reading on rub rail was .388”.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 11 of 31
FORWARD RAKE EXTERIOR
The rub rail on the starboard side is pushed inward as shown on the picture below.
The forward rake was covers with a thick layer of barnacles. The barnacles were removed in several areas for inspection. The weld seams that are eaten away by stray current, pitting ,and some scaling. Note: a review of the original report, which was dated May 2018, shows heavy pitting. At the time of the previous report, the hull was sand blasted.
There is a bolt and washer repair as shown on the right side picture.
The ultra sound reading on the left side picture shows a fair reading of .324”. The reading on the starboard side was .305”.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 12 of 31
AFT RAKE EXTERIOR
The tabs that support the chaffing gear for the bow insert are in very poor condition and will be to be replaced.
There was a fair amount of pitting on the transom below the water line. Also, there are rust blooms above the water line.
There also was a fair amount of marine growth on the transom.
The cut out readings were . 317” port side, .310” center, and .312” starboard side. These readings were found to be satisfactory. However, there was still the rust blooms and pitting.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 13 of 31
BOTTOM EXTERIOR
Bottom was heavily coated with barnacles. Several areas were randomly scraped for inspection.
Noted loss of bottom paint along with rusting of the bottom. The interior was ultra sounded for a better idea of the overall condition of the bottom.
DECK
The deck appears to be in satisfactory condition with light rusting and some oil canning of the deck. The deck has very little paint protection. Radom ultra sound reading taken the bow is .319” six feet in from the starboard side. Going back from the bow sixteen feet and four feet in from the coming .314”. On the starboard side sixteen feet aft of the bow and five feet from the coaming, there is a reading of .296”.
The catwalks were found to be in good condition.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 14 of 31
SPUDS: Noted on deck there are two steel spuds: one is 25’ long and one has the end cut off and measures 21’ 9”. The lower end was cut off.
The 25’ spud forward end wing is bent. The mounting holes are corroded and in poor condition.
Both units are rusted with no protective coatings.
The spud tubes have some light rusting and scaling at the base. The weld appears to be in good order.
MANHOLES: four manholes: two on each side located outboard of the coaming. There are four
Barier aluminum flush mount hatches. The hatch seals were replaced at the time of my inspection.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 15 of 31
DECK RING AND HATCHES
All hatches and deck rings are in good condition
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 16 of 31
COAMING: steel coaming with cap and 25 vertical support. The forward end of the coaming is open. The forward section on both port and starboard sides is rusted at the bottom. The coaming cap is distorted and damaged.
DECK HARDWARE
Twenty-four inch kevel cleats and two horn bitts, which are well secured with no defects noted.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 17 of 31
WINCHES: the vessel is equipped with two Pull Master hydraulic winches. Serial number on the aft winch is 92125; the forward winch ID plate is missing. The winches are well secured. The cables are in poor condition. The winches were not tested for operation.
FORWARD WINCH AFT WINCH
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 18 of 31
INTERIOR COMPARTMENT #1 - FORWARD RAKE
The steel framing in compartment #1 is in good condition. The bottom frames and side frames and the first 12” of the vertical stanchions are heavily rusted.
The underside of the deck and upper portion of the framing still holds most of its protective coating.
The bottom has standing water and sludge. Due to buildup of biologic marine growth on the exterior bottom and standing water and sludge in the interior of compartment, ultrasounds were taken where accessible from the interior. The bottom frames make a 2’x 4” grid. All readings were taken close to center creating a 2’x 4’ grid pattern. From a visual inspection and ultrasound reading, there is no need for steel replacement in compartment #1. However, located at Bay #4 frame #4 is a reading of .280”. This reading is .005” below the normal metal loss. Compartment
#1 will need to be pumped dry, all steel cleaned, and new protective coating applied to all surfaces.
FORWARD RAKE BOTTOM
FORWARD RAKE DECK
BH BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6 BAY 7 BAY 8 BAY 9 BAY 10 BAY 11 BAY 12 BH
4 0.320 0.315 0.315 0.280 0.310 0.310 0.310 0.360 0.305 0.315 0.310 Water 4
3 Water Water Water Water Water Water Water Water Water Water Water Water 3
2 Water 0.300 Water 0.300 Water 0.300 0.295 Water Water Water Water Water 2
1 0.300 N/A 0.295 N/A 0.290 N/A 0.315 0.295 0.310 0.305 0.310 0.315 1
HL N/A N/A N/A 0.330 N/A N/A N/A N/A N/A N/A N/A N/A HL
P
O
R
T
S
T
A
R
FRONT
BH BAY 1 BAY2 BAY3 BAY 4 BAY 5 BAY 6 BAY 7 BAY 8 BAY 9 BAY 10 BAY 11 BAY 12 BH
4 Hatch N/A 0.310 N/A 0.270 0.285 0.305 0.315 0.320 0.320 0.310 N/A 4
3 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 3
2 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 2
1 N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A 1
HL N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A HL
S
T
A
R
P
O
R
T
FRONT
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 19 of 31
COMPARTMENT #1 FORWARD - RAKE (cont.)
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 20 of 31
INTERIOR COMPARTMENT #2
Compartment #2 is in fair condition. The steel framing is heavily scaling. However, the scaling appears to be the protective coating. There was no significant metal loss detected to the steel framing. However, there were three concrete patches, water, and sludge and the exterior of bottom has biological marine growth. The interior bottom frames make a 2’x 4’ grid pattern and was used to take ultrasound reading creating a 2’x 4’ ultrasound pattern. There appears to be multiple areas of the bottom that will need to be replaced. Note, the areas of replacement. Each area of replacement is 2’x 4’. Compartment #2 will need to be pumped dry all steel cleaned and new protective coating applied to all surfaces.
a) Bay #1 at frame #9
b) Bay #2 at frame #9
c) Bay #6 at frame #9
d) Bay #3 at frame #6
e) Bay #5 at frame #6
f) Bay #2 at frame #5
g) Bay #5 at frame #5
h) Bay #4 at frame #3
COMPARTMENT # 2 BOTTOM
BH BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6 BH
9 Concrete Concrete Water Water 0.285 0.235 9
8 0.300 0.295 Water Water 0.290 0.305 8
7 0.300 0.295 0.305 Water 0.300 0.310 7
6 0.300 0.305 Concrete 0.290 0.250 0.290 6
5 0.305 0.245 0.305 Water 0.280 0.300 5
4 0.315 0.305 0.300 0.310 0.360 0.300 4
3 0.315 0.305 0.305 0.260 0.310 0.290 3
2 Water 0.295 0.300 0.310 Water Water 2
1 Water Water Water Water Water Water 1
BH Water Water Water Water Water Water BH
S
T
A
R
B
O
A
R
D
P
O
R
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 21 of 31
INTERIOR COMPARTMENT #2 (cont.)
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 22 of 31
INTERIOR COMPARTMENT #2 (cont.)
The decking over compartment #2 appears to be in fair condition. Ultrasound readings were taken from the interior using the 2’x 4’ grid pattern that the deck frames make. Bay #3 frame #4 reading falls .005 below exceptable metal loss. Note, area of replacement is 2’x 4’.
COMPARTMENT # 2 DECK
BH BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6 BH
9 Hatch 0.320 0.315 0.320 0.320 0.320 9
8 0.320 0.315 0.315 0.315 0.315 0.320 8
7 0.325 0.305 0.310 0.325 0.320 0.320 7
6 0.325 0.315 0.310 0.310 0.320 0.320 6
5 0.325 0.300 0.320 0.320 0.320 0.320 5
4 0.325 0.320 0.320 0.280 0.315 0.320 4
3 0.325 0.310 0.305 0.320 0.315 0.320 3
2 0.325 0.285 0.310 0.320 0.320 0.320 2
1 0.325 0.320 0.320 0.290 0.320 0.325 1
BH 0.325 0.310 0.320 0.320 0.320 N/A BH
S
T
A
R
B
O
A
R
D
P
O
R
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 23 of 31
INTERIOR COMPARTMENT #3
Compartment #3 is in fair condition. The steel framing has lightly scaling. The bottom is heavily scaling. There was no significant metal loss detected to the steel framing. The bottom has standing water and sludge, and the exterior of bottom has biological marine growth. The interior bottom frames make a 2’x 4’ grid pattern and was used to take ultrasound reading creating a 2’x 4’ ultrasound pattern. There appears to be multiple areas of the bottom that will need to be replaced.
Note, the areas of replacement. Each area of replacement is 2’x 4’. Compartment #3 will need to be pumped dry all steel cleaned and new protective coating applied to all surfaces.
a) Bay #6 at frame #8
b) Bay #5 at frame #3
c) Bay #1 at frame #2
COMPARTMENT # 3 BOTTOM
BH BAY 6 BAY 5 BAY 4 BAY 3 BAY 2 BAY 1 BH
9 0.305 Water Water 0.300 0.335 9
8 0.280 0.300 Water Water 0.310 0.310 8
7 0.285 0.295 0.290 Water 0.305 0.310 7
6 0.290 0.300 0.310 Water 0.310 0.305 6
5 0.340 0.290 Water Water 0.315 0.300 5
4 0.290 0.305 Water Water 0.300 0.290 4
3 0.300 0.280 Water Water 0.305 0.320 3
2 0.295 0.300 Water Water 0.310 0.280 2
1 0.295 0.295 0.285 Water 0.300 0.315 1
BH Water Water Water Water Water Water BH
S
T
A
R
B
O
A
R
D
P
O
R
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 24 of 31
INTERIOR COMPARTMENT #3 (cont.)
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 25 of 31
COMPARTMENT #3 (cont.)
The decking over compartment #3 appears to be in fair condition. Ultrasound readings were taken from the interior using the 2’x 4’ grid pattern that the deck framing makes.
COMPARTMENT # 3 DECK
BH BAY 6 BAY 5 BAY 4 BAY 3 BAY 2 BAY 1 BH
9 0.320 0.305 N/A 0.320 0.315 0.320 9
8 0.325 0.320 0.315 0.320 0.315 0.320 8
7 0.325 0.315 0.315 0.310 0.315 0.320 7
6 0.325 0.320 0.315 0.310 0.315 0.325 6
5 0.325 0.325 0.320 0.310 0.320 0.320 5
4 0.290 0.325 0.320 0.320 0.340 0.340 4
3 0.295 0.320 0.315 0.320 0.320 0.325 3
2 0.320 0.320 0.320 0.320 0.325 0.325 2
1 0.295 0.315 0.320 0.315 0.320 0.320 1
BH N/A 0.320 N/A 0.305 0.320 Hatch BH
S
T
A
R
B
O
A
R
D
P
O
R
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 26 of 31
INTERIOR COMPARTMENT #4 - AFT RAKE
The steel framing in compartment #4 is in good condition. The bottom frames, side frames, and the first 16” of the vertical stanchions are lightly rusted. The bottom has standing water and sludge. The underside of the deck and upper portion of the frames still holds most of its protective coating.
Due to buildup of biologic marine growth on the exterior bottom and standing water and sludge in the interior of compartment, ultrasounds were taken where accessible from the interior. The bottom frames make a 2’x 4” grid all readings were taken close to center creating a 2’x 4’ grid pattern. From a visual inspection and ultrasound readings, there is no need for steel replacement in compartment #4. However, located at Bay #9 frame #2, there is a reading of .275”. This reading is
.010 below the normal metal loss. Compartment #4 will need to be pumped dry all steel cleaned and new protective coating applied to all surfaces.
AFT RAKE BOTTOM
HL BAY 1 BAY 2 BAY 3 BAY 4 BAY 5 BAY 6 BAY 7 BAY 8 BAY 9 BAY 10 BAY 11 BAY 12 HL
4 N/A N/A N/A 0.320 PW PW PW PW N/A N/A N/A N/A 4
3 0.310 0.310 0.310 N/A 0.310 PW PW 0.315 0.315 0.320 0.315 0.310 3
2 Water Water 0.300 0.355 Water Water Water Water 0.275 Water Water Water 2
1 Water Water Water Water Water Water Water Water Water Water 0.285 0.285 1
BH Water Water Water Water Water Water Water Water Water Water Water Water BH
S
T
A
R
P
O
R
BACK
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 27 of 31
INTERIOR COMPARTMENT #4 - AFT RAKE (cont.)
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 28 of 31
RECOMMENDATIONS
1) Replace steel from the lower rub rail to the chine of the forward rake, aft rake, port hull side, and starboard hull side.
2) Repair the starboard lower rub rail. This repair can be done in section versus replacing the entire rub rail.
3) The rust bloom areas above the water line can be replaced in section versus replacing the entire area.
4) Since the exterior of the barge had limited access due to the barge setting on the railway cart and covered with barnacles, an evaluation of the bottom was taken by interior ultra-soundings.
It would appear that not all of the bottom will need to be removed. However, there are sections that will need to be cut away for steel replacement. I recommend the following:
a) Clean the interior bottom of all mud, concrete and debris.
b) Sand blast the barnacles off the bottom.
c) Areas of steel plate that have heavy scaling and heavy pitting will need to be replaced.
d) Proper coating (epoxy) should be applied to interior after plate replacement
5) As per ultrasound readings, the following areas will need replaced. The areas are given by interior locations:
Compartment #2
a) Bay #1 at frame #9
b) Bay #2 at frame #9
c) Bay #6 at frame #9
d) Bay #3 at frame #6
e) Bay #5 at frame #6
f) Bay #2 at frame #5
g) Bay #5 at frame #5
h) Bay #4 at frame #3
Compartment #3
a) Bay #6 at frame #8
b) Bay #5 at frame #3
c) Bay #1 at frame #2
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 29 of 31
RECOMMENDATIONS (cont.)
6) Repair the corners of upper rub rail. (If so desired)
7) Replace the cables for both winches.
8) Repair spud. Also, sand blast and paint with units.
9) Install sacrificial anodes.
10) Repair the coaming, if so desired.
11) Replace the steel tabs that support the pads on the aft rake bow support.
12) Prime and paint the exterior once all repairs are completed.
Marine Surveyor June 29, 2022
INSPECTION REPORT #5793 PAGE 30 of 31
SURVEYOR’S COMMENTS
Overall, there is minimal loss of steel for this barge. The problem is stray current issues, which have caused a problem for structural integrity. From the natural waterline down to the chines, including both rakes, there is an excessive amount of stray current damage. I have also noted that while underload, there are rust blooms that formed above the waterline on the aft rake. On the starboard side lower rub rail, there is a considerable amount of stray current to the underside of the rub rail.
The deck shows normal wear and tear for a barge of its age, with some rusting with very little paint protection remaining. There is oil canning throughout the deck. The coaming is well secured and does have some minor damage, but it is still usable.
The bottom was covered with barnacles, which could not be removed at the time inspection since the barge was inspected on the rail cart, which allowed very limited access. In order to get an idea of the condition of the bottom, the bottom had to be ultrasounded in the interior.
MARINE SURVEYOR ⬧ MARINE CONSULTANT
38 OAK HILL LANE ⬧ ELKTON, MD 21921
INSPECTION REPORT #5793 PAGE 31 of 31
DISCLAIMER
My inspection of this barge represents reasonable care and skill, but does not include inspection of those sections requiring structural removals and disassembling. My conclusion does not constitute a guarantee or warranty of the barge’s condition or of its parts, but it is an expression of my opinion only. No liability is assumed by me for errors of judgment or omission, or for subsequent structural weakness in the barge.
This report should be considered as an entire document. No single section is meant to be used, except as part of the whole. It is current to the named client for 30 days of undisturbed layup of the vessel’s first use. Subsequent updating and transfer of the report is solely the right of the surveyor.
The content of this report remains the sole property of said marine surveyor and may not be used without the author of the survey written permission. The use of this report shall constitute an acceptance of the above mentioned conditions.
REPORT SIGNED AND SUBMITTED WITHOUT PREJUDICE
Kenneth E. Henry, Sr., AMS #370
Marine Surveyor
MEMBER ABYC, ASNT, and IAAI
SOCIETY OF ACCREDITED MARINE SURVEYORS
INTERNATIONAL INSTITUTE OF MARINE SURVEYING