BDC3 24-25 - Addendum#1- Bill Baggs - Restroom Remodel #2
Closed State & local contract opportunity Posted
- Solicitation number
- ITB-09804
- State
- Florida
- Responses due
Opportunity facts
- Jurisdictions
- NIGP codes
- 91052 Maintenance And Repair Services, Building (Not Otherwise Classified)
- 90930 Building Construction (Not Otherwise Classified)
- 91468 Plumbing
- 91484 Trade Services, Construction (Not Otherwise Classified)
- 91427 Carpentry
- 90923 Building Construction, Residential (Apartments, Etc.)
- 91065 Remodeling And Alterations
- UNSPSC codes
- 72101500 Building maintenance and repair services
- 72101521 Building framing service
- 72111111 General residential construction contractor service
- 72121103 Commercial and office building renovation and repair service
- 72121400 Specialized public building construction services
- 72151100 Plumbing construction services
- 72154000 Specialty building and trades services
Opportunity details come from vendor.myfloridamarketplace.com. Updated .
About this opportunity
This is a state contract opportunity posted by the Florida Department of Environmental Protection (DEP) for the Bill Baggs Cape Florida State Park Restroom Remodel project, Bid No. BDC03-24/25. The project involves the remodel of an existing restroom facility, including the replacement of the electrical meter base, the relocation and installation of a new electrical panel, and the removal and replacement of all existing electrical wiring, controls, and fixtures to comply with current electrical codes. The project requires the contractor to visit the site and determine the locations of the existing utilities, as this information is not provided in the plans. The contractor must also address any exterior lighting that may remain and requires power and controls. Bids for this project are due on August 12, 2024, and the signed Addendum #1 must be included with the bid submission.
There are no set-aside designations or restrictions on the types of organizations that can respond to this solicitation. The DEP has not provided any information about incumbent vendors or current contractors, nor have they indicated an award value or budget range for this project. Contractors will need to review the provided documents and visit the site to determine the full scope of work and submit a responsive bid.
Opportunity text
July 25, 2024
NOTICE TO APPLICANTS
ADDENDUM NO. ONE (1)
Bill Baggs Cape Florida State Park- Restroom Remodel
DEP BID NO. BDC03-24/25
TO BIDDERS AND PLAN HOLDERS ON THE ABOVE REFERENCED PROJECT: PLEASE NOTE CONTENTS HEREIN AND INCLUDE, SIGNED, WITH YOUR BID SUBMISSION.
NOTICE
It will be required that this addendum be signed in acknowledgment of receipt and that it be included with your Bid when same is submitted to Alisha Sadler, Contracts Specialist, Bureau of Design and Construction, 3800 Commonwealth Blvd., MS #520, Tallahassee, Florida, 32399-3000. Failure to do so may be grounds for rejection of the Bid.
_______________________________________
Signature of Contractor and Date
The following statements supersede & supplement the corresponding items in the specifications & drawings:
- Question: (Plan Sheet E101) - Is the meter base to be replaced in same location and terminated to existing feeder?
Answer: Yes, the meter base is to be replaced at same location- coordinate with utility for disconnect/reconnect of service for replacement of meter.
- Question: (Plan Sheet E101) - Location of existing panel is indicated on the plan - Is this to be the location of new panel?
Answer: The location of the existing panel as depicted on Sheet E102.0 shall be the location of the new panel.
- Question: (Plan Sheet E101) Grounding per utility Co - Indicates Detail 2/E101 - This detail would be used at the first means of disconnect (Panel) and not meter - Clarify.
Answer: Correct, detail 2 needs to point to the ground of the new panel.
- Question: (Plan Sheet E101) - Existing Service Feeder size is not indicated on the riser - Please provide information. Also, power riser Note 1 references "New Connection"
Answer: The existing service is to be reused - coordinate with utility for disconnect/reconnect of service for replacement of meter.
- Question: (Plan Sheet E101) Campsite power -voltage/amperage/quantity/location and no breakers indicated on panel schedule. Provide additional information.
Answer: Please disregard this note, it is an error, there are no existing campsites or future campsites to be considered.
- Question: (Plan Sheet E101) Power riser note 4 - Surge Device. No breaker is indicated on the panel. Clarify where termination and means of disconnect to be.
Answer: Please connect the SPD in parallel with the branch panel as directed by the manufacturer.
- Question: (Plan Sheet E102) Keyed Lighting Note 1 - "Lights are manual on/auto off" with the exception of the service corridor there are no controls indicated. Clarify method and location of controls.
Answer: This note is an error; no light fixtures shall be controlled by the public. The service corridor shall have a simple wall mounted switch at each interior entrance into corridor for park staff use. All other lighting shall be on photocell control for interior and any existing exterior lighting.
- Question: (Plan Sheet E102) Photocell noted on power plan (Top left of Bldg.) noted on legend for "outdoor lights" - No outdoor lights are indicated on plan - verify circuitry to be controlled.
Answer: The restroom is a remodel of an existing structure, there may be exterior lighting that shall remain and require power and controls.
- Question: (Plan Sheet E102) - Photocell - if to control interior fixtures - will need a contactor for photocell to control due to multiple circuits - Clarify.
Answer: Correct, all lighting fixtures outside of service corridor shall be on photocell.
- Question: (Plan Sheet E102) Lighting fixture schedule NOTE "D" - No Emergency/half shaded fixtures are indicated on the plan - Clarify/verify locations and quantities
Answer: This note is referring to the 8 fixtures noted on plan as a circle with X within and one section filled in solid, the fixture is Lithonia LHQM LED RM6 exit sign, shading indicates illuminated face.
- Question: (Plan Sheet E101) - Power riser note 1 - No civil site plan provided for location of existing utility.
Answer: This note is in error; contractor shall visit site and determine location of existing utilities.
- Question: No electrical demolition is indicated on the plan - Provide plan/scope of demolition
Answer: Contractor shall review sheet s100, existing/demo and proposed floor plan. There are relocation and addition of interior walls. Due to age of existing electrical items, location of fixtures that may conflict with proposed changes, all existing electrical shall be considered abandoned and removed, new electrical wiring, controls and fixtures to be installed according to current electrical codes.
In all other respects, the contract documents of which this is an Addendum, and attachments relative thereto, shall remain in full force and effect.