J061--FY25: Lake Nona Medium Voltage Repair

Closed Special Notice Posted

Solicitation number
36C24825Q0885
Agency
Responses due
Set-aside
No set-aside

Opportunity facts

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Network Contracting Office 08 has issued a Special Notice for urgent medium voltage electrical repairs at the Orlando VA Medical Center at Lake Nona. The notice addresses critical failures in multiple emergency and normal power circuits serving the clinic and domiciliary facilities, including catastrophic failures in generator power circuits DAG-3 and DAG-15, as well as the normal power circuit DAN-2. Hi-Pot testing has revealed severe insulation breakdowns, splice degradation, and complete short circuits that have left the facility operating without redundant emergency power systems. The electrical issues pose significant operational risks, with visual inspections confirming corrosion, swelling, and electrical burning in multiple manholes throughout the duct bank system. This emergency situation requires immediate contractor intervention to restore reliable power infrastructure to these critical healthcare facilities.

The Special Notice invites qualified electrical contractors to participate in a mandatory site visit scheduled for June 17, 2025, at 10:00 AM to assess the scope of work and prepare for an upcoming Request for Quote. Contractors must pre-register by June 16, 2025, at 11:00 AM by providing names of no more than two attendees to the specified VA contacts, and must bring proper identification to access the facility. The site visit will include visual inspection of the failed circuits and discussion of technical requirements outlined in the government's Trouble Call reports, with contractor questions addressed on-site to be incorporated into the forthcoming RFQ. This opportunity targets electrical contractors under NAICS code 238210 specializing in electric wire and power distribution equipment maintenance and repair. While this notice serves informational and planning purposes only, it represents preparation for a critical infrastructure repair contract to restore emergency power redundancy and replace multiple failing medium voltage circuits at this VA medical facility.

Notice text

The Department of Veteran Affairs, Network Contracting Office 08 invites interested Contractors to attend a site visit for the purpose of assessing the issues identified in the government-generated Trouble Call report. This site visit will assist prospective offers in evaluating the work environment and technical requirements in preparation for submitting a quote under the upcoming Request for Quote (RFQ).

Instructions:

Interested parties must pre-register attendees (no more than two) by providing names to Robert.edwards2@va.gov and rohan.mckenzie@va.gov no later than June 16, 2025, 11:00 AM. Please arrive on time and bring proper identification to gain access to the facility.

Site Visit Details:

Date: June 17, 2025

Time: 10:00 AM (local time)

Location: Orlando VA Medical Center at Lake Nona, 13800 Veterans Way, Orlando, FL 32827

Meeting Point: Inside the lobby near the piano

Purpose: Visual inspection and discussion of the issue described in Trouble Call Report

Follow-up: Contractor questions will be address on-site and incorporated into the forthcoming RFQ as appropriate.

Background:

Emergency (generator) power circuit(s) to the Lake Nona clinic are faulted and/or unreliable.

The medium voltage circuit DAG-3 is the emergency (generator) circuit powering the Clinic substation SS-CG2; and is the alternate power source for Clinic substation SS-CG1. It was Hi-Pot tested and the report indicated a catastrophic failure on B-phase, requiring both substations to be placed on the alternate circuit (DAG-15) with no redundancy. A visual inspection of manholes EA1-1 and EA1-2 in the duct bank series noted splices in them that show signs corrosion and degradation. Troubleshooting, testing was performed on the circuit and damage to the B-phase conductor insulation is suspected to be localized the within the ductwork itself requiring emergent replacement.

The medium voltage circuit DAG-15 is the emergency (generator) circuit powering the Clinic substation SS-CG1 and is the alternate power source for Clinic substation SS-CG2. It was Hi-Pot tested and the report indicated signs of leakage, likely from several splices/phases in the duct bank series manholes. A visual assessment was performed in conjunction with the Hi-Pot test and noted signs of swelling on several splices. Circuit DAG15 is the sole operable emergency (generator) circuit to the Clinic substations SS-CG1/2 (in its current switched state) and in urgent need of replacement and/or repair.

The Normal power circuit to the Lake Nona Domiciliary is unreliable. The medium voltage circuit DAN-2 is the sole normal power circuit powering the Domiciliary substation SS-DG1. It was quickly identified to have sustained a catastrophic splice failure on only C-phase on 12Nov24 in manhole NA2-5. Only C- phase splice was repaired, and the circuit was put back in service in >24hrs. During the visual assessment splices were noted in manholes NA2-5, NA2-6, NA2-7, and NA2-8 with various signs of corrosion and swelling indicative of impending failure. Circuit DAN-2 requires urgent replacement.

DBN-7 Hospital (Normal Power) circuit - A visual assessment confirmed smoke and electrical burning signs from manhole NB2-3 near the golf cart yard of the warehouse. Suspected leaking splice damage. IMG_1005 1.3gp.

Attachments:

ATTACHMENT A - Trouble Call Report of the Hi-Pot Cable test DAG-3

ATTACHMENT B - Trouble Call Report of the Hi-Pot Cable test DAG-15

Note: This notice is for informational and planning purposes only. It does not constitute a solicitation or guarantee of future contract award.

Files

File Type Posted
ATTACHMENT B HI-POT TEST SHEET DAG-15.pdf PDF
36C24825Q0885.docx DOCX document
ATTACHMENT A HI-POT TEST SHEET DAG-3.pdf PDF

Similar open opportunities

Opportunity Agency Set-aside Responses due
J061--triennial electrical maintenance - amendment 4 POP: 12/01/2026 - 11/30/2027 plus 4 option years Slvhcs New Orleans, Louisiana 70119, United States · NAICS 238210 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
J061--SOURCES SOUGHT NOTICE - Triennial Electrical Inspection Testing and Maintenance Services Requirement - Louis A Johnson VA Medical Center 36C24527Q0039 Department of Veterans Affairs Louis A Johnson VA Medical Center Clarksburg, West Virginia 26301, United States · NAICS 238210 Veterans Integrated Service Network 5 No set-aside
J061--Triennial Circuit Breaker and Feeder Testing NAICS 238210 Veterans Integrated Service Network 21 No set-aside
657A5-26-111, Triennial Electrical Testing Marion, Illinois 62959, United States · NAICS 238210 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
H259-- electrical 5-year ARC flash study (VA-27-00002938) NAICS 541350 Veterans Integrated Service Network 12 No set-aside