This document is a Hi-Pot Test Sheet for electrical cable circuit DAG-3, dated 4/11/2025, detailing insulation resistance (IR) and high potential (Hi-Pot) test results for a medium voltage cable. The test measurements reveal significant electrical issues, particularly with the blue phase conductor, which shows multiple problematic test results: the initial IR measurement for blue-to-earth was below the 400 threshold, and the Hi-Pot test indicates a "dead short" condition. After testing, the measurements confirm the blue phase has a complete short circuit, with IR voltages showing shorts across multiple phase combinations (blue-to-earth, blue-to-white, blue-to-red). The test was conducted using test voltages ranging from 1000V to 15,000V, with test durations of 1 minute, and was performed and signed by John Griffis. These test results align with the related federal contract opportunity's background describing emergency power circuit failures at the Lake Nona VA Medical Center, specifically highlighting the catastrophic failure of the medium voltage circuit DAG-3's B-phase conductor.

View the file

Other files

File Type Posted
ATTACHMENT B HI-POT TEST SHEET DAG-15.pdf PDF
36C24825Q0885.docx DOCX document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PANEL DETAILS

CIRCUIT

DAG -3

CABLE DETAILS

4/0 15KV

CABLE MAKE

DATE

4/11/2025

IR VALUE MEASURMENT

(BEFORE HIPOT)

TEST VOLTAGE DURATION IR VALUE REMARKS

R-E 1000 1 MIN. 11 G OHMS

W-E 1000 1 MIN. 7.2 G OHMS

B-E 1000 1 MIN.

42.1 M OHMS BELOW THE 400 THRESHOLD

R-W 1000 1 MIN.

10.2 G OHMS

W-B 1000 1 MIN. 3.5 G OHMS THIS WOULD BE INDICATIVE OF BLUE BEING DEFECTIVE

B-R 1000 1 MIN.

11 G OHMS

HIPOT TEST TEST VOLTAGE DURATION LEAKAGE CURRENT

(IN mA)

REMARKS

R- PH SHORTING W-B-E 15,000 1 MIN.

2.9 M OHMS

W-PH SHORTING B-R-E 15,000 1 MIN.

2.8 M OHMS

B-PH SHORTING R-W-E 15,000 1 MIN. TRIP DEAD SHORT WHEN TESTED

IR VALUE MEASURMENT

(AFTER HIPOT)

TEST VOLTAGE DURATION IR VOLTAGE REMARKS

R-E 5000 1 MIN. 10,500 M OHMS

W-E 5000 1 MIN. 450 M OHMS

B-E 5000 1 MIN. SHORT BLUE HAS A DEAD SHORT

R-W 5000 1 MIN. 10,500 M OHMS

W-B 5000 1 MIN. SHORT

B-R 5000 1 MIN. SHORT

TESTED BY WITNESSED BY