J049--amendment 0001 to RFQ 36C24526Q0401 uploaded answers to rfis and generator descriptions louis a johnson VAMC

Closed Solicitation Posted

This opportunity was awarded. See the award notice from .

Solicitation number
36C24526Q0401
Agency
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

Place of performance
Department of Veterans Affairs Louis A Johnson VA Medical Center Clarksburg, West Virginia 26301, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Integrated Service Network 5 is soliciting quotes for generator testing and emergency repair services at the Louis A. Johnson VA Medical Center in Clarksburg, West Virginia, under a Blanket Purchase Agreement (BPA). Required services include monthly operational testing in compliance with NFPA 110 standards (minimum 30 continuous minutes under facility load), supplemental load bank testing annually as needed, triennial 4-hour load tests at 75% nameplate capacity, and 24/7/365 emergency repair services with a maximum 2-hour on-site response time. Contractors must be EGSA-certified or factory-trained, qualified to test medium voltage systems (4160V and 480V), compliant with NFPA 70E and OSHA standards, and capable of performing lockout/tagout procedures, with all reports submitted within 72 hours in audit-ready format. The evaluation criteria consist of Technical Qualifications (40%), Past Performance (30%), and Price (30%), with pricing to cover monthly testing reports, emergency labor rates for both regular and after-hours work, load bank testing, and triennial testing in year three. Quotes are due April 14, 2026, at 10:00 AM Eastern Time, and a mandatory site visit was held on April 3, 2026.

This solicitation is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with the contracting officer authorized to amend to open competition for small businesses if no acceptable SDVOSB quotes are received. Mountaineer Generator has been identified as the current responsible party for generator maintenance activities. The total contract estimated value is $12.5 million, covering a base year pricing period plus four additional one-year option periods. The facility maintains five generators with varying capacities: three Caterpillar units (1000 kVA, 1250 kVA, and one stationary unit), one Kato unit (625 kVA at 4160V), one Kohler unit (128 kVA), and one portable Baldor unit (225 kVA), with the most recent annual load bank testing conducted on March 28, 2026. All services will be performed at the Louis A. Johnson VA Medical Center located at 1 Medical Center Drive, Clarksburg, West Virginia 26301, with prevailing wage requirements applicable under the Service Contract Act Wage Determination 2015-4353_C.

Notice text

2 versions

Update #2 · Latest ·

GENSET #1

GENSET #2

GENSET #3

Manufacturer/Make/Year:

Caterpillar

Caterpillar

Kato

Model No:

SR-4

C32

500SS9D

Serial/Order No:

6NA01031

G1G00044

7319

Load Rating:

(Emergency/Standby/Prime)

1000 kva

1250 kva

625KVA

Power Factor:

.8

.8

.8

Frequency:

60 Hertz

60 Hertz

60 hertz

Load in Amperage:

1000 amps

1000 amps

87

Output Voltage:

480

480 volts

4160 volts

Phase:

3-phase

3-phase

3-phase

Building:

Bld 17

Bld 17

Bld 17

Location (Area/Room):

Generator room

Generator Rm

Generator Rm

GENSET #4

GENSET #5 (portable)

Manufacturer/Make/Year:

Kohler

Baldor

Model No:

100RE0ZJF

TS225-3J

Serial/Order No:

3346GMJL0001

P1205240012

Load Rating:

(Emergency/Standby/Prime)

128 kva

225 kva

Power Factor:

.8

.8

Frequency:

60 Hertz

60 Hertz

Load in Amperage:

153 amps

625 amps

Output Voltage:

480

480 volts

Phase:

3-phase

3-phase

Building:

Parking Garage

Grounds

Location (Area/Room):

Parking Garage

Grounds (portable)

Who will be responsible for the generator maintenance (monthly, quarterly, semi, annual, & triennial) an when was the last time the annual maintenance was completed?

Mountaineer Generator.

When was the last annual load bank testing conducted?

             3/28/26.

Does the KATO 500kW (625KVA) 4160v generator have an integrated load bank?

NO

Update #1 ·

BPA RFQ

Files

File Type Posted
36C24526Q0401 0001_1.docx DOCX document
36C24526Q0401 - RFI ANSWERS.pdf PDF
SAM-Service Contract Act Wage Determination 2015-4353_C.pdf PDF
36C24526Q0401.pdf PDF
36C24526Q0401_1.docx DOCX document

Notice history

Notice Type Posted
J049--award notice 36C24526Q0401 Award Award Notice
This notice Latest solicitation Solicitation

Similar open opportunities

Opportunity Agency Set-aside Responses due
J061--triennial electrical maintenance - amendment 4 POP: 12/01/2026 - 11/30/2027 plus 4 option years Slvhcs New Orleans, Louisiana 70119, United States · NAICS 238210 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
J061--586-Switchgear and ATS Investigation and Repair Service (VA-27-00015294) Department of Veterans Affairs G.V. Sonny Montgomery VA Medical Center Jackson MS 39216 · NAICS 811310 Veterans Integrated Service Network 16 Service-Disabled Veteran-Owned Small Business
657A5-26-111, Triennial Electrical Testing Marion, Illinois 62959, United States · NAICS 238210 Veterans Integrated Service Network 15 Service-Disabled Veteran-Owned Small Business Sole Source
J061--Eaton Powerware System Replacement Manchester Vamc Manchester NH 03104 · NAICS 811310 Veterans Integrated Service Network 1 Service-Disabled Veteran-Owned Small Business
WTX Elevator Inspections and Load Testing Services Texas 79720, United States · NAICS 238290 Veterans Integrated Service Network 17 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity

GovTribe for Federal Contractors