J049--amendment 0001 to RFQ 36C24526Q0401 uploaded answers to rfis and generator descriptions louis a johnson VAMC
Closed Solicitation Posted
This opportunity was awarded. See the award notice from .
- Solicitation number
- 36C24526Q0401
- Agency
-
Veterans Integrated Service Network 5
Veterans Health Administration, Department of Veterans Affairs
- Responses due
- Set-aside
- Service-Disabled Veteran-Owned Small Business
Opportunity facts
- NAICS code
- 811310 Commercial and Industrial Machinery and Equipment (except Automotive and Electronic) Repair and Maintenance
- Place of performance
- Department of Veterans Affairs Louis A Johnson VA Medical Center Clarksburg, West Virginia 26301, United States
- Points of contact
Notice details come from SAM.gov. Updated .
About this opportunity
The Department of Veterans Affairs Veterans Integrated Service Network 5 is soliciting quotes for generator testing and emergency repair services at the Louis A. Johnson VA Medical Center in Clarksburg, West Virginia, under a Blanket Purchase Agreement (BPA). Required services include monthly operational testing in compliance with NFPA 110 standards (minimum 30 continuous minutes under facility load), supplemental load bank testing annually as needed, triennial 4-hour load tests at 75% nameplate capacity, and 24/7/365 emergency repair services with a maximum 2-hour on-site response time. Contractors must be EGSA-certified or factory-trained, qualified to test medium voltage systems (4160V and 480V), compliant with NFPA 70E and OSHA standards, and capable of performing lockout/tagout procedures, with all reports submitted within 72 hours in audit-ready format. The evaluation criteria consist of Technical Qualifications (40%), Past Performance (30%), and Price (30%), with pricing to cover monthly testing reports, emergency labor rates for both regular and after-hours work, load bank testing, and triennial testing in year three. Quotes are due April 14, 2026, at 10:00 AM Eastern Time, and a mandatory site visit was held on April 3, 2026.
This solicitation is set aside exclusively for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with the contracting officer authorized to amend to open competition for small businesses if no acceptable SDVOSB quotes are received. Mountaineer Generator has been identified as the current responsible party for generator maintenance activities. The total contract estimated value is $12.5 million, covering a base year pricing period plus four additional one-year option periods. The facility maintains five generators with varying capacities: three Caterpillar units (1000 kVA, 1250 kVA, and one stationary unit), one Kato unit (625 kVA at 4160V), one Kohler unit (128 kVA), and one portable Baldor unit (225 kVA), with the most recent annual load bank testing conducted on March 28, 2026. All services will be performed at the Louis A. Johnson VA Medical Center located at 1 Medical Center Drive, Clarksburg, West Virginia 26301, with prevailing wage requirements applicable under the Service Contract Act Wage Determination 2015-4353_C.
Notice text
2 versions
Update #2 · Latest ·
GENSET #1
GENSET #2
GENSET #3
Manufacturer/Make/Year:
Caterpillar
Caterpillar
Kato
Model No:
SR-4
C32
500SS9D
Serial/Order No:
6NA01031
G1G00044
7319
Load Rating:
(Emergency/Standby/Prime)
1000 kva
1250 kva
625KVA
Power Factor:
.8
.8
.8
Frequency:
60 Hertz
60 Hertz
60 hertz
Load in Amperage:
1000 amps
1000 amps
87
Output Voltage:
480
480 volts
4160 volts
Phase:
3-phase
3-phase
3-phase
Building:
Bld 17
Bld 17
Bld 17
Location (Area/Room):
Generator room
Generator Rm
Generator Rm
GENSET #4
GENSET #5 (portable)
Manufacturer/Make/Year:
Kohler
Baldor
Model No:
100RE0ZJF
TS225-3J
Serial/Order No:
3346GMJL0001
P1205240012
Load Rating:
(Emergency/Standby/Prime)
128 kva
225 kva
Power Factor:
.8
.8
Frequency:
60 Hertz
60 Hertz
Load in Amperage:
153 amps
625 amps
Output Voltage:
480
480 volts
Phase:
3-phase
3-phase
Building:
Parking Garage
Grounds
Location (Area/Room):
Parking Garage
Grounds (portable)
Who will be responsible for the generator maintenance (monthly, quarterly, semi, annual, & triennial) an when was the last time the annual maintenance was completed?
Mountaineer Generator.
When was the last annual load bank testing conducted?
             3/28/26.
Does the KATO 500kW (625KVA) 4160v generator have an integrated load bank?
NO
Update #1 ·
BPA RFQ
Files
| File | Type | Posted |
|---|---|---|
| 36C24526Q0401 0001_1.docx | DOCX document | |
| 36C24526Q0401 - RFI ANSWERS.pdf | ||
| SAM-Service Contract Act Wage Determination 2015-4353_C.pdf | ||
| 36C24526Q0401.pdf | ||
| 36C24526Q0401_1.docx | DOCX document |
Notice history
| Notice | Type | Posted |
|---|---|---|
| J049--award notice 36C24526Q0401 | Award Notice | |
| This notice | Solicitation |
Similar open opportunities
| Opportunity | Agency | Set-aside | Responses due |
|---|---|---|---|
| J061--triennial electrical maintenance - amendment 4 POP: 12/01/2026 - 11/30/2027 plus 4 option years | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| J061--586-Switchgear and ATS Investigation and Repair Service (VA-27-00015294) | Veterans Integrated Service Network 16 | Service-Disabled Veteran-Owned Small Business | |
| 657A5-26-111, Triennial Electrical Testing | Veterans Integrated Service Network 15 | Service-Disabled Veteran-Owned Small Business Sole Source | |
| J061--Eaton Powerware System Replacement | Veterans Integrated Service Network 1 | Service-Disabled Veteran-Owned Small Business | |
| WTX Elevator Inspections and Load Testing Services | Veterans Integrated Service Network 17 | Service-Disabled Veteran-Owned Small Business |
On GovTribe
Work this opportunity
- Track it in your pipeline
- Find teaming partners
- Similar opportunities
- Ask GovTribe AI about this opportunity