This document is a generator inventory and maintenance record for five gensets located at a facility, primarily in Building 17. The inventory includes three stationary generators in the main generator room: a Caterpillar SR-4 (1000 kVA, 480V), a Caterpillar C32 (1250 kVA, 480V), and a Kato 500SS9D (625 kVA, 4160V). Two additional generators are located elsewhere: a Kohler 100RE0ZJF (128 kVA, 480V) in the parking garage and a portable Baldor TS225-3J (225 kVA, 480V) on the grounds. All units operate at 60 Hertz with a 0.8 power factor and three-phase configuration, with amperage ratings ranging from 87 to 1000 amps depending on the unit.

Maintenance and testing responsibilities are assigned to Mountaineer Generator, which handles all scheduled maintenance activities including monthly, quarterly, semi-annual, annual, and triennial intervals. The most recent annual load bank testing was conducted on 3/28/26. The Kato 4160V generator does not have an integrated load bank, which may require external load testing equipment for operational validation. The document serves as a baseline asset record for facility power generation capacity and maintenance tracking purposes.

View the file

Other files

File Type Posted
36C24526Q0401 0001_1.docx DOCX document
36C24526Q0401.pdf PDF
36C24526Q0401_1.docx DOCX document
SAM-Service Contract Act Wage Determination 2015-4353_C.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENSET #1 GENSET #2 GENSET #3

Manufacturer/Make/Year: Caterpillar Caterpillar Kato

Model No: SR-4 C32 500SS9D Serial/Order No: 6NA01031 G1G00044 7319

Load Rating:

(Emergency/Standby/Prime) 1000 kva 1250 kva 625KVA

Power Factor: .8 .8 .8 Frequency: 60 Hertz 60 Hertz 60 hertz

Load in Amperage: 1000 amps 1000 amps 87 Output Voltage: 480 480 volts 4160 volts

Phase: 3-phase 3-phase 3-phase

Building: Bld 17 Bld 17 Bld 17 Location (Area/Room): Generator room Generator Rm Generator Rm

GENSET #4 GENSET #5 (portable)

Manufacturer/Make/Year: Kohler Baldor Model No: 100RE0ZJF TS225-3J

Serial/Order No: 3346GMJL0001 P1205240012 Load Rating:

(Emergency/Standby/Prime) 128 kva 225 kva

Power Factor: .8 .8 Frequency: 60 Hertz 60 Hertz

Load in Amperage: 153 amps 625 amps Output Voltage: 480 480 volts

Phase: 3-phase 3-phase

Building: Parking Garage Grounds Location (Area/Room): Parking Garage Grounds (portable)

1. Who will be responsible for the generator maintenance (monthly, quarterly, semi, annual, & triennial) an when was the last time the annual maintenance was completed?

Mountaineer Generator.

2. When was the last annual load bank testing conducted?

3/28/26.

3. Does the KATO 500kW (625KVA) 4160v generator have an integrated load bank?

NO