36C24526Q0401 - RFI ANSWERS.pdf
PDF 104 KB Posted
- Solicitation number
- 36C24526Q0401
About this file
This document is a generator inventory and maintenance record for five gensets located at a facility, primarily in Building 17. The inventory includes three stationary generators in the main generator room: a Caterpillar SR-4 (1000 kVA, 480V), a Caterpillar C32 (1250 kVA, 480V), and a Kato 500SS9D (625 kVA, 4160V). Two additional generators are located elsewhere: a Kohler 100RE0ZJF (128 kVA, 480V) in the parking garage and a portable Baldor TS225-3J (225 kVA, 480V) on the grounds. All units operate at 60 Hertz with a 0.8 power factor and three-phase configuration, with amperage ratings ranging from 87 to 1000 amps depending on the unit.
Maintenance and testing responsibilities are assigned to Mountaineer Generator, which handles all scheduled maintenance activities including monthly, quarterly, semi-annual, annual, and triennial intervals. The most recent annual load bank testing was conducted on 3/28/26. The Kato 4160V generator does not have an integrated load bank, which may require external load testing equipment for operational validation. The document serves as a baseline asset record for facility power generation capacity and maintenance tracking purposes.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24526Q0401 0001_1.docx | DOCX document | |
| 36C24526Q0401.pdf | ||
| 36C24526Q0401_1.docx | DOCX document | |
| SAM-Service Contract Act Wage Determination 2015-4353_C.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENSET #1 GENSET #2 GENSET #3
Manufacturer/Make/Year: Caterpillar Caterpillar Kato
Model No: SR-4 C32 500SS9D Serial/Order No: 6NA01031 G1G00044 7319
Load Rating:
(Emergency/Standby/Prime) 1000 kva 1250 kva 625KVA
Power Factor: .8 .8 .8 Frequency: 60 Hertz 60 Hertz 60 hertz
Load in Amperage: 1000 amps 1000 amps 87 Output Voltage: 480 480 volts 4160 volts
Phase: 3-phase 3-phase 3-phase
Building: Bld 17 Bld 17 Bld 17 Location (Area/Room): Generator room Generator Rm Generator Rm
GENSET #4 GENSET #5 (portable)
Manufacturer/Make/Year: Kohler Baldor Model No: 100RE0ZJF TS225-3J
Serial/Order No: 3346GMJL0001 P1205240012 Load Rating:
(Emergency/Standby/Prime) 128 kva 225 kva
Power Factor: .8 .8 Frequency: 60 Hertz 60 Hertz
Load in Amperage: 153 amps 625 amps Output Voltage: 480 480 volts
Phase: 3-phase 3-phase
Building: Parking Garage Grounds Location (Area/Room): Parking Garage Grounds (portable)
1. Who will be responsible for the generator maintenance (monthly, quarterly, semi, annual, & triennial) an when was the last time the annual maintenance was completed?
Mountaineer Generator.
2. When was the last annual load bank testing conducted?
3/28/26.
3. Does the KATO 500kW (625KVA) 4160v generator have an integrated load bank?
NO
File details come from the government source that posted it. Updated .