B118 Fire Panel

Closed Solicitation Posted

Solicitation number
W50S8S26QA013
Agency
Responses due
Set-aside
Total Small Business

Opportunity facts

Place of performance
Swanton, Ohio 43558, United States

Notice details come from SAM.gov. Updated .

About this opportunity

The 180th Fighter Wing seeks sealed bids for fire alarm control panel system upgrade and installation at Building 118, Swanton Air National Guard Base, Ohio, with bids due September 10, 2026. The procurement is a 100% small business set-aside with a brand name requirement for Monaco equipment.

Place of performance is Swanton, OH 43558. Work comprises two phases: Phase 1 requires a NICET-certified designer to provide stamped fire protection system design and demolition of existing Simplex and Monaco panels with labeled inputs and outputs; Phase 2 requires installation of a new Monaco MAPP X panel with expansion cards, NFPA-compliant battery backup system, antenna and lightning arrestor, and replacement of approximately 90 smoke detectors, 12 heat detectors, 4 duct detectors, 18 pull stations, and 22 horn strobes. All work must comply with manufacturer instructions, NFPA 72, and UFC 3-600-1 standards. The contractor must perform complete 100% functional and acceptance testing witnessed by the Contracting Officer and Base Fire Department.

Period of performance is 90 calendar days from notice to proceed. The labor rate for Fire Alarm System Mechanic is $29.15 per hour on a firm fixed-price basis. Performance occurs Monday–Friday, 0700–1530 hours, excluding federal holidays and base closures. Work on aircraft parking apron requires Foreign Object Debris (FOD) checks. The contractor must provide all personnel, materials, equipment, supervision, and quality control; the Government furnishes utilities only. Contractor must obtain base identification and vehicle passes and complete antiterrorism and OPSEC training. No performance or payment bonds are required; an alternative payment protection equal to 100% of contract price (irrevocable letter of credit, escrow agreement, certificates of deposit, or payment bond) must be submitted within 10 days of award. Offers remain valid for 30 days after bid opening. Amendment 1, effective September 2, extended the due date from September 3 and incorporated RFI responses; offerors must acknowledge the amendment. Inspection and acceptance occur at 180th Civil Engineering Squadron, 2660 S Eber Road, Building 105 Warehouse, Swanton, Ohio 43558-9645. Payment is processed through Wide Area Workflow (WAWF).

Notice text

2 versions

Update #2 · Latest ·

Solicitation has been amended: Quoters must acknowledge amendment in section 19.

Amendment 1 (2 September 2026):

Request for Information (RFIs) have been received and answered. Q&A Document is attached to this posting along with the new 1442 acknowledging the amendment to include Q&As. Additionally, the offers due date has been changed from 3 September 2026 at 10 AM Eastern to 10 September 2026 10 AM Eastern time. This change allows time for acknowledgement of the amendment.

~~~~~~~~~~~~~~~~~~~~~~~~~~~~

The 180th Fighter Wing is issuing a Request for Quotes to award a single firm fixed-price contract for commercial construction services, non-personal, to provide all plant, labor, transportation, materials, tools, equipment, and supervision necessary for roof repairs on buildings 101 and 136, located at the 180th Fighter Wing (FW), Swanton, Ohio Air National Guard Base. This project includes a Brand Name requirement for the fire panel (Monaco) and the justification is attached to this posting. Objective is 

Phase 1 – Design & Demolition:

  • Provide a complete, stamped Fire Protection System design from a NICET certified designer.
  • Demo the existing Simplex Panel, carefully labeling all inputs and outputs for transfer to the new system.
  • Demo the existing Monaco M-2 Panel, carefully labeling all inputs and outputs.
  • Demo the existing Monaco BT2-8, antenna, and lightning arrestor.

Phase 2 – FACP Installation and Upgrade:

  • Install a new Monaco MAPP X panel, complete with all necessary expansion cards and devices to accommodate all existing and new equipment.
  • Install a new NFPA-compliant battery backup system and cabinet.
  • Install a new antenna and lightning arrestor system for the new panel.
  • Replace approximately 90 existing smoke detectors with new, compatible models.
  • Replace approximately 12 existing heat detectors.
  • Replace approximately 4 existing duct detectors.
  • Replace approximately 18 existing pull stations.
  • Replace approximately 22 existing horn strobes.
  • Install all new copper wiring as required to connect all devices to the new FACP.
  • Fully program the new FACP to manage all connected initiating and notification devices.
  • Perform a complete 100% functional and acceptance test of the entire system in accordance with NFPA and UFC standards, to be witnessed by the COR and Base Fire Department.

In accordance with the attached Performance Work Statement. 

The contract duration will be 90 days after award. This project is set aside 100% for Small Business. The North American Industry Classification (NAICS) Code is 238210, with a size standard of $19,000,000.00. The magnitude is between $25,000 and $100,000. 

Alternative payment protections apply under clause 52.228-13. The contractor shall submit one of the following payment protections: An irrevocable letter of credit (ILC), A tripartite escrow agreement, Certificates of deposit, or a payment bond. The amount of the payment protection shall be 100 percent of the contract price. The submission of the payment protection is required within 10 days of contract award. The payment protection shall provide protection for the full contract performance period plus a one-year period. Except for escrow agreements and payment bonds, which provide their own protection procedures, the Contracting Officer is authorized to access funds under the payment protection when it has been alleged in writing by a supplier of labor or material that a nonpayment has occurred, and to withhold such funds pending resolution by administrative or judicial proceedings or mutual agreement of the parties. When a tripartite escrow agreement is used, the Contractor shall utilize only suppliers of labor and material that signed the escrow agreement.

An optional site visit will be held on Wednesday August 26th, 9am local time, at the 180th Fighter Wing 2660 S Eber Rd, Swanton, Ohio 43558. Interested parties are required to RSVP to 180.fw.contracting@us.af.mil with the number of visitors attending, names, and company information by Tusday August 25th, 4pm local time. REAL ID drivers license is required for access to the installation, those without compliant identification will not be allowed on base. 

Any questions related to this posting can be sent to 180.fw.contracting@us.af.mil. 

Update #1 ·

The 180th Fighter Wing is issuing a Request for Quotes to award a single firm fixed-price contract for commercial construction services, non-personal, to provide all plant, labor, transportation, materials, tools, equipment, and supervision necessary for roof repairs on buildings 101 and 136, located at the 180th Fighter Wing (FW), Swanton, Ohio Air National Guard Base. This project includes a Brand Name requirement for the fire panel (Monaco) and the justification is attached to this posting. Objective is 

Phase 1 – Design & Demolition:

  • Provide a complete, stamped Fire Protection System design from a NICET certified designer.
  • Demo the existing Simplex Panel, carefully labeling all inputs and outputs for transfer to the new system.
  • Demo the existing Monaco M-2 Panel, carefully labeling all inputs and outputs.
  • Demo the existing Monaco BT2-8, antenna, and lightning arrestor.

Phase 2 – FACP Installation and Upgrade:

  • Install a new Monaco MAPP X panel, complete with all necessary expansion cards and devices to accommodate all existing and new equipment.
  • Install a new NFPA-compliant battery backup system and cabinet.
  • Install a new antenna and lightning arrestor system for the new panel.
  • Replace approximately 90 existing smoke detectors with new, compatible models.
  • Replace approximately 12 existing heat detectors.
  • Replace approximately 4 existing duct detectors.
  • Replace approximately 18 existing pull stations.
  • Replace approximately 22 existing horn strobes.
  • Install all new copper wiring as required to connect all devices to the new FACP.
  • Fully program the new FACP to manage all connected initiating and notification devices.
  • Perform a complete 100% functional and acceptance test of the entire system in accordance with NFPA and UFC standards, to be witnessed by the COR and Base Fire Department.

In accordance with the attached Performance Work Statement. 

The contract duration will be 90 days after award. This project is set aside 100% for Small Business. The North American Industry Classification (NAICS) Code is 238210, with a size standard of $19,000,000.00. The magnitude is between $25,000 and $100,000. 

Alternative payment protections apply under clause 52.228-13. The contractor shall submit one of the following payment protections: An irrevocable letter of credit (ILC), A tripartite escrow agreement, Certificates of deposit, or a payment bond. The amount of the payment protection shall be 100 percent of the contract price. The submission of the payment protection is required within 10 days of contract award. The payment protection shall provide protection for the full contract performance period plus a one-year period. Except for escrow agreements and payment bonds, which provide their own protection procedures, the Contracting Officer is authorized to access funds under the payment protection when it has been alleged in writing by a supplier of labor or material that a nonpayment has occurred, and to withhold such funds pending resolution by administrative or judicial proceedings or mutual agreement of the parties. When a tripartite escrow agreement is used, the Contractor shall utilize only suppliers of labor and material that signed the escrow agreement.

An optional site visit will be held on Wednesday August 26th, 9am local time, at the 180th Fighter Wing 2660 S Eber Rd, Swanton, Ohio 43558. Interested parties are required to RSVP to 180.fw.contracting@us.af.mil with the number of visitors attending, names, and company information by Tusday August 25th, 4pm local time. REAL ID drivers license is required for access to the installation, those without compliant identification will not be allowed on base. 

Any questions related to this posting can be sent to 180.fw.contracting@us.af.mil. 

Files

Similar open opportunities

Opportunity Agency Set-aside Responses due
2-STEP SEALED BID - TINKER AFB WWYK250019 Remove and Replace Fire Sprinkler in Plasma Booth Dust Collectors and Replace the Building F/A System, B3221 Tinker AFB, Oklahoma 73145, United States · NAICS 236220 Air Force Sustainment Center Total Small Business
Fire Alarm/Suppression Inspection, Testing, and Maintenance Rome, New York 13441, United States · NAICS 561621 Air Force Research Laboratory No set-aside
Fire alarm replacement IDIQ Arlington, Virginia, United States · NAICS 238210 Office of Acquisition Management Total Small Business
H312--Fire Alarm Maintenance Service Contract FY27 - NEW Base + Four - 583 Indianapolis, Indiana 46202, United States · NAICS 561621 Veterans Integrated Service Network 10 Service-Disabled Veteran-Owned Small Business
Z1DA--Upgrade Fire Alarm System Construction 676-22-110 Tomah, Wisconsin 54660, United States · NAICS 238210 Veterans Integrated Service Network 12 Service-Disabled Veteran-Owned Small Business

On GovTribe

Work this opportunity

  • Track it in your pipeline
  • Find teaming partners
  • Similar opportunities
  • Ask GovTribe AI about this opportunity