4120--618-24-115 Replace Coil MAU #3 and #38

Closed Solicitation Posted

This opportunity was awarded. See the award notice from , or the latest solicitation from .

Solicitation number
36C26326B0002
Agency
Veterans Integrated Service Network 23 Veterans Health Administration, Department of Veterans Affairs
Responses due
Set-aside
Service-Disabled Veteran-Owned Small Business

Opportunity facts

NAICS code
238220 Plumbing, Heating, and Air-Conditioning Contractors
PSC
4120 Air Conditioning Equipment
Place of performance
Minneapolis, Minnesota 55417, United States
Points of contact

Notice details come from SAM.gov. Updated .

About this opportunity

The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23 is soliciting competitive bids for the replacement of two failing steam coils at the Minneapolis VA Health Care System, specifically Makeup Air Unit (MAU) #3 located in the Energy Center (Building 69) and MAU #38 located in the main hospital penthouse (Building 70). The scope of work includes removing and replacing the existing steam coils with freeze-proof Armstrong Centifeed Duramix models, replacing the MAU #3 steam trap with two parallel Armstrong AIC Series Float & Thermostatic steam traps for continuous service during maintenance, and furnishing all associated piping, valves, insulation, hangers, and labor necessary for installation per contract documents and applicable codes. Contractors must meet stringent safety and compliance requirements, including obtaining VA security clearances, completing OSHA training certification, and maintaining infection control protocols during all work. The submission deadline for bids is November 17, 2025, at 2:00 PM CST, with a pre-bid site visit scheduled for October 27, 2025, at the Minneapolis VA Medical Center. No evaluation criteria documentation was explicitly provided in the solicitation files, though standard federal procurement practices would typically emphasize cost, technical capability, and compliance with set-aside requirements.

This solicitation is issued as a total set-aside for Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with contractors required to be verified SDVOSB firms listed in the veterans.certify.sba.gov database and subject to subcontracting limitations specified in VAAR 852.219-75. The estimated contract value ranges between $250,000 and $500,000, classified under NAICS code 238220 (Plumbing, Heating, and Air-Conditioning Contractors) and PSC code 4120 (Air Conditioning Equipment). The contract period of performance is 150 calendar days from the Notice to Proceed, with work scheduled Monday through Friday from 7:00 AM to 5:00 PM, with substantial completion targeted for day 130. Prevailing wage rates established for Hennepin County, Minnesota under Davis-Bacon requirements apply, with minimum wage requirements of $17.75 per hour for workers on contracts entered into on or after January 30, 2022. The place of performance is Minneapolis, Minnesota 55417, and all work must be coordinated directly with VA personnel at the Minneapolis VA Medical Center facility.

Notice text

This is for Solicitiation 36C26326B0002

A. The MVAHCS has two failing steam coils that require replacement. These coils are located in the Energy Center (Building 69) & the penthouse of the main hospital (Building 70). The coils in these locations will need to be removed and replaced with freeze-proof models. The steam trap serving the Makeup Air Unit (MAU #3) in the Energy Center will be removed and replaced with (2) steam traps ran in parallel for continuous service during maintenance operations.
2. Bid Items:
A. Bid Item #1 – Provide lump sum (LS) pricing to remove existing MAU #3 & #38 steam coils and MAU #3 steam trap and furnish & install freeze proof coils, MAU #3 steam traps and associated piping, valves, insulation, hangers, etc. as necessary per contract documents, applicable codes and industry & VA standards.
3. Statement of Work:
A. Remove and replace Makeup Air Unit (MAU #3) steam coil located in Building 69 (Energy Center).
1. Replace with freeze proof steam coil that meets or exceeds coil specifications below (Brand Name or equivalent):
• ARMSTRONG CENTIFEED DURAMIX (Brand Name or Equivalent) – Qty. (1), FACE & BYPASS COIL HORIZONTAL
• CBH2-4L-A11-W08-BE-hand Centifeed Horizontal Duramix
• To heat 8,700 scfm from -30 to 70 F using 982 pph of 5 psig steam at coil
• Total heat load : 940 MBH, APD : 0.55'' w.g.
• Stainless Steel construction
2. Replace existing steam trap with (2) traps installed in a parallel configuration for continuous operations of MAU #3 when servicing the traps.
• ARMSTRONG AIC SERIES FLOAT & THERMOSTATIC STEAM TRAP (Brand Name or Equivalent) – Qty. (2)
• 1-1/2” 100 PSI flanged connection horizontal flow steam trap (100-AICF-H-6)
• Ductile iron body & cap
• Graphite gasket
• Stainless steel seat, internals & valve
• Hastelloy wafer thermostatic air vent
• Maximum allowable pressure – 580 PSIG
• Maximum operating pressure – 465 PSIG
• Maximum allowable temperature – 572 deg F
• Trap sizing – 2:1 SF @ 1/2 DIFF (14” MIN), 982#/HR*2=1964 #/HR
B. Remove and replace Makeup Air Unit. (MAU #38) steam coil located in the Penthouse of Bldg 70 (Main Hospital)
1. Replace with freeze proof steam coil that meets or exceeds coil specifications below (Brand name or Equivalent):
• ARMSTRONG - CBV2-8F-A9/10-W08-BEF-LH-1-110923-4-3, VERTICAL CENTIFEED DURAMIX (Brand Name or Equivalent) - 1 EA
• DURAMIX IFB STM COIL (2) 4'' inlets and (1) 3'' 150 lbs RFSO SS 304 L flanged Connections.
• To heat 45,000 scfm of air from -20 F to 50.8 F using 3,685 pph of 25 psig at coil.
• Total heat load : 3,440,880 ( 1 MW ), APD : 0.64" w.g.
• Retromix option - 1 ea, split coil - trap separately
Additional Steam Coil Notes:
1) 5/8’’ SS 304 L inner tube for low pressure operation.
2) 150 lbs SS 304 L RFSO flange included.
3) Belimo electric actuator in the face included.
4) VA med. Application : coil cleaned prior to shipment.
5) Epressure design included.
6) Same end connection at the bottom since this is a Duramix coil.
C. Contractor shall furnish all supervision, labor, materials, equipment, transportation and testing necessary to perform construction work for the “Replace Steam Coils” Project – VAMC Minneapolis Project Number 618-24-115 per specifications and scope of work.
D. This includes:
a. Determining the proper size and quantity of all repair materials required for this project.
b. Providing all tools, materials and equipment associated with replacing the Steam Coils and any necessary rigging, personnel lifts and scaffolding needed to safely complete the project.
c. Performing Lock out/Tag out at all sources of stored energy on affected equipment – Elec, Gas, Steam Water, etc. Refer to 013526 – Safety Requirements regarding procedures.
d. Isolating steam/condensate piping and disconnecting from MAU. Remove piping to allow for removal of coil section.
e. Installing new steam coils that meet the specifications above. Provide necessary caulking and bolting per manufacturer’s requirements.
f. Installing new piping, insulation, equipment, specialties and accessories serving the replaced steam coils as required according to latest industry standards, ensuring proper air venting and vacuum relief for new coil operation.
g. Pressure testing newly installed piping between the coils and isolation point, prior to installing insulation. A hydrostatic test will be performed at 1.5 times the system design pressure. Contractor to send test reports to COR in closeout documentation.
h. Installing mineral fiber insulation on all new steam and condensate pipes. Insulation thickness to match existing.
i. Startup and confirmation the new coils are operating in conjunction with the Building Automation System (BAS). Interface all input/output signals to Metasys (Johnson Controls, Inc.).
j. Field verifying all existing conditions prior to construction start. Contractor shall notify COR of any discrepancies between specifications and existing conditions. It is highly encouraged the contractor and any subcontractors field verify existing conditions prior to submitting bids.
k. Protecting any items not to be removed from damage. Any damage shall be corrected by the contractor with no additional time and/or money.
4. Period of Performance (PoP): Contract PoP will be from Notice to Proceed (NTP) date plus 150 days.

Attachments

Files attached to this notice, newest first
File Type Posted
S02- 36C26326B0002 10.16.25.docx DOCX document
Attach A-SOW R2.pdf PDF
Attach C - Prevailing Wage Rates.pdf PDF
Attach B - Questions Request Form - 1 page.pdf PDF
Attach D - VAAR 852.219-75 Limitations on Subcontracting-Cert of Compliance_JAN 2023 [D.pdf PDF
Attach E- Replace Coil specs.pdf PDF

Notice history

Notices posted for this opportunity, newest first
Notice Type Posted
4120--618-24-115, Replace Coil MAU #3 and #38 36C26326C0012; PO#: 618C60104 Award Award Notice
4120--618-24-115 Replace Coil MAU #3 and #38 Latest solicitation Solicitation
4120--618-24-115 Replace Coil MAU #3 and #38 Solicitation
4120--618-24-115 Replace Coil MAU #3 and #38 This notice Solicitation
4120--618-24-115 Replace Coil MAU #3 and #38 Original Pre-Solicitation