Current Vendor Q and As.xlsx

XLSX spreadsheet 14 KB Posted

Attached to
FEMA -Self-Supporting Tower, Log Periodic Antenna, Grounding, and Transmission Line Installation
Solicitation number
WX03345Y2025T
Issued by

About this file

The file is a Q&A document for a FEMA solicitation (WX03345Y2025T) for a self-supporting tower, log periodic antenna, grounding, and transmission line installation project. The opportunity is a new requirement with an estimated contract value between $10,000 and $250,000, with a 90-day performance period from the award date. Key technical details include installing a USAP 3002SS 100-foot self-supporting tower with a climbing ladder kit and 80-foot safety climb, which will be provided by FEMA. The project involves tower, antenna, grounding, and transmission line installation on an existing foundation, with specific requirements such as pointing the antenna at 113 true north using a compass and terminating coax with specific EIA flanges. Vendors have sought clarification on various technical aspects, including anchor bolts, tower specifications, and conduit routing, with FEMA providing detailed responses to ensure clear project understanding.

View the file

Other files

File Type Posted
Current Vendor Q and As updated 6.27 .xlsx XLSX spreadsheet
Current Vendor Q and As. Updated 6.4.xlsx XLSX spreadsheet
Current Vendor Q and As Updated 6.4.xlsx XLSX spreadsheet
Current Vendor Q and As updated 6.3.xlsx XLSX spreadsheet
Solicitation WX03345Y2025T updated 6.3.pdf PDF
Current Vendor Q and As. 06.02.xlsx XLSX spreadsheet
Current Vendor Q and As 06022025 1028AM.xlsx XLSX spreadsheet
Current Vendor Q and As.xlsx XLSX spreadsheet
Solicitation WX03345Y2025T.pdf PDF
Statement of Work.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sheet1

Quest. #TimestampDescriptionAsked BySeller Organization
1Fri 5/30/2025 8:16 AM1.Could you kindly confirm whether this initiative represents a new undertaking, or is there an incumbent currently delivering these services? If an incumbent exists, may we request the relevant details of their contract, including the contract number?
2.Could you share the anticipated contract value associated with this opportunity?Seller RepProposalHelper
Fir 5/30/2025 9:37 AMBuyer Response: 1. This is a new requirement. 2. The estimated range is over $10,000 and up to $250,000
2Fri 5/30/2025 2:40 PMQuestion 1

This question is in related to the external ground ring.

Was the ground ring not installed during the foundation installation?

It was part of the foundation scope.

Question 2 Is there a spec sheet on the USAP model 3002 SS Self Supporting Tower that details the tower section weights?

Question 3

Will it be possible for the awarded contractor to ship items related to the project directly to the project location prior to start of work.Seller RepVertical Technology Services, LLC
Mon 06/02/2025 10:27AMBuyer Response: Q1: The installation requires Ground ring Q2: Yes. Q3: . We will coordinate advance shipment of related items for the project with the appropriate point of contacts once awarded.
3Mon 6/2/2025 11:49 AM1. Is there a cost estimate , budget or ballpark figure for the project listed? 2. Is there an actual start date for the project?
Mon 6/2/2025 12:30 PMBuyer Response: Per the period of performance, all work shall be completed by the contractor within 90 days from the award date of the resulting order. The estimated range is over $10,000 and up to $250,000Seller RepConstruct Connect
4Tues 6/3/2025 9:52:00 AMThe solicitation specifically calls out the tower, antenna, grounding and transmission line installation. There is no reference to the foundation installation aside from a foundation drawing. Is the foundation installation part of the scope of work, or will the foundation be by others?
Buyer Response: The foundation will not be part of the scope of work. The foundation will be in place when the project starts.
5Wed 6/4/2025 9:17AM1.Will the anchor bolts and anchor bolt templates be provided with this tower? We see that FEMA is providing the tower and antenna but it does not specifically state if the anchor bolts, anchor hardware and templates are being provided.
2.Please confirm we can used the stamp tower drawing as provided as Attachement I, on page 15 of the SOW and we do not need to have our own stamped drawings created. Can you please provide the original PDF? This one is scanned and inserted in the document so quality is lost.Seller RepElk Mountain Technology LLC
Wed 6/4/2025 10:01AMBuyer Response Q1 : The anchor bolts will be imbedded in the foundation and the anchor bolt templates will be provided. Q2: The document attached with Statement of Work will be available for the contractor. Tower will be installed on an existing foundation that was tailored for the tower being installed. So site work and pouring foundation NO. Erecting and installing antenna YES
6Fri 6/6/2025 10:21 AM1.Item 11 requests that the coax be "terminate with 1 5/8” EIA Flange at the antenna". The EIA flange is typically 7/8". They make a 1 5/8" coax EIA flange connector but this project requests AVA5 which is 7/8 cable. Please confirm the attached connector with a 7/8" EIA flange is what is desired.
2.The project states that the new coax should be 400' long and references conduit. We assume that we are pulling the new AVA5 7/8" coax through a conduit that has been installed by others as part of the foundation installation? Can you please provide a few pictures of the tower foundation and the transition from the conduit to the tower foundation and building? What size is the conduit? There is a picture of the building entry port in the SOW however no conduit is visible so we are trying to understand the coax routing effort.SellerElk Mountain Technology LLC
Buyer Response: AWAITING RESPONSE
7Tues 6/17/2025 2:43PMPlease clarify the following: "SPEC-PDF PG2,35. Install USAP 3002SS 100 Ft Self Supporting Tower & Mast with rotor bypass modification (Attachments C and F), with Climbing ladder kit, and 80-foot safety climb according to manufacturer’s specifications." Please confirm that the climbing ladder kit and 80-foor safety climb are both provided by FEMA.SellerSitemaster
Wed 6/18/2025 6:26AMBuyer Response: Yes, the climbing ladder kit and 80-foot safety climb will be provided by FEMA.
8Tue 6/17/2025 3:07 PMWhat is the required method for determining the following: 4. Antenna will be pointed at 113° true north. (Attachments A, E, and H)SellerSitemaster
Buyer Response: The use of a compass is sufficient.