The document is a Compliance Assistance Offer letter from the Florida Department of Environmental Protection (FDEP) South District, dated May 3, 2023, addressed to Florida Fish and Wildlife Conservation regarding the Fisheating Creek Campground water system (Facility ID: 5220179) in Glades County. The letter follows a Sanitary Survey Inspection conducted on January 31, 2023, which identified several potential non-compliance issues with state water system regulations, including the absence of a bacteriological sampling plan, an uninspected hydropneumatics tank, vegetation overgrowth in the well area, a dirty sight glass on the hydropneumatics tank, a leaking well with biogrowth, and lack of documentation for annual aerator and clearwell cleaning.
The document outlines specific deficiencies with their corresponding rule references and required corrective actions, such as submitting an updated bacteriological sampling plan, providing documentation of tank inspection and cleaning, addressing well leakage and biogrowth, cleaning the hydropneumatic sight glass, and documenting aerator and clearwell maintenance. The FDEP requires a response within 30 days, offering three options: describing corrective actions, providing mitigating information, or arranging a facility visit. The inspection report includes photographic evidence of the identified issues, and some deficiencies were already marked as corrected during the inspection, such as chlorine residual levels and a hole near the well. The letter warns that failure to respond promptly may result in formal enforcement proceedings.
View the file
Other files for this state and local contract opportunity
| File | Type | Posted |
|---|---|---|
| FWC 1920-85- Price Sheet.pdf | ||
| North Lift Station Specs.pdf | ||
| South Lift Station Specs.pdf | ||
| WWTP Inspection Report 11-13-24.pdf | ||
| FWC 24.25 -102 FINAL.pdf | ||
| FWC 24.25-102 Addendum #2 QAs FINAL.pdf | ||
| FWC 24.25 -102 FINAL.pdf | ||
| FWC 24.25-102 Addendum #1 Calendar of Events.pdf |
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
www.FloridaDEP.gov
FLORIDA DEPARTMENT OF
Environmental Protection
South District PO Box 2549
Fort Myers FL 33902-2549 SouthDistrict@FloridaDEP.gov
Ron DeSantis Governor
Jeanette Nuñez
Lt. Governor
Shawn Hamilton Secretary
May 3, 2023
Florida Fish and Wildlife Conservation 3900 Commonwealth Blvd MS115 Tallahasee, FL 32399
Re: Compliance Assistance Offer
Fisheating Creek Campground Facility ID: 5220179 Glades County - PW
To Whom It May Concern:
A Saniatry Survey Inspection was conducted at your site on January 31, 2023.
During this inspection, potential non-compliance was noted. The purpose of this letter is to offer compliance assistance as a means of resolving this/these matter(s).
Specifically, potential non-compliance with the requirements of Chapters 373 and 403, Florida Statutes and Chapters 62-550 and 62-555, Florida Administrative Code were observed. Please see the attached inspection report for a full account of Department observations and recommendations.
• A Bacteriological sampling plan was not on site.
• The hydropneumatics tank inspection report was not available or the hydropneumatics tank has not been inspected in the past 5 years.
• Vegetation overgrowth was noted in the well area.
• The sight glass on the hydropneumatics tank was dirty and the level of the tank could not be determined.
• The well was leaking and biogrowth was noted.
• Aerator and clearwell are supposed to be cleaned every year. No documentation showing the last time the aerator and the clearwell were cleaned.
http://www.floridadep.gov/
Compliance Assistance Offer Fisheating Creek Campground; Facility ID: 5220179 May 3, 2023
We request you review the item(s) of concern noted and respond within 30 days of receipt of this Compliance Assistance Offer. Your response should include one of the following:
1. Describe what has been done to resolve the non-compliance issue or provide a schedule describing how/when the issue will be addressed.
2. Provide the requested information, or information that mitigates the concerns or demonstrates them to be invalid, or
3. Arrange for the case manager to visit your facility to discuss the item(s) of concern.
It is the Department’s desire that you are able adequately address the aforementioned issues so that this matter can be closed. Your failure to respond promptly may result in the initiation of formal enforcement proceedings.
Please address your response and any questions to Vanessa Kraft of the South District Office at 239-344-5678 or via e-mail at Vanessa.Kraft@FloridaDEP.gov.
We look forward to your cooperation with this matter.
Sincerely, Elizabeth Sweigert Assistant Director of District Management South District Florida Department of Environmental Protection
Enclosures: Inspection Report cc: Joseph Warren: watersolutionsofswfl@gmail.com Jeanine Phelps: JPhelps@fisheatingcreekoutpost.com mailto:Vanessa.Kraft@FloridaDEP.gov mailto:watersolutionsofswfl@gmail.com mailto:JPhelps@fisheatingcreekoutpost.com
Florida Department of Environmental Protection South District Public Water System Sanitary Survey Inspection Report
Water system: System PWS #: Survey date:
Facility type class: ________________ ___- __ _ Source type: 4-Log approved:
Facility address:
Facility phone(s): Facility email/fax:
Facility contact: Facility contact phone(s):
Facility contact email/fax:
Owner name: Company name:
Owner/Corp address: City: State: Zip:
Owner/Corp phone(s): Owner e-contact(s):
Operator name: Certification:
Operator phone(s): Operator email/fax:
On-site Rep: Immediate Action Required? Inspection recap given?
GENERAL INFORMATION
Number of Service Connections Population Served Plant Design Capacity Average Day (from MORs) Max. Day (from MORs) Total Storage Capacity Comments:
OPERATION & MAINTENANCE
Certified Operator: Yes No Not required Plant visits conducted by:
O&M Log: Yes No O&M Manual: Yes No Visitation Frequency
Hrs/day: Required Actual
Hrs/wk: Required Actual
Days/wk: Required Actual
Non-consecutive Days? Yes No N/A MORs submitted regularly? Yes No N/A Data missing from MORs? Yes No N/A
CHLORINATION (Disinfection) Type:
Capacity Units Total Each Chlorine Feed Rate Avg. Amount of Cl2 gas used Chlorine Residuals: Plant Remote Remote tap location Injection Points Booster Pump Info Comments:
AERATION (Gases, Fe, & Mn Removal) Type Capacity Aerator Condition Visible Algae Growth Protective Screen Condition Comments:
RAW WATER SOURCE
GROUND; Number of Wells SURFACE/UDI; Source PURCHASED from PWS ID # Emergency Water Source Emergency Water Capacity
AUXILIARY POWER SOURCE
Yes None Not Required
Source Capacity of Standby (kW) Switchover: Automatic Manual Standby Plan: Yes No Hrs Operated Under Load What equipment does it operate?
Well pumps High Service Pumps Treatment Equipment
Satisfy 1/2 max-day demand? Yes No Unk Comments:
DISTRIBUTION SYSTEM
Flow Measuring Device Meter Size & Type Meter tested w/i 5 yrs? Yes No Unk N/A Backflow Prevention : Yes No Cross-connections Cross-connection Control Program: Yes No N/A Coliform Sampling Plan: Yes No Stage 2 DBPs Sampling Plan: Yes No N/A Lead & Copper Sampling Plan: Yes No N/A Comments:
SERVICE AREA CHARACTERISTICS:
Food Service: Yes No N/A
Water System: PWS ID # Survey Date
STORAGE FACILITIES
Tank Type
Capacity
Material
By-pass Piping
Gravity Drain
PRV/ARV
Protected Openings
Pressure Gauge
Sight Glass or Level Indicator Fittings for Sight Glass Access Padlocked
Last Inspection Date (for tanks with access manholes) On/Off Pressure
Height to Bottom of Elevated Tank Height to Max.
Water Level
Comments:
HIGH SERVICE (HSP), BACKWASH (BWP), TRANSFER (TP) and OTHER (OP) PUMPS Pump Purpose
Pump Number
Type
Capacity (gpm)
Motor HP
Date Installed
Comments:
PWS ID #Water System:____________________
GROUND WATER SOURCE
Well Name (System Identification)
Florida Well ID
Year Drilled
Depth Drilled
Length (outside casing)
Diameter (outside casing)
Is inundation of well possible? Yes No Yes No Yes No Yes No
6’ X 6’ X 4” Concrete Pad Yes No Yes No Yes No Yes No
PUMP
Type
Rated Capacity (gpm)
Motor Horsepower
Well casing 12” above grade? Yes No Yes No Yes No Yes No
Well Casing Sanitary Seal Yes No Yes No Yes No Yes No
Raw Water Sampling Tap Yes No Yes No Yes No Yes No
Above Ground Check Valve Yes No Yes No Yes No Yes No
Fence/Housing Yes No Yes No Yes No Yes No
Well Vent Protection Yes No Yes No Yes No Yes No
COMMENTS:
TREATMENT PROCESSES IN USE:
Is additional treatment needed? Yes No If so, for control of what deficiencies?
MONITORING VIOLATIONS MCL VIOLATIONS
MONITORING COMMENTS:
PWS ID #Water System:____________________
DEFICIENCIES:
Deficiency Rule Reference Corrective Action Severity Corrected
Any deficiency marked with an asterisk (*) is a repeat violation.
ADDITIONAL COMMENTS:
Inspector: _______________________ Approved by: _____________ ____
Photos by Megan Jarabek on 1/31/2023
Fisheating Creek Campground (PWS ID: 5220179) I certify that these photos represent the true on-site conditions observed and have not been altered in any way.
Photo 1: Well and pumps Photo 2: Leak and biogrowth
Photo 3: Hole next to well Photo 4: Chlorine Storage
Photo 5: Sight glass on hydropneumatic Photo 6: Aerators
Photo 7: Hole filled in at well Photo 8: Remote chlorine residual fixed
Photo 9: POE chlorine residual fixed