Wapello 23-05-26-01_Drawings_Final.pdf

PDF 14 MB Posted

Attached to
Office/Shop Buildings for George Wyth State Park and Upper Iowa Wildlife Management Area
Solicitation number
25CRDLWBGANTO-0014
Issued by
Black Hawk County, Iowa

About this file

This file contains construction drawings from the Iowa Department of Natural Resources for an office and storage building project at Lake Wapello State Park in Davis County, Iowa (Project #23-05-26-01). The drawings detail architectural, mechanical, electrical, and plumbing specifications for a new combined office and storage facility. The plans include site preparation, foundation work, building construction, interior finishing, HVAC systems, electrical systems, lighting, plumbing fixtures, and sanitary systems. The building features both office space and a larger storage/shop area with overhead doors, ADA-compliant restroom facilities, mechanical/utility rooms, and basic break room amenities.

The drawings specify detailed requirements for materials and installation including concrete foundations, wood frame construction, metal roofing, electrical service rated at 120/240V with a 225A main circuit breaker, HVAC equipment including unit heaters and exhaust fans, plumbing fixtures, lighting systems with occupancy sensors and emergency backup, and site utilities including water, septic, and electrical service connections. The plans include specific details for ADA compliance, energy efficiency measures, and commercial-grade construction suitable for a state park maintenance facility. All work must comply with applicable state and local building codes as well as DNR facility standards.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ryan E Richey Digitally signed by Ryan E Richey DN: C=US, E=ryan.richey@dnr.iowa.gov, O=Iowa Department of Natural Resources, OU=Engineering Section - L&W Bureau, CN=Ryan E Richey Date: 2023.03.20 08:46:25-05'00'

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T O

F N

A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N G

S

ER

V

IC

ES

W A

LL

A

C E

BU

IL

D

IN

G

E.

TH

S T.

, D

ES

M O

IN

ES

, I A

-0

P:

.7

.8

F:

.7

.8

SURVEY CONTROL POINTS

C1

SURVEY CONTROL NOTES

SU

RV

EY

/D

IM

EN

SI

O

N P

LA

N

GENERAL NOTES

TREES

X XX 8" FILTER SOCK

ELEVATION

SPOT ELEVATION882.67 884.50

ELECTRICAL LINE

LEGEND

EXISTING/PROPOSED

E

WATER MAINW 2"

SANITARY SEWERS 6"

STORM SEWERST8"

SURVEY CONTROL POINT #14

N: 300972.318 E: 1895387.673

ELEV: 833.395

PK NAIL IN CONC

SURVEY CONTROL POINT #12

N: 300957.300 E: 1895040.970

ELEV: 856.614

PK NAIL IN CONC

SURVEY CONTROL POINT #13

N: 300962.474 E: 1894964.671

ELEV: 855.222

PK NAIL IN CONC

SURVEY CONTROL POINT #11

N: 300932.379 E: 1895093.089

ELEV: 855.206

PK NAIL IN CONC

DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T O

F N

A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N G

S

ER

V

IC

ES

W A

LL

A

C E

BU

IL

D

IN

G

E.

TH

S T.

, D

ES

M O

IN

ES

, I A

-0

P:

.7

.8

F:

.7

.8

C2

G

RA

D

IN

G /U

TIL

ITY

P

LA

N

GRADING NOTES

UTILITY NOTES

TREES

X XX 8" FILTER SOCK

ELEVATION

SPOT ELEVATION882.67 884.50

ELECTRICAL LINE

LEGEND

EXISTING/PROPOSED

E

WATER MAINW 2"

SANITARY SEWERS 6"

STORM SEWERST8"

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T O

F N

A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N G

S

ER

V

IC

ES

W A

LL

A

C E

BU

IL

D

IN

G

E.

TH

S T.

, D

ES

M O

IN

ES

, I A

-0

P:

.7

.8

F:

.7

.8

C3

D

ET

A

IL

S

4" PAINTED

WHITE STRIPE

(TYP.)

ACCESS AISLE AND

PARKING STALL TO

HAVE NO MORE THAN

2% SLOPE IN ANY

DIRECTION

2'

45°

11' 5'

PAVEMENT

MARKINGS FOR

PARKING STALLS

DETAIL

NOT TO SCALE

5'5'5'

HANDICAP SIGN

5'

5'

6' WHEEL STOP (TYP.)

MUTCD R7-8

SOLID GREEN LEGEND AND BORDER

REFLECTIVE WHITE BACKGROUND

WHITE ACCESSIBILITY SYMBOL ON

BLUE BACKGROUND

"U"-CHANNEL

POST (2 LBS./FT.)

RESERVED

PARKING

7'

GROUND

SURFACE

3.5-FOOT DEPTH

1'-6"

NOTES

1. 12"x18" ACCESSIBILITY SIGN (R7-8) SHALL BE

MOUNTED 7' FROM FINISH GRADE TO BOTTOM

EDGE OF SIGN FACE.

2. SIGNAGE FOR TO BE LOCATED ON END OF

PARKING STALL, 2' BACK FROM EDGE OF

PAVEMENT, CENTERED ON STALL. "U" CHANNEL

CAN BE DRIVEN INTO GROUND AT SAID

LOCATION TO A DEPTH OF 3.5 FEET.

3. ALL SIGNAGE SHALL BE ENGINEER GRADE

.080 ALUMINUM REFLECTIVE SIGN MEETING THE

REQUIREMENTS OF THE MUTCD AND ADAAG.

4. SURFACE MOUNTING BASE TO BE 15-INCH

DIAMETER ALUMINUM BASE (OR EQUIVALENT)

THAT IS COMPATIBLE WITH 2 LBS./FT. "U"

CHANNEL.

HANDICAP SIGN DETAIL

NOT TO SCALE

5.5'5'5'

5'5.5'

10'10'10'

6-INCH PCC CONCRETE

ADA PARKING SPACE

6-INCH GRAVEL PARKING AREA

5'

TREES

X XX 8" FILTER SOCK

ELEVATION

SPOT ELEVATION882.67 884.50

ELECTRICAL LINE

LEGEND

EXISTING/PROPOSED

E

WATER MAINW 2"

SANITARY SEWERS 6"

STORM SEWERST8"

DATE

BY REVISION

DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

C4

SA

N

ITA

RY

/S

EP

TIC

P

LA

N

TREES

X XX 8" FILTER SOCK

ELEVATION

SPOT ELEVATION882.67 884.50

ELECTRICAL LINE

LEGEND

EXISTING/PROPOSED

E

WATER MAINW 2"

SANITARY SEWERS 6"

STORM SEWERST8"

SSI

M-000

M E

C H

A N

I C

A L

G

E N

E R

N

O T

S

D

Y M

B O

L S i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

CU

F

EF

LV

MOD

EF

UH

UH

UH

M-100

F L

O O

R

P

L A

N

M

E C

H A

N I C

A L

NORTH

1/4" = 1'-0"

FLOOR PLAN - MECHANICAL

i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

M-200

M E

C H

A N

I C

D

T

A I L

S i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

M-300

M E

C H

A N

I C

C H

E D

U L

E S

BNC

1/13/23

ADDENDUM 1

i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

WH

CP

P-100

F L

O O

R

P

L A

P

L U

M B

I N

G

NORTH

1/4" = 1'-0"

UNDERFLOOR PLAN - PLUMBING

NORTH

1/4" = 1'-0"

FLOOR PLAN - PLUMBING

i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

P-200

L

U M

B I N

G

D

E T

A I L

S i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

P-300

L

U M

B I N

G

S

C H

E D

U L

E S i n f o k c l e n g i n e e r i n g c o m t h

S t r e e t

W e s t

D e s

M o i n e s

I o w a

PROJECT NUMBER:

DATE:

NO. DATE

BY REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N

SU

LT

A

N T:

23-05-26-01

03.21.2023

N

EW

O

FF

IC

E

S

TO

RA

G E

BU

IL

D

IN

G F

O R:

LA

KE

W A

PE

LL

O S

TA

TE

P A

RK

C

A M

PG

RO

UN

D

R O

A D

D

RA

KE

SV

IL

LE

, I A

IO

W

A D

EP

A

RT

M

EN

T

O F

N A

TU

RA

L

RE

SO

UR

C

ES

EN

G

IN

EE

RI

N

G S

ER

V

IC

ES

W

A

LL

A C

E

BU

IL

D

IN

G

E.

TH

S

T.

, D

ES

M

O

IN

ES

, I

A

-0

P:

.7

.8

F:

.7

.8

GENERAL SYMBOLS

JUNCTION BOX, CEILING OR FLOOR MOUNTED.

JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.

J

J

EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE

DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE

A101

SIM

KEYNOTE#

XXX

X

SHEET REFERENCE

LIGHTING SYMBOLS

ROUND LIGHT FIXTURE - RECESSED

SUSPENDED STRIP LIGHT FIXTURE

EMERGENCY LIGHT FIXTURE, WALL MOUNT, +96" OR AS NOTED

EXIT SIGN, WALL MOUNT +96", SHADED AREAS INDICATE NUMBER OF

FACES, ARROWS INDICATE SIGN ARROWS

EXTERIOR LIGHT FIXTURE, WALL MOUNT +10', OR AS NOTED

SINGLE POLE SWITCH, WALL MOUNT +48", OR AS NOTED,

LETTER INDICATES SWITCH LEG

OCCUPANCY SENSOR, WALL MOUNT +48" OR AS NOTED, NUMBER INDICATES TYPE,

LETTER INDICATES SWITCH LEG, REFER TO LIGHTING CONTROLS SCHEDULE

OS

a c

2X2 LIGHT FIXTURE - RECESSED

F1(6')

+10'-6" c

EM

UPPERCASE LETTERING

INDICATES FIXTURE TYPE.

REFER TO LUMINAIRE SCHEDULE

+## INDICATES FIXTURE MOUNTING HEIGHT

FROM BOTTOM OF FIXTURE TO FINISHED

FLOOR. COORDINATE ALL FIXTURE

ELEVATIONS WITH ARCHITECTURAL RCP

PRIOR TO ROUGH-IN AND SHOP SUBMITTALS.

LOWERCASE LETTERING INDICATES SWITCH LEG.

SHADING AND/OR "EM#" INDICATES

EMERGENCY OPERATION FIXTURE. NUMBER

INDICATES EMERGENCY CIRCUIT NUMBER.

LIGHTING PLANS NOTATION KEY

POWER SYMBOLS

DUPLEX RECEPTACLE, WALL MOUNT +18", OR AS NOTED

DUPLEX GFCI RECEPTACLE, WALL MOUNT +18", OR AS NOTED

G

DUPLEX GFCI WEATHER RESISTANT RECEPTACLE WITH WEATHER-PROOF

IN-USE COVER, WALL MOUNT +24", OR AS NOTED

EQUIPMENT CONNECTION, REFER TO ELECTRICAL EQUIPMENT CONNECTION

SCHEDULE FOR CONNECTION TYPE

W

MOTORIZED DOOR OPERATOR CONTROL STATION, WALL MOUNT, +48", OR AS NOTED

UTILITY METERM

PANELBOARD - SURFACE MOUNTED

J CORD REEL, CEILING MOUNTED - REFER TO DETAIL

DISCONNECT SWITCH

SPECIAL EQUIPMENT CONNECTION

DUPLEX GFCI RECEPTACLE, WALL MOUNT, ABOVE COUNTER, OR AS NOTED

G,A

TV RECEPTACLE, WALL MOUNT +60", OR AS NOTED

TV

+60"

1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL

OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY

COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.

COORDINATE WITH BUILDING STRUCTURE, ARCHICTURE, MECHANICAL SHEET METAL, ALL

PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT

ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL

DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR

REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.

2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND

CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE

SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;

ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN

REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.

GENERAL NOTES - ELECTRICAL

GENERAL NOTE:

UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES HAVE BEEN SHOWN BASED UPON

INFORMATION OBTAINED FROM FIELD LOCATIONS BY UTILITY COMPANIES, AVAILABLE SURVEYS

AND RECORDS. THEIR LOCATIONS MUST BE CONSIDERED APPROXIMATE ONLY. IT IS ALSO

POSSIBLE THAT THERE MAY BE OTHER UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES IN

EXISTENCE THAT ARE NOT SHOWN. IT IS THE RESPONSIBILITY OF EACH INDIVIDUAL PARTY

REFERENCING THIS PLAN TO DETERMINE THE EXACT LOCATION AND TYPE OF UNDERGROUND

FACILITIES ON THE SITE. HAND EXCAVATE AT CRITICAL POINTS AS NECESSARY TO VERIFY

LOCATIONS, SIZES, ELEVATIONS, FLOW LINES, ETC. IF A PROBLEM OR INTERFERENCE EXISTS, NOTIFY ARCHITECT/ENGINEER BEFORE PROCEEDING.

IOWA

ONE CALL

1-800-292-8989

CALL - BEFORE - YOU - DIG

1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL LOCAL, STATE, AND

NATIONAL CODES.

2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE

ELECTRICAL INSTALLATION. VERIFY WITH LOCAL OFFICIALS WHEN PERMITS ARE OBTAINED.

NOTIFY DESIGN TEAM OF ANY DESCREPANCIES BETWEEN THE PROJECT MANUAL OR

DRAWINGS AND THE GOVERNING CODE.

3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH

DISABILITIES ACT.

4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE

CODES.

CODE NOTES - ELECTRICAL

1. BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO BID.

2. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO

CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.

3. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL

AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER

OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF

INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.

4. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.

MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND

OPERATIONAL SYSTEM.

5. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO

NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.

6. DO NOT INSTALL BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE SAME WALL.

MAINTAIN MINIMUM OF 8” DISTANCE BETWEEN BOXES WHEREVER APPLICABLE.

7. BALANCE PANEL LOADS DURING INSTALLATION. CIRCUIT NUMBERING SHOWN ON PLANS

MAY BE ADJUSTED TO ACCOMODATE.

8. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND

EXISTING PANELS WITH CIRCUITS MODIFIED AS A RESULT OF THIS PROJECT. USE

OWNER’S CURRENT ROOM NUMBERS AND EQUIPMENT NAMES.

9. CONTRATOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND ROOFS

THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL PENETRATIONS IN

ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY. REFER TO

ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.

INSTALLATION NOTES - ELECTRICAL

1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.

2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.

3. PROVIDE GFCI TYPE RECEPTACLES AT ALL LOCATIONS REQUIRED BY THE NEC.

4. INSTALL WALL MOUNTED RECEPTACLES AT +18" ABOVE FINISHED FLOOR UNLESS OTHERWISE

NOTED.

5. INSTALL WALL MOUNTED LIGHT SWITCHES AT +46” ABOVE FINISHED FLOOR UNLESS

OTHERWISE NOTED. EXCEPTION; INSTALL DEVICES ABOVE AN OBSTRUCTED HIGH FORWARD

REACH OBSTACLE GREATER THEN 20 INCHES IN DEPTH AT +42”.

6. INSTALL ABOVE COUNTERTOP RECEPTACLES +8” ABOVE COUNTERTOP OR AS OTHERWISE

INDICATED.

7. AT A COMMON COUNTERTOP, INSTALL ALL RECEPTACLES AND SWITCHES AT THE SAME

HEIGHT UNLESS OTHERWISE SPECIFICALLY INDICATED.

DEVICE INSTALLATION AND MATERIALS - ELECTRICAL

1. UNLESS NOTED OTHERWISE, CONNECT ALL EMERGENCY BATTERY FIXTURES WITH AN UN-

SWITCHED LEG OF THE LIGHTING CIRCUIT THAT SERVES THE FIXTURES SPACE. MAINTAIN

NORMAL SWITCHING SCHEME OF EMERGENCY FIXTURES UNDER NORMAL OPERATION.

INSTALL PER EMERGENCY FIXTURE OR TRANSFER DEVICE INSTRUCTIONS.

2. VERIFY CEILING TYPE (IE. GRID, GYP) WITH ARCHITECTURAL REFLECTED CEILING PLANS

PRIOR TO RELEASE OF LIGHTING FIXTURE EQUIPMENT PACKAGE. ADJUST FIXTURE TYPE,

CONSTRUCTION, FLANGE, OR OTHER COORDINATION DETAILS AS REQUIRED FOR CEILING

TYPE.

3. LIGHTING CONTROLS SENSORS ARE SHOWN ON PLANS AT SUGGESTED LOCATIONS ONLY.

VERIFY LOCATIONS WITH MANUFACTURER GUIDELINES AND INSTALLATION

RECOMMENDATIONS. ADJUST LOCATIONS AS REQURIED TO MEET MANUFACTURER

GUIDELINES.

4. PROVIDE LIGHTING CONTROLS AS A COMPLETE SYSTEM AND INCLUDE MATERIAL AND

INSTALLATION FOR ALL POWER PACKS, ACCESSORIES, CONTROLLERS, AND WIRING

REQUIRED FOR OPERATION.

INSTALLATION NOTES - LIGHTING

REFER TO EQUIPMENT CONNECTION SCHEDULE FOR COORDINATION DETAILS BETWEEN

MECHANICAL AND ELECTRICAL SYSTEMS.

PROVIDE AND INSTALL ELECTRICAL SYSTEMS UNDER THIS CONTRACT MEETING THE

REQUIREMENTS OF THE SPECIFIED MECHANICAL, FIRE PROTECTION, AND PLUMBING

SYSTEMS. REFERENCE THE ENTIRE PROJECT DOCUMENTS, MANUALS, SCHEDULES, DETAILS,

AND NOTES.

PROVIDE ELECTRICAL CONNECTIONS AND ACCESSORIES INCLUDING STARTERS,

DISCONNECTS, CONTROL WIRING, ETC. AS REQUIRED FOR THE BUILDING MECHANICAL

EQUIPMENT. INFORMATION HEREIN AND ON THE DRAWINGS IS FOR GENERAL DESCRIPTION

AND ESTIMATING PURPOSES ONLY. VERIFY VOLTAGE, AMPERAGE, PHASE, INRUSH, ETC. FOR

EACH ITEM OF EQUIPMENT BEFORE PROCEEDING WITH INSTALLATION. INSTALL EQUIPMENT

PER WIRING DETAILS AND INSTRUCTIONS FURNISHED BY THE SUPPLIERS OF THE EQUIPMENT

TO PROVIDE PROPER OPERATION.

REVIEW MECHANICAL EQUIPMENT SHOP DRAWINGS FOR COMPLIANCE AND COORDINATION

WITH ELECTRICAL CONNECTIONS. NOTIFY ENGINEER IF CHANGES TO ELECTRICAL

CONNECTIONS, WIRING, AND BREAKER REQUIREMENTS ARE NECESSARY TO ACCOMMODATE

EQUIPMENT BEING SUPPLIED.

a. DO NOT RELEASE ELECTRICAL DISTRIBUTION EQUIPMENT UNTIL ALL MECHANICAL

EQUIPMENT REQUIRING ELECTRICAL INFRASTRCTURE HAS BEEN SUBMITTED AND

APPROVED. MAKE COORDINATION ADJUSTMENTS TO BREAKER SIZES AND SIMILAR

CHANGES TO ELECTRICAL EQUIPMENT PRIOR TO SUBMITTAL RELEASE. COORDINATE

SCHEDULING OF SHOP DRAWINGS WITH ALL TRADES.

PROVIDE DISCONNECTS RATED FOR EQUIPMENT AS REQUIRED AND AS INDICATED WITHIN

EQUIPMENT CONNECTION SCHEDULE. COORDINATE DISCONNECT MOUNTING TO ALLOW

EQUIPMENT REMOVAL WITHOUT DISCONNECT REMOVAL AND TO MINIMIZE WIRING WORK

REQUIRED.

PROVIDE HEAVY DUTY TYPE DISCONNECTS RATED FOR THE INSTALLED ENVIRONMENT.

PROVIDE MINIMUM NEMA 3R RATED DISCONNECTS FOR EXTERIOR INSTALLATIONS OR AS

NOTED.

VERIFY LOCATIONS OF ALL EQUIPMENT. REFER TO MECHANICAL, PLUMBING, AND

ARCHITECTURAL DRAWINGS AND COORDINATE WITH THE ASSOCIATED SUB-CONTRACTOR.

ADJUST ELECTRICAL INSTALLATION AS REQUIRED.

BUILDING EQUIPMENT COORDINATION NOTES - ELECTRICAL

1.

2.

3.

4.

5.

6.

7.

1. THE DELIVERY METHOD FOR THIS PROJECT IS INDIVIDUAL SUB-CONTRACTS TO ONE GENERAL

CONTRACTOR. THIS CONTRACTOR IS RESPONSIBLE FOR MEETING WITH ALL SUB-

CONTRACTORS TO COORDINATE LOCATIONS AND INSTALLATION OF MECHANICAL AND

ELECTRICAL WORK WITH ALL OTHER TRADES. REWORK OF INSTALLED EQUIPMENT WILL BE AT

CONTRACTORS EXPENSE.

PROJECT DELIVERY NOTES - ELECTRICAL

ELECTRICAL ABBREVIATIONS

A DEVICE MOUNTED +8" ABOVE

COUNTER TOP (VERIFY LOCATION)

AFF ABOVE FINISHED FLOOR

ATS AUTOMATIC TRANSFER SWITCH

C CEILING

CB CIRCUIT BREAKER

CT CURRENT TRANSFORMER

E EXISTING ITEM TO REMAIN

EC ELECTRICAL CONTRACTOR

EM EMERGENCY LIGHT FIXTURE

ER NEW LOCATION OF EXISTING ITEM

F ROUGH IN FOR FUTURE DEVICE

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FSD FIRE SMOKE DAMPER

G GROUND FAULT CIRCUIT INTERRUPTER

GND GROUND

KVA KILO-VOLT-AMPERES

KW KILOWATTS

MC MECHANICAL CONTRACTOR

MCB MAIN CIRCUIT BREAKER

MDP MAIN DISTRIBUTION PANEL

MLO MAIN LUGS ONLY

N NEW DEVICE IN EXISTING LOCATION

NIC NOT IN CONTRACT

NM NONMETALLIC

NTS NOT TO SCALE

OC ON CENTER

OFCI OWNER FURNISHED

CONTRACTOR INSTALLED

OFOI OWNER FURNISHED,

OWNER INSTALLED

R EXISTING ITEM TO BE REMOVED

RR EXISTING ITEM TO BE REMOVED AND

RELOCATED

RN EXISTING ITEM TO BE REMOVED AND

REPLACED WITH NEW

SCCR SHORT CIRCUIT CURRENT RATING

T TAMPER PROOF DEVICE

TCC TEMPERATURE CONTROL CONTRACTOR

TV TELEVISION

TYP TYPICAL

UPS UNINTERRUPTIBLE POWER SUPPLY

V VOLTS

VA VOLT-AMPERES

WG WIREGUARD COVER

WP WEATHERPROOF DEVICE

WR WEATHER RESISTANT DEVICE

+24" INDICATES MOUNTING HEIGHT CENTER

LINE OF DEVICE TO FINISHED FLOOR

**NOTE: ALL SYMBOLS MAY NOT APPLY TO THIS PROJECT**

DATA BOX ROUGH-IN ONLY

TELECOMMUNICATIONS INFRASTRUCTURE SYMBOLS

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

B U

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-000

E L E

C T

R

IC

A L N

O T

T

W

W

ST

S T

SAN

UNDERGROUND POWER

UNDERGROUND POWER

UNDERGROUND POWER

WATERLINE NOT LOCATED

TELEPED

PHONELINE ON NORTH SIDE ROAD

T

PANEL A

S H

O P

A N

D O

F F

IC

IL

D

IN

G

REFER TO ONE-LINE DIAGRAM

ON SHEET E-300

FUTURE TELEPHONE LINE. ROUTE (1) EMPTY 2"

PVC CONDUIT WITH PULL STRING TO PEDESTAL

FOR TELEPHONE UTILITY CABLING. COORDINATE

FINAL ROUTING AND BUILDING ENRANCE PRIOR

TO ROUGH-IN.

TELEPHONE DEMARC

A- 19

FUEL PUMP LOCATION. SEE CIVIL PLANS.

COORDINATE FINAL LOCATION WITH OWNER

AND CIVIL PRIOR TO ROUGH-IN.

EXISTING UTILITY PRIMARY

UNDERGROUND LINE

UTILITY METER. REFER TO ONE-

LINE DIAGRAM ON SHEET E-300.

COORDINATE PRIMARY

CONNECTION, ROUTING, AND HAND

HOLE WITH UTILITY COMPANY.

UTILITY PAD MOUNT TRANSFORMER.

REFER TO ONE-LINE DIAGRAM E-300.

NEW UNDERGROUND STORM.

SEE CIVIL PLANS.

EXISTING UNDERGROUND WATER.

SEE CIVIL PLANS.

NEW UNDERGROUND SEWER.

SEE CIVIL PLANS.

EXISTING TELEPHONE LINE. SEE

CIVIL PLANS.

1. UTILITIES SHOWN ON ELECTRICAL SITE PLAN ARE SCHEMATIC ONLY. VERIFY ALL SITE

CONDITIONS AND DIMENSIONS ON SITE PRIOR TO SUBMITTING BID AND ORDERING

EQUIPMENT.

2. REPAIR ALL AFFECTED SURFACES AND RESTORE TO EXISTING CONDITIONS AT COMPLETION

OF PROJECT.

3. WARNING - CALL BEFORE YOU DIG: LAW REQUIRES ANYONE DOING EXCAVATION, FENCING,

PLANTING OR DRILLING TO CALL 48 HOURS IN ADVANCE. HAND DIG WITHIN 18 INCHES OF ANY

LOCATE MARK OR FLAG. ONE-CALL 811.

SITE NOTES - ELECTRICAL

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-001

E L E

C T

R

IC

A L S

IT

E

P L

A N

1" = 30'-0"

ELECTRICAL SITE PLAN

KEYNOTES

1 MOUNT ABOVE STORAGE LOFT. COORDINATE FINAL

LOCATION WITH OWNER AND ARCHITECTURAL DRAWINGS.

ACRYLICSHOWERS FREEWILL K-12100-C

W

J

G GG

W W

G

G

G

G

G

G G G

G

W

TV

J

J J

G

G

POWER GENERAL NOTES

A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND

ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A

SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE UNTIL

PROPER AND TIMELY COORDINATION WITH ALL TRADES ASSOCIATED

WITH THE INSTALLATION HAS TRANSPIRED. ITEMS TO BE

COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO: BUILDING

STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT FIXTURES,

CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,

MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS

FOR THIS PROJECT.

B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS

WITH M.C. AND FINAL MECHANICAL SHOP DRAWINGS.

C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS

THROUGH THE BUILDING. COORDINATE FIRE RATED WALL

PENETRATIONS AND PROVIDE CONDUIT SLEEVES AND FIRE

STOPPING TO MAINTAIN RATING.

+60"

G,A

+60"

G,A

EF

EF

REF.

WH

A

F

UH

UH

UH

MOD

CU

MICROWAVE

DRYER

WASHER

AIR COMP.

+120"

EMERGENCY FUEL PUMP PUSHBUTTON SHUT-OFF STATION IN NEMA 3R

ENCLOSURE. PROVIDE SIGN WITH ENGRAVED WHITE LETTERING

READING "EMERGENCY FUEL PUMP POWER SHUT-OFF". (EATON

10250T5B62-S108 OR EQUAL)

PANEL A

A- 4

G,A

+60"

1 1 1

A-9 A-9A-9

A-7

A-27

A-7

A-9

A-9

A-7 A-7 A-7

A-27

A-21 A-21

A-21

A-5

A-5 A-5 A-5

A-5

A-5

A-27

A-27

A-21

A-21

A-21

A-32,34

A-36,38

A-8

A-17

A-17 A-17

A-17

A-10

A-27

A-19

A-20

A-12

A-24,26

A-22

A-28,30

A-25

A-18

A-12

A-11 A-13 A-15

+48" AFF

WELDER RCPTs 50A-2P

NEMA 14-50R

+48"+48"+48"+48"

+48"

+48"

+48"

+48" +48"

+48"

+48"

+48"

ON/OFF TOGGLE

SWITCH FOR FUEL

TANK POWER

UTILITY METER.

REFER TO ONE-LINE

DIAGRAM ON SHEET

E-300.

+48"

+48"

MOD

A-12

A-33,35

E-300

Typ

A-23

A-29

A-31

DISPOSAL

GAS DETCTION

CONTROL PANEL

A- 2

+48" A-7

+48"

A-9 +60"

A- 37

CP

A-14

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-200

E L E

C T

R

IC

A L P

L A

N S

KEYNOTES

1 OVERHEAD DOOR MOTORIZED CONTROLLER. INSTALL

DEVICES PER MANUFACTURER INCLUDING ALL LOW

VOLTAGE SENSORS AND SWITCHES. PROVIDE EQUIPMENT

DISCONNECT WHERE NECESSARY.

2 CONNECT TO LOCAL LIGHTING SWITCH.

3 FUTURE TELEPHONE UTILITY DEMARC LOCATION. STUB UP

EMPTY 2" CONDUIT TO THIS LOCATION. REFER TO E-001

ELECTRICAL SITE PLAN.

4 VERIFY THE FINAL LOCATION WITH OWNER AND ARCHITECT

PRIOR TO ROUGH-IN.

5 DATA ROUGH-IN LOCATION ONLY. INSTALL DUAL GANG

JUNCTION BOX WITH SINGLE GANG MUD RING, STAINLESS

STEEL FACE PLATE AND ROUTE (1) 1" EMPTY CONDUIT TO

ABOVE ACCESSIBLE CEILING WITH BUSHING AND PULL

STRING.

1/4" = 1'-0"

ELECTRICAL FLOOR PLAN - POWER

3 3

1O S

T C

OS

OS

E1-W A-1

E1 A-3

E1-W A-1

W1 A-6

E1-W A-1

F2 f A-3

F2 f A-3

F4 e A-3

F4 d A-3

F1 z A-1

F1 y A-1

F1 y A-1

F1 a A-1

EM

+9'-0"

X1-W A-1

F3 h A-3

F3 h A-3

F3 h A-3

F3 h A-3

F3 b A-3

F3 b A-3

F3 b A-3

F3 b A-3

E1 A-3

E1 A-3

F2 g A-3

F3 c A-3

F3 c A-3

X1 A-3

X1 A-3

PANEL A

a a b b c d e f h c g h

F3 h A-3

F3 h A-3

F3 b A-3

F3 b A-3 b h

E1 A-3

W1 A-6

+9'-0"

EM

F1 x A-1

F1 x A-1

F1 x A-1

F1 x A-1

F1 z A-1

F1 z A-1 yz y z

F1 z A-1

F1 z A-1

F1 y A-1

F1 y A-1

F1 a A-1

F1 a A-1 x

2 2 2 2

3 3 3 3

F1 x A-1

A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND

ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A

SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE

UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES

ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS

TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:

BUILDING STRUCTURE, SHEET METAL, ALL PIPING SYSTEMS,

LIGHT FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL

GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND

SPECIFICATIONS FOR THIS PROJECT.

LIGHTING GENERAL NOTES

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-201

L

IG

H T

IN

G

P L

A N

S

1/4" = 1'-0"

ELECTRICAL REFLECTED CEILING PLAN - LIGHTING

KEYNOTES

1 CONNECT TO ASTRONOMICAL TIMECLOCK IN MECH ROOM.

2 MOUNT ON UNDERSIDE OF STORAGE LOFTT. COORDINATE

FINAL LOCATION WITH OWNER AND ARCHITECTURAL

DRAWINGS.

3 MOUNT ABOVE STORAGE LOFT. COORDINATE FINAL

LOCATION WITH OWNER AND ARCHITECTURAL DRAWINGS.

A. DIAGRAM INDICATES OVERALL LAYOUT OF ELECTRICAL

DISTRIBUTION SYSTEM. REFER TO FLOOR PLANS FOR

EQUIPMENT LOCATIONS.

B. USE COPPER CONDUCTORS UNLESS OTHERWISE INDICATED.

C. MATCH NEUTRAL CONDUCTOR SIZE TO THE PHASE

CONDUCTORS UNLESS OTHERWISE NOTED.

D. ALL WIRING SHALL BE IN RACEWAY AS NOTED. REFER TO

SPECIFICATIONS FOR CONDUIT APPLICATION REQUIREMENTS.

E. INSTALL UTILITY TRANSFORMER PAD, METERING EQUIPMENT,

AND SERVICE ENTRANCE FEEDERS IN ACCORDANCE WITH

UTILITY COMPANY REQUIREMENTS.

RISER DIAGRAM GENERAL NOTES

1. SECONDARY SERVICE FEEDERS TO METER BY UTILITY

COMPANY. COORDINATE CONDUIT REQUIREMENTS.

RISER DIAGRAM KEYED NOTES

UTIL XFMR

240D/120YV

B

PRIMARY CONDUCTORS

BY UTILITY COMPANY

PANEL A

MCB

120/240V

225A

E-300

A

PER NEC

BY UTILITY CO.

UTILITY METER SOCKET.

INTEGRAL CTS.

METER

SERVICE

ENTRANCE RATED.

BUILDING

MAIN

DISCONNECT

GND

NEUT

GND

MAIN TELECOMMUNICATIONS

GROUND BAR

INCOMING FEEDER.

REFER TO BUILDING

FEEDER INFORMATION

ON ONE-LINE DIAGRAM.

A. ALL AVAILABLE GROUNDING ELECTRODES WHICH ARE PRESENT AT THE BUILDING OR

STRUCTURE SHALL BE BONDED TOGETHER TO FORM THE GROUNDING ELECTRODE

SYSTEM (GES). ADDITIONAL CODE-REQUIRED GROUNDING CONNECTIONS NOT

SHOWN SHALL BE PROVIDED. CONNECTIONS WHICH ARE ENCASED, UNDERGROUND,

OR INACCESSIBLE SHALL BE EXOTHERMIC WELD.

B. ALL BONDING JUMPERS CONNECTING GROUNDING ELECTRODES TO THE GES SHALL

BE SIZED EQUAL TO THE GROUNDING ELECTRODE CONDUCTOR (GEC) IN

ACCORDANCE WITH NEC 250.53(C). OTHER BONDING JUMPERS SHALL BE SIZED AS

OTHERWISE DESCRIBED IN NEC ARTICLE 250. CONDUCTORS SHALL BE BARE

COPPER UNLESS OTHERWISE NOTED.

C. REFER TO SPECIFICATIONS FOR ADDITIONAL PRODUCT AND MATERIAL

REQUIREMENTS. GROUNDING AND BONDING METHODS AND MATERIALS SHALL

COMPLY WITH NEC ARTICLE 250.

D. REFER TO TECHNOLOGY DETAILS FOR ADDITIONAL REQUIREMENTS RELATED TO

TELECOM GROUNDING.

NOTES

#1/0 CU

INSULATED

EXOTHERMIC WELD TO

BUILDING STRUCTURAL

STEEL

'-0

(T Y

P A

L L S

ID

E

S

#2 BARE COPPER

CONDUCTOR 36"

BELOW GRADE. 20'

IN LENGTH MIN.

(TYP.)

5/8" X 10'-0" GROUND

RODS EQUALLY

SPACED,

EXOTHERMIC WELD

TO #2 BARE COPPER

GROUND ROD

CONDUCTOR (TYP.)

LAY CABLE IN CIRCLE

PATTERN BETWEEN

GROUND RODS (TYP.)

BOND ACROSS SEPARATION IN

BUILDING STRUCTURES.

INCLUDE FIRE WALLS,

EXPANSION JOINTS, ETC.

COLD WATER

PIPE ENTRY *

GROUNDING ELECTRODE

#4 AWG BARE COPPER

OR 1/2" STEEL

REINFORCING ROD

CONCRETE

FOUNDATION

EXOTHERMIC WELD

TO CONNECT STEEL

ROD TO COPPER

CONDUCTOR

20'-0" MIN

#4 CU

BUILDING

GAS PIPING

#6 CU

NONMETALLIC

PROTECTIVE SLEEVE

#2 CU

#2 CU BARE WIRE

WATER PIPE

GROUND CLAMP

WATER PIPE

GROUND CLAMPWATER METER

GAS PIPE

GROUND CLAMP

SIZE GROUNDING ELECTRODE CONDUCTOR AND BONDING PER NEC 250.66 AND TABLE BELOW.

ALL CONDUCTORS TO BE COPPER.

TABLE BASED ON NEC 2017

TABLE 250.66 GROUDING ELECTRODE CONDUCTOR FOR ALTERNATING-CURRENT SYSTEMS

SIZE OF LARGEST UNGROUDNING CONDUCTOR OR

EQUIVALENT AREA FOR PARALLEL CONDUCTORS (AWG/KCMIL)

SIZE OF GROUNDING ELECTRODE

CONDUCTOR (AWG/KCMIL)

COPPER ALUMINUM OR COPPER-CLAD AL COPPER

#2 OR SMALLER #1/0 OR SMALLER #8

#1 OR #1/0 #2/0 OR #3/0 #6

#2/0 OR #3/0 #4/0 OR 250 #4

OVER #3/0 THROUGH 350 OVER 250 THROUGH 500 #2

OVER 350 THROUGH 600 OVER 500 THROUGH 900 #1/0

OVER 600 THROUGH 1100 OVER 900 THROUGH 1750 #2/0

OVER 1100 OVER 1750 #3/0

REFER TO TELECOMMUNICATIONS

DETAILS FOR GROUNDING DETAILS

BUILDING

STRUCTURAL STEEL

MULTI-GROUND

ROD ASSEMBLY

CONCRETE ENCASED

ELECTRODE

MAIN BONDING

JUMPER

** SIZE BONDING JUMPER PER NEC 250.102. USE TABLE ABOVE FOR ALL CONDUCTORS BETWEEN #2 AND 1100. ALL INCOMING CONDUCTORS OVER 1100 CU OR 1750 AL SHALL BE SIZED PER THE TABLE

250.102(C). SERVICE EQUIPMENT SHALL BE SUPPLIED WITH BONDING JUMPER FROM THE

MANUFACTURER.

REMOVABLE LINK

RED (LOAD)

BLK

RED (LINE)

WHT

RED (LOAD)

RED (LINE)

LINE

NEUTRAL

BRANCH CIRCUIT

WHITE / NEUTRAL

(TYP.)

L O A D

24VDC SENSOR

CEILING OR WALL SURFACE MOUNTED

RED +24 VDC

BLK COMMON

BLU OUTPUT

RED +24 VDC

BLK COMMON

BLU OUTPUT

CONTROL CONDUCTORS TO

ADDITIONAL SENSORS WITHOUT

POWER PACKS WHERE USED

BLK

WHT

LINE

NEUTRAL

BRANCH CIRCUIT

(TYP.)

L O A D

STANDARD POWER PACK

SATELLITE POWER PACK

WHERE USED

L O A D

ADJUSTABLE STOP.

COORDINATE WITH OWNER

DURING CONSTRUCTION TO

SET MAXIMUM PULL LENGTH.

JUNCTION BOX AND

RECEPTACLE FOR CORD REEL

CONNECTION. MOUNTED BELOW

ACCESSIBLE CEILING WHERE

PRESENT.

ROOF JOIST

UNISTRUT CHANNEL

ATTACHED TO BOTTOM OF

SUPPORT

BOLT CORD REEL TO STRUT

CHANNEL PER

MANUFACTURER

INSTALLATION INSTRUCTION.

CORD REEL SHALL BE HUBBELL

KELLEMS "HBL45123R220"

INDUSTRIAL POWER CORD REEL OR

APPROVED EQUAL. (2) DUPLEX

RECEPTACLES, 20A RATED, 45' CORD,

GREY FINISH.

ACOUSTICAL CEILING TILE

(WHERE PRESENT)

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-300

O N

E -L

IN

E

D

E T

A

IL

S

NOTE: ALL CONDUCTORS THHN COPPER UNLESS OTHERWISE NOTED.

FEEDER SCHEDULE

TAG PHASE GROUND CONDUIT

A 1- SET (3) - - (1) 2"

B 1- SET (4) #3 - (1) 1 1/4"

NOT TO SCALE

ONE-LINE DIAGRAM

NOT TO SCALE

GROUNIND ELECTRODE DETAIL

NOT TO SCALE

OCCUPANCY SENSOR LIGHTING CONTROL DETAIL

NOT TO SCALE

RETRACTABLE CORD REEL

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

IL

D

IN

G

E

TH

S

T.

D E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-400

E L E

C T

R

IC

A L S

C H

E D

U L

E S

HOA HAND-OFF-AUTO

GF GROUND FAULT CIRCUIT INTERRUPTION VFD VARIABLE FREQUENCY DRIVE

FDS FUSED DISCONNECT SWITCH, HEAVY DUTY TS TOGGLE SWITCH WITH PLUG FUSE

FAR FIRE ALARM SHUTDOWN RELAY TOR TIME DELAY OFF RELAY

ECB ENCLOSED CIRCUIT BREAKER ST SHUNT TRIP

CP CORD AND PLUG PROVIDED WITH UNIT SS START/STOP PUSHBUTTON

CSD COMBINATION STARTER/DISCONNECT SSP START/STOP PUSHBUTTON WITH PILOT

CB CIRCUIT BREAKER IN PANEL SD SUPPLY AIR DUCT DETECTOR

BO PROVIDED BY OTHERS RSR RUN STATUS RELAY , NORMALLY OPEN

4X NEMA 4X ENCLOSURE RD RETURN AIR DUCT DETECTOR

4 NEMA 4 ENCLOSURE NFD NON-FUSED DISCONNECT SWITCH, HEAVY DUTY

3R NEMA 3R ENCLOSURE MMS MANUAL MOTOR STARTER WITH FUSES

1 NEMA 1 ENCLOSURE INT INTEGRAL WITH EQUIPMENT FROM FACTORY

ABBREVIATIONS:

1. INCLUDE AUXILLIARY CONTACTS AND LOW-VOLTAGE WIRING TO AUXILLIARY EQUIPMENT THAT RUNS IN TANDEM WITH EQUIPMENT, (I.E. 120V DAMPERS WITH 480V MOTORS).

GENERAL NOTES:

EQUIPMENT CONNECTION SCHEDULE

TAG

ELECTRICAL CHARACTERISTICS DISCONNECT

REMARKS

VOLTAGE PHASE

MOTOR HP

KW MCA TYPE

SIZE

(AMPS)

NEMA

RATING

FUSE SIZE

(AMPS)

CP-1 120 V 1 0.08 CB

CU-1 240 V 1 12 NFD 30 3R PROVIDE AND INSTALL DISCONNECT

EF-1 120 V 1 FHP INT CONNECT TO LOCAL OCCUPANCY SENSOR WITH LIGHTS IN SPACE.

EF-2 120 V

1/4

HOA 20 1 POWER MOTORIZED DAMPER TO OPEN/CLOSE WITH FAN. INSTALL PROVIDED

HOA.

F-1 120 V 1 FHP CB

MOD-1 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.

MOD-2 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.

UH-1 120 V 1 2.4

UH-2 120 V 1 2.4

UH-3 120 V 1 2.4

WH-1 240 V 1 4.5 CB

DESIGNED BY: DEB

ALL OTHER SPACES SENSORS PROGRAMMED FOR VACANCY MODE, MANUAL ON/AUTOMATIC OFF OPERATION 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM.DIMMING CONTROL OF FIXTURES WITHIN

DAYLIGHT ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.

CORRIDORS, VESTIBULES,

COMMON SPACES:

SENSORS PROGRAMMED FOR OCCUPANCY MODE, AUTOMATIC ON/OFF OPERATION, 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM. DIMMING CONTROL OF FIXTURES WITHIN DAYLIGHT

ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.

9. UNLESS INDICATED OTHERWISE, LIGHTING CONTROL SCHEMES/OPERATION SHALL BE AS FOLLOWS:

8. ETD'S AND ALL EMERGENCY LIGHTING CONTROLS COMPONENTS SHALL BE TESTED AND LISTED AS COMPATIBLE BY MANUFACTURER WITH NORMAL LIGHTING CONTROLS IN ALL AREAS.

7. WHERE APPROVED EQUAL MANUFACTURER PRODUCTS SENSOR COVERAGE OR LOAD RATINGS DIFFER FROM BASIS OF DESIGN, CONTRACTOR AND MANUFACTURER ARE RESPONSIBLE FOR PROVIDING ADDITIONAL

DEVICES AS NECCESARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.

6. PROVIDE FACTORY AUTHORIZED REPRESENTATIVE TO DEMONSTRATE TYPICAL INSTALLATION AND COMMISSIONING OF EQUIPMENT.

5. INSTALL LOW VOLTAGE POWER PACKS AND ROOM CONTROLLERS ABOVE NEARBY ACCESSIBLE CEILING TILES OR IN MECHANICAL/STORAGE SPACES ADJACENT TO CONTROLLED FIXTURES. DO NOT INSTALL

POWERPACKS EXPOSED IN COMMON SPACES OR IN INACCESSIBLE LOCATIONS.

4. WHERE WIRELESS LIGHTING CONTROLS ARE PROVIDED. POWERPACKS SHALL BE PROVIDED AND INSTALLED WITHIN MANUFACTURER RECOMENDED DISTANCES TO ENSURE CONTROLLER OPERATION.

3. PROVIDE LIGHTING CONTROLS WITH MANUFACTURER COMPLIANT POWER PACKS AND LOW VOLTAGE ROOM CONTROLLERS IN QUANTITY REQUIRED TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM.

MANUFACTURER OR MANUFACTURERS REP TO PROVIDE DEVICE QUANTITES, LAYOUTS AND TYPICAL WIRING DETAILS DURING SHOP SUBMITTAL PROCESS. PROVIDE DIMMING COMPATIBLE DEVICES WHERE DIMMING CONTROLS ARE SHOWN. COORDINATE DIMMING TYPE WITH LIGHTING FIXTURES SHOWN. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE DIMMING TYPE.

2 ALL DEVICES PROVIDED WITH MANUFACTURER LIMITED 5 YEAR WARRANTY.

1. ALL DEVICES SHALL BE U.L. OR SIMILARLY LISTED.

NOTES:

LIGHTING CONTROLS SCHEDULE

TYPE DESCRIPTION ELECTRICAL MOUNTING SENSOR TYPE COVERAGE APPROVED

MANUFACTURERS

OS 1 WALL SWITCH OCCUPANCY SENSOR. DEVICE FINISH MATCHING WIRING DEVICES SPEC.

RATED FOR MIN 1/6 HP MOTOR. INTEGRAL AUTOMATIC SELF-ADAPTIVE COVERAGE

THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER SETTINGS.

120V WALL SWITCH /

SINGLE GANG

PASSIVE INFRARED 1000 SQ FT / 180

DEG

HUBBELL, CRESTRON, ACUITY,

WATTSTOPPER, GREENGATE,

AS APPROVED BY ENGINEER.

OS 2 CEILING MOUNTED OCCUPANCY/VACANCY SENSOR. LIGHTING CONTROLS NETWORK

COMPATIBLE DEVICE. ROOM CONTROLLER COMPATIBLE, ENABLING MULTI-ZONE SWITCHING

CONTROL AND MULTI-SOURCE DIMMING. WHITE FINISH. AUTOMATIC SELF-ADAPTIVE

COVERAGE THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER

SETTINGS. INDOOR USE.

LOW VOLTAGE CEILING / 8'-12'

MH

PASSIVE INFRARED 1000 SQ FT / 360

DEG

HUBBELL, CRESTRON, ACUITY,

WATTSTOPPER, AS APPROVED

BY ENGINEER.

DESIGNED BY: DEB

7. CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND FILLING OUT ALL UTILITY REBATE FORMS FOR OWNER.

6. AIM AND TARGET ADJUSTABLE INTERIOR AND EXTERIOR LIGHT FIXTURES UNDER THE OBSERVATION AND IN COMPLIANCE WITH RECOMMENDATIONS OF THE ARCHITECT.

INCLUDE LABOR AND MATERIAL COSTS MADE NECESSARY BY THIS REQUIREMENT.

5. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE NECESSARY TO INSTALL AND SUPPORT THE LUMINAIRES.

4. VERIFY COMPATIBILITY OF LIGHT FIXTURES WITH CEILING MATERIAL, ADJACENT CONSTRUCTION, AND ADJACENT FINISHES PRIOR TO SHOP DRAWINGS SUBMITTAL

NOTIFY THE ARCHITECT OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION.

3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS, DETAILS, AND CONFIGURATIONS OF ALL LUMINAIRES. IF ARCHITECTURAL DRAWINGS DO NOT CLARIFY EXACT MOUNTING LOCATION OR DETAIL, ISSUE AN RFI FOR ARCHITECT TO SPECIFICALLY CLARIFY PRIOR TO FIXTURE ROUGH-IN.

2. INCLUDE A MINIMUM 1 YEAR WARRANTY FOR LIGHTING FIXTURES, WHERE NOT OTHERWISE SPECIFIED.

1. ALL FIXTURES SHALL BE U.L. OR SIMILARLY LISTED.

NOTES:

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER MODEL DESCRIPTION FINISH LUMENS CRI DRIVER TYPE SOURCE-CCT VOLTAGE LOAD-VA APPROVED EQUALS

E1 LITHONIA LIGHTING ELM2L-120/347-SDRT EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY

WHITE EM N/A N/A

LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

E1-W LITHONIA LIGHTING ELM2L-UVOLT-SDRT / ELAWG1

EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY, WIRE GUARD

WHITE EM N/A N/A

LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

F1 LITHONIA LIGHTING

CLX-L48-5000LM-HEF-FDL-WD-120-GZ10-LUGR-40K-80C

RI-PLR

CORD SET INSTALLATION, CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION, GLARE REFLECTOR ACCESSORY. DAMP LISTED. PROVIDE AN ALLOWANCE FOR PLUG-READY LUMINAIRE.

CONTRACTOR TO VERIFY OR PROVIDE SO CORD IF NOT INCLUDED WITH LUMINIARE. CONTRACTOR TO INSTALL IN

FIELD.

WHITE 5000 80 0-10V DIMMING TO 10%

LED-4000K 120 V 32 VA AS APPROVED BY ENGINEER

F2 LITHONIA LIGHTING L4-13LM-40K-120-G4-80CRI-ZXT // WPR-CSS-WET RECESSED 4" ROUND DOWNLIGHT, PARABOLIC REFLECTOR, WIDE DISTRIBUTION, DAMP LOCATION

SEMI-SPECULAR 1300 80 0-10V DIMMING TO 10%

LED - 4000K 120 V 20 VA

ALPHABET LIGHTING, COOPER HALO OR

AS APPROVED BY ENGINEER

F3 CREE ZR24C-40K-10V-FD RECESSED 2x2 , SWITCHABLE CCT AND LUMEN PACKAGE

WHITE 80 0-10V DIMMING TO 10%

LED-4000K 120 V 0 VA

WILLIAMS, COLUMBIA, OR AS APPROVED

BY ENGINEER

F4 LITHONIA LIGHTING CLX-L48-3000LM-HEF-FDL-WD-120-GZ10-40K-80CRI CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION WHITE 3000 80 0-10V DIMMING TO 10% LED-4000K 120 V 20 VA AS APPROVED BY ENGINEER

W1 HUBBELL LIGHTING TRP1-24L-15-3K8-4W-UNV-DBT-PC-EH BUILDING MOUNTED WALL PACK, TYPE 4 DISTRIBUTION, -30 DEGREE RATED EMERGENCY BATTERY PACK

BRONZE 1700 80 NON-DIMMING

LED-3000K 120 V 20 VA

LITHONIA LIGHTING, COOPER

MCGRAW-EDISON, OR AS APPROVED BY

ENGINEER

X1 LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD / ELAWG1 BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS

WHITE N/A N/A N/A

RED LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

X1-W LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD / ELAWG1 BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS, WIRE GUARD

WHITE N/A N/A N/A

RED LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

NOTES:

TOTAL EST. DEMAND: 162 A

TOTAL CONN.: 184 A

RECEPTACLE 21140 VA 73.65% 15570 VA TOTAL EST. DEMAND: 38846 VA

POWER 22400 VA 100.00% 22400 VA TOTAL CONN. LOAD: 44241 VA

LIGHTING 701 VA 125.00% 876 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED... PANEL TOTALS

"G" INDICATES GFCI TYPE BREAKER

LEGEND:

202 A 167 A

24261 VA 19980 VA

SPARE 1 -- 20 A 41 0 0 42 20 A -- 1 SPARE

SPARE 1 -- 20 A 39 0 0 40 20 A -- 1 SPARE

GAS DETECTION 1 20 A 37 920 2250 38

35 3250 2250 36

30 A 2 WH-1

WELDER 2 50 A

33 3250 2080 34

DISPOSAL 1 20 A 31 800 2080 32

30 A 2 CU-1

REFRIGERATOR 1 G 20 A 29 1200 1750 30

RCPT LAUNDRY, MECH 1 20 A 27 900 1750 28

50 A 2 DRYER

WASHER 1 G 20 A 25 1200 600 26

MICROWAVE 1 20 A 23 800 600 24

20 A 2 AIR COMPRESSOR

RCPT BREAK ROOM 1 20 A 21 1080 290 22 20 A 1 UH-3

FUEL PUMP/EMERGENCY SHUT OFF 1 20 A 19 1500 290 20 20 A 1 UH-2

RCPT EXTERIOR 1 20 A 17 720 290 18 20 A 1 UH-1

DOOR OPENER 1 20 A 15 920 0 16 20 A -- 1 SPARE

DOOR OPENER 1 20 A 13 920 4500 14 20 A 1 CP-1

DOOR OPENER 1 20 A 11 920 1100 12 20 A 1 EF-2

RCPT SHOP 1 20 A 9 1080 100 10 20 A 1 EF-1

RCPT SHOP 1 20 A 7 1080 1270 8 20 A 1 F-1

RCPT OFFICE 1 20 A 5 1080 40 6 20 A 1 EXTERIOR LIGHTING

OFFICE LIGHTING 1 20 A 3 110 360 4 20 A 1 CORD REELS

SHOP LIGHTING 1 20 A 1 551 360 2 20 A 1 CORD REELS

CIRCUIT DESCRIPTION P AMP

CKT

NO A B

CKT

NO AMP P CIRCUIT DESCRIPTION

INTEGRAL SURGE PROTECTION DEVICE

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 3 MAINS RATING: 225 A

SUPPLY FROM: PHASES: 1 MAINS TYPE: MCB

LOCATION: VOLTAGE: 120/240 SINGLE SCCR RATING: 25,000 A

BRANCH PANEL: A

MECH/ELEC

UTILITY METER

- INCREASE TO 54 SPACE IF REQUIRED FOR INTEGRAL SPD. PROVIDE SPARES

FOR REMAINING UNUSED SPACES.

23-05-26-01_Drawings_signed
23-05-26-01_A-001 Plot - Signed
23-05-26-01_A-002 Plot (1)
23-05-26-01_A-003 Plot (1)
23-05-26-01 Wapello Shop and Office Design Sheet C1
23-05-26-01 Wapello Shop and Office Design-C1
23-05-26-01 Wapello Shop and Office Design Sheet C2
23-05-26-01 Wapello Shop and Office Design-C2
23-05-26-01 Wapello Shop and Office Design Sheet C3
23-05-26-01 Wapello Shop and Office Design-C3
23-05-26-01 Wapello Shop and Office Design Sheet C4
23-05-26-01 Wapello Shop and Office Design-C4
23-05-26-01_A-010 Plot (1)
23-05-26-01_A-020 Plot (1)
23-05-26-01_A-100 Plot (1)
23-05-26-01_A-101 Plot (1)
23-05-26-01_A-110 Plot (1)
23-05-26-01_A-200 Plot (1)
23-05-26-01_A-201 Plot (1)
23-05-26-01_A-300 Plot (1)
23-05-26-01_A-301 Plot (1)
23-05-26-01_A-400 Plot (1)
23-05-26-01_A-401 Plot (1)
23-05-26-01_A-600 Plot (1)
2023-03-21 - IDNR Lake Wapello State Park - 100% CD - Mechanical
IDNR Lake Wapello - Shop_Mech_KCL-M000
IDNR Lake Wapello - Shop_Mech_KCL-M100
IDNR Lake Wapello - Shop_Mech_KCL-M200
IDNR Lake Wapello - Shop_Mech_KCL-M300
IDNR Lake Wapello - Shop_Mech_KCL-P100
IDNR Lake Wapello - Shop_Mech_KCL-P200
IDNR Lake Wapello - Shop_Mech_KCL-P300
2023-03-21 - IDNR Lake Wapello State Park - 100% CD - Electrical
E-000 - ELECTRICAL NOTES
E-001 - ELECTRICAL SITE PLAN
E-200 - ELECTRICAL PLANS
E-201 - LIGHTING PLANS
E-300 - ONE-LINE & DETAILS
E-400 - ELECTRICAL SCHEDULES