Wapello 23-05-26-01_Drawings_Final.pdf
PDF 14 MB Posted
- Attached to
- Office/Shop Buildings for George Wyth State Park and Upper Iowa Wildlife Management Area
- Solicitation number
- 25CRDLWBGANTO-0014
- Issued by
- Black Hawk County, Iowa
About this file
This file contains construction drawings from the Iowa Department of Natural Resources for an office and storage building project at Lake Wapello State Park in Davis County, Iowa (Project #23-05-26-01). The drawings detail architectural, mechanical, electrical, and plumbing specifications for a new combined office and storage facility. The plans include site preparation, foundation work, building construction, interior finishing, HVAC systems, electrical systems, lighting, plumbing fixtures, and sanitary systems. The building features both office space and a larger storage/shop area with overhead doors, ADA-compliant restroom facilities, mechanical/utility rooms, and basic break room amenities.
The drawings specify detailed requirements for materials and installation including concrete foundations, wood frame construction, metal roofing, electrical service rated at 120/240V with a 225A main circuit breaker, HVAC equipment including unit heaters and exhaust fans, plumbing fixtures, lighting systems with occupancy sensors and emergency backup, and site utilities including water, septic, and electrical service connections. The plans include specific details for ADA compliance, energy efficiency measures, and commercial-grade construction suitable for a state park maintenance facility. All work must comply with applicable state and local building codes as well as DNR facility standards.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ryan E Richey Digitally signed by Ryan E Richey DN: C=US, E=ryan.richey@dnr.iowa.gov, O=Iowa Department of Natural Resources, OU=Engineering Section - L&W Bureau, CN=Ryan E Richey Date: 2023.03.20 08:46:25-05'00'
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T O
F N
A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N G
S
ER
V
IC
ES
W A
LL
A
C E
BU
IL
D
IN
G
E.
TH
S T.
, D
ES
M O
IN
ES
, I A
-0
P:
.7
.8
F:
.7
.8
SURVEY CONTROL POINTS
C1
SURVEY CONTROL NOTES
SU
RV
EY
/D
IM
EN
SI
O
N P
LA
N
GENERAL NOTES
TREES
X XX 8" FILTER SOCK
ELEVATION
SPOT ELEVATION882.67 884.50
ELECTRICAL LINE
LEGEND
EXISTING/PROPOSED
E
WATER MAINW 2"
SANITARY SEWERS 6"
STORM SEWERST8"
SURVEY CONTROL POINT #14
N: 300972.318 E: 1895387.673
ELEV: 833.395
PK NAIL IN CONC
SURVEY CONTROL POINT #12
N: 300957.300 E: 1895040.970
ELEV: 856.614
PK NAIL IN CONC
SURVEY CONTROL POINT #13
N: 300962.474 E: 1894964.671
ELEV: 855.222
PK NAIL IN CONC
SURVEY CONTROL POINT #11
N: 300932.379 E: 1895093.089
ELEV: 855.206
PK NAIL IN CONC
DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T O
F N
A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N G
S
ER
V
IC
ES
W A
LL
A
C E
BU
IL
D
IN
G
E.
TH
S T.
, D
ES
M O
IN
ES
, I A
-0
P:
.7
.8
F:
.7
.8
C2
G
RA
D
IN
G /U
TIL
ITY
P
LA
N
GRADING NOTES
UTILITY NOTES
TREES
X XX 8" FILTER SOCK
ELEVATION
SPOT ELEVATION882.67 884.50
ELECTRICAL LINE
LEGEND
EXISTING/PROPOSED
E
WATER MAINW 2"
SANITARY SEWERS 6"
STORM SEWERST8"
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T O
F N
A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N G
S
ER
V
IC
ES
W A
LL
A
C E
BU
IL
D
IN
G
E.
TH
S T.
, D
ES
M O
IN
ES
, I A
-0
P:
.7
.8
F:
.7
.8
C3
D
ET
A
IL
S
4" PAINTED
WHITE STRIPE
(TYP.)
ACCESS AISLE AND
PARKING STALL TO
HAVE NO MORE THAN
2% SLOPE IN ANY
DIRECTION
2'
45°
11' 5'
PAVEMENT
MARKINGS FOR
PARKING STALLS
DETAIL
NOT TO SCALE
5'5'5'
HANDICAP SIGN
5'
5'
6' WHEEL STOP (TYP.)
MUTCD R7-8
SOLID GREEN LEGEND AND BORDER
REFLECTIVE WHITE BACKGROUND
WHITE ACCESSIBILITY SYMBOL ON
BLUE BACKGROUND
"U"-CHANNEL
POST (2 LBS./FT.)
RESERVED
PARKING
7'
GROUND
SURFACE
3.5-FOOT DEPTH
1'-6"
NOTES
1. 12"x18" ACCESSIBILITY SIGN (R7-8) SHALL BE
MOUNTED 7' FROM FINISH GRADE TO BOTTOM
EDGE OF SIGN FACE.
2. SIGNAGE FOR TO BE LOCATED ON END OF
PARKING STALL, 2' BACK FROM EDGE OF
PAVEMENT, CENTERED ON STALL. "U" CHANNEL
CAN BE DRIVEN INTO GROUND AT SAID
LOCATION TO A DEPTH OF 3.5 FEET.
3. ALL SIGNAGE SHALL BE ENGINEER GRADE
.080 ALUMINUM REFLECTIVE SIGN MEETING THE
REQUIREMENTS OF THE MUTCD AND ADAAG.
4. SURFACE MOUNTING BASE TO BE 15-INCH
DIAMETER ALUMINUM BASE (OR EQUIVALENT)
THAT IS COMPATIBLE WITH 2 LBS./FT. "U"
CHANNEL.
HANDICAP SIGN DETAIL
NOT TO SCALE
5.5'5'5'
5'5.5'
10'10'10'
6-INCH PCC CONCRETE
ADA PARKING SPACE
6-INCH GRAVEL PARKING AREA
5'
TREES
X XX 8" FILTER SOCK
ELEVATION
SPOT ELEVATION882.67 884.50
ELECTRICAL LINE
LEGEND
EXISTING/PROPOSED
E
WATER MAINW 2"
SANITARY SEWERS 6"
STORM SEWERST8"
DATE
BY REVISION
DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
C4
SA
N
ITA
RY
/S
EP
TIC
P
LA
N
TREES
X XX 8" FILTER SOCK
ELEVATION
SPOT ELEVATION882.67 884.50
ELECTRICAL LINE
LEGEND
EXISTING/PROPOSED
E
WATER MAINW 2"
SANITARY SEWERS 6"
STORM SEWERST8"
SSI
M-000
M E
C H
A N
I C
A L
G
E N
E R
N
O T
S
D
Y M
B O
L S i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
CU
F
EF
LV
MOD
EF
UH
UH
UH
M-100
F L
O O
R
P
L A
N
M
E C
H A
N I C
A L
NORTH
1/4" = 1'-0"
FLOOR PLAN - MECHANICAL
i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
M-200
M E
C H
A N
I C
D
T
A I L
S i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
M-300
M E
C H
A N
I C
C H
E D
U L
E S
BNC
1/13/23
ADDENDUM 1
i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
WH
CP
P-100
F L
O O
R
P
L A
P
L U
M B
I N
G
NORTH
1/4" = 1'-0"
UNDERFLOOR PLAN - PLUMBING
NORTH
1/4" = 1'-0"
FLOOR PLAN - PLUMBING
i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
P-200
L
U M
B I N
G
D
E T
A I L
S i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
P-300
L
U M
B I N
G
S
C H
E D
U L
E S i n f o k c l e n g i n e e r i n g c o m t h
S t r e e t
W e s t
D e s
M o i n e s
I o w a
PROJECT NUMBER:
DATE:
NO. DATE
BY REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N
SU
LT
A
N T:
23-05-26-01
03.21.2023
N
EW
O
FF
IC
E
S
TO
RA
G E
BU
IL
D
IN
G F
O R:
LA
KE
W A
PE
LL
O S
TA
TE
P A
RK
C
A M
PG
RO
UN
D
R O
A D
D
RA
KE
SV
IL
LE
, I A
IO
W
A D
EP
A
RT
M
EN
T
O F
N A
TU
RA
L
RE
SO
UR
C
ES
EN
G
IN
EE
RI
N
G S
ER
V
IC
ES
W
A
LL
A C
E
BU
IL
D
IN
G
E.
TH
S
T.
, D
ES
M
O
IN
ES
, I
A
-0
P:
.7
.8
F:
.7
.8
GENERAL SYMBOLS
JUNCTION BOX, CEILING OR FLOOR MOUNTED.
JUNCTION BOX, WALL MOUNTED, ELEVATION AS NOTED.
J
J
EQUIPMENT IDENTIFICATION TAG. REFER TO EQUIPMENT CONNECTION SCHEDULE
DETAIL DRAWING REFERENCE TAG, SIM-SIMILAR, TYP-TYPICAL, OPP-OPPOSITE
A101
SIM
KEYNOTE#
XXX
X
SHEET REFERENCE
LIGHTING SYMBOLS
ROUND LIGHT FIXTURE - RECESSED
SUSPENDED STRIP LIGHT FIXTURE
EMERGENCY LIGHT FIXTURE, WALL MOUNT, +96" OR AS NOTED
EXIT SIGN, WALL MOUNT +96", SHADED AREAS INDICATE NUMBER OF
FACES, ARROWS INDICATE SIGN ARROWS
EXTERIOR LIGHT FIXTURE, WALL MOUNT +10', OR AS NOTED
SINGLE POLE SWITCH, WALL MOUNT +48", OR AS NOTED,
LETTER INDICATES SWITCH LEG
OCCUPANCY SENSOR, WALL MOUNT +48" OR AS NOTED, NUMBER INDICATES TYPE,
LETTER INDICATES SWITCH LEG, REFER TO LIGHTING CONTROLS SCHEDULE
OS
a c
2X2 LIGHT FIXTURE - RECESSED
F1(6')
+10'-6" c
EM
UPPERCASE LETTERING
INDICATES FIXTURE TYPE.
REFER TO LUMINAIRE SCHEDULE
+## INDICATES FIXTURE MOUNTING HEIGHT
FROM BOTTOM OF FIXTURE TO FINISHED
FLOOR. COORDINATE ALL FIXTURE
ELEVATIONS WITH ARCHITECTURAL RCP
PRIOR TO ROUGH-IN AND SHOP SUBMITTALS.
LOWERCASE LETTERING INDICATES SWITCH LEG.
SHADING AND/OR "EM#" INDICATES
EMERGENCY OPERATION FIXTURE. NUMBER
INDICATES EMERGENCY CIRCUIT NUMBER.
LIGHTING PLANS NOTATION KEY
POWER SYMBOLS
DUPLEX RECEPTACLE, WALL MOUNT +18", OR AS NOTED
DUPLEX GFCI RECEPTACLE, WALL MOUNT +18", OR AS NOTED
G
DUPLEX GFCI WEATHER RESISTANT RECEPTACLE WITH WEATHER-PROOF
IN-USE COVER, WALL MOUNT +24", OR AS NOTED
EQUIPMENT CONNECTION, REFER TO ELECTRICAL EQUIPMENT CONNECTION
SCHEDULE FOR CONNECTION TYPE
W
MOTORIZED DOOR OPERATOR CONTROL STATION, WALL MOUNT, +48", OR AS NOTED
UTILITY METERM
PANELBOARD - SURFACE MOUNTED
J CORD REEL, CEILING MOUNTED - REFER TO DETAIL
DISCONNECT SWITCH
SPECIAL EQUIPMENT CONNECTION
DUPLEX GFCI RECEPTACLE, WALL MOUNT, ABOVE COUNTER, OR AS NOTED
G,A
TV RECEPTACLE, WALL MOUNT +60", OR AS NOTED
TV
+60"
1. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND ELECTRICAL WORK WITH ALL
OTHER TRADES. BEGIN INSTALLATION AND ROUGH-IN ONLY AFTER PROPER AND TIMELY
COORDINATION WITH ALL TRADES ASSOCIATED WITH THE INSTALLATION IS COMPLETE.
COORDINATE WITH BUILDING STRUCTURE, ARCHICTURE, MECHANICAL SHEET METAL, ALL
PIPING SYSTEMS, LIGHT FIXTURES, CONDUITS, CABLE TRAYS, EQUIPMENT
ACCESS/CLEARANCE, ETC. REFER TO ALL GENERAL, MECHANICAL, AND ELECTRICAL
DRAWINGS AND SPECIFICATIONS FOR THIS PROJECT. CONTRACTOR IS RESPONSIBLE FOR
REWORK OF INSTALLED EQUIPMENT RESULTING FROM INSUFFICIENT COORDINATION.
2. ELECTRICAL DRAWINGS ARE ONLY A PORTION OF THE COMPLETE SET OF PLANS AND
CONTRACT DOCUMENTS. THE ELECTRICAL SCOPE OF WORK IS DEFINED BY THE COMPLETE
SET OF CONTRACT DOCUMENTS. THIS INCLUDES BUT IS NOT LIMITED TO REFERENCING;
ARCHITECTURAL PLANS FOR DIMENSIONS AND DETAILS; EQUIPMENT PLANS FOR ROUGH-IN
REQUIREMENTS, MECHANICAL PLANS FOR EQUIPMENT SIZES AND LOCATIONS.
GENERAL NOTES - ELECTRICAL
GENERAL NOTE:
UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES HAVE BEEN SHOWN BASED UPON
INFORMATION OBTAINED FROM FIELD LOCATIONS BY UTILITY COMPANIES, AVAILABLE SURVEYS
AND RECORDS. THEIR LOCATIONS MUST BE CONSIDERED APPROXIMATE ONLY. IT IS ALSO
POSSIBLE THAT THERE MAY BE OTHER UNDERGROUND FACILITIES, STRUCTURES, AND UTILITIES IN
EXISTENCE THAT ARE NOT SHOWN. IT IS THE RESPONSIBILITY OF EACH INDIVIDUAL PARTY
REFERENCING THIS PLAN TO DETERMINE THE EXACT LOCATION AND TYPE OF UNDERGROUND
FACILITIES ON THE SITE. HAND EXCAVATE AT CRITICAL POINTS AS NECESSARY TO VERIFY
LOCATIONS, SIZES, ELEVATIONS, FLOW LINES, ETC. IF A PROBLEM OR INTERFERENCE EXISTS, NOTIFY ARCHITECT/ENGINEER BEFORE PROCEEDING.
IOWA
ONE CALL
1-800-292-8989
CALL - BEFORE - YOU - DIG
1. PROVIDE ELECTRICAL INSTALLATION IN ACCORDANCE WITH ALL LOCAL, STATE, AND
NATIONAL CODES.
2. THE CURRENT ADOPTED EDITION OF THE ELECTRICAL CODE IS THE STANDARD FOR THE
ELECTRICAL INSTALLATION. VERIFY WITH LOCAL OFFICIALS WHEN PERMITS ARE OBTAINED.
NOTIFY DESIGN TEAM OF ANY DESCREPANCIES BETWEEN THE PROJECT MANUAL OR
DRAWINGS AND THE GOVERNING CODE.
3. INSTALLATION SHALL FOLLOW REQUIREMENTS OF THE ADAAG –AMERICANS WITH
DISABILITIES ACT.
4. REFER TO PROJECT MANUAL AND PROJECT CODE REVIEW SHEET FOR LIST OF APPLICABLE
CODES.
CODE NOTES - ELECTRICAL
1. BECOME FAMILIAR WITH EXISTING CONDITIONS PRIOR TO BID.
2. INCREASE CONDUCTOR SIZES ON 20A 120V-1 PHASE CIRCUITS EXCEEDING 100 FEET TO
CENTER OF LOAD TO ACCOUNT FOR VOLTAGE DROP.
3. RACEWAYS AND BOXES ARE SHOWN DIAGRAMMATICALLY ONLY AND INDICATE GENERAL
AND APPROXIMATE LOCATIONS. LAYOUTS DO NOT ALWAYS SHOW THE TOTAL NUMBER
OF RACEWAYS OR BOXES FOR THE CIRCUITS REQUIRED, NOR ARE THE LOCATIONS OF
INDICATED RUNS INTENDED TO SHOW THE ACTUAL ROUTING OF THE RACEWAYS.
4. LIGHT FIXTURES, SWITCHES, DEVICES, ETC. ARE SHOWN IN PREFERRED LOCATION.
MODIFY CONDUIT, HANGERS, CIRCUITING, ETC. TO PROVIDE A COMPLETE AND
OPERATIONAL SYSTEM.
5. PROVIDE A DEDICATED GREEN INSULATED GROUND CONDUCTOR TO ALL DEVICES. DO
NOT USE CONDUIT SYSTEM AS THE ONLY EQUIPMENT GROUNDING METHOD.
6. DO NOT INSTALL BOXES BACK-TO-BACK ON OPPOSITE SIDES OF THE SAME WALL.
MAINTAIN MINIMUM OF 8” DISTANCE BETWEEN BOXES WHEREVER APPLICABLE.
7. BALANCE PANEL LOADS DURING INSTALLATION. CIRCUIT NUMBERING SHOWN ON PLANS
MAY BE ADJUSTED TO ACCOMODATE.
8. PROVIDE TYPED PANEL DIRECTORY AT PROJECT COMPLETION FOR NEW PANELS AND
EXISTING PANELS WITH CIRCUITS MODIFIED AS A RESULT OF THIS PROJECT. USE
OWNER’S CURRENT ROOM NUMBERS AND EQUIPMENT NAMES.
9. CONTRATOR IS RESPONSIBLE FOR OPENINGS IN WALLS, FLOORS, CEILINGS, AND ROOFS
THAT ARE REQUIRED TO COMPLETE THEIR SCOPE OF WORK. SEAL PENETRATIONS IN
ACCORDANCE WITH THE RATING OF THE AFFECTED ASSEMBLY. REFER TO
ARCHITECTURAL CODE PLAN FOR RATED WALLS, FLOORS, AND CEILINGS.
INSTALLATION NOTES - ELECTRICAL
1. PROVIDE NORMAL WIRING DEVICES AS GRAY UNLESS OTHERWISE NOTED.
2. PROVIDE DEVICES COVER PLATES AS STAINLESS STEEL. MATCH WIRING DEVICES COLOR.
3. PROVIDE GFCI TYPE RECEPTACLES AT ALL LOCATIONS REQUIRED BY THE NEC.
4. INSTALL WALL MOUNTED RECEPTACLES AT +18" ABOVE FINISHED FLOOR UNLESS OTHERWISE
NOTED.
5. INSTALL WALL MOUNTED LIGHT SWITCHES AT +46” ABOVE FINISHED FLOOR UNLESS
OTHERWISE NOTED. EXCEPTION; INSTALL DEVICES ABOVE AN OBSTRUCTED HIGH FORWARD
REACH OBSTACLE GREATER THEN 20 INCHES IN DEPTH AT +42”.
6. INSTALL ABOVE COUNTERTOP RECEPTACLES +8” ABOVE COUNTERTOP OR AS OTHERWISE
INDICATED.
7. AT A COMMON COUNTERTOP, INSTALL ALL RECEPTACLES AND SWITCHES AT THE SAME
HEIGHT UNLESS OTHERWISE SPECIFICALLY INDICATED.
DEVICE INSTALLATION AND MATERIALS - ELECTRICAL
1. UNLESS NOTED OTHERWISE, CONNECT ALL EMERGENCY BATTERY FIXTURES WITH AN UN-
SWITCHED LEG OF THE LIGHTING CIRCUIT THAT SERVES THE FIXTURES SPACE. MAINTAIN
NORMAL SWITCHING SCHEME OF EMERGENCY FIXTURES UNDER NORMAL OPERATION.
INSTALL PER EMERGENCY FIXTURE OR TRANSFER DEVICE INSTRUCTIONS.
2. VERIFY CEILING TYPE (IE. GRID, GYP) WITH ARCHITECTURAL REFLECTED CEILING PLANS
PRIOR TO RELEASE OF LIGHTING FIXTURE EQUIPMENT PACKAGE. ADJUST FIXTURE TYPE,
CONSTRUCTION, FLANGE, OR OTHER COORDINATION DETAILS AS REQUIRED FOR CEILING
TYPE.
3. LIGHTING CONTROLS SENSORS ARE SHOWN ON PLANS AT SUGGESTED LOCATIONS ONLY.
VERIFY LOCATIONS WITH MANUFACTURER GUIDELINES AND INSTALLATION
RECOMMENDATIONS. ADJUST LOCATIONS AS REQURIED TO MEET MANUFACTURER
GUIDELINES.
4. PROVIDE LIGHTING CONTROLS AS A COMPLETE SYSTEM AND INCLUDE MATERIAL AND
INSTALLATION FOR ALL POWER PACKS, ACCESSORIES, CONTROLLERS, AND WIRING
REQUIRED FOR OPERATION.
INSTALLATION NOTES - LIGHTING
REFER TO EQUIPMENT CONNECTION SCHEDULE FOR COORDINATION DETAILS BETWEEN
MECHANICAL AND ELECTRICAL SYSTEMS.
PROVIDE AND INSTALL ELECTRICAL SYSTEMS UNDER THIS CONTRACT MEETING THE
REQUIREMENTS OF THE SPECIFIED MECHANICAL, FIRE PROTECTION, AND PLUMBING
SYSTEMS. REFERENCE THE ENTIRE PROJECT DOCUMENTS, MANUALS, SCHEDULES, DETAILS,
AND NOTES.
PROVIDE ELECTRICAL CONNECTIONS AND ACCESSORIES INCLUDING STARTERS,
DISCONNECTS, CONTROL WIRING, ETC. AS REQUIRED FOR THE BUILDING MECHANICAL
EQUIPMENT. INFORMATION HEREIN AND ON THE DRAWINGS IS FOR GENERAL DESCRIPTION
AND ESTIMATING PURPOSES ONLY. VERIFY VOLTAGE, AMPERAGE, PHASE, INRUSH, ETC. FOR
EACH ITEM OF EQUIPMENT BEFORE PROCEEDING WITH INSTALLATION. INSTALL EQUIPMENT
PER WIRING DETAILS AND INSTRUCTIONS FURNISHED BY THE SUPPLIERS OF THE EQUIPMENT
TO PROVIDE PROPER OPERATION.
REVIEW MECHANICAL EQUIPMENT SHOP DRAWINGS FOR COMPLIANCE AND COORDINATION
WITH ELECTRICAL CONNECTIONS. NOTIFY ENGINEER IF CHANGES TO ELECTRICAL
CONNECTIONS, WIRING, AND BREAKER REQUIREMENTS ARE NECESSARY TO ACCOMMODATE
EQUIPMENT BEING SUPPLIED.
a. DO NOT RELEASE ELECTRICAL DISTRIBUTION EQUIPMENT UNTIL ALL MECHANICAL
EQUIPMENT REQUIRING ELECTRICAL INFRASTRCTURE HAS BEEN SUBMITTED AND
APPROVED. MAKE COORDINATION ADJUSTMENTS TO BREAKER SIZES AND SIMILAR
CHANGES TO ELECTRICAL EQUIPMENT PRIOR TO SUBMITTAL RELEASE. COORDINATE
SCHEDULING OF SHOP DRAWINGS WITH ALL TRADES.
PROVIDE DISCONNECTS RATED FOR EQUIPMENT AS REQUIRED AND AS INDICATED WITHIN
EQUIPMENT CONNECTION SCHEDULE. COORDINATE DISCONNECT MOUNTING TO ALLOW
EQUIPMENT REMOVAL WITHOUT DISCONNECT REMOVAL AND TO MINIMIZE WIRING WORK
REQUIRED.
PROVIDE HEAVY DUTY TYPE DISCONNECTS RATED FOR THE INSTALLED ENVIRONMENT.
PROVIDE MINIMUM NEMA 3R RATED DISCONNECTS FOR EXTERIOR INSTALLATIONS OR AS
NOTED.
VERIFY LOCATIONS OF ALL EQUIPMENT. REFER TO MECHANICAL, PLUMBING, AND
ARCHITECTURAL DRAWINGS AND COORDINATE WITH THE ASSOCIATED SUB-CONTRACTOR.
ADJUST ELECTRICAL INSTALLATION AS REQUIRED.
BUILDING EQUIPMENT COORDINATION NOTES - ELECTRICAL
1.
2.
3.
4.
5.
6.
7.
1. THE DELIVERY METHOD FOR THIS PROJECT IS INDIVIDUAL SUB-CONTRACTS TO ONE GENERAL
CONTRACTOR. THIS CONTRACTOR IS RESPONSIBLE FOR MEETING WITH ALL SUB-
CONTRACTORS TO COORDINATE LOCATIONS AND INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. REWORK OF INSTALLED EQUIPMENT WILL BE AT
CONTRACTORS EXPENSE.
PROJECT DELIVERY NOTES - ELECTRICAL
ELECTRICAL ABBREVIATIONS
A DEVICE MOUNTED +8" ABOVE
COUNTER TOP (VERIFY LOCATION)
AFF ABOVE FINISHED FLOOR
ATS AUTOMATIC TRANSFER SWITCH
C CEILING
CB CIRCUIT BREAKER
CT CURRENT TRANSFORMER
E EXISTING ITEM TO REMAIN
EC ELECTRICAL CONTRACTOR
EM EMERGENCY LIGHT FIXTURE
ER NEW LOCATION OF EXISTING ITEM
F ROUGH IN FOR FUTURE DEVICE
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FSD FIRE SMOKE DAMPER
G GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
KVA KILO-VOLT-AMPERES
KW KILOWATTS
MC MECHANICAL CONTRACTOR
MCB MAIN CIRCUIT BREAKER
MDP MAIN DISTRIBUTION PANEL
MLO MAIN LUGS ONLY
N NEW DEVICE IN EXISTING LOCATION
NIC NOT IN CONTRACT
NM NONMETALLIC
NTS NOT TO SCALE
OC ON CENTER
OFCI OWNER FURNISHED
CONTRACTOR INSTALLED
OFOI OWNER FURNISHED,
OWNER INSTALLED
R EXISTING ITEM TO BE REMOVED
RR EXISTING ITEM TO BE REMOVED AND
RELOCATED
RN EXISTING ITEM TO BE REMOVED AND
REPLACED WITH NEW
SCCR SHORT CIRCUIT CURRENT RATING
T TAMPER PROOF DEVICE
TCC TEMPERATURE CONTROL CONTRACTOR
TV TELEVISION
TYP TYPICAL
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
VA VOLT-AMPERES
WG WIREGUARD COVER
WP WEATHERPROOF DEVICE
WR WEATHER RESISTANT DEVICE
+24" INDICATES MOUNTING HEIGHT CENTER
LINE OF DEVICE TO FINISHED FLOOR
**NOTE: ALL SYMBOLS MAY NOT APPLY TO THIS PROJECT**
DATA BOX ROUGH-IN ONLY
TELECOMMUNICATIONS INFRASTRUCTURE SYMBOLS
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
B U
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-000
E L E
C T
R
IC
A L N
O T
T
W
W
ST
S T
SAN
UNDERGROUND POWER
UNDERGROUND POWER
UNDERGROUND POWER
WATERLINE NOT LOCATED
TELEPED
PHONELINE ON NORTH SIDE ROAD
T
PANEL A
S H
O P
A N
D O
F F
IC
IL
D
IN
G
REFER TO ONE-LINE DIAGRAM
ON SHEET E-300
FUTURE TELEPHONE LINE. ROUTE (1) EMPTY 2"
PVC CONDUIT WITH PULL STRING TO PEDESTAL
FOR TELEPHONE UTILITY CABLING. COORDINATE
FINAL ROUTING AND BUILDING ENRANCE PRIOR
TO ROUGH-IN.
TELEPHONE DEMARC
A- 19
FUEL PUMP LOCATION. SEE CIVIL PLANS.
COORDINATE FINAL LOCATION WITH OWNER
AND CIVIL PRIOR TO ROUGH-IN.
EXISTING UTILITY PRIMARY
UNDERGROUND LINE
UTILITY METER. REFER TO ONE-
LINE DIAGRAM ON SHEET E-300.
COORDINATE PRIMARY
CONNECTION, ROUTING, AND HAND
HOLE WITH UTILITY COMPANY.
UTILITY PAD MOUNT TRANSFORMER.
REFER TO ONE-LINE DIAGRAM E-300.
NEW UNDERGROUND STORM.
SEE CIVIL PLANS.
EXISTING UNDERGROUND WATER.
SEE CIVIL PLANS.
NEW UNDERGROUND SEWER.
SEE CIVIL PLANS.
EXISTING TELEPHONE LINE. SEE
CIVIL PLANS.
1. UTILITIES SHOWN ON ELECTRICAL SITE PLAN ARE SCHEMATIC ONLY. VERIFY ALL SITE
CONDITIONS AND DIMENSIONS ON SITE PRIOR TO SUBMITTING BID AND ORDERING
EQUIPMENT.
2. REPAIR ALL AFFECTED SURFACES AND RESTORE TO EXISTING CONDITIONS AT COMPLETION
OF PROJECT.
3. WARNING - CALL BEFORE YOU DIG: LAW REQUIRES ANYONE DOING EXCAVATION, FENCING,
PLANTING OR DRILLING TO CALL 48 HOURS IN ADVANCE. HAND DIG WITHIN 18 INCHES OF ANY
LOCATE MARK OR FLAG. ONE-CALL 811.
SITE NOTES - ELECTRICAL
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-001
E L E
C T
R
IC
A L S
IT
E
P L
A N
1" = 30'-0"
ELECTRICAL SITE PLAN
KEYNOTES
1 MOUNT ABOVE STORAGE LOFT. COORDINATE FINAL
LOCATION WITH OWNER AND ARCHITECTURAL DRAWINGS.
ACRYLICSHOWERS FREEWILL K-12100-C
W
J
G GG
W W
G
G
G
G
G
G G G
G
W
TV
J
J J
G
G
POWER GENERAL NOTES
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE UNTIL
PROPER AND TIMELY COORDINATION WITH ALL TRADES ASSOCIATED
WITH THE INSTALLATION HAS TRANSPIRED. ITEMS TO BE
COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO: BUILDING
STRUCTURE, SHEET METAL, PIPING SYSTEMS, LIGHT FIXTURES,
CONDUITS, CABLE TRAYS, ETC. REFER TO ALL GENERAL,
MECHANICAL, AND ELECTRICAL DRAWINGS AND SPECIFICATIONS
FOR THIS PROJECT.
B. COORDINATE ELECTRICAL REQUIREMENTS FOR MECHANICAL UNITS
WITH M.C. AND FINAL MECHANICAL SHOP DRAWINGS.
C. PROVIDE PENETRATIONS REQUIRED FOR ROUTING RACEWAYS
THROUGH THE BUILDING. COORDINATE FIRE RATED WALL
PENETRATIONS AND PROVIDE CONDUIT SLEEVES AND FIRE
STOPPING TO MAINTAIN RATING.
+60"
G,A
+60"
G,A
EF
EF
REF.
WH
A
F
UH
UH
UH
MOD
CU
MICROWAVE
DRYER
WASHER
AIR COMP.
+120"
EMERGENCY FUEL PUMP PUSHBUTTON SHUT-OFF STATION IN NEMA 3R
ENCLOSURE. PROVIDE SIGN WITH ENGRAVED WHITE LETTERING
READING "EMERGENCY FUEL PUMP POWER SHUT-OFF". (EATON
10250T5B62-S108 OR EQUAL)
PANEL A
A- 4
G,A
+60"
1 1 1
A-9 A-9A-9
A-7
A-27
A-7
A-9
A-9
A-7 A-7 A-7
A-27
A-21 A-21
A-21
A-5
A-5 A-5 A-5
A-5
A-5
A-27
A-27
A-21
A-21
A-21
A-32,34
A-36,38
A-8
A-17
A-17 A-17
A-17
A-10
A-27
A-19
A-20
A-12
A-24,26
A-22
A-28,30
A-25
A-18
A-12
A-11 A-13 A-15
+48" AFF
WELDER RCPTs 50A-2P
NEMA 14-50R
+48"+48"+48"+48"
+48"
+48"
+48"
+48" +48"
+48"
+48"
+48"
ON/OFF TOGGLE
SWITCH FOR FUEL
TANK POWER
UTILITY METER.
REFER TO ONE-LINE
DIAGRAM ON SHEET
E-300.
+48"
+48"
MOD
A-12
A-33,35
E-300
Typ
A-23
A-29
A-31
DISPOSAL
GAS DETCTION
CONTROL PANEL
A- 2
+48" A-7
+48"
A-9 +60"
A- 37
CP
A-14
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-200
E L E
C T
R
IC
A L P
L A
N S
KEYNOTES
1 OVERHEAD DOOR MOTORIZED CONTROLLER. INSTALL
DEVICES PER MANUFACTURER INCLUDING ALL LOW
VOLTAGE SENSORS AND SWITCHES. PROVIDE EQUIPMENT
DISCONNECT WHERE NECESSARY.
2 CONNECT TO LOCAL LIGHTING SWITCH.
3 FUTURE TELEPHONE UTILITY DEMARC LOCATION. STUB UP
EMPTY 2" CONDUIT TO THIS LOCATION. REFER TO E-001
ELECTRICAL SITE PLAN.
4 VERIFY THE FINAL LOCATION WITH OWNER AND ARCHITECT
PRIOR TO ROUGH-IN.
5 DATA ROUGH-IN LOCATION ONLY. INSTALL DUAL GANG
JUNCTION BOX WITH SINGLE GANG MUD RING, STAINLESS
STEEL FACE PLATE AND ROUTE (1) 1" EMPTY CONDUIT TO
ABOVE ACCESSIBLE CEILING WITH BUSHING AND PULL
STRING.
1/4" = 1'-0"
ELECTRICAL FLOOR PLAN - POWER
3 3
1O S
T C
OS
OS
E1-W A-1
E1 A-3
E1-W A-1
W1 A-6
E1-W A-1
F2 f A-3
F2 f A-3
F4 e A-3
F4 d A-3
F1 z A-1
F1 y A-1
F1 y A-1
F1 a A-1
EM
+9'-0"
X1-W A-1
F3 h A-3
F3 h A-3
F3 h A-3
F3 h A-3
F3 b A-3
F3 b A-3
F3 b A-3
F3 b A-3
E1 A-3
E1 A-3
F2 g A-3
F3 c A-3
F3 c A-3
X1 A-3
X1 A-3
PANEL A
a a b b c d e f h c g h
F3 h A-3
F3 h A-3
F3 b A-3
F3 b A-3 b h
E1 A-3
W1 A-6
+9'-0"
EM
F1 x A-1
F1 x A-1
F1 x A-1
F1 x A-1
F1 z A-1
F1 z A-1 yz y z
F1 z A-1
F1 z A-1
F1 y A-1
F1 y A-1
F1 a A-1
F1 a A-1 x
2 2 2 2
3 3 3 3
F1 x A-1
A. COORDINATE LOCATION/INSTALLATION OF MECHANICAL AND
ELECTRICAL WORK WITH ALL OTHER TRADES. NO ASPECT OF A
SYSTEM INSTALLATION OR ITS ROUGH-IN SHALL COMMENCE
UNTIL PROPER AND TIMELY COORDINATION WITH ALL TRADES
ASSOCIATED WITH THE INSTALLATION HAS TRANSPIRED. ITEMS
TO BE COORDINATED SHALL INCLUDE BUT NOT BE LIMITED TO:
BUILDING STRUCTURE, SHEET METAL, ALL PIPING SYSTEMS,
LIGHT FIXTURES, CONDUITS, CABLE TRAYS, ETC. REFER TO ALL
GENERAL, MECHANICAL, AND ELECTRICAL DRAWINGS AND
SPECIFICATIONS FOR THIS PROJECT.
LIGHTING GENERAL NOTES
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-201
L
IG
H T
IN
G
P L
A N
S
1/4" = 1'-0"
ELECTRICAL REFLECTED CEILING PLAN - LIGHTING
KEYNOTES
1 CONNECT TO ASTRONOMICAL TIMECLOCK IN MECH ROOM.
2 MOUNT ON UNDERSIDE OF STORAGE LOFTT. COORDINATE
FINAL LOCATION WITH OWNER AND ARCHITECTURAL
DRAWINGS.
3 MOUNT ABOVE STORAGE LOFT. COORDINATE FINAL
LOCATION WITH OWNER AND ARCHITECTURAL DRAWINGS.
A. DIAGRAM INDICATES OVERALL LAYOUT OF ELECTRICAL
DISTRIBUTION SYSTEM. REFER TO FLOOR PLANS FOR
EQUIPMENT LOCATIONS.
B. USE COPPER CONDUCTORS UNLESS OTHERWISE INDICATED.
C. MATCH NEUTRAL CONDUCTOR SIZE TO THE PHASE
CONDUCTORS UNLESS OTHERWISE NOTED.
D. ALL WIRING SHALL BE IN RACEWAY AS NOTED. REFER TO
SPECIFICATIONS FOR CONDUIT APPLICATION REQUIREMENTS.
E. INSTALL UTILITY TRANSFORMER PAD, METERING EQUIPMENT,
AND SERVICE ENTRANCE FEEDERS IN ACCORDANCE WITH
UTILITY COMPANY REQUIREMENTS.
RISER DIAGRAM GENERAL NOTES
1. SECONDARY SERVICE FEEDERS TO METER BY UTILITY
COMPANY. COORDINATE CONDUIT REQUIREMENTS.
RISER DIAGRAM KEYED NOTES
UTIL XFMR
240D/120YV
B
PRIMARY CONDUCTORS
BY UTILITY COMPANY
PANEL A
MCB
120/240V
225A
E-300
A
PER NEC
BY UTILITY CO.
UTILITY METER SOCKET.
INTEGRAL CTS.
METER
SERVICE
ENTRANCE RATED.
BUILDING
MAIN
DISCONNECT
GND
NEUT
GND
MAIN TELECOMMUNICATIONS
GROUND BAR
INCOMING FEEDER.
REFER TO BUILDING
FEEDER INFORMATION
ON ONE-LINE DIAGRAM.
A. ALL AVAILABLE GROUNDING ELECTRODES WHICH ARE PRESENT AT THE BUILDING OR
STRUCTURE SHALL BE BONDED TOGETHER TO FORM THE GROUNDING ELECTRODE
SYSTEM (GES). ADDITIONAL CODE-REQUIRED GROUNDING CONNECTIONS NOT
SHOWN SHALL BE PROVIDED. CONNECTIONS WHICH ARE ENCASED, UNDERGROUND,
OR INACCESSIBLE SHALL BE EXOTHERMIC WELD.
B. ALL BONDING JUMPERS CONNECTING GROUNDING ELECTRODES TO THE GES SHALL
BE SIZED EQUAL TO THE GROUNDING ELECTRODE CONDUCTOR (GEC) IN
ACCORDANCE WITH NEC 250.53(C). OTHER BONDING JUMPERS SHALL BE SIZED AS
OTHERWISE DESCRIBED IN NEC ARTICLE 250. CONDUCTORS SHALL BE BARE
COPPER UNLESS OTHERWISE NOTED.
C. REFER TO SPECIFICATIONS FOR ADDITIONAL PRODUCT AND MATERIAL
REQUIREMENTS. GROUNDING AND BONDING METHODS AND MATERIALS SHALL
COMPLY WITH NEC ARTICLE 250.
D. REFER TO TECHNOLOGY DETAILS FOR ADDITIONAL REQUIREMENTS RELATED TO
TELECOM GROUNDING.
NOTES
#1/0 CU
INSULATED
EXOTHERMIC WELD TO
BUILDING STRUCTURAL
STEEL
'-0
(T Y
P A
L L S
ID
E
S
#2 BARE COPPER
CONDUCTOR 36"
BELOW GRADE. 20'
IN LENGTH MIN.
(TYP.)
5/8" X 10'-0" GROUND
RODS EQUALLY
SPACED,
EXOTHERMIC WELD
TO #2 BARE COPPER
GROUND ROD
CONDUCTOR (TYP.)
LAY CABLE IN CIRCLE
PATTERN BETWEEN
GROUND RODS (TYP.)
BOND ACROSS SEPARATION IN
BUILDING STRUCTURES.
INCLUDE FIRE WALLS,
EXPANSION JOINTS, ETC.
COLD WATER
PIPE ENTRY *
GROUNDING ELECTRODE
#4 AWG BARE COPPER
OR 1/2" STEEL
REINFORCING ROD
CONCRETE
FOUNDATION
EXOTHERMIC WELD
TO CONNECT STEEL
ROD TO COPPER
CONDUCTOR
20'-0" MIN
#4 CU
BUILDING
GAS PIPING
#6 CU
NONMETALLIC
PROTECTIVE SLEEVE
#2 CU
#2 CU BARE WIRE
WATER PIPE
GROUND CLAMP
WATER PIPE
GROUND CLAMPWATER METER
GAS PIPE
GROUND CLAMP
SIZE GROUNDING ELECTRODE CONDUCTOR AND BONDING PER NEC 250.66 AND TABLE BELOW.
ALL CONDUCTORS TO BE COPPER.
TABLE BASED ON NEC 2017
TABLE 250.66 GROUDING ELECTRODE CONDUCTOR FOR ALTERNATING-CURRENT SYSTEMS
SIZE OF LARGEST UNGROUDNING CONDUCTOR OR
EQUIVALENT AREA FOR PARALLEL CONDUCTORS (AWG/KCMIL)
SIZE OF GROUNDING ELECTRODE
CONDUCTOR (AWG/KCMIL)
COPPER ALUMINUM OR COPPER-CLAD AL COPPER
#2 OR SMALLER #1/0 OR SMALLER #8
#1 OR #1/0 #2/0 OR #3/0 #6
#2/0 OR #3/0 #4/0 OR 250 #4
OVER #3/0 THROUGH 350 OVER 250 THROUGH 500 #2
OVER 350 THROUGH 600 OVER 500 THROUGH 900 #1/0
OVER 600 THROUGH 1100 OVER 900 THROUGH 1750 #2/0
OVER 1100 OVER 1750 #3/0
REFER TO TELECOMMUNICATIONS
DETAILS FOR GROUNDING DETAILS
BUILDING
STRUCTURAL STEEL
MULTI-GROUND
ROD ASSEMBLY
CONCRETE ENCASED
ELECTRODE
MAIN BONDING
JUMPER
** SIZE BONDING JUMPER PER NEC 250.102. USE TABLE ABOVE FOR ALL CONDUCTORS BETWEEN #2 AND 1100. ALL INCOMING CONDUCTORS OVER 1100 CU OR 1750 AL SHALL BE SIZED PER THE TABLE
250.102(C). SERVICE EQUIPMENT SHALL BE SUPPLIED WITH BONDING JUMPER FROM THE
MANUFACTURER.
REMOVABLE LINK
RED (LOAD)
BLK
RED (LINE)
WHT
RED (LOAD)
RED (LINE)
LINE
NEUTRAL
BRANCH CIRCUIT
WHITE / NEUTRAL
(TYP.)
L O A D
24VDC SENSOR
CEILING OR WALL SURFACE MOUNTED
RED +24 VDC
BLK COMMON
BLU OUTPUT
RED +24 VDC
BLK COMMON
BLU OUTPUT
CONTROL CONDUCTORS TO
ADDITIONAL SENSORS WITHOUT
POWER PACKS WHERE USED
BLK
WHT
LINE
NEUTRAL
BRANCH CIRCUIT
(TYP.)
L O A D
STANDARD POWER PACK
SATELLITE POWER PACK
WHERE USED
L O A D
ADJUSTABLE STOP.
COORDINATE WITH OWNER
DURING CONSTRUCTION TO
SET MAXIMUM PULL LENGTH.
JUNCTION BOX AND
RECEPTACLE FOR CORD REEL
CONNECTION. MOUNTED BELOW
ACCESSIBLE CEILING WHERE
PRESENT.
ROOF JOIST
UNISTRUT CHANNEL
ATTACHED TO BOTTOM OF
SUPPORT
BOLT CORD REEL TO STRUT
CHANNEL PER
MANUFACTURER
INSTALLATION INSTRUCTION.
CORD REEL SHALL BE HUBBELL
KELLEMS "HBL45123R220"
INDUSTRIAL POWER CORD REEL OR
APPROVED EQUAL. (2) DUPLEX
RECEPTACLES, 20A RATED, 45' CORD,
GREY FINISH.
ACOUSTICAL CEILING TILE
(WHERE PRESENT)
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-300
O N
E -L
IN
E
D
E T
A
IL
S
NOTE: ALL CONDUCTORS THHN COPPER UNLESS OTHERWISE NOTED.
FEEDER SCHEDULE
TAG PHASE GROUND CONDUIT
A 1- SET (3) - - (1) 2"
B 1- SET (4) #3 - (1) 1 1/4"
NOT TO SCALE
ONE-LINE DIAGRAM
NOT TO SCALE
GROUNIND ELECTRODE DETAIL
NOT TO SCALE
OCCUPANCY SENSOR LIGHTING CONTROL DETAIL
NOT TO SCALE
RETRACTABLE CORD REEL
DEB
JTL
in fo k c le n g in e e ri n g .c o m
4t h
S tr ee t
W es t D es
M oi ne s, Io w a
5.
4.
IO
W
A D
E P A
R T M
E N
T O
F
N A
T U
R A
L R
E S O
U R
C E S
E N
G
IN
E E R
IN
G
S E R
V
IC
E S
W A
LL
A
IL
D
IN
G
E
TH
S
T.
D E S M
O
IN
E S
IA
-0
P
.7
.8
F
.7
.8
S E A
L
PROJECT NUMBER:
DATE:
NO.
DATE
BY
REVISION
DRAWN BY:
CHK'D BY:
SHEET No:
C O
N S U
LT
A
N T:
23-05-26-01
03.21.2023
N E W
O F F
IC
E
S
TO
R A
G E B
U
IL
D
IN
G F
O R
L a k e
W a p e llo S ta te
P a rk
C
A M
P G
R O
U N
D R
A O
D D
R A
K E S V
IL
LE
IA
E-400
E L E
C T
R
IC
A L S
C H
E D
U L
E S
HOA HAND-OFF-AUTO
GF GROUND FAULT CIRCUIT INTERRUPTION VFD VARIABLE FREQUENCY DRIVE
FDS FUSED DISCONNECT SWITCH, HEAVY DUTY TS TOGGLE SWITCH WITH PLUG FUSE
FAR FIRE ALARM SHUTDOWN RELAY TOR TIME DELAY OFF RELAY
ECB ENCLOSED CIRCUIT BREAKER ST SHUNT TRIP
CP CORD AND PLUG PROVIDED WITH UNIT SS START/STOP PUSHBUTTON
CSD COMBINATION STARTER/DISCONNECT SSP START/STOP PUSHBUTTON WITH PILOT
CB CIRCUIT BREAKER IN PANEL SD SUPPLY AIR DUCT DETECTOR
BO PROVIDED BY OTHERS RSR RUN STATUS RELAY , NORMALLY OPEN
4X NEMA 4X ENCLOSURE RD RETURN AIR DUCT DETECTOR
4 NEMA 4 ENCLOSURE NFD NON-FUSED DISCONNECT SWITCH, HEAVY DUTY
3R NEMA 3R ENCLOSURE MMS MANUAL MOTOR STARTER WITH FUSES
1 NEMA 1 ENCLOSURE INT INTEGRAL WITH EQUIPMENT FROM FACTORY
ABBREVIATIONS:
1. INCLUDE AUXILLIARY CONTACTS AND LOW-VOLTAGE WIRING TO AUXILLIARY EQUIPMENT THAT RUNS IN TANDEM WITH EQUIPMENT, (I.E. 120V DAMPERS WITH 480V MOTORS).
GENERAL NOTES:
EQUIPMENT CONNECTION SCHEDULE
TAG
ELECTRICAL CHARACTERISTICS DISCONNECT
REMARKS
VOLTAGE PHASE
MOTOR HP
KW MCA TYPE
SIZE
(AMPS)
NEMA
RATING
FUSE SIZE
(AMPS)
CP-1 120 V 1 0.08 CB
CU-1 240 V 1 12 NFD 30 3R PROVIDE AND INSTALL DISCONNECT
EF-1 120 V 1 FHP INT CONNECT TO LOCAL OCCUPANCY SENSOR WITH LIGHTS IN SPACE.
EF-2 120 V
1/4
HOA 20 1 POWER MOTORIZED DAMPER TO OPEN/CLOSE WITH FAN. INSTALL PROVIDED
HOA.
F-1 120 V 1 FHP CB
MOD-1 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.
MOD-2 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.
UH-1 120 V 1 2.4
UH-2 120 V 1 2.4
UH-3 120 V 1 2.4
WH-1 240 V 1 4.5 CB
DESIGNED BY: DEB
ALL OTHER SPACES SENSORS PROGRAMMED FOR VACANCY MODE, MANUAL ON/AUTOMATIC OFF OPERATION 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM.DIMMING CONTROL OF FIXTURES WITHIN
DAYLIGHT ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.
CORRIDORS, VESTIBULES,
COMMON SPACES:
SENSORS PROGRAMMED FOR OCCUPANCY MODE, AUTOMATIC ON/OFF OPERATION, 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM. DIMMING CONTROL OF FIXTURES WITHIN DAYLIGHT
ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.
9. UNLESS INDICATED OTHERWISE, LIGHTING CONTROL SCHEMES/OPERATION SHALL BE AS FOLLOWS:
8. ETD'S AND ALL EMERGENCY LIGHTING CONTROLS COMPONENTS SHALL BE TESTED AND LISTED AS COMPATIBLE BY MANUFACTURER WITH NORMAL LIGHTING CONTROLS IN ALL AREAS.
7. WHERE APPROVED EQUAL MANUFACTURER PRODUCTS SENSOR COVERAGE OR LOAD RATINGS DIFFER FROM BASIS OF DESIGN, CONTRACTOR AND MANUFACTURER ARE RESPONSIBLE FOR PROVIDING ADDITIONAL
DEVICES AS NECCESARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.
6. PROVIDE FACTORY AUTHORIZED REPRESENTATIVE TO DEMONSTRATE TYPICAL INSTALLATION AND COMMISSIONING OF EQUIPMENT.
5. INSTALL LOW VOLTAGE POWER PACKS AND ROOM CONTROLLERS ABOVE NEARBY ACCESSIBLE CEILING TILES OR IN MECHANICAL/STORAGE SPACES ADJACENT TO CONTROLLED FIXTURES. DO NOT INSTALL
POWERPACKS EXPOSED IN COMMON SPACES OR IN INACCESSIBLE LOCATIONS.
4. WHERE WIRELESS LIGHTING CONTROLS ARE PROVIDED. POWERPACKS SHALL BE PROVIDED AND INSTALLED WITHIN MANUFACTURER RECOMENDED DISTANCES TO ENSURE CONTROLLER OPERATION.
3. PROVIDE LIGHTING CONTROLS WITH MANUFACTURER COMPLIANT POWER PACKS AND LOW VOLTAGE ROOM CONTROLLERS IN QUANTITY REQUIRED TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM.
MANUFACTURER OR MANUFACTURERS REP TO PROVIDE DEVICE QUANTITES, LAYOUTS AND TYPICAL WIRING DETAILS DURING SHOP SUBMITTAL PROCESS. PROVIDE DIMMING COMPATIBLE DEVICES WHERE DIMMING CONTROLS ARE SHOWN. COORDINATE DIMMING TYPE WITH LIGHTING FIXTURES SHOWN. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE DIMMING TYPE.
2 ALL DEVICES PROVIDED WITH MANUFACTURER LIMITED 5 YEAR WARRANTY.
1. ALL DEVICES SHALL BE U.L. OR SIMILARLY LISTED.
NOTES:
LIGHTING CONTROLS SCHEDULE
TYPE DESCRIPTION ELECTRICAL MOUNTING SENSOR TYPE COVERAGE APPROVED
MANUFACTURERS
OS 1 WALL SWITCH OCCUPANCY SENSOR. DEVICE FINISH MATCHING WIRING DEVICES SPEC.
RATED FOR MIN 1/6 HP MOTOR. INTEGRAL AUTOMATIC SELF-ADAPTIVE COVERAGE
THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER SETTINGS.
120V WALL SWITCH /
SINGLE GANG
PASSIVE INFRARED 1000 SQ FT / 180
DEG
HUBBELL, CRESTRON, ACUITY,
WATTSTOPPER, GREENGATE,
AS APPROVED BY ENGINEER.
OS 2 CEILING MOUNTED OCCUPANCY/VACANCY SENSOR. LIGHTING CONTROLS NETWORK
COMPATIBLE DEVICE. ROOM CONTROLLER COMPATIBLE, ENABLING MULTI-ZONE SWITCHING
CONTROL AND MULTI-SOURCE DIMMING. WHITE FINISH. AUTOMATIC SELF-ADAPTIVE
COVERAGE THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER
SETTINGS. INDOOR USE.
LOW VOLTAGE CEILING / 8'-12'
MH
PASSIVE INFRARED 1000 SQ FT / 360
DEG
HUBBELL, CRESTRON, ACUITY,
WATTSTOPPER, AS APPROVED
BY ENGINEER.
DESIGNED BY: DEB
7. CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND FILLING OUT ALL UTILITY REBATE FORMS FOR OWNER.
6. AIM AND TARGET ADJUSTABLE INTERIOR AND EXTERIOR LIGHT FIXTURES UNDER THE OBSERVATION AND IN COMPLIANCE WITH RECOMMENDATIONS OF THE ARCHITECT.
INCLUDE LABOR AND MATERIAL COSTS MADE NECESSARY BY THIS REQUIREMENT.
5. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE NECESSARY TO INSTALL AND SUPPORT THE LUMINAIRES.
4. VERIFY COMPATIBILITY OF LIGHT FIXTURES WITH CEILING MATERIAL, ADJACENT CONSTRUCTION, AND ADJACENT FINISHES PRIOR TO SHOP DRAWINGS SUBMITTAL
NOTIFY THE ARCHITECT OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION.
3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS, DETAILS, AND CONFIGURATIONS OF ALL LUMINAIRES. IF ARCHITECTURAL DRAWINGS DO NOT CLARIFY EXACT MOUNTING LOCATION OR DETAIL, ISSUE AN RFI FOR ARCHITECT TO SPECIFICALLY CLARIFY PRIOR TO FIXTURE ROUGH-IN.
2. INCLUDE A MINIMUM 1 YEAR WARRANTY FOR LIGHTING FIXTURES, WHERE NOT OTHERWISE SPECIFIED.
1. ALL FIXTURES SHALL BE U.L. OR SIMILARLY LISTED.
NOTES:
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER MODEL DESCRIPTION FINISH LUMENS CRI DRIVER TYPE SOURCE-CCT VOLTAGE LOAD-VA APPROVED EQUALS
E1 LITHONIA LIGHTING ELM2L-120/347-SDRT EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY
WHITE EM N/A N/A
LED 120 V 2 VA
ISO-LITE, DUAL-LITE, OR AS APPROVED
BY ENGINEER
E1-W LITHONIA LIGHTING ELM2L-UVOLT-SDRT / ELAWG1
EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY, WIRE GUARD
WHITE EM N/A N/A
LED 120 V 2 VA
ISO-LITE, DUAL-LITE, OR AS APPROVED
BY ENGINEER
F1 LITHONIA LIGHTING
CLX-L48-5000LM-HEF-FDL-WD-120-GZ10-LUGR-40K-80C
RI-PLR
CORD SET INSTALLATION, CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION, GLARE REFLECTOR ACCESSORY. DAMP LISTED. PROVIDE AN ALLOWANCE FOR PLUG-READY LUMINAIRE.
CONTRACTOR TO VERIFY OR PROVIDE SO CORD IF NOT INCLUDED WITH LUMINIARE. CONTRACTOR TO INSTALL IN
FIELD.
WHITE 5000 80 0-10V DIMMING TO 10%
LED-4000K 120 V 32 VA AS APPROVED BY ENGINEER
F2 LITHONIA LIGHTING L4-13LM-40K-120-G4-80CRI-ZXT // WPR-CSS-WET RECESSED 4" ROUND DOWNLIGHT, PARABOLIC REFLECTOR, WIDE DISTRIBUTION, DAMP LOCATION
SEMI-SPECULAR 1300 80 0-10V DIMMING TO 10%
LED - 4000K 120 V 20 VA
ALPHABET LIGHTING, COOPER HALO OR
AS APPROVED BY ENGINEER
F3 CREE ZR24C-40K-10V-FD RECESSED 2x2 , SWITCHABLE CCT AND LUMEN PACKAGE
WHITE 80 0-10V DIMMING TO 10%
LED-4000K 120 V 0 VA
WILLIAMS, COLUMBIA, OR AS APPROVED
BY ENGINEER
F4 LITHONIA LIGHTING CLX-L48-3000LM-HEF-FDL-WD-120-GZ10-40K-80CRI CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION WHITE 3000 80 0-10V DIMMING TO 10% LED-4000K 120 V 20 VA AS APPROVED BY ENGINEER
W1 HUBBELL LIGHTING TRP1-24L-15-3K8-4W-UNV-DBT-PC-EH BUILDING MOUNTED WALL PACK, TYPE 4 DISTRIBUTION, -30 DEGREE RATED EMERGENCY BATTERY PACK
BRONZE 1700 80 NON-DIMMING
LED-3000K 120 V 20 VA
LITHONIA LIGHTING, COOPER
MCGRAW-EDISON, OR AS APPROVED BY
ENGINEER
X1 LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD / ELAWG1 BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS
WHITE N/A N/A N/A
RED LED 120 V 2 VA
ISO-LITE, DUAL-LITE, OR AS APPROVED
BY ENGINEER
X1-W LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD / ELAWG1 BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS, WIRE GUARD
WHITE N/A N/A N/A
RED LED 120 V 2 VA
ISO-LITE, DUAL-LITE, OR AS APPROVED
BY ENGINEER
NOTES:
TOTAL EST. DEMAND: 162 A
TOTAL CONN.: 184 A
RECEPTACLE 21140 VA 73.65% 15570 VA TOTAL EST. DEMAND: 38846 VA
POWER 22400 VA 100.00% 22400 VA TOTAL CONN. LOAD: 44241 VA
LIGHTING 701 VA 125.00% 876 VA
LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED... PANEL TOTALS
"G" INDICATES GFCI TYPE BREAKER
LEGEND:
202 A 167 A
24261 VA 19980 VA
SPARE 1 -- 20 A 41 0 0 42 20 A -- 1 SPARE
SPARE 1 -- 20 A 39 0 0 40 20 A -- 1 SPARE
GAS DETECTION 1 20 A 37 920 2250 38
35 3250 2250 36
30 A 2 WH-1
WELDER 2 50 A
33 3250 2080 34
DISPOSAL 1 20 A 31 800 2080 32
30 A 2 CU-1
REFRIGERATOR 1 G 20 A 29 1200 1750 30
RCPT LAUNDRY, MECH 1 20 A 27 900 1750 28
50 A 2 DRYER
WASHER 1 G 20 A 25 1200 600 26
MICROWAVE 1 20 A 23 800 600 24
20 A 2 AIR COMPRESSOR
RCPT BREAK ROOM 1 20 A 21 1080 290 22 20 A 1 UH-3
FUEL PUMP/EMERGENCY SHUT OFF 1 20 A 19 1500 290 20 20 A 1 UH-2
RCPT EXTERIOR 1 20 A 17 720 290 18 20 A 1 UH-1
DOOR OPENER 1 20 A 15 920 0 16 20 A -- 1 SPARE
DOOR OPENER 1 20 A 13 920 4500 14 20 A 1 CP-1
DOOR OPENER 1 20 A 11 920 1100 12 20 A 1 EF-2
RCPT SHOP 1 20 A 9 1080 100 10 20 A 1 EF-1
RCPT SHOP 1 20 A 7 1080 1270 8 20 A 1 F-1
RCPT OFFICE 1 20 A 5 1080 40 6 20 A 1 EXTERIOR LIGHTING
OFFICE LIGHTING 1 20 A 3 110 360 4 20 A 1 CORD REELS
SHOP LIGHTING 1 20 A 1 551 360 2 20 A 1 CORD REELS
CIRCUIT DESCRIPTION P AMP
CKT
NO A B
CKT
NO AMP P CIRCUIT DESCRIPTION
INTEGRAL SURGE PROTECTION DEVICE
NOTES:
ENCLOSURE: TYPE 1 MCB RATING: 225 A
MOUNTING: SURFACE WIRES: 3 MAINS RATING: 225 A
SUPPLY FROM: PHASES: 1 MAINS TYPE: MCB
LOCATION: VOLTAGE: 120/240 SINGLE SCCR RATING: 25,000 A
BRANCH PANEL: A
MECH/ELEC
UTILITY METER
- INCREASE TO 54 SPACE IF REQUIRED FOR INTEGRAL SPD. PROVIDE SPARES
FOR REMAINING UNUSED SPACES.
| 23-05-26-01_Drawings_signed |
| 23-05-26-01_A-001 Plot - Signed |
| 23-05-26-01_A-002 Plot (1) |
| 23-05-26-01_A-003 Plot (1) |
| 23-05-26-01 Wapello Shop and Office Design Sheet C1 |
| 23-05-26-01 Wapello Shop and Office Design-C1 |
| 23-05-26-01 Wapello Shop and Office Design Sheet C2 |
| 23-05-26-01 Wapello Shop and Office Design-C2 |
| 23-05-26-01 Wapello Shop and Office Design Sheet C3 |
| 23-05-26-01 Wapello Shop and Office Design-C3 |
| 23-05-26-01 Wapello Shop and Office Design Sheet C4 |
| 23-05-26-01 Wapello Shop and Office Design-C4 |
| 23-05-26-01_A-010 Plot (1) |
| 23-05-26-01_A-020 Plot (1) |
| 23-05-26-01_A-100 Plot (1) |
| 23-05-26-01_A-101 Plot (1) |
| 23-05-26-01_A-110 Plot (1) |
| 23-05-26-01_A-200 Plot (1) |
| 23-05-26-01_A-201 Plot (1) |
| 23-05-26-01_A-300 Plot (1) |
| 23-05-26-01_A-301 Plot (1) |
| 23-05-26-01_A-400 Plot (1) |
| 23-05-26-01_A-401 Plot (1) |
| 23-05-26-01_A-600 Plot (1) |
| 2023-03-21 - IDNR Lake Wapello State Park - 100% CD - Mechanical |
| IDNR Lake Wapello - Shop_Mech_KCL-M000 |
| IDNR Lake Wapello - Shop_Mech_KCL-M100 |
| IDNR Lake Wapello - Shop_Mech_KCL-M200 |
| IDNR Lake Wapello - Shop_Mech_KCL-M300 |
| IDNR Lake Wapello - Shop_Mech_KCL-P100 |
| IDNR Lake Wapello - Shop_Mech_KCL-P200 |
| IDNR Lake Wapello - Shop_Mech_KCL-P300 |
| 2023-03-21 - IDNR Lake Wapello State Park - 100% CD - Electrical |
| E-000 - ELECTRICAL NOTES |
| E-001 - ELECTRICAL SITE PLAN |
| E-200 - ELECTRICAL PLANS |
| E-201 - LIGHTING PLANS |
| E-300 - ONE-LINE & DETAILS |
| E-400 - ELECTRICAL SCHEDULES |