Office/Shop Buildings for George Wyth State Park and Upper Iowa Wildlife Management Area
Solicitation number
25CRDLWBGANTO-0014
Issued by
Black Hawk County, Iowa

About this file

This is Addendum No. 3 issued by the Iowa Department of Natural Resources Land & Waters Bureau for the Lake Wapello State Park Office and Storage Building project in Davis County, Iowa (Project #23-05-26-01) dated April 13-14, 2023. The addendum approves the substitution of Alumination Plank System 6" aluminum soffit panels in Wood Grain - Douglas Fir color for the specified decorative soffit under the overhang canopy. It also provides clarifications on mechanical and electrical specifications, including approval of Anemostat as a manufacturer for diffusers, registers and grilles, and METALUX as an approved manufacturer for light fixture types F3 and F4.

The addendum includes detailed electrical schedules showing panel configurations, lighting fixture specifications, equipment connection details, and lighting controls. Technical clarifications are provided for the lighting fixture schedule and circuit 3 load on Panel A. The document includes comprehensive lighting control requirements and equipment connection specifications for various building systems including exhaust fans, unit heaters, and other mechanical equipment. Drawing E-400 is referenced as being attached to provide additional electrical schedule details.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IOWA DEPARTMENT OF NATURAL RESOURCES ADDENDUM No. 3

LAND & WATERS BUREAU

WALLACE STATE OFFICE BUILDING

LAKE WAPELLO STATE PARK

OFFICE AND STORAGE BUILDING

DAVIS COUNTY, IOWA

PROJECT NUMBER: 23-05-26-01

April 13, 2023

This Addendum is issued to modify, explain or correct the original Drawings and Specifications, and is hereby made a part of the Contract Documents. Please attach this Addendum to the Project Manual in your possession. Insert the number and issue date of this Addendum in the blank space provided on the Proposal Form.

Substitutions:

1. Alumination – Plank System 6” aluminum soffit panels are an approved substitution to the specified decorative soffit under the overhang canopy. Color to be Wood Grain - Douglas Fir.

• Please review the attached addendum, prepared by KCL Engineering, for more information.

IDNR

Lake Wapello State Park Office & Storage Building

Addendum #3

April 14, 2023

This addendum is issued to modify, clarify, or amend the original Project Drawings and Specifications and is hereby made part of the Contract Documents. The

Contractor shall be responsible for incorporating items in this Addendum to the

Work. The following shall take precedence over anything to the contrary in the

Drawings or Specifications.

Mechanical – Approved Manufacturers:

Spec Section Item Manufacturer

15855 Diffusers, Registers & Grilles Anemostat

Electrical Drawings:

1. Drawing E-400 – ELECTRICAL SCHEDULES:

a. Clarify the lighting fixture schedule.

b. Clarify load for circuit 3 on Panel A.

Electrical – Approved Manufacturers:

The following shall be added to specifications as approved manufacturers:

Light Fixture Type Manufacturer

F3 METALUX

F4 METALUX

Drawings Attached: E-400.

End of Electrical Addendum.

DEB

JTL

in fo k c le n g in e e ri n g .c o m

4t h

S tr ee t

W es t D es

M oi ne s, Io w a

5.

4.

IO

W

A D

E P A

R T M

E N

T O

F

N A

T U

R A

L R

E S O

U R

C E S

E N

G

IN

E E R

IN

G

S E R

V

IC

E S

W A

LL

A

C E

B U

IL

D

IN

G

E

TH

S

T.

D

E S M

O

IN

E S

IA

-0

P

.7

.8

F

.7

.8

S E A

L

PROJECT NUMBER:

DATE:

NO.

DATE

BY

REVISION

DRAWN BY:

CHK'D BY:

SHEET No:

C O

N S U

LT

A

N T:

23-05-26-01

03.21.2023

N E W

O F F

IC

E

S

TO

R A

G E B

U

IL

D

IN

G F

O R

L a k e

W a p e llo S ta te

P a rk

C

A M

P G

R O

U N

D R

A O

D D

R A

K E S V

IL

LE

IA

E-400

E L E

C T

R

IC

A L S

C H

E D

U L E

S

HOA HAND-OFF-AUTO

GF GROUND FAULT CIRCUIT INTERRUPTION VFD VARIABLE FREQUENCY DRIVE

FDS FUSED DISCONNECT SWITCH, HEAVY DUTY TS TOGGLE SWITCH WITH PLUG FUSE

FAR FIRE ALARM SHUTDOWN RELAY TOR TIME DELAY OFF RELAY

ECB ENCLOSED CIRCUIT BREAKER ST SHUNT TRIP

CP CORD AND PLUG PROVIDED WITH UNIT SS START/STOP PUSHBUTTON

CSD COMBINATION STARTER/DISCONNECT SSP START/STOP PUSHBUTTON WITH PILOT

CB CIRCUIT BREAKER IN PANEL SD SUPPLY AIR DUCT DETECTOR

BO PROVIDED BY OTHERS RSR RUN STATUS RELAY , NORMALLY OPEN

4X NEMA 4X ENCLOSURE RD RETURN AIR DUCT DETECTOR

4 NEMA 4 ENCLOSURE NFD NON-FUSED DISCONNECT SWITCH, HEAVY DUTY

3R NEMA 3R ENCLOSURE MMS MANUAL MOTOR STARTER WITH FUSES

1 NEMA 1 ENCLOSURE INT INTEGRAL WITH EQUIPMENT FROM FACTORY

ABBREVIATIONS:

1. INCLUDE AUXILLIARY CONTACTS AND LOW-VOLTAGE WIRING TO AUXILLIARY EQUIPMENT THAT RUNS IN TANDEM WITH EQUIPMENT, (I.E. 120V DAMPERS WITH 480V MOTORS).

GENERAL NOTES:

EQUIPMENT CONNECTION SCHEDULE

TAG

ELECTRICAL CHARACTERISTICS DISCONNECT

REMARKS

VOLTAGE PHASE

MOTOR HP

KW MCA TYPE

SIZE

(AMPS)

NEMA

RATING

FUSE SIZE

(AMPS)

CP-1 120 V 1 0.08 CB

CU-1 240 V 1 12 NFD 30 3R PROVIDE AND INSTALL DISCONNECT

EF-1 120 V 1 FHP INT CONNECT TO LOCAL OCCUPANCY SENSOR WITH LIGHTS IN SPACE.

EF-2 120 V

1/4

HOA 20 1 POWER MOTORIZED DAMPER TO OPEN/CLOSE WITH FAN. INSTALL PROVIDED

HOA.

F-1 120 V 1 FHP CB

MOD-1 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.

MOD-2 120 V 1 POWER MOTORIZED LOUVER TO OPEN/CLOSE WITH FAN.

UH-1 120 V 1 2.4

UH-2 120 V 1 2.4

UH-3 120 V 1 2.4

WH-1 240 V 1 4.5 CB

DESIGNED BY: DEB

ALL OTHER SPACES SENSORS PROGRAMMED FOR VACANCY MODE, MANUAL ON/AUTOMATIC OFF OPERATION 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM.DIMMING CONTROL OF FIXTURES WITHIN

DAYLIGHT ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.

CORRIDORS, VESTIBULES,

COMMON SPACES:

SENSORS PROGRAMMED FOR OCCUPANCY MODE, AUTOMATIC ON/OFF OPERATION, 20 MINUTES MINNIMUM, 30 MINUTES MAXIMUM. DIMMING CONTROL OF FIXTURES WITHIN DAYLIGHT

ZONES SHALL BE BY ALWAYS ON DAYLIGHT SENSOR.

9. UNLESS INDICATED OTHERWISE, LIGHTING CONTROL SCHEMES/OPERATION SHALL BE AS FOLLOWS:

8. ETD'S AND ALL EMERGENCY LIGHTING CONTROLS COMPONENTS SHALL BE TESTED AND LISTED AS COMPATIBLE BY MANUFACTURER WITH NORMAL LIGHTING CONTROLS IN ALL AREAS.

7. WHERE APPROVED EQUAL MANUFACTURER PRODUCTS SENSOR COVERAGE OR LOAD RATINGS DIFFER FROM BASIS OF DESIGN, CONTRACTOR AND MANUFACTURER ARE RESPONSIBLE FOR PROVIDING ADDITIONAL

DEVICES AS NECCESARY TO PROVIDE A COMPLETE AND OPERABLE SYSTEM.

6. PROVIDE FACTORY AUTHORIZED REPRESENTATIVE TO DEMONSTRATE TYPICAL INSTALLATION AND COMMISSIONING OF EQUIPMENT.

5. INSTALL LOW VOLTAGE POWER PACKS AND ROOM CONTROLLERS ABOVE NEARBY ACCESSIBLE CEILING TILES OR IN MECHANICAL/STORAGE SPACES ADJACENT TO CONTROLLED FIXTURES. DO NOT INSTALL

POWERPACKS EXPOSED IN COMMON SPACES OR IN INACCESSIBLE LOCATIONS.

4. WHERE WIRELESS LIGHTING CONTROLS ARE PROVIDED. POWERPACKS SHALL BE PROVIDED AND INSTALLED WITHIN MANUFACTURER RECOMENDED DISTANCES TO ENSURE CONTROLLER OPERATION.

3. PROVIDE LIGHTING CONTROLS WITH MANUFACTURER COMPLIANT POWER PACKS AND LOW VOLTAGE ROOM CONTROLLERS IN QUANTITY REQUIRED TO INSTALL A COMPLETE AND OPERATIONAL SYSTEM.

MANUFACTURER OR MANUFACTURERS REP TO PROVIDE DEVICE QUANTITES, LAYOUTS AND TYPICAL WIRING DETAILS DURING SHOP SUBMITTAL PROCESS. PROVIDE DIMMING COMPATIBLE DEVICES WHERE DIMMING CONTROLS ARE SHOWN. COORDINATE DIMMING TYPE WITH LIGHTING FIXTURES SHOWN. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE DIMMING TYPE.

2 ALL DEVICES PROVIDED WITH MANUFACTURER LIMITED 5 YEAR WARRANTY.

1. ALL DEVICES SHALL BE U.L. OR SIMILARLY LISTED.

NOTES:

LIGHTING CONTROLS SCHEDULE

TYPE DESCRIPTION ELECTRICAL MOUNTING SENSOR TYPE COVERAGE APPROVED

MANUFACTURERS

OS 1 WALL SWITCH OCCUPANCY SENSOR. DEVICE FINISH MATCHING WIRING DEVICES SPEC.

RATED FOR MIN 1/6 HP MOTOR. INTEGRAL AUTOMATIC SELF-ADAPTIVE COVERAGE

THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER SETTINGS.

120V WALL SWITCH /

SINGLE GANG

PASSIVE INFRARED 1000 SQ FT / 180

DEG

HUBBELL, CRESTRON, ACUITY,

WATTSTOPPER, GREENGATE,

AS APPROVED BY ENGINEER.

OS 2 CEILING MOUNTED OCCUPANCY/VACANCY SENSOR. LIGHTING CONTROLS NETWORK

COMPATIBLE DEVICE. ROOM CONTROLLER COMPATIBLE, ENABLING MULTI-ZONE SWITCHING

CONTROL AND MULTI-SOURCE DIMMING. WHITE FINISH. AUTOMATIC SELF-ADAPTIVE

COVERAGE THRESHOLD AND FALSE ON/FALSE OFF CORRECTION. 8-30 MINUTE TIMER

SETTINGS. INDOOR USE.

LOW VOLTAGE CEILING / 8'-12'

MH

PASSIVE INFRARED 1000 SQ FT / 360

DEG

HUBBELL, CRESTRON, ACUITY,

WATTSTOPPER, AS APPROVED

BY ENGINEER.

DESIGNED BY: DEB

7. CONTRACTOR IS RESPONSIBLE FOR OBTAINING AND FILLING OUT ALL UTILITY REBATE FORMS FOR OWNER.

6. AIM AND TARGET ADJUSTABLE INTERIOR AND EXTERIOR LIGHT FIXTURES UNDER THE OBSERVATION AND IN COMPLIANCE WITH RECOMMENDATIONS OF THE ARCHITECT.

INCLUDE LABOR AND MATERIAL COSTS MADE NECESSARY BY THIS REQUIREMENT.

5. CONTRACTOR IS RESPONSIBLE FOR ALL MISCELLANEOUS HARDWARE NECESSARY TO INSTALL AND SUPPORT THE LUMINAIRES.

4. VERIFY COMPATIBILITY OF LIGHT FIXTURES WITH CEILING MATERIAL, ADJACENT CONSTRUCTION, AND ADJACENT FINISHES PRIOR TO SHOP DRAWINGS SUBMITTAL

NOTIFY THE ARCHITECT OF ANY CONFLICTS WITH THE PROPOSED INSTALLATION.

3. REFER TO ARCHITECTURAL DOCUMENTS FOR EXACT MOUNTING LOCATIONS, DETAILS, AND CONFIGURATIONS OF ALL LUMINAIRES. IF ARCHITECTURAL DRAWINGS DO NOT CLARIFY EXACT MOUNTING LOCATION OR DETAIL, ISSUE AN RFI FOR ARCHITECT TO SPECIFICALLY CLARIFY PRIOR TO FIXTURE ROUGH-IN.

2. INCLUDE A MINIMUM 1 YEAR WARRANTY FOR LIGHTING FIXTURES, WHERE NOT OTHERWISE SPECIFIED.

1. ALL FIXTURES SHALL BE U.L. OR SIMILARLY LISTED.

NOTES:

LIGHTING FIXTURE SCHEDULE

TYPE MANUFACTURER MODEL DESCRIPTION FINISH LUMENS CRI DRIVER TYPE SOURCE-CCT VOLTAGE LOAD-VA APPROVED EQUALS

E1 LITHONIA LIGHTING ELM2L-120/347-SDRT EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY

WHITE EM N/A N/A

LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

E1-W LITHONIA LIGHTING ELM2L-UVOLT-SDRT / ELAWG1

EMERGENCY UNIT, WALL OR CEILING MOUNTED, 2 LED ADJUSTABLE LAMP HEADS, MAINTENANCE FREE BATTERY, WIRE GUARD

WHITE EM N/A N/A

LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

F1 LITHONIA LIGHTING

CLX-L48-5000LM-HEF-FDL-WD-120-GZ10-LUGR-40K-80C

RI-PLR

CORD SET INSTALLATION, CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION, GLARE REFLECTOR ACCESSORY. DAMP LISTED. PROVIDE AN ALLOWANCE FOR PLUG-READY LUMINAIRE.

CONTRACTOR TO VERIFY OR PROVIDE SO CORD IF NOT INCLUDED WITH LUMINIARE. CONTRACTOR TO INSTALL IN

FIELD.

WHITE 5000 80 0-10V DIMMING TO 10%

LED-4000K 120 V 32 VA AS APPROVED BY ENGINEER

F2 LITHONIA LIGHTING L4-13LM-40K-120-G4-80CRI-ZXT // WPR-CSS-WET RECESSED 4" ROUND DOWNLIGHT, PARABOLIC REFLECTOR, WIDE DISTRIBUTION, DAMP LOCATION

SEMI-SPECULAR 1300 80 0-10V DIMMING TO 10%

LED - 4000K 120 V 12 VA

ALPHABET LIGHTING, COOPER HALO OR

AS APPROVED BY ENGINEER

F3 CREE LIGHTING ZR-22-30L-840-105-UNV RECESSED 2x2 TROFFER, SMOOTH ACRYLIC LENS, DAMP LOCATION RATED

WHITE 3400 80 0-10V DIMMING TO 10%

LED-4000K 120 V 26 VA

WILLIAMS, COLUMBIA, OR AS APPROVED

BY ENGINEER

F4 LITHONIA LIGHTING CLX-L48-3000LM-HEF-FDL-WD-120-GZ10-40K-80CRI CHAIN HUNG 4' UTILITY STRIPLIGHT, FLAT ACRYLIC LENS, GENERAL DISTRIBUTION WHITE 3000 80 0-10V DIMMING TO 10% LED-4000K 120 V 25 VA AS APPROVED BY ENGINEER

W1 HUBBELL LIGHTING TRP1-24L-15-3K8-4W-UNV-DBT-PC-EH BUILDING MOUNTED WALL PACK, TYPE 4 DISTRIBUTION, -30 DEGREE RATED EMERGENCY BATTERY PACK

BRONZE 1700 80 NON-DIMMING

LED-3000K 120 V 15 VA

LITHONIA LIGHTING, COOPER

MCGRAW-EDISON, OR AS APPROVED BY

ENGINEER

X1 LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS

WHITE N/A N/A N/A

RED LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

X1-W LITHONIA LIGHTING LQM-S-W-3-R-MVOLT-EL-N-SD / ELAWG1 BACK MOUNTED EXIT SIGN, SINGLE FACE, THERMOPLASTIC HOUSING, SELF-DIAGNOSTICS, WIRE GUARD

WHITE N/A N/A N/A

RED LED 120 V 2 VA

ISO-LITE, DUAL-LITE, OR AS APPROVED

BY ENGINEER

NOTES:

TOTAL EST. DEMAND: 164 A

TOTAL CONN.: 186 A

RECEPTACLE 21140 VA 73.65% 15570 VA TOTAL EST. DEMAND: 39271 VA

POWER 22400 VA 100.00% 22400 VA TOTAL CONN. LOAD: 44581 VA

LIGHTING 1041 VA 125.00% 1301 VA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED... PANEL TOTALS

"G" INDICATES GFCI TYPE BREAKER

LEGEND:

202 A 169 A

24251 VA 20330 VA

SPARE 1 -- 20 A 41 0 0 42 20 A -- 1 SPARE

SPARE 1 -- 20 A 39 0 0 40 20 A -- 1 SPARE

GAS DETECTION 1 20 A 37 920 2250 38

35 3250 2250 36

30 A 2 WH-1

WELDER 2 50 A

33 3250 2080 34

DISPOSAL 1 20 A 31 800 2080 32

30 A 2 CU-1

REFRIGERATOR 1 G 20 A 29 1200 1750 30

RCPT LAUNDRY, MECH 1 20 A 27 900 1750 28

50 A 2 DRYER

WASHER 1 G 20 A 25 1200 600 26

MICROWAVE 1 20 A 23 800 600 24

20 A 2 AIR COMPRESSOR

RCPT BREAK ROOM 1 20 A 21 1080 290 22 20 A 1 UH-3

FUEL PUMP/EMERGENCY SHUT OFF 1 20 A 19 1500 290 20 20 A 1 UH-2

RCPT EXTERIOR 1 20 A 17 720 290 18 20 A 1 UH-1

DOOR OPENER 1 20 A 15 920 0 16 20 A -- 1 SPARE

DOOR OPENER 1 20 A 13 920 4500 14 20 A 1 CP-1

DOOR OPENER 1 20 A 11 920 1100 12 20 A 1 EF-2

RCPT SHOP 1 20 A 9 1080 100 10 20 A 1 EF-1

RCPT SHOP 1 20 A 7 1080 1270 8 20 A 1 F-1

RCPT OFFICE 1 20 A 5 1080 30 6 20 A 1 EXTERIOR LIGHTING

OFFICE LIGHTING 1 20 A 3 460 360 4 20 A 1 CORD REELS

SHOP LIGHTING 1 20 A 1 551 360 2 20 A 1 CORD REELS

CIRCUIT DESCRIPTION P AMP

CKT

NO A B

CKT

NO AMP P CIRCUIT DESCRIPTION

INTEGRAL SURGE PROTECTION DEVICE

NOTES:

ENCLOSURE: TYPE 1 MCB RATING: 225 A

MOUNTING: SURFACE WIRES: 3 MAINS RATING: 225 A

SUPPLY FROM: PHASES: 1 MAINS TYPE: MCB

LOCATION: VOLTAGE: 120/240 SINGLE SCCR RATING: 25,000 A

BRANCH PANEL: A

ADDENDUM 1

04/14/23

DLB

23-05-26-01_Addendum 3
IDNR Wapello_Elec Addendum 3
2023-04-13 - IDNR Lake Wapello State Park - ADD3 - E-400