M-1
NTS
o
ACCU AIR COOLED CONDENSING UNIT
ACLD AIR COOLED
ACU AIR CONDITION UNIT (S)
ACV ALARM CHECK VALVE
ADP APPARATUS DEW POINT
AHU AIR HANDLING UNIT
AIR COND AIR CONDITION (-ING,-ED)
AL ALUMINUM
ALT ALTITUDE
AMB AMBIENT
AMP AMPERE(AMP, AMPS)
APPROX APPROXIMATE
AVG AVERAGE
AWG AMERICAN WIRE GAUGE
BARO BAROMETER(-TRIC)
BARO PR PRESSURE, BAROMETRIC
BHP BRAKE HORSEPOWER
BP BOILING POINT
CAP CAPACITY
CCW COUNTER CLOCKWISE
CHW CHILLED WATER
CKT CIRCUIT
CLASS CLASSIFICATION
CLG LOAD COOLING LOAD
COEF COEFFICIENT
CONN CONNECTION
CONT CONTINUE
C
CMH CUBIC METER PER HOUR
CU M CUBIC METER
CENTIGRADE/ CELCIUS
CFCI
CONTRACTOR INSTALLED
CONTRACTOR FURNISHED
CIP CAST IRON PIPE
CWP
CU MM CUBIC MILLIMETER
Cv COEFFICIENT, VALVE FLOW
CW CLOCKWISE OR COLD WATER
CIRCULATING WATER PUMP
DB DECIBEL OR DRY BULB
COMPRESSORCPRSR
DBT DRY BULB TEMPERATURE
DCWS DOMESTIC COLD WATER SUPPLY
DEG or ° DEGREE
DFW DIESEL OIL
DOMESTIC HOT WATER RETURN
DOMESTIC HOT WATER SUPPLY
DHWR
DHWS
DIRECT EXPANSIONDX
DRY PIPE VALVEDPV
DOUBLE POLE DOUBLE THROWDPDT
DEWPOINT TEMPERATUREDPT
DIVISIONDIV
DIFFERENCEDIFF
DIAGRAMDIAG
DIAMETERDIA or
DWG DRAWING
EXPANSION JOINTEXPJT
ENTERING WATER TEMPEWT
EVAPORAT (-E,-ING,-ED,-OR)EVAP
EXTERNAL STATIC PRESSUREESP
EXPLOSION PROOFEP
EQUIPMENTEQPT
ENTERINGENT
EFFICIENCYEFF
EQUIVALENT DIRECT RADIATIONEDR
ECONOMIZERECON
ECCENTRICECC
ENTERING AIR TEMPERATUREEAT
FUEL OILFO
FA FACE AREA OR FRESH AIR
FHC FIRE HOSE CABINET
FHY FIRE HYDRANT
FLA FULL LOAD AMPERES
F FARENHEIT
FLR FLOOR
FEED WATER PUMPFWP
FACE VELOCITYFVEL
FLUSH VALVEFV
FRP
FREQUENCYFREQ
FEMALE PIPE THREADFPT
FIBERGLASS REINFORCED PLASTIC
Ft or ' FEET
FXTR FIXTURE
GALVANIZED STEELGALVS
GAGE OR GAUGEGA
GR GRAMS
GOVERNMENT INSTALLED
GOVERNMENT FURNISHED GFGI
CONTRACTOR INSTALLED
GOVERNMENT FURNISHEDGFCI
GAL GALLONS
GALLONS PER MINUTEGPM
HERTZHZ
HORIZONTALHORIZ
HOT WATER HEATERHWH
HOT WATERHW
HOUR(S)HR
HORSEPOWERHP
MERCURYHG
HEADHD
HB HOSE BIBB
DIAMETER, INSIDEID
ISOMETRICISO
IRON PIPE SIZEIPS
J JOULE
K THERMAL CONDUCTIVITY
K THERMAL CONDUCTIVITY
kG kCAL/HR
KILOGRAM
kG/SQ CM KILOGRAM PER SQ. CENTIMETER kG/SQ CM A
KILOCALORIE PER HOUR
(ABSOLUTE)
KILOGRAM PER SQ. CENTIMETER
kG/SQ CM G
(GAUGE)
KILOGRAM PER SQ. CENTIMETER
kG/SM KILOGRAM PER SQ. METER kG/SM A kG/SM G
(ABSOLUTE)
KILOGRAM PER SQ. METER
KILOGRAM PER SQ. METER (GAGE)
kW KILOWATT kWH KILOWATT HOUR kJ KILOJOULE kPa KILO PASCAL
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LG LENGTH
LH LATENT HEAT
LWT LEAVING WATER TEMPERATURE
LIQUID LINELL
L LITERS
LPD LITERS PER DAY
LPH LITERS PER HOUR
LPS
LM LINEAR METER
LITERS PER SECOND
LAV LAVATORY
LPM LITERS PER MINUTE
LT LAUNDRY TRAY
NUMBERNO
NORMALLY OPENN.O.
NOT IN CONTRACTNIC
NORMALLY CLOSEDN.C.
NOISE CRITERIANC
NCK
MAX
NOT TO SCALENTS
MIN
MPH
M METERS
MAXIMUM
MINIMUM OR MINUTE
METERS PER HOUR
MPS METERS PER SECOND
MM MILLIMETER
NPT NATIONAL TAPER PIPE (THREAD)
NOT APPLICABLEN/A
NECK
MECH MECHANICAL
OS&Y OUTSIDE SCREW & YOKE
OD
OAIL OUTSIDE AIR INTAKE LOUVER
OA OUTSIDE AIR
OUTSIDE DIAMETER
OPNG OPENING
OXY OXYGEN
PERCENT
PRESSURE REDUCING VALVEPRV
PARTS PER MILLIONPPM
POINT OF CONNECTIONPOC
PLUMBINGPLMB
PHASE (ELECTRIC)PH
PRESSURE GAGEPG
PD
POLEP
PRESSURE DROP OR DIFFERENCE
Pa PASCAL
POL PETROLEUM, OIL AND LUBRICANTS
QUANTITYQTY
QUARTQT
REFRIGERATION TONRT
REVOLUTIONS PER MINUTERPM
RADIATORRDTR
RETURN AIRRA
THERMAL RESISTANCER
REFRIGERANT (134A, 22, ETC)R134A,R22
RH RELATIVE HUMIDITY
SUPPLY AIRSA
SYMBOLSYM
SUCTIONSUCT
STORAGESTOR
STEELSTL
STANDARDSTD
STEAMST
SAYBOLT SECONDS UNIVERSALSSU
STAINLESS STEELSST
SAYBOLT SECONDS FUROLSSF
SQUARESQ
SPECIFICATIONSPEC
SINGLE POLE DOUBLE THROWSPDT
SM
LPH, STANDARD CONDITIONSSLPH
LPS, STANDARD CONDITIONSSLPS
SG
SLPD LPD, STANDARD CONDITIONS
SL SENSIBLE LOAD
SH SENSIBLE HEAT
SPECIFIC GRAVITY
SF SAFETY FACTOR
SEC SECOND
SCH SCHEDULE
STATIC PRESSURE
SQUARE METER
SP
SBM
SAN SANITARY
SUBMERSIBLE
TYPICALTYP
THERMOSTATTSTAT
TONS OF REFRIGERATIONTONS
THICKNESSTHK
THERMOMETERTHERM
TEMPERATURETEMP
TEMPERATURE DIFFERENCETD
UNIT HEATERUH
HEAT TRANSFER COEFFICIENTU
WTRPRF
WT
WSHR
WITHW/
WH
WIDTHWD
WCLD
WC
WBT
WB
WATTW
VP
VOL
VISC
VERTICALVERT
VENTILATIONVENT
VELOCITYVEL
VARIABLE AIR VOLUMEVAV
VAC VACUUM
VLV VALVE
V VOLT
WATERPROOF
WEIGHT
WASHER
WATTHOUR OR WATER HEATER
WATER-COOLED
WATER CLOSET
WET BULB TEMPERATURE
WET BULB
PRESSURE, DYNAMIC(VELOCITY)
VOLUME
VISCOSITY
VTR VENT THRU ROOF
UR URINAL
A B B R E V I A T I O N S
MECHANICAL MATERIAL INDICATIONS AND SYMBOLS
FS
VFM
OFM
AVA
PRESSURE RELIEF
TEMPERATURE
EXPANSION LOOP
EXPANSION JOINT
ANCHOR, INTERMEDIATE
ALIGNMENT GUIDE
AIR VENT, AUTOMATIC
SQUARE HEAD BALANCING COCK
QUICK OPENING
NEEDLE
LOCK SHIELD
FLEXIBLE CONNECTOR
FLOWMETER, ORIFICE
FLOWMETER, VENTURI
FLOW SWITCH
PRESSURE GAUGE AND COCK
STRAINER
THERMOMETER
PRESSURE REDUCING
RELIEF OR SAFETY
SLEEVE
BLOW OFF STRAINER
INLINE PUMP
SAFETY
FLOAT
valves, special duty
S
M
GATE, NORMALLY CLOSED
GLOBE
SOLENOID
3 WAY MANUAL
GATE, NORMALLY OPEN
PLUG
MOTOR OPERATED GATE
MOTOR OPERATED GLOBE
3 WAY ELECMOTOR CONTROL
3 WAY AIR MOTOR CONTROLLER
HOSE GATE
HOSE GLOBE
POST INDICATOR
OS Y
ANGLE GLOBE
ANGLE GATE
SWING GATE CHECK
S
M
P
M
M
ALARM CHECK
DRY PIPE
DELUGE
PREACTION
TAMPER DETECTION SWITCH
QUICK OPENING DEVICE
NON-RISING STEM
DIAPHRAGM
SOLENOID
MOTOR ELECTRIC
valve actuators fittings
TEE, SINGLE SWEEP
UNION, SCREWED
UNION, FLANGED
CONNECTION, TOP
ELBOW, 90°
ELBOW, TURNED UP
ELBOW, TURNED DOWN
TEE, OUTLET UP
TEE, OUTLET DOWN
CONNECTION, BOTTOM
REDUCER, CONCENTRIC
(STRAIGHT, INVERT)
REDUCER, ECCENTRIC
(STRAIGHT, DOWN)
REDUCER, ECCENTRIC
TEE
ELBOW, 45°
LATERAL
SOLVENT CEMENT
BELL AND SPIGOT
SCREWED
FLANGED
WELDED
SOLDERED/BRAZED
M
NS
BUTTERFLY
BALL
DIAPHRAGM
GATE
INDICATING BUTTERFLY
KEY OPERATED
CHECK
SIDEWALL SPRINKLER
UPRIGHT SPRINKLER
DELUGE VALVE
WALL MOUNTED TEST HEADER
FIRE ALARM BELL
HOSE STATION DRY STANDPIPE
MINI HORN
HORN SPEAKER
WALL HYDRANT 2 HOSE OUTLET
SMOKE DETECTOR
PENDENT SPRINKLER DROP NIPPLE
NIPPLED UP UPRIGHT SPRINKLER
OUTSIDE SPRINKLER
CUTTING POINT
CAP
NON-SPRINKLERED SPACE
RISER
(SEE SPRINKLER SCHEDULE)
PENDENT SPRINKLER
CONNECTION (2-WAY SHOWN)
SIAMESE FIRE DEPARTMENT
CONNECTION
SINGLE FIRE DEPARTMENT
valves
POTABLE COLD WATER
POTABLE HOT WATER
POTABLE HOT WATER RETURN
PIPE SLEEVE
BACKFLOW PREVENTER
PITCH OR PIPE, UP(U), DOWN(D)
VENT THRU ROOF
SURFACE CLEANOUT
FLOOR CLEANOUT
FLOOR DRAIN
PIPE SLEEVE WITH FIRE STOPPING
HOSE BIBB
FLOOR SINK (200mm x 200mm)
HOT WATER (60°C)
HOT WATER (82.22°C)
VENT
SANITARY SEWER
COMPRESSED AIR
FUEL OIL SUPPLY
FUEL OIL RETURN
FLOOR DRAIN WITH CLEANOUT
FLOOR DRAIN WITH DEEP TRAP
FLOOR DRAIN WITH NO TRAP
FLOOR DRAIN WITH TRAP TIME
FD
FCO
SCO
200x200
FIRE PROTECTION WATER SUPPLY
MAIN SUPPLY SPRINKLER
WET STANDPIPE
DRY STANDPIPE
COMBINATION STANDPIPE
plumbing sprinkler
DSP
WSP
CSP
S
F
PLAN ELEV
82.22°C
60°C
S
A
FOS
FOR
RD
RS
RL
D
CWS
CWR
LPC
BBD
PC
VPD
MU
FOD
FOV
FOG
FOS
FOR
HWS
M
HCS
HCR
FILL
MU
HWR
LOW PRESSURE CONDENSATE
BOILER BLOW DOWN
PUMPED CONDENSATE
VACUUM PUMP DISCHARGE
MAKE UP WATER
FUEL OIL DRAIN
FUEL OIL TANK VENT
FUEL OIL GAUGE
FUEL OIL SUPPLY
FUEL OIL RETURN
CONTROL AIR MAIN
DUAL TEMPERATURE RETURN
FILL LINE
MAKE UP WATER
DUAL TEMPERATURE SUPPLY
WATER SUPPLY
LOW TEMPERATURE HOT
WATER RETURN
LOW TEMPERATURE HOT
SPLITTER DAMPER
REFRIGERANT DISCHARGE
REFRIGERANT SUCTION
REFRIGERANT LIQUID
DRAIN
CHILLED WATER SUPPLY
CHILLED WATER RETURN
dampers piping heating air conditioning and refrigeration
DU 13mm
47.2
94.4
DG
300x150
500/300L
R
AD
FC
SG
SR
RG
RR
810mm x 400mm
810mm x 400mm
810mm x 400mm
EG
ER
810mm x 400mm
DIRECTION OF FLOW
FLEXIBLE CONNECTION
TRANSITION
(810mm WIDTH x 400mm DEPTH)
DUCT SIZES SHOWN
RISE(R), DOWN(D)
CHANGE OF ELEVATION
VERTICAL OR HORIZONTAL
ACCESS DOOR,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
OUTSIDE AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
POSITIVE PRESS.,
SUPPLY AIR DUCT SECTION,
FIRST FIGURE IS ON TOP
SECTION, NEGATIVE PRESS.,
RETURN OR EXHAUST AIR DUCT
SUPPLY OR RETURN
FLEXIBLE AIR DUCT,
TRANSITION
SQUARE TO ROUND
REGISTER, CEILING
EXHAUST AIR GRILLE OR
REGISTER, SIDEWALL
SUPPLY AIR GRILLE OR
REGISTER, CEILING
RETURN AIR GRILLE OR
OR REGISTER, CEILING
SUPPLY AIR MODULAR DIFFUSER
DOOR GRILLE (300mmx150mmH)
(500mmWx300mmH, 94.4 LPS)
LOUVER, DOOR OR WALL
(13mm, 47.2 LPS)
DOOR UNDERCUT
duct works grilles, registers and diffusers
LEGEND & ABBREVIATION
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
REPAIR BUILDING
M-2
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
GENERAL NOTES & SCOPE OF WORK
MECHANICAL GENERAL NOTES
GOVERNMENT.
ACTIVITIES, AND THE LIKE SHALL BE DONE BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE
16. DISPOSAL OF CONSTRUCTION DEBRIS, WASTE MATERIALS, MATERIALS RESULTING FROM DEMOLITION
WITH SHUT-OFF VALVE WITHIN 1M OF THE UNIT.
15. ALL CONDENSATE DRAINS FROM COOLING UNIT (AS NOTED ON THE DRAWINGS) SHALL BE PROVIDED
UNTIL ALL WATER BEING FLUSHED IS CLEAR AS TAP WATER.
14. PIPING SYSTEM SHALL BE FLUSHED, PURGED & CLEANED PER SPECS REQUIREMENTS AND FLUSHED
RECTANGULAR MAINS.
DUCT. PROVIDE SPIN-IN TYPE FITTINGS AT ALL ROUND DUCT TAKE-OFFS FROM SQUARE OR
USE RADIUS ELBOWS. PROVIDE AIR SPLITTER DAMPERS AT ALL BRANCH TAKE-OFFS FROM THE MAIN
13. PROVIDE TURNING VANES IN ALL ELBOWS THAT CHANGE AIR DIRECTION MORE THAN 30 DEGREES OR
CREATE CONDENSATION, FROM SINK BODIES EXPOSED TO AIR BELOW THE FLOOR.
PIPING RECEIVING AIR CONDITIONING CONDENSATE DRAINS, OR ANY OTHER COLD LIQUID WHICH MAY
12. INSTALL CONDENSATE DRAINS AT A MINIMUM SLOPE OF 1/4 INCH PER 1 FOOT. INSULATE ALL SEWER
ACTUATED DAMPERS IN AREA WITH GYPBOARD OR CONCEALED CEILINGS.
PANELS TO INSURE THAT THE EQUIPMENT CAN BE MAINTAINED ADEQUATELY. PROVIDE REMOTELY
INSPECTION 12"x12" ACCESS PANELS FOR TWO VALVES. COORDINATE THE LOCATION OF ACCESS
SMOKE DETECTOR, BACKDRAFT DAMPERS AND FOR ANY ITEM INDISE DUCTS REQUIRING SERVICING OR
DOORS IN DUCTS AT ALL AUTOMATIC CONTROL DAMPERS, FIRE DAMPERS, FIRE/SMOKE DAMPERS, DUCT
11. PROVIDE ACCESS PANELS TO ALL CONCEALED VALVES, DAMPERS, AND EQUIPMENT. PROVIDE ACCESS
STATIC PRESSURE CALSS 500PA AND DUCTWORK SHALL MEET THE REQUIREMENTS OF SEAL CLASS C.
10. ALL SUPPLY, RETURN AND EXHAUST AIR DUCTWORK SHALL BE CONSTRUCTED ACCORDING TO SMACNA
APPROVAL.
ADJUSTING AND BALANCING (TAB) REPORT SHALL BE SUBMITTED TO THE COR FOR REVIEW AND
STANDARD TECHNICAL SPECIFICATIONS FOR MISCELLANEOUS PROJECTS, KOREA. THE HVAC TESTING, STRICT ACCORDANCE WITH APPLICABLE SECTIONS OF DIVISION 22 & 23 - MECHANICAL. O & MA
9. ALL MECHANICAL SYSTEMS SHALL BE TESTED, ADJUSTED AND BALANCED BY THE CONTRACTOR IN
CONDITIONS AND SUBMITTED TO THE CONTRACTING OFFICER FOR APPROAL.
DETAILS SHALL BE PREPARED IN THE FIELD BY THE CONTRACTOR ACCORDING TO ACTUAL FIELD
8. SOME DETAILS SHOWN ON THIS CONTRACT DRAWINGS MAY NOT MATCH EXACT FIELD CONDITIONS. SUCH
PROJECT. THE DETAILS SHALL BE UTILIZED WHILE PERFORMING THE MECHANICAL SCOPE OF WORK.
7. FOR O & MA PROJECTS, KOREA, OCT. 1, 2003 DEPARTMENT OF THE ARMY FORM AS A PART OF THIS
CONTRACTING OFFICER.
6. THE CONTRACTOR SHALL SUBMIT MANUFACTURERS INSTALLATION SHOP DRAWINGS FOR APPROVAL BY THE
CONTRACT SHALL BE REPAIRED OR REPLACED BY THIS CONTRACTOR AT HIS OWN COST.
EQUIPMENT, DUCT WORK, PIPING ETC. ANY DAMAGED DUE TO THE WORK PERFORMED UNDER THIS
5. CONNECTION TO EXISTING SYSTEM SHALL BE DONE IN SUCH A MANNER AS NOT DAMAGE ANY EXISTING
AS WALLS, CEILING, ROOF, PIPE, DUCT, EQUIPMENT AND ELECTRICAL ITEMS.
SYSTEM AT NO ADDITIONAL COST TO THE GOVERNMENT, INCLUDING, BUT NOT LIMITED TO ITEMS SUCH
AS NECESSARY TO ALLOW FOR INSTALLATION AND REPLACEMENT OF MECH. AND FIRE PROTECTION
4. THE CONTRACTOR SHALL BE RESPONSIBLE FOR REMOVAL AND REINSTALLATION OF ALL OBSTRUCTIONS
CAUSED BY THIS PROJECT AND TO MATCH CONDITION TO ADJACENT AREAS AT HIS OWN COST.
3. THE CONTRACTOR SHALL BE RESPONSIBLE TO CONSTRUCT OR REPAIR ALL DAMAGES TO EXISTING AREAS
CLEARANCE, EQUIPMENT PAD SIZE, INSTALLATION LOCATIONS, AND ADDITIONAL ITEMS.
2. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
PRIOR TO COMMENCING ANY CONSTRUCTION OR RENOVATION.
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITION AND DIMENSIONS
NOTE :
SWITCH WILL NOT BE IN EXCESS OF 61 METERS.
LEAST ONE SHUTOFF SWITCH PER FLOOR SO THAT THE TRAVEL DISTANCE TO THE NEAREST SHUTOFF
MOTORIZED DAMPER. LOCATION SHALL BE ADJACENT TO MANUAL FIRE ALARM PULL BOXES AND WITH AT
LABEL AS PER AT/FP REQUIREMENTS AND DISABLE THE FAN WHEN ACTIVATED AND CLOSE THE
9. THE BUILDING SHALL HAVE AN EMERGENCY SHUT DOWN SWITCH IN A CLEAR PLASTIC ENCLOSURE WITH
BY A LICENSED OR CERTIFIED INSTALLER.
8. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPECIFICATION
7. ANY PIPES THAT PENETRATE FIRE RATED WALL (EXISTING/ NEW) SHALL BE SEALED PER SPEC.
CONDUITS AND ALL NECESSARY ACCESSORIES FOR H.V.A.C CONTROLS.
6. THE MECHANICAL/CONTROLS CONTRACTOR SHALL PROVIDE ALL THE WIRINGS, RELAYS, CONTROLLERS, PROVIDE REMOTELY ACTUATED DAMPERS IN AREAS WITH GYPBOARD OR CONCEALED CEILINGS.
5. PROVIDE VOLUME DAMPERS ON DUCTWORK BRANCH LINES WHETHER SHOWN ON THE DRAWINGS OR NOT.
LISTED.
DAMPER RATINGS SHALL BE COMPATIBLE WITH THE FIRE WALL OR FLOOR. FIRE DAMPERS SHALL BE UL
4. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATIONS THROUGH FIRE RATED WALLS AND FLOORS. FIRE
ARCHITECTURAL DRAWINGS FOR CEILING TYPES.
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCHITECTURAL CEILING TYPES. REFER TO
THE CONTRACTING OFFICER.
2. THE CONTRACTOR SHALL SUBMIT MECHANICAL SYSTEM INSTALLATION SHOP DRAWINGS FOR APPROVAL BY
CLEARANCE, INSTALLATION LOCATIONS AND ADDITIONAL ITEMS.
1. THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS FOR NEW WORK SUCH AS EQUIPMENT & SERVICE
A. REPAIR/MAINTENANCE (K-WORK)
SCOPE OF WORK
NONE.
B. CONSTRUCTION (L-WORK)
ON DRAWINGS.
HAMMER ARRESTERS, VALVES, CONTROL, ACCESS DOORS AND ALL ASSOCIATED ACCESSORIES AS SHOWN
HEATER, DOMESTIC HOT WATER RECIRCULATION PUMP, ELECTRIC WATER COOLER, TRAP PRIMER, WATER
SEWER AND VENT PIPING SYSTEM INCLUDING PLUMBING FIXTURES, ELECTRIC DOMESTIC HOT WATER
4. REPAIR THE PLUMBING SYSTEM BY INSTALLING NEW DOMESTIC COLD AND HOT WATER PIPING SYSTEM, CONSTRUCTION TO VERIFY THAT THE H.V.A.C. SYSTEM WORKS PROPERLY.
3. PERFORM DALT (DUCT AIR LEAKAGE TEST) AND T.A.B (TESTING, ADJUSTING, AND BALANCING) AFTER
AND ALL ASSOCIATED ACCESSORIES FOR VENTILATION SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, DIFFUSERS, GRILLES, LOUVERS, DUCTS, INSULATIONS, ACCESS DOORS, EQUIPMENT SUPPORT
OUTSIDE AIR SUPPLY UNIT, CONTROLLER, CO2 SENSOR, HVAC EMERGENCY SHUTDOWN SWITCH, DAMPERS,
2. REPAIR THE VENTILATION SYSTEM BY INSTALLING NEW EXHAUST FANS, ENERGY RECOVERY VENTILATOR, REMOTE CONTROLLER INDICATORS AND LABELS SHALL BE IN ENGLISH.
HEATING AND COOLING SYSTEM AS SHOWN ON DRAWINGS.
CONTROLS, ACCESS DOORS, EQUIPMENT SUPPORT (CONC. PAD) AND ALL ASSOCIATED ACCESSORIES FOR
ELECTRIC WALL HEATERS, ELECTRIC CEILING HEATERS, PIPES, VALVES, CONTROLLER, INSULATIONS, UNITS & INDOOR UNITS, SPLIT AIR CONDITIONING INDOOR & OUTDOOR UNIT, ELECTRIC UNIT HEATERS,
1. REPAIR THE HEATING AND COOLING SYSTEM BY INSTALLING NEW VRF DUCT-FREE HEAT PUMP OUTDOOR
M-3
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
EQUIPMENT SCHEDULES - 1
QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O NQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM QTYITEM D E S C R I P T I O N
E Q U I P M E N T S C H E D U L E S - 1
THE CONTRACT DOCUMENT REQUIRMENTS.
SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR
NOTE : NOTE :
HPO
SAFETIES & OPERATING ACCESSORIES. ETL LISTED. 3 YEARS WARRANTY.
SENSOR FOR A SAFE AND TROUBLE FREE OPERATION AND ALL NECESSARY
AT LOW AMBIENT CONDITIONS, MULTI CONNECTION PIPING KIT, ALL NECESSARY
ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES
REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID VALVES,
OVERLOAD PROTECTION, OVER CURRENT RELAY, R-410A REFRIGERANT CHARGE,
WITH ELECTRONIC EXPANSION VALVES, HIGH PRESSURE SWITCHES, INVERTER
& HEATING REQUIREMENTS, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE
CAPABLE OF CHANGING SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING
HEATING EVEN DURING DEFROST OPERATIONS,ELECTRONICALLY CONTROLLED AND
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS
ELECTRICAL RATING
COMPRESSOR
HEATING CAPACITY
COOLING CAPACITY
HPO
ERV
AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
CONTROLLER, WALL MOUNTED WIRE CO2 SENSOR, HANGING VIBRATION ISOLATORS
MERV OF 13 WHEN TESTED IAW ASHRAE STANDARD 52.2), WALL MOUNTED WIRE
DAMPER, FILTERS (PRE FILTER WITH A MERV OF 8 AND FINAL FILTER WITH A
FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT. BYPASS MODE WITH
STREAM AND MOTORIZED DAMPER ON EXHAUST AIR STREAM. DIRECT-EXPANSION
3-SPEED EXHAUST FAN, EQUIPPED WITH MOTORIZED DAMPER ON OUTDOOR AIR
FACTORY ASSEMBLED, INSTALLATION FLEXIBILITY, 3-SPEED SUPPLY FAN AND
ELECTRIC POWER INPUT
LOW
MEDIUM
HIGH
FAN CAPACITY
HEATING CAPACITY
MFR. LG MODEL NO. ARUM072BTE5 OR APPROVED EQUAL.
208 VOLTS, 3 PH, 60 Hz
: 82.1 AMP MCA / 110 AMP MOP
: 3 / INVERTER DC SCROLL
: 87,000 W (297,000 BTU/HR)
: 77,300 W (264,000 BTU/HR)
208 VOLTS, 3 PH, 60 Hz
: 22.6 AMP MCA / 35 AMP MOP
: 1 / INVERTER DC SCROLL
: 23,730 W (81,000 BTU/HR)
: 21,100 W (72,000 BTU/HR)
HP
MFR. LG MODEL NO. ARNU093TRC4 OR APPROVED EQUAL.
HP
MFR. LG MODEL NO. ARNU123TRC4 OR APPROVED EQUAL.
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WALL MOUNTED WIRE CONTROLLER, WIRELESS REMOTE CONTROLLER, AND ALL
MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON CHANGES,
CONDENSATE PUMP SYSTEM, AUTOMATICALLY SWITCHES TO COOLING OR HEATING
AIR LOUVERS FOR 4-WAY DISCHARGE, CLEANABLE FILTERS, BUILT-IN
BLDC INVERTER MOTOR, TURBO FAN, TOTAL VIRUS FILTER, ADJUSTABLE 2x2
DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
HP
HP
OAU OUTSIDE AIR SUPPLY UNIT
: 0.18 kW, 208 V, 1 PH, 60 Hz
: 708/477/477 CFM
: 13,510 W (46,115 BTU/HR)
: 14,090 W (48,100 BTU/HR)
ARNU483B8Z4 OR APPROVED EQUAL.MFR. LG MODEL NO.
3 YEARS WARRANTY.
ACCESS DOOR, AND ALL NECESSARY SAFETIES & OPERATING ACCESSORIES.
LIFT/PUMP, CONDENSATE DRAIN PAN, 7-DAY PROGRAMMABLE CONTROLLER,
FACTORY MOUNTED RETURN AIR & DISCHARGE AIR THERMISTOR. CONDENSATE
AND LOW RPM PROTECTION. MERV 13 FILTER MODULES W/PLENUMS AVAILABLE.
ANTI-FUNGAL TREATMENT. THE FAN MOTOR INCLUDES THERMAL, OVERCURRENT
MOTOR, RETURN AIR IS FILTERED WITH A REMOVABLE, WASHABLE FILTER WITH
FACTORY ASSEMBLED, COATED METAL CASE WITH HANGER BRACKETS, BLDC FAN
: 0.48 Kw, 208 V, 1 PH, 60 Hz
: 482 CFM @ 0.28 WG.ESP.
: 588 CFM @ 0.40 WG.ESP.
: 588 CFM @ 0.60 WG.ESP.
: 11,720 W (39,990 BTU/HR)
: 9,120 W (31,120 BTU/HR)
SAFETIES & OPERATING ACCESSORIES. ETL LISTED. 3 YEARS WARRANTY.
SENSOR FOR A SAFE AND TROUBLE FREE OPERATION AND ALL NECESSARY
AT LOW AMBIENT CONDITIONS, MULTI CONNECTION PIPING KIT, ALL NECESSARY
ADVANCED PROPORTIONAL INTEGRAL DERIVATIVE (PID) CONTROL TO OPERATES
REFRIGERANT SHUTOFF VALVES, VIBRATION ISOLATORS, SOLENOID VALVES,
OVERLOAD PROTECTION, OVER CURRENT RELAY, R-410A REFRIGERANT CHARGE,
WITH ELECTRONIC EXPANSION VALVES, HIGH PRESSURE SWITCHES, INVERTER
& HEATING REQUIREMENTS, WEATHER-PROOF, INVERTER COMPRESSOR, COMPLETE
CAPABLE OF CHANGING SPEED LINEARY TO FOLLOW THE VARIATION IN COOLING
HEATING EVEN DURING DEFROST OPERATIONS,ELECTRONICALLY CONTROLLED AND
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT CAPABLE OF CONTINOUS
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WALL MOUNTED WIRE CONTROLLER, WIRELESS REMOTE CONTROLLER, AND ALL
MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON CHANGES,
CONDENSATE PUMP SYSTEM, AUTOMATICALLY SWITCHES TO COOLING OR HEATING
AIR LOUVERS FOR 4-WAY DISCHARGE, CLEANABLE FILTERS, BUILT-IN
BLDC INVERTER MOTOR, TURBO FAN, TOTAL VIRUS FILTER, ADJUSTABLE 3x3
DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WALL MOUNTED WIRE CONTROLLER, WIRELESS REMOTE CONTROLLER, AND ALL
MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON CHANGES,
CONDENSATE PUMP SYSTEM, AUTOMATICALLY SWITCHES TO COOLING OR HEATING
AIR LOUVERS FOR 4-WAY DISCHARGE, CLEANABLE FILTERS, BUILT-IN
BLDC INVERTER MOTOR, TURBO FAN, TOTAL VIRUS FILTER, ADJUSTABLE 3x3
DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
: 0.03 kW, 208 V, 1 PH, 60 Hz
: 283/265/251 CFM
: 3,194 W (10,900 BTU/HR)
: 2,813 W (9,600 BTU/HR)
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WALL MOUNTED WIRE CONTROLLER, WIRELESS REMOTE CONTROLLER, AND ALL
MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON CHANGES,
CONDENSATE PUMP SYSTEM, AUTOMATICALLY SWITCHES TO COOLING OR HEATING
AIR LOUVERS FOR 4-WAY DISCHARGE, CLEANABLE FILTERS, BUILT-IN
BLDC INVERTER MOTOR, TURBO FAN, TOTAL VIRUS FILTER, ADJUSTABLE 2x2
DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
: 0.03 kW, 208 V, 1 PH, 60 Hz
: 307/283/247 CFM
: 3,980 W (13,600 BTU/HR)
: 3,600 W (12,300 BTU/HR)
: 0.144 kW, 208 V, 1 PH, 60 Hz
: 812/741/635 CFM
: 9,230 W (31,500 BTU/HR)
: 8,200 W (28,000 BTU/HR)
: 0.144 kW, 208 V, 1 PH, 60 Hz
: 742/671/600 CFM
: 8,000 W (27,300 BTU/HR)
: 7,090 W (24,200 BTU/HR)
MFR. LG MODEL NO. ARNU283TMA4 OR APPROVED EQUAL.
MFR. LG MODEL NO. ARNU243TNA4 OR APPROVED EQUAL.
NECESSARY SAFETIES & OPERATING ACCESSORIES. 3 YEARS WARRANTY.
FILTER, CLEANABLE FILTERS, WIRELESS REMOTE CONTROLLER AND ALL
REFRIGERATION COMPONENTS, DRAIN PUMP, CONTROL SYSTEM, TOTAL VIRUS
INDOOR UNIT, CONSISTING OF DC INVERTER COMPRESSOR, AIR-COOLED COIL,
VARIABLE REFRIGERANT FLOW HEAT PUMP OUTDOOR UNIT WITH WALL MOUNTED
AC
: 15 Amps, 208 V, 1 PH, 60 Hz
: MAX. 282 CFM
: 2,800 W (9,550 BTU/HR)
MFR. LG MODEL NO. SW11BAKWAS OR APPROVED EQUAL.
HP
: 0.144 kW, 208 V, 1 PH, 60 Hz
: 918/812/706 CFM
: 11,890 W (40,600 BTU/HR)
: 10,600 W (36,200 BTU/HR)
MFR. LG MODEL NO. ARNU363TMA4 OR APPROVED EQUAL.
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WALL MOUNTED WIRE CONTROLLER, WIRELESS REMOTE CONTROLLER, AND ALL
MODE TO MAINTAIN THE OPTIMUM ROOM TEMPERATURE DURING SEASON CHANGES,
CONDENSATE PUMP SYSTEM, AUTOMATICALLY SWITCHES TO COOLING OR HEATING
AIR LOUVERS FOR 4-WAY DISCHARGE, CLEANABLE FILTERS, BUILT-IN
BLDC INVERTER MOTOR, TURBO FAN, TOTAL VIRUS FILTER, ADJUSTABLE 3x3
DIRECT-EXPANSION FAN COIL TO MATCHED WITH HEAT PUMP OUTDOOR UNIT.
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
& CO2 SENSOR) OR APPROVED EQUAL.
MFR. LG MODEL NO. LZ-H1000N W/ PQRCVSL0 & PES-C0RV0 (CONTROLLER
MFR. LG MODEL NO. ARUM264BTE5 OR APPROVED EQUAL.
VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)
VARIABLE REFRIGERANT FLOW HEAT PUMP (OUTDOOR UNIT)
VARIABLE REFRIGERANT FLOW HEAT PUMP
VARIABLE REFRIGERANT FLOW HEAT PUMP
VARIABLE REFRIGERANT FLOW HEAT PUMP
VARIABLE REFRIGERANT FLOW HEAT PUMP
VARIABLE REFRIGERANT FLOW HEAT PUMP SPLIT AIR CONDITIONING INDOOR & OUTDOOR UNIT
ENERGY RECOVERY VENTILATOR
HP VARIABLE REFRIGERANT FLOW HEAT PUMP
NECESSARY ACCESSORIES. ETL-LISTED. 3 YEARS WARRANTY.
WIRELESS REMOTE CONTROLLER, WALL MOUNTED WIRE CONTROLLER, AND ALL
TO MAINTAIN THE ROOM TEMPERATURE DURING SEASON CHANGES, BRACKETS,
CLEANABLE FILTERS, AUTOMATICALLY SWITCHES TO COOLING OR HEATING MODE
LOUVERS FOR 1-WAY DISCHARGE, BUILT-IN CONDENSATE PUMP SYSTEM,
TURBO FAN, TOTAL VIRUS FILTER, BLDC INVERTER MOTOR, ADJUSTABLE AIR
CEILING CASSETTE MOUNTED DUCT FREE UNIT FOR COOLING AND HEATING.
AIR FLOW RATE
: 0.04 kW, 208 V, 1 PH, 60 Hz
: 353/325/290 CFM
: 3,980 W (13,600 BTU/HR)
: 3,600 W (12,300 BTU/HR)
MFR. LG MODEL NO. ARNU123TUC4 OR APPROVED EQUAL.
DWH
ELECTRICAL RATING
STORAGE CAPACITY
RECOVERY CAPACITY
QTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEMQTY D E S C R I P T I O NITEM D E S C R I P T I O NQTYITEM
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF M-4
NTS
EQUIPMENT SCHEDULES - 2
EH
ACCESSORIES. UL LISTED.
BUILT-IN ADJUSTABLE THERMOSTAT, EQUIPPED WITH MANUFACTURE STANDARD
TRANSVERSE FLOW BLOWER, NICKEL CHROMIUM ELECTRIC HEATING ELEMENT,
ACTION CIRCULATES AND HEAT RESISTANT, THERMALLY PROTECTED MOTOR AND
OVER TEMPERATURE PROTECTED BY THERMAL FUSE, QUIET FAN AND DOWN FLOW
GALVANIZED STEEL HOUSING AND WHITE COLOR POLYMERIC GRILLE FINISHED,
CUT A HOLE IN A WALL TO FLUSH MOUNTING TYPE, RCED-AIR HEATER,
ELECTRIC POWER INPUT
COOLING CAPACITY
: 3.62 Amp, 208 V, 1 PH, 60 Hz
: 2,560 BTU/HR (750 W)
MFR. BROAN MODEL NO. 192 OR APPROVED EQUAL.
EUH
AND ALL NECESSARY ACCESSORIES. UL LISTED.
HEATING ELEMENT, COMPLETE WITH BUILT-IN CONTROL REMOTE THERMOSTAT
HEAVY 18 GAUGE STEEL CASING, DIRECT DRIVE PROPELLER FAN, ELECTRIC
CEILING HUNG, HORIZONTAL DISCHARGE, ADJUSTABLE LOUVER, COMPLETE WITH
ELEC. RATING
MOTOR
HEATING CAPACITY
FAN CAPACITY
EWC
CONFORM TO ADA/ARI STANDARD 1010.
MECHANICALLY AIR COOLED WITH AIR COOLED CONDENSER & COMPRESSOR SHALL
PUSH PADS AND BUILT-IN PRESSURE REGULATOR W/BOTTLE FILLING STATION.
WALL MOUNTED TYPE, BUBBLER SHAL BE ACTIVATED BY DEPRESSING EITHER
POWER
CAPACITY
: 4.0 F.L.AMPS, 115 V, 1 PH, 60 HZ
: 30.3 LPH, 32.2°C TO 10°C.
MFR. "ELKAY" MODEL LMABF8WS, OR APPROVED EQUAL.
HRP
AND ALL NECESSARY SAFETIES AND OPERATING ACCESSORIES.
BRONZE BODY, STAINLESS STEEL IMPELLER, MECHANICAL SEAL AND MOTOR
IN-LINE CLOSED COUPLE SINGLE-STAGE, STAINLESS STEEL TYPE SHAFT,
MOTOR
CAPACITY
MFR. TACO MODEL NO. 110 SERIES 113 OR APPROVED EQUAL.
ELECTRIC WALL HEATER
ELECTRIC CEILING HEATER
WITH MANUFACTURE STANDARD ACCESSORIES. UL LISTED.
LOUVERS BUILT-IN ADJUSTABLE THERMOSTAT, WALL THERMOSTAT. EQUIPPED
PROCESS, FEATURE AUTOMATIC THERMAL CUTOUT AND RESET, ADJUSTABLE
STEEL ENCLOSURE FINISHED WITH BAKED ENAMEL ELECTROSTATIC PAINTING
DOWNFLOW CEILING RECESSED MOUNTED, TOTALLY ENCLOSED, HEAVY GAUGE
ELECTRIC POWER INPUT
HEATING CAPACITY
: 14.2 Amp, 208 V, 1 PH, 60 Hz
: 10,230 BTU/HR (3,000 W)
MFR. QMARK MODEL NO. CDF548RE OR APPROVED EQUAL.
ELECTRIC UNIT HEATER
MFR. CHROMALOX MODEL NO. LUH-04-21-34 OR APPROVED EQUAL.
MOTOR
CAPACITY
SAFETIES AND OPERATING ACCESSORIES. UL LISTED.
EXPLOSION PROOF MOTOR, SPARK RESISTANT, ROOF CURBS AND ALL NECESSARY
MOUNTING PLATE, BACKDRAFT DAMPER, BIRD-SCREEN AND DISCONNECT SWITCH,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, ALUMINUM HOUSING, REMOVABLE
MOTOR
CAPACITY
MFR. GREENHECK MODEL NO. CUE-090-VG OR APPROVED EQUAL.
MOTOR
CAPACITY
RF
RF
RF
ROOF EXHAUST FAN (FOR M.TOILET/SHOWER)
SAFETIES AND OPERATING ACCESSORIES. UL LISTED.
EXPLOSION PROOF MOTOR, SPARK RESISTANT, ROOF CURBS AND ALL NECESSARY
MOUNTING PLATE, BACKDRAFT DAMPER, BIRD-SCREEN AND DISCONNECT SWITCH,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, ALUMINUM HOUSING, REMOVABLE
ROOF EXHAUST FAN (FOR LAB)
MFR. GREENHECK MODEL NO. CUE-080-VG OR APPROVED EQUAL.
MFR. GREENHECK MODEL NO. CUBE-099 OR APPROVED EQUAL.
: 1,522 RPM
: 0.05 Bhp, 115 V, 1 PH, 60 Hz
: 141 LPS (300 CFM) AT 93 Pa SP
: 1,331 RPM
: 0.06 Bhp, 115 V, 1 PH, 60 Hz
: 198 LPS (420 CFM) AT 93 Pa SP
: 1,366 RPM
: 0.16 Bhp, 115 V, 1 PH, 60 Hz
: 370 LPS (785 CFM) AT 93 Pa SP
: 83.3 A, 208 V, 3PH, 60Hz
: 119 GALLONS (450 LITER)
: 123 GPH @ 100°F RISE
MFR. A.O. Smith MODEL NO. DVE-120-30 OR APPROVED EQUAL.
MOTOR
CAPACITY
SAFETIES AND OPERATING ACCESSORIES. UL LISTED.
EXPLOSION PROOF MOTOR, SPARK RESISTANT, ROOF CURBS AND ALL NECESSARY
MOUNTING PLATE, BACKDRAFT DAMPER, BIRD-SCREEN AND DISCONNECT SWITCH,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, ALUMINUM HOUSING, REMOVABLE
: 1,286 RPM
: 0.05 Bhp, 115 V, 1 PH, 60 Hz
: 174 LPS (370 CFM) AT 93 Pa SP
RF
ELECTRIC POWER INPUT
COOLING CAPACITY
MFR. BROAN MODEL NO. 192 OR APPROVED EQUAL.
ELECTRIC WALL HEATER
ACCESSORIES. UL LISTED.
BUILT-IN ADJUSTABLE THERMOSTAT, EQUIPPED WITH MANUFACTURE STANDARD
TRANSVERSE FLOW BLOWER, NICKEL CHROMIUM ELECTRIC HEATING ELEMENT,
ACTION CIRCULATES AND HEAT RESISTANT, THERMALLY PROTECTED MOTOR AND
OVER TEMPERATURE PROTECTED BY THERMAL FUSE, QUIET FAN AND DOWN FLOW
GALVANIZED STEEL HOUSING AND WHITE COLOR POLYMERIC GRILLE FINISHED,
CUT A HOLE IN A WALL TO FLUSH MOUNTING TYPE, RCED-AIR HEATER,
EH
: 4.1 Amp, 240 V, 1 PH, 60 Hz
: 3,413 BTU/HR (1,000 W)
ELECTRIC CEILING HEATER
WITH MANUFACTURE STANDARD ACCESSORIES. UL LISTED.
LOUVERS BUILT-IN ADJUSTABLE THERMOSTAT, WALL THERMOSTAT. EQUIPPED
PROCESS, FEATURE AUTOMATIC THERMAL CUTOUT AND RESET, ADJUSTABLE
STEEL ENCLOSURE FINISHED WITH BAKED ENAMEL ELECTROSTATIC PAINTING
DOWNFLOW CEILING RECESSED MOUNTED, TOTALLY ENCLOSED, HEAVY GAUGE
ECH
ELECTRIC POWER INPUT
HEATING CAPACITY
: 18.3 Amp, 208 V, 1 PH, 60 Hz
: 12,960 BTU/HR (3,800 W)
MFR. QMARK MODEL NO. CDF558RE OR APPROVED EQUAL.
ECH
QTYITEM D E S C R I P T I O NQTYITEM D E S C R I P T I O N
THE CONTRACT DOCUMENT REQUIRMENTS.
SHALL BE RESPONSIBLE FOR VERIFYING ACTUAL QUANTITIES BASED ON
QUANTITIES ARE SHOWN FOR ESTIMATING PURPOSE ONLY, THE CONTRACTOR
NOTE : NOTE :
E Q U I P M E N T S C H E D U L E S - 2
MFR. GREENHECK MODEL NO. CUE-090-VG OR APPROVED EQUAL.
EES
INLET WATER : 20 GPM (1.3 LPS), 32 MM
MFR. GUARDIAN MODEL G1902P, OR APPROVED EQUAL.
ELECTRIC DOMESTIC HOT WATER HEATER
DOMESTIC HOT WATER RECIRCULATION PUMP
ELECTRIC WATER COOLER
EMERGENCY EYEWASH AND SHOWER STATION
UL-LISTED.
ACCESSORIES, AND ALL NECESSARY SAFETIES AND OPERATING ACCESSORIES.
PRESSURE AND TEMPERATURE RELIEF VALVE, MANUFACTURE STANDARD CONTROL
DUTY INCOLOY ELEMENTS, ANODE RODS FOR MAXIMUM CORROSION PROTECTION,
PROTECTED BY THERMAL FUSE, ASME CODE REQUIREMENTS COMPLETE, HEAVY-
PACKAGED TYPE, FACTORY ASSEMBLED, FLOOR MOUNTED TYPE, OVER TEMP.
NECESSARY SAFETIES AND OPERATING ACCESSORIES. UL LISTED.
EXPLOSION PROOF MOTOR, EXPLOSION RESISTANT MOTOR, ROOF CURBS AND ALL
MOUNTING PLATE, BACKDRAFT DAMPER, BIRD-SCREEN AND DISCONNECT SWITCH,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, ALUMINUM HOUSING, REMOVABLE
: 1/8 HP, 115V, 1PH, 60HZ, 1750 RPM
: 0.3 LPS AT 15 FEET TDH
EES AND ALL NECESSARY SAFETIES AND OPERATING ACCESSORIES.
STANDARD Z358.1-1998 SPECIFICATIONS, FLASHING STROBE LIGHT FOR EACH
SWITCH, DISPLAYS RED BLINKING ALARM LIGHT WHEN ACTIVATED, MEET ANSI
COLD WATER, UNIT SHALL BE COMPLETELY SELF CONTAINED, SILENCING
BY PUSH HANDLE, THERMOSTATIC MIXING VALVE PRECISELY BLENDS HOT AND
EYE WASH HEAD AND SPRAY, SHOWER OPERATED BY PULL CHAIN AND EYE WASH
SHOWER HEAD CHROME PLATED BRASS YOKE ASSEMBLY WITH TWIN AREATED
COMBINATION EYEWASH AND SHOWER SAFETY STATION, 250mm DIAMETER
: 3.0 kW, 208 V, 1 Ph, 60 Hz
: 1/50 HP, 240 V, 1 Ph, 60 Hz
: 3.0 kW
: 146 LPS
RF
MOTOR
CAPACITY
SAFETIES AND OPERATING ACCESSORIES. UL LISTED.
EXPLOSION PROOF MOTOR, SPARK RESISTANT, ROOF CURBS AND ALL NECESSARY
MOUNTING PLATE, BACKDRAFT DAMPER, BIRD-SCREEN AND DISCONNECT SWITCH,
ROOF MOUNTED CENTRIFUGAL DIRECT DRIVE, ALUMINUM HOUSING, REMOVABLE
ROOF EXHAUST FAN (FOR EYE WASHER ROOM)
MFR. GREENHECK MODEL NO. CUE-070-VG OR APPROVED EQUAL.
: 1,524 RPM
: 0.02 Bhp, 115 V, 1 PH, 60 Hz
: 66 LPS (140 CFM) AT 93 Pa SP
ROOF EXHAUST FAN (FOR W.TOILET/SHOWER & JANITOR RM)
ROOF EXHAUST FAN (FOR MECH & ELEC ROOM)
1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
NEW H.V.A.C PIPING ENLARGED PLAN
SCALE = 1:50
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
HP
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
METAL PIPE TRAY (TYP.)
(TYPICAL)
ACCESS DOOR
LINE(TYP.)
DRAIN
LINES (TYP.)
LIQUID & VAPOR
LINES (TYP.)
LIQUID & VAPOR
(TYP.)
DRAIN LINE
(TYP.)
DRAIN LINEMUD AREA
FEC FEC
FEC
DN
DN
ROOM
MECH/ELEC
ROOM
COMM
STORAGE
VEST
VEST
CORRIDOR
OFFICE
ROOM
CONFERENCE
JAN 104
SHOWER
W.TOILET/
SHOWER
M.TOILET/
OFFICE
LOCKER ROOM
READY/WAITING/
LAB
ROOM
MUD
ROOM
WASHER
EYE
NEW H.V.A.C PIPING ENLARGED PLAN
NOTE :
ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.
5. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING, CONDUITS, AND ALL NECESSARY
FITTINGS, GROOVE JOINTS & MECHANICAL JOINTS. THE VRF SYSTEM SHALL BE PRESSURE TESTED & VACUUM TESTED.
ARE NOT LIMITED TO THE FOLLOWING: PUSH-ON FITTINGS, EXTRUDED FITTINGS, FLARE FITTINGS, PRESS-CONNECT
MANUFACTURER'S INSTALLATION REQUIREMENTS. THE LIST OF FITTINGS AND JOINTS THAT ARE PROHIBITED INCLUDE BUT
4. VRF SYSTEMS PIPING/TUBING SHALL HAVE ALL BRAZED CONNECTIONS THAT MEET ASME B31.5 REQUIREMENTS AND THE
3. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S SPEC BY A CERTIFIED INSTALLER.
2. REFRIGERANT PIPE SIZE & INSTALLATION SHALL BE AS PER MANUFACTURER'S RECOMMENDATION.
1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PIPEWORK PRIOR TO PIPEWORK INSTALLATION.
T T
T
T
T
T T
5,8504,370 3,800 3,880 5,200
23,100
PIPE SIZE
VAPOR LIQUID DRAINITEM NO.
25 mm
VAPOR LIQUID DRAINITEM NO.
9.52 mm
25 mm
15.88 mm
OAU
HPO
15.88 mm28.58 mm
HP
HP
HP
HP
HP
HP
ERV
HPO
15.88 mm 9.52 mm
12.7 mm 6.35 mm 25 mm
25 mm25 mm
25 mm
25 mm
25 mm
15.88 mm 9.52 mm
9.52 mm
9.52 mm15.88 mm
15.88 mm
12.7 mm 6.35 mm
6.35 mm 12.7 mm
6.35 mm 12.7 mm
HPO
OUTDOOR UNIT
DUCT-FREE HEAT PUMP
PIPE CHASE (TYP.)
EUH
UNIT HEATER
ELECTRIC
HPO
OUTDOOR UNIT
DUCT-FREE HEAT PUMP
ERV
VENTILATOR UNIT
ENERGY RECOVERY
OAU
SUPPLY UNIT
OUTSIDE AIR
AC
INDOOR UNIT
SPLIT A/C
AC
OUTDOOR UNIT
SPLIT A/C
DETAIL SEE 2 OF SHEET M-10
NEW CONC. PAD FOR
HP
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
HP
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
HP
CEILING MOUNTED, 1-WAY
DUCT-FREE HEAT PUMP
HP
(TYP OF 2)
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
HP
HP
(TYP OF 3)
CEILING MOUNTED, 4-WAY
DUCT-FREE HEAT PUMP
HP
HP
EH
(TYP OF 2)
ELECTRIC WALL HEATER
EH
EH
ELECTRIC WALL HEATER
ECH
CEILING HEATER
ELECTRIC
ECH
CEILING HEATER
ELECTRIC
LINES (TYP.)
LIQUID & VAPOR
(TYPICAL)
SEE DETAIL 4 OF SHEET M-10
CONNECTOR VIPER MANUFACTURER
REFRIGERANT PIPE Y-BRANCH
WALL & ABOVE CEILING)
CONCEALED IN THE
WIRING SHALL BE
CONDUIT (ALL CONTROL
WIRING AND RECESSED
WITH JUNCTION BOX,
RECESSED CONTROLLER
LINES (TYP.)
LIQUID & VAPOR
(TYP.)
DRAIN LINE
LINES (TYP.)
LIQUID & VAPOR
LINES (TYP.)
LIQUID & VAPOR
LINES (TYP.)
LIQUID & VAPOR
M5
M-5
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
1 NEW H.V.A.C ENLARGED PLAN
NEW H.V.A.C ENLARGED PLAN
SCALE = 1:50
AIR DUCT APPROVED (TYPICAL)
BARRIER EXTERIOR COVER UL 181
INCOMBUSTIBLE POLYETHYLENE VAPOR
NE 1000 CORE + POLY INSULATION +
PE POLY ACOUSTICAL FLEXIBLE DUCT
CO2 SENSOR
CONTROLLER
METAL BIRD SCREEN (TYP OF 2)
HOODED WALL CAP WITH STS
STAINLESS STEEL SQUARE SHAPE
H.V.A.C SHUT-OFF SWITCH"
LABELLED AS "EMERGENCY
SWITCH W/ CLEAR FLIP-COVER
HVAC EMERGENCY SHUT-OFF
RF
ROOF EXHAUST FAN
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
MUD AREA
FEC FEC
FEC
DN
DN
ROOM
MECH/ELEC
ROOM
COMM
STORAGE
VEST
VEST
CORRIDOR
OFFICE
ROOM
CONFERENCE
JAN
SHOWER
W.TOILET/
SHOWER
M.TOILET/
OFFICE
LOCKER ROOM
READY/WAITING/
LAB
ROOM
MUD
ROOM
WASHER
EYE
MD
VD
VD
VD
VD
VD
VD
VD
VD
MD BDD
VDVD
VDVDVD
VDVDVD
VD
VDVDVD
VD
VD
VD
VD
VD
VD
VD
600Wx300H O.A.I.L
O.A:300 CFM
W x
H
O
A I
L
O
A
C F
M
5,8504,370 3,800 3,880 5,200
23,100
OAU
SUPPLY UNIT
OUTSIDE AIR
ERV
VENTILATOR UNIT
ENERGY RECOVERY
150 150
150150
200200
150 150
200 200
150150
150150
150150
RF
ROOF EXHAUST FAN
RF
ROOF EXHAUST FAN
RF
ROOF EXHAUST FAN
RF
EXHAUST FAN
ROOF
(TYP OF 11)
RETURN DIFFUSER
ROUND PAN
0 300
NOTE :
CONDUITS, AND ALL NECESSARY ACCESSORIES TO INSTALL THE CONTROLS SYSTEM.
4. THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES, RELAYS, WIRING,
3. PROVIDE DIFFUSERS AND GRILLE FRAMES COMPATIBLE WITH ARCH. CEILING TYPES.
SPEC BY A CERTIFIED INSTALLER.
2. INSTALLATION OF THE HVAC SYSTEM SHALL BE IN COMPLIANCE WITH MANUFACTURER'S
INSTALLATION.
1. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DUCTWORK PRIOR TO PIPEWORK
E.AO.A
(TYP OF 11)
SUPPLY DIFFUSER
ROUND PAN
MOTORIZED DAMPER
MODUTROL MOTOR W/
MD
MOTORIZED DAMPER
MODUTROL MOTOR W/
C C
400x250
23 LPS
150 NCD
29 LPS
150 NCD
11 LPS
150 NCD
30 LPS
150 NCD 30 LPS
150 NCD
108 LPS
200x200 EG
33 LPS
150x150 EG
165 LPS
250x250 EG
33 LPS
150x150 EG
23 LPS
150 NCD
334 LPS
350x350 SR
29 LPS
150 NCD
29 LPS
150 NCD
29 LPS
150 NCD
23 LPS
150 NCD
28 LPS
150 NCD
28 LPS
150 NCD
28 LPS
150 NCD
11 LPS
150 NCD
11 LPS
150 NCD
11 LPS
150 NCD
23 LPS
150 NCD
30 LPS
150 NCD
30 LPS
150 NCD
28 LPS
150 NCD
30 LPS
150 NCD
30 LPS
150 NCD
250x200
150x100
150x100 150x100
250x200
33 LPS
150x150 EG
M6
M-6
50mm WATER METER
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
DWH
HOT WATER HEATER
ELECTRIC DOMESTIC
3-WAY MIXING VALVE
THERMOSTATIC
A x 2
WALL HYDRANT
20mm NON-FREEZE
(TYPICAL)
ISOLATION VALVE
ENLARGED PARTIAL PLAN
NEW DOMESTIC WATER PIPING
MUD AREA
ROOM
MECH/ELEC
ROOM
COMM
STORAGE
VEST
VEST
CORRIDOR
OFFICE
ROOM
CONFERENCE
JAN
SHOWER
W.TOILET/
SHOWER
M.TOILET/
OFFICE
LAB
ROOM
MUD
5,8504,370 3,800 3,880 5,200
23,100
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
SCALE = 1:50
NEW DOMESTIC WATER PIPING ENLARGED PARTIAL PLAN
HB
NOTE ON INSTALLATION OF PIPE INSULATION :
WHEN THE INSTALLATION OF THE PIPE INSULATION IS COMPLETED.
4. THE CONTRACTOR SHALL INVITE THE MECHANICAL ENGINEER FOR QUALITY INSPECTION
OF 50 WHEN TESTED IN ACCORDANCE WITH ASTM E84.
HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAX. SMOKE DEVELOPED INDEX
3. LAGGING ADHESIVES SHALL BE NONFLAMMABLE AND FIRERESISTANT AND SHALL
2. INSULATION MATERIALS RECOGNIZED UNDER UL94 AND LISTED IN FM APP GUIDE.
AND SHALL COMPLY WITH ASTM C534/C534M, GRADE 1, TYPE I OR II.
1. INSULATION MATERIALS SHALL CONFORM TO TABLE1 OF OMA SPEC 23 07 00,
NOTE :
VALVES AND WATER HAMMER ARRESTORS.
3. PROVIDE CEILING / WALL ACCESS PANEL FOR ISOLATION
PIPING) PRIOR TO PLUMBING PIPING INSTALLATION.
PIPING (HOT & COLD WATER PIPING, SEWER AND VENT
2. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR PLUMBING
1. ALL PIPE LINES SHALL BE COPPER TUBE.
P-5a
P-10
EES
SHOWER STATION
EMERGENCY EYEWASH/
EWC
WATER COOLER
ELECTRIC
LOCKER ROOM
READY/WAITING/
P-7
P-5
P-5
P-5
P-5
P-5
P-1
P-1 P-1
P-1
P-8
P-3
P-3
P-3
P-4P-4
SEE CIVIL DRAWING
NEW DOMESTIC WATER MAIN PIPE
CONN. TO UNDERGROUND
50mm DOMESTIC WATER LINE
HRP
RECIRCULATION PUMP
DOMESTIC HOT WATER
TO F.D
VALVE
REDUCING
PRESSURE
PRIMER
TRAP
BACK-FLOW PREVENTER
20,40,50
B
A WATER HAMMER ARRESTER (TYP.)
A
A
A
B
A
A
B
WALL HYDRANT
20mm NON-FREEZE
B
ARRESTER (TYP.)
WATER HAMMER
FEC FEC
FEC
DN
DN
(TYP OF 8)
HOSE BIBB
NON-FREEZE
20mm
VALVE (TYP.)
BALANCING
VALVE (TYP.)
BALANCING
32,32,20
25 32
25 3225
40,32,20
20,20,32
20,20,32
40,32,2050,40,2050,40,20
20,20,32
15 15
20,32,50
20,20,32
40,32,20
40,32,20
20,20,20
25,20,20
M7
M-7
ROOM
WASHER
EYE
EWC
WATER COOLER
ELECTRIC
PRIMER
TRAP
FROM
50 FD
SEE CIVIL DRAWING
NEW SEWER MAIN PIPE
CONN. TO UNDERGROUND
100mm SEWER LINE
32 32
EES
SHOWER STATION
EMERGENCY EYEWASH/
1:50
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
ENLARGED PARTIAL PLAN
NEW SEWER & VENT PIPING
GRAPHIC SCALE
SCALE: 1:50
0 1000 2000
MUD AREA
ROOM
MECH/ELEC
ROOM
COMM
STORAGE
VEST
VEST
CORRIDOR
OFFICE
ROOM
CONFERENCE
JAN
SHOWER
W.TOILET/
SHOWER
M.TOILET/
OFFICE
LOCKER ROOM
READY/WAITING/
LAB
ROOM
MUD
5,8504,370 3,800 3,880 5,200
23,100
SCALE = 1:50
NEW SEWER & VENT PIPING ENLARGED PARTIAL PLAN
GLOBE VALVE & HB
WITH 25mm LOCKABLE
50mm DRAIN PIPE
P-10
P-5a
PLUMBING FIXTURES SCHEDULE
PLUMBING FIXTURES QTY
COLD HOT TRAP VENT
REMARKSSYMBOL
P-1
P-5
LOCAL PIPE CONNECTION
P-3 3
1515 401
2SHOWERP-4 80 40
KSAJ-100 OR APPROVED EQUAL
SHALL BE KOSDO INC. MODEL
1P-7 KITCHEN SINK STAINLESS STEEL1515 50 32
-15 50WATER CLOSET (F.T) 100 3.8 LITERS/FLUSH
50 5020 -URINAL AUTOMATIC SENSOR
1P-5a
W/ AERATOR
COUNTER TOP TYPE,
LAVATORY 1515 50 32
LAVATORY 1515 50 32 MAX.0.5 GPM @60 PSI
1515 80 40P-8 1SERVICE SINK
W/ INTEGRAL BACK
STAINLESS STEEL,
P-10 LAUNDRY SINK
GROUND FL. MUD ROOM
DOUBLE BOWL, FOR
FEC FEC
FEC
DN
DN
P-7
P-8P-5
P-5
P-5
P-5
P-5
P-4 P-4
P-3
P-3
P-3
P-1
P-1
P-1
P-1
B
C
A
REMARKS
RATING
FU
QTYSYMBOL
P.D.I
1-11
12-32 20
33-60 25
WATER HAMMER ARRESTER SCHEDULE
CONN.
PIPE
INSTRUCTIONS.
PER PDI-WH 201 AND MANUFACTURER'S
2. SIZE AND LOCATE WATER HAMMER ARRESTORS
COMPRESSION CHAMBER W/EXPANSION BELLOWS.
1. COPPER CONSTRUCTION PRESSURIZED
80 VTR
80 VTR
100 FCO
50 FCO
50 FCO 50 FCO
100 WCO
50 FD 50 FD
80 SD
SD
TROUGH
50 FLOOR
100 100
50 50
32 32
M8
M-8
ROOM
WASHER
EYE
100 FCO
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
OFF
C
OL
120 VAC
NOTE :
LADDER DIAGRAM
SWITCH
"H-O-A"
T
SWITCH
"ON-OFF"
OFF
120 VAC
T
C
OL
ON FAN MOTOR
UNIT HEATER
LADDER DIAGRAM
THE ROOM TEMPERATURE AT 10°C FOR FREEZING PROTECTION.
SUPPLY FAN OPERATION IN AN "ON-OFF" SEQUENCE TO MAINTAIN
2. UNIT MOUNTED THERMOSTAT T CONTROLS THE UNIT HEATER
HEATER SUPPLY FAN CONTINUOUSLY UNTIL MANUALLY STOPPED.
1. "ON/OFF" SELECTOR SWITCH TO "ON" POSITION RUNS THE UNIT
ELECTRIC UNIT HEATER
NOT TO SCALE
EXHAUST FAN CONTROL
NOT TO SCALE
LADDER DIAGRAM
TO INSTALL THE CONTROLS SYSTEM.
RELAYS, WIRING, CONDUITS, AND ALL NECESSARY ACCESSORIES
THE CONTROLS CONTRACTOR SHALL PROVIDE ALL THE SWITCHES,
EXHAUST FAN CONTROL
NOT TO SCALE
ENERGIZES THE EXHAUST FAN.
2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION
THE EXHAUST FAN CONTINUOUSLY UNTIL MANUALLY STOPPED.
1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS
EXHAUST FAN
HAND
AUTO
SWITCH
"H-O-A"
MD
DAMPER
MOTORIZED
OL
120 VAC
AUTO
HAND
C
MD
OFF
TF
C
TF
FAN
EXHAUST
INTERRUPTION
CLOSED ON POWER
WITH SPRING RETURN,
MOTORIZED LOUVER
OUTSIDE AIR
WATER LINE
CW MAKE-UP
PTHW
VALVE (TYP)
VACUUM RELIEF
(TYP)
THERMOMETER
THERMOSTAT
IMMERSION
MIXING VALVE
THERMOSTATIC
HWTR
HWTRR
AQUASTAT
A
RELIEF VALVE
TEMPERATURE
PRESSURE/
60°C
DOMESTIC WATER HEATER SECTION
DOMESTIC HOT WATER RECIRCULATION PUMP SECTION
NOT TO SCALE
A AQUASTAT
DESCRIPTION OF CONTROL COMPONENTS
SYMBOL D E S C R I P T I O N
PTHW
PIPE MOUNTED THERMOSTAT
COMPLETE WITH WELL ADAPTER AND TUBE OF HEAT CONDUCTIVE COMPOUND AND MANUAL RESET.
IMMERSION TYPE, SENSING ELEMENT ACTUATES ENCLOSED SNAP ACTING SWITCH BREAKS ON TEMPERATURE RISE, SET-POINT
TEMPERATURE RANGE
INPUT VOLTAGE
: 93.30°C (200°F)
: 43.30°C-143.30°C (110°F-290°F)
: 120 VAC
PIPE MOUNTED WITH SPDT SWITCH BREAKS CONTACT ON TEMPERATURE RISE, MAKES CONTACT ON TEMPERATURE DROP.
: 38°C TO 49°C (100°F TO 120°F)
: 120 VAC
SET POINT
INPUT VOLTAGE
49°C
WATER RETURN TEMP. DROPS TO 37°C (100°F) OR LOWER.
DOMESTIC HOT WATER RECIRCULATING PUMP WHEN DOMESTIC HOT
RETURN TEMPERATURE REACHES 49°C (120°F) AND RUNS THE
WATER RECIRCULATING PUMP WHEN THE DOMESTIC HOT WATER
3. PIPE MOUNTED THERMOSTAT PTHW STOPS THE DOMESTIC HOT
ENERGIZES THE DOMESTIC HOT WATER RECIRCULATION PUMP.
2. "HAND-OFF-AUTO" SELECTOR SWITCH TO "AUTO" POSITION
UNTIL MANUALLY STOPPED.
THE DOMESTIC HOT WATER RECIRCULATING PUMP CONTINUOUSLY
1. "HAND-OFF-AUTO" SELECTOR SWITCH TO "HAND" POSITION RUNS
HOT WATER SUPPLY TEMP. TO THE FIXTURES AT 49°C (120°F).
3. THERMOSTATIC 3-WAY MIXING VALVE MODULATES TO MAINTAIN
DOMESTIC HOT WATER SUPPLY TEMPERATURE AT 60°C (140°F).
OPERATION IN AN "ON-OFF" SEQUENCE TO MAINTAIN THE
2. WHEN ENERGIZED, AQUASTAT A CONTROLS THE BURNER
OF THE DOMESTIC WATER HEATER.
1. "ON-OFF" SWITCH TO "ON" POSITION ENERGIZES THE BURNER
LADDER DIAGRAM
120 VAC
A
WATER HEATER
DOMESTIC HOT
OFF
AUTO
HAND
C
OL
PUMP
RECIRCULATION
HOT WATER
DOMESTICTI
CONTROL
PRIMARY
DOMESTIC WATER HEATER AND DOMESTIC HOT WATER RECIRCULATION PUMP
MECH. CONTROL DIAGRAMS
HOT WATER HEATER
ELEC. DOMESTIC
DWH
M
M
RECIRCULATION PUMP
DOMESTIC HOT WATER
HRP
EUH
UNIT HEATER
ELECTRIC
M-9
EXHAUST FAN
ROOF
RF
EXHAUST FAN
WHEN THE EXHAUST FAN IS TURNED-OFF.
EXHAUST FAN IS OPERATING AND SHALL RETURN TO FULLY CLOSED
2. THE OUTSIDE AIR MOTORIZED LOUVER SHALL OPEN WHEN THE
FAN WHEN THE ROOM TEMPERATURE DROPS TO 26°C.
TEMPERATURE REACHES 29°C OR HIGHER AND STOPS THE EXHAUST
1. ROOM THERMOSTAT TF RUNS THE EXHAUST FAN WHEN THE ROOM
EXHAUST FAN CONTROL
NOT TO SCALE
MD TF
M
RF
5 EXHAUST FAN
ROOFRF
2 EXHAUST FAN
ROOF
ELECTRICAL WORK
W/TIMER BY
LIGHT SWITCH
"ON-OFF"
LADDER DIAGRAM
OL
120 VAC
AUTO
C
MD
OFF
C
FAN
EXHAUST
R1
DAMPER (OAU-1)
MOTORIZED
HAND
LIGHT SWITCH
R1
DAMPER (OAU-1)
MOTORIZED
OUTSIDE AIR
REPAIR BUILDING
EXHAUST FAN (RF-5) IS OPERATING.
INTERLOCKED WITH EXHAUST FAN (RF-5) AND RUNS WHEN THE
EXHAUSTED. OUTSIDE AIR SUPPLY UNIT (OAU-1) IS ELECTRICALLY
SUPPLY UNIT MUST ENTER THE LAB TO REPLACE THE AIR BEING
2. WHEN A EXHAUST FAN IS ENERGIZED, CONDITIONED OUTSIDE AIR
POSITION.
1. EXHAUST FAN (RF-5) SHALL RUN WHEN LIGHT SWITCH IN IN "ON"
MECH. DETAILS - 1
FIN. GRADE
150 150
SECTION
PLAN
N F S M
150150ACTUAL EQUIPMENT SIZE
AT EXPOSED EDGES
20mm CHAMFERS#4 @300 O.C.
50 CLR
CONC. PAD
150 150 150150ACTUAL EQUIPMENT SIZE
A C
T U
A L
E Q
U I
P M
E N
T
S I
Z E
EQUIPMENT UNIT
GRAVEL BASE
150mm THK.
1 INDOOR HEAT PUMP UNIT INSTALLATION DETAIL
SECTION
REMOTE CONTROL
FULL BOX
ELECTRICAL CONC. BOX
CEILING
ROOM
(CEILING CASETTE 4-WAY TYPE)
INDOOR HEAT PUMP
ENLARGED SECTION
ROOM
R.L/R.G
DRAIN PIPE
CEILING
PUMP
HEAT
(TYP)
HANGERMIN 300
FOR SERVICE
ACCESS DOOR
600x600 CEILING
CABLE
POWER
CEILING
R.L/R.G
DRAIN PIPE
(CEILING CASETTE 4-WAY TYPE)
INDOOR HEAT PUMP
MAX.700
SEE
Y JOINT DETAIL
LIQUID PIPE 6.35A/ 9.52A
TAPE
Y-JOINT
INLET
INSULATION REFRIGERANT LIQUID/ GAS PIPE
COVER
OUTLET
SECTION
GAS PIPE 12.7/ 15.88
PIPE INSULATION:19T
EPDM
VCTF-SB1.25x2C
CABLE LINE
CONCRETE PAD DETAIL
FILTER DRIER
LIQUID LINE
CONDENSATE DRAIN
DRAIN PUMP
CONDENSATE
THERMOSTAT
SWITCH
DISCONNECT
FUSED
VAPOR LINE
(OUTDOOR UNIT)
DUCT-FREE HEAT PUMP
(INDOOR UNIT)
DUCT-FREE HEAT PUMP
SWITCH
FUSED DISCONNECT
WEATHERPROOF
ISOLATORS
SPRING
HANGER ROD
HANGER PLATE
VENTILATOR
ENERGY RECOVERY
E.R.V EQUIPMENT INSTALLATION
TYPICAL REFRIGERANT PIPING DIAGRAM3
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
DRAIN HOSE
HANGER (TYP.)1/50-1/100 SLOPE
NOTE :
6" (150mm) LARGER THAN UNIT SIZE AND
ALL EQUIPMENT CONC PAD SIZE SHALL BE
FINAL PAD SIZE SHALL BE CORDINATED
WITH MANUFACTURER.
M-10
MECH. DETAILS - 2
MECHANICAL
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG YONGSAN-CASEY
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
A
B C D
E F G H
SHEET OF
MALE PIECE-SNAP LOCK
50mm
50mm
TACK WELD
EQUIPMENT CASING
GASKET MIN 8 THK
o
"BOTTOMS"
SPACING BETWEEN
APPROXIMATE 50
100 O.C (OR METAL SCREW)
BOLT & NUT 8 x 25 LG @
(TYP)
GALV STEEL SHT
U-STRAP 20 GA
HEAD @ 100 O.C
RIVET, SOLID FLAT
WITH UL 214)
FABRIC (COMPLY
FIBROUS GLASS
PRE-INSULATED
(TYP)
40 x 40 x 6
STEEL ANGLE
MIN. 100
3 FLEXIBLE CONNECTION AND ANGLE FLANGE CONNECTION
UNDER HOOD
SWITCH MOUNTED
DISCONNECT
WEATHERPROOF
EXHAUST DUCT
ELECTRICAL CONDUIT
THE EXHAUST FAN
DAMPER HARDWIRED TO
LOW LEAKAGE MOTORIZED
(REFER TO SPECIFICATIONS)
ROOF EXHAUST FAN
RECOMMENDATIONS)
FAN MANUFACTURER'S
ROOF OPENING (REFER TO
CONCRETE DECK
AS REQUIRED TO SUIT
DUCT C/W TRANSITION
CW
STRAINER
GLOBE VALVE
TO SYSTEM
REDUCER
COCK (TYP. OF 2)
6 SHUT-OFF
PRESSURE REDUCING VALVE
(TYP. OF 2)
PRESSURE GAGE
REDUCING TEE (TYP.)
UNION (TYP.)
(TYP. OF 3)
GATE VALVE
TYPE BACK-FLOW PREVENTER
REDUCED PRESSURE PRINCIPLE
METAL GAGE
DOOR BACKFRAME
LOCKS
NO.
HINGES
NO.
(mm)
DOOR SIZE
300x300
400x500
600x600 3
2 1-S
2-S
2-S
AND LESS
STATIC
50mm W.G.
(REQ'D 2)
FASTENER
DOOR
GASKET
DUCT
FASTENER
APPROVED
FASTENER
DOOR
GASKET DUCT
S = SIDE OPPOSITE HINGESNOTE :
HINGE
OR PIANO
BUTT HINGE
HINGE POS. 2
HINGE POS. 3
TYPE 2
TYPE 1
ROOF MOUNTED EXHAUST FAN CEILING ACCESS DOOR
BACK FLOW PREVENTER & PRESSURE REDUCING STATION
CMU WALL
WALL CLAMP
NYLON SEAT
REMOVABLE
25 NPT
CEMENT FILL
BRASS CASING
NPT
CONNECTION
20 HOSE
INSULATION
EXTERIOR
BRASS BOX
NICKEL
130 x 170
WALL OPENING
WALL THICKNESS
KEY HANDLE
ELBOW
90° UNION
SWEAT 50 COPPER
20 NPT INLET
WALL HYDRANT4 UNIT HEATER SUPPORT DETAIL
PLAN VIEW ELEVATION
UNIT HEATER
EXPANSION BOLT
CMU WALL
BOLT OR WELD ANGLE CONNECTIONS
NOTE:
WITH 6mm STEEL BACKUP PLATE
ON GYP WALL, THROUGH BOLT
WHERE UNIT HEATERS ARE LOCATED
EXPANSION BOLT TO CMU WALL.
CMU WALLUNIT HEATER
CEILING
15 DIA RODS
(TYPICAL)
DOUBLE NUT
SHOWN ON SCHEDULE
MOUNTING HEIGHT AS
50x50x6 's
NOTE :
FROM THE FLOOR (OR PAD)
HEATER SHALL BE DROPPED UP MIN.ƒ" CLEARANCE
•" HOSE BIBB
SERVICE LINE
COLD WATER
AND PRESSURE RELIEF VALVE
COMBINATION TEMPERATURE
MAXIMUM 2" NIPPLE
SUPPLY LINE
HOT WATER
VACUUM BREAKER
ADAPTER (TYP)
WATER HEATER
ELECTRIC
DRAIN
TO NEAREST
RELIEF DRAIN
7 8ELECTRIC WATER HEATER (TYP.)
SPRING
FOOT PEDAL
CHAIN
HAND CONTROL
EYEWASH
SIGN FURNISHED
HAND CONTROL
SHOWER
32mm SUPPLY
32mm WASTE
BREAKER
PRESSURE VACUUM
H…