A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
SCOPE OF WORKS
LEGEND, GENERAL NOTES AND
E-1
ELECTRICAL
SCOPE OF WORK
1.
4.
2.
5.
3.
7.
8.
6.
A. CONSTRUCTION ( L )
W/COVER PLATES ASSOCIATED WIRING & CONDUIT.
INSTALL NEW WATTHOUR METER, PANELBOARDS, RECEPTACLES
TERMINAL BLOCKS, EQUIPMENT RACK AND ASSOCIATED WIRE & CONDUIT.
TERMINAL BOARD, TELEPHONE/DATA OUTLETS W/COVER PLATES,
INSTALL NEW TELECOMMUNICATION SYSTEM INCLUDING TELEPHONE
ASSOCIATED WIRING AND CONDUIT.
INSTALL CATV DISTRIBUTION CANBINET, PULLBOXES, CATV OUTLETS &
SYSTEMS.
BOXES, CONTROL/POWER WIRES AND CONDUIT FOR MECHANICAL
INSTALL NEW SAFETY SWTICHES, MOTOR CONTROLLERS, JUNCTION
CONTACTORS, PHOTOCELL, WIRES AND CONDUIT.
TOGGLE SWITCHES, 3 WAY SWITCHES, DIMMING SWITCH, LIGHTING
INSTALL NEW INTERIOR/ EXTRIOR LIGHTING FIXTURES, EXIT LIGHTS,
ACCESSORIES INCLUDING TELECOMMUNICATION MANHOLE.
INSTALL NEW EXTERIOR UNDERGROUND TELECOMMUNICATION LINE AND
AND ASSOCIATED WIRING AND CONDUIT.
(WATTAGE AS REQ'D) DEVICE, FIRE ALARM BUILDING TRANSMITTER
SIGNAL STROBES (15 OR 75 CANDELA), MICROPHONE, SPEAKER
& HEAT DETECTORS, ADDRESSABLE MODULE, ANTENNA, VISUAL/
NOTIFICATION SYSTEM PANEL, MANUAL PULL STATION, SMOKE
INSTALL NEW ADDRESSABLE FIRE ALARM CONTROL AND MASS
INSTALL NEW EXTERIOR UNDERGROUND POWER DISTIBUTION LINE.
GENERAL NOTES
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
350mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
3.
4.
6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION
SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE
7.
5.
CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT
THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING
TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.
DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT
F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING
12.
13.
14.
10.
11.
8.
9.
15.
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
SAFETY SWITCH
C CONTROL CIRCUIT
3-WAY SWITCH, 15A-125V
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
CABNET TYPE, RATED WATT ON LTG SCHEDULE
LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER
ON LTG SCHEDULE, WET LOCATION
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
FAULT PROTECTED TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
FIXTURE A MINIMUM DISTANCE OF 458mm.
FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING
FMCP
FTR
AUXILIARY
DESCRIPTIONSYMBOL
STROBES
WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL
BUILDING TRANSMITTER UNIT FOR FIRE ALARM
SYSTEM
L
WP
FAULT PROTECTED TYPE, WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDED
TYPE
SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING
L
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
W/EMERGENCY UNIT
TYPE
QUADPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
L
L
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
16.
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
THE MANUFACTURER AND MODEL OF NEW BUILDING TRANSMITTER EQUIPMENT
IN THE CENTRAL FIRE DEPARTMENT.
THE EQUIPMENT SHOULD BE TESTED WITH THE RECEIVING SYSTEM(D21)
SHALL BE COORDINATED WITH THE CENTRAL FIRE DEPARTMENT.
RECEPTACLE
AND WALL
WIRING CONCEALED OR EXPOSED IN/ON THE CEILING
CEILING OR CONCEALED IN NEW WALL.
ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS
3S
TYPE WITH PLUG
SINGLE RECEPTACLE, 2P-3W-20A-125/250V, GROUNDING
L
FIRE ALARM & MNSCONTROL PANEL
F
F/M
FIRE ALARM & MNS CIRCUIT
T LAN/TEL LINE
L
ON LTG SCHEDULE, FOR INDIRECT LIGHT
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
REQUIRED
DIMMING CONTROL SWITCH, 15A-125V, LED, WIRING AS
EPS
DIMS
EXPLOSION PROOF
SINGLE POLE TOGGLE SWITCH, 15A-125V,
REPAIR BUILDING
L
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY UNIT
E
FOR ABBREVIATION, LEGEND, GENERAL NOTES1.
& SCOPE OF WORK,
NOTES
SEE SHEET NO. E-1.
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
DN
MUD AREA
DN
EE
1/150
3m 6m1.5m
1WAY: SPARE W/PULL WIRE & CAP
PVC CONDUIT
NEW U/G SEC LINE, 3WAY OF 103dia
EXIST ELECTRICAL MANHOLE (TYPCIAL)
U /G
U /G
U/G
U/G
U/G
S
S
S
S S
S
WHM
NEMA 3R ENCL.
TR TYPE, W/CT'S 400/5Ax3EA, 3PH, 120/208V, 60Hz SYSTEM, WITH NEW ADVANCED DIGITAL WATTHOUR METER, REPLACE THE DETERIORATED EXISTING WHM
MDP
EXIST/NEW EXTERIOR POWER LINE DISTRIBUTION PLAN
SCALE : 1/150
DISTRIBUTION PLAN
EXIST/NEW EXTERIOR POWER LINE
E-2
IN EXIST U/G DUCTWAY (TYPICAL)
NEW U/G SEC LINE, 2SETS OF 4-4/0
1WAY: 4-4/0
1WAY: 4-4/0
REPAIR BUILDING
(3P-225AF-150AT) WITH NEW (3P-400AF-400AT).
EXISTING PANALEBOARD/ REPLACE EXISTING CIRCUIT BREAKER
PRI.:22.9KV, SEC.: 120/208V
EXISTING PAD MOUNTED TRANSFORMER, 3PH, 225KVA,
C C
C
CC
C
C
C
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
0 2m
1/200
4m 8m
U/G
U /G
U/G U/G
U /G
U /G
U /G
U /G
U /G
U/G
U/GU/GU/GU/GU/GU/GU/GU/GU/GU/G
C T
V
CTV
CTV CTV CTV
F /O C
T V
F /O C
T V
F /O C
T V
F/O & CTV
F /O C
T V
F/O & CTVF/O & CTVF/O & CTVF/O & CTVF/O & CTVF/O & CTVF/O & CTVF/O & CTV
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
NOTES
CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS
SEE SHEET NO. E-1.
1.
2.
3.
THE CONTRACTOR SHALL VERIFY EXISTING4.
UNDERGROUND TELECOMM LINE'S ACTUAL
CONDITION PRIOR TO WORK.
NEW SINGLE MODE FIBER OPTIC CABLE
AND TELEPHONE CABLE SHALL BE INSTALLED
TO FIX NEW TELECOM CABLES.
5.
COORDINATED WITH BASE SIGNAL COMPANY.
AND TYPE OF SPLICE KITS SHALL BE
ON THE EXISTING MANHOLES,
SCALE : 1/200
EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRIBUITION PLAN-1
LINE DISTRIBUITION PLAN-1
EXIST/NEW EXTERIOR TELECOMMUNICATION
E-3
REPAIR BUILDING
FOR EXTERIOR CATV CABLE WIRING.
CONTRACTOR SHALL COORDINATE WITH LG U + (PLUS)
(TYPICAL)
1-RG-11 COAXIAL CABLE FOR CATV IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE &
CABLE IN EXIST 103mmD U/G DUCT WAY
NEW U/G CATV LINE, 1-RG-11/U COAXIAL
EXIST TELECOMMUNICATION MANHOLE/
CABLE IN EXIST U/G DUCT WAY (TYPCIAL)
NEW U/G CATV LINE, 1-RG-11/U COAXIAL
CABLE TO SPLITTER IN CATV CABINET
EXISTING CATV CABINET/ CONNECT 1-RG-11/U COAXIAL
MODE FIBER OPTIC CABLE
NEW SPLICE KIT FOR 1-12 CORE SINGLE
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
DN
MUD AREA
DN
0 2m
1/200
4m 8m
(4'(H)x4'(W)x4'(D))/
NEW TELECOMMUNICATION HANDHOLE SET
U /G
U /G
U /G
U /G
U/G
U/G
U/G
U/G U/G U/G U/GF/O & CTVF/O & CTVF/O & CTV
F/O &
CTV
F/O &
CTV
F/O &
CTV
F /O C
T V
F /O C
T V
F /O C
T V
F /O C
T V
TELEPHONE CABLE
NEW SPLICE KIT FOR 1-25 PAIR AWG#24,
F/O,TEL,CTV
U /G
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
NOTES
CONTRACTOR SHALL PROVIDE ADEQUATE SUPPORTS
SEE SHEET NO. E-1.
1.
2.
3.
THE CONTRACTOR SHALL VERIFY EXISTING4.
UNDERGROUND TELECOMM LINE'S ACTUAL
CONDITION PRIOR TO WORK.
NEW SINGLE MODE FIBER OPTIC CABLE
AND TELEPHONE CABLE SHALL BE INSTALLED
TO FIX NEW TELECOM CABLES.
5.
COORDINATED WITH BASE SIGNAL COMPANY.
AND TYPE OF SPLICE KITS SHALL BE
ON THE EXISTING MANHOLES,
MESH 3x3" CELL INNER DUCT
1WAY: 1-RG-11/U COAXIAL CABLE IN FABRIC
3x3" CELL INNER DUCT
1-25PAIR TELEPHONE CABLE IN FABRIC MESH
1WAY: 1-12 SINGLE MODE FIBER OPTIC CABLE &
NEW 2WAY OF 103mm PVC CONDUIT
SCALE : 1/200
EXIST/NEW EXTERIOR TELECOMMUNICATION LINE DISTRIBUITION PLAN-2
LINE DISTRIBUITION PLAN-2
EXIST/NEW EXTERIOR TELECOMMUNICATION
E-4
REPAIR BUILDING
FOR EXTERIOR CATV CABLE WIRING.
CONTRACTOR SHALL COORDINATE WITH LG U + (PLUS)
1-RG-11 COAXIAL CABLE FOR CATV IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE &
1-RG-11 COAXIAL CABLE FOR CATV IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE &
1-RG-11 COAXIAL CABLE FOR CATV IN EXIST U/G DUCT WAY
NEW 1-12 CORE SINGLE MODE FIBER OPTIC CABLE &
EXIST TELECOMMUNICATION MANHOLE
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-5
1/100
SCALE :
S S
STORAGE
DN
DN
SHOWER
M.TOILET/
SHOWER
W.TOILET/
J/C
MUD AREA
OFFICE
OFFICE
LAB
WASHER RM
EYE
CORRIDOR
VESTVEST
RM
CONFERENCE
MOUNT
TV WALL
LOCKER ROOM
READY / WAITING /
FEC
106109
FEC
L L
L
L L L
LLL
LL L
L
L L
L L
L
LLLLLLLL
LL
LL
L
L
L L
L L L L
L
L L
L
LL
L
L L
L L
L
L
L
L
L
LL
L
L
L
X X L
L L
LL
L
L L
L
L L
S
EP EP
EPEP
E P
S S
S S
S
S
S
S
S S
S
SS
S S
S
S 3 S
S3 S3
S
MUD ROOM
L
L
L L dim
"P1"
P1-2
P1-1 P1-5
L S
NEW LIGHTING PLAN
RF
RF
J
F
J
F
* ADDITIONAL LEGEND(THIS SHEET ONLY)
RF
RF
LL
L
P1-4
P1-3
"MDP"
L
MDP-8
NEW LIGHTING PLAN
ROOF EXHAUST FAN
0.06HP, 115V, 1 PH (MECH ITEM)
ROOF EXHAUST FAN
0.05BHP, 115V, 1 PH (MECH ITEM)
W/ PHOTOCELL, NEMA 1 ENCL.
LIGHTING CONTRACTOR "LC"
SEALING FITTING (TYPICAL)
REPAIR BUILDING
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-6 m m
308mm
NS-4a & 4bNS-3a & 3b
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
AS REQUIRED, OR APPROVED EQUAL.
WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING
WITH BATTERY CHARGER, SINGLE FACE (NS-3a) OR
(MAX INPUT) OR 7.22W(MAX INPUT), BATTERY BACK-UP
DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V, 4.99W
m m
1220m m
0m m
DOUBLE FACE (NS-3b) OR APPROVED EQUAL.
NS-5a & 5b NS-6a & 6b
NS-8
245mm
254mm
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
OR APPROVED EQUAL.
WET LOCATION SHOWER LIGHT TRIM, AS REQUIRED
FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES,
WALL
ELECTRICAL
LIGHTING FIXTURE DETAILS
TYPE, UL LISTED
AND ACCESSORIES W/BUILT-IN PHOTOCELL, WET LOCATION
WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
LIGHTING FIXUTURE 1PH, 120V, 22W LED MODULES, WITH CONVERTER
NS-10NS-9
NS-11 NS-12
222mm m m
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 25W, UL LISTED, PMMA LIGHT GUIDE PLATE,
WITH CONVERTER & ACCESSORIES AS REQUIRED,
(NS-4a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-4b)
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE PLATE, WITH
CONVERTER & ACCESSORIES AS REQUIRED, (NS-5a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-5b)
CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)
REQUIRED (OPTION: DIMMING CONTROL DRIVER)
FIXTURE, 1PH, 120V, 50W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER &
ACCESSORIES, (NS-6a) & WITH SELF TEST/DIAGNOSTIC EM UNIT (NS-6b) AS
NS-7a & 7b
CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)
ACCESSORIES AS REQUIRED, (NS-7a) & SELF TEST/DIAGNOSTIC EM UNIT(NS-7b)
FIXTURE, 1PH, 120V, 45W, UL LISTED, PMMA LIGHT GUIDE WITH CONVERTER AND
CEILING SURFACE MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 22W,
WET LOCATION TYPE, WITH CONVERTER & ACCESSORIES AS
REQUIRED, UL LISTED POWER UNIT
ACCESSORIES AS REQUIRED, UL LISTED
SURFACE MOUNTED LED LIGHT FIXTURE, 1PH, 120V, 17W,
(NS-7a) & W/ EM UNIT(NS-13b)
NS-13a & 13b
EXPLOSION PROOF TYPE, CLASS I DIVISION 1, 2, UL LISTED (NS-13a)
CEILING SURFACE MOUNTED FLUORESCENT LIGHT FIXTURE, 1PH, 120V, 64W,
WITH BALLAST & ACCESSORIES AS REQUIRED (SIZE: W-11.25" L-52" H-8.5 "),
REMARKSQ'TY
WATTS
MOUNTING METHOD
TYPE
LAMP
NAMENO
ROOM OCE STD DET 40-06-04
LIGHT FIXTURE SCHEDULE
TYPE
LED 1
50 2 W/ "EM" UNIT
CEILING RECESSED
1NS-7b 45
45 1
45 1
45 1
50 7NS-6a
25 3NS-4b
VEST.
NS-6b
NS-6a
NS-5b
NS-13b
NS-7b
NS-7a
NS-7b
NS-7b
NS-6a
NS-6b
NS-6b
NS-4a 25
W/ "EM" UNIT
W/ "EM" UNIT
W/ "EM" UNITNS-5b
W/ "EM" UNIT
364NS-13a
W/ "EM" UNIT
NS-5b
W/ "EM" UNIT
W/ "EM" UNIT
W/ "EM" UNIT
102 OFFICE NS-6a
NS-6b
STORAGE
NS-5a
W/ "EM" UNIT
NS-5b
NS-5a
103 DIMMING CONTROL
DIMMING CONTROL
CONFERENCE RM
NS-5b
NS-7a
NS-12 17 1
W/ "EM" UNIT
W/ "EM" UNIT
W/ "EM" UNIT
W/ "EM" UNIT
CEILING RECESSED
ABOVE THE MIRROR TOP
SURFACE MOUNTED UNDER CABINET
NS-10 22
- EXIT SIGN
- EXTERIOR LIGHT
1/4.99NS-3
WALL MOUNTED
NS-11 22 1- EXTERIOR LIGHT CEILING SURFACE
WALL MOUNTED ABOVE THE DOOR TOP
W.TOILET/SHOWER
M.TOILET/SHOWER
MECH/ELEC ROOM
COMM ROOM
STORAGE
110 VEST
MUD ROOM
EYE WASHER RM
LAB
LOCKER ROOM
READY / WAITING /
OFFICE
CORRIDOR
ABOVE THE MIRROR TOP
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-7
ELECTRICAL
NS-8
NS-9
NS-9
CEILING SURFACE
WALL MOUNTED
WALL MOUNTED
CEILING SURFACE
CEILING RECESSED
NS-8
NS-9 18
CEILING RECESSED
CEILING RECESSED
CEILING SURFACE
W/ "EM" UNIT
LIGHT FIXTURE SCHEDULE
G N
C
OFF
AUTO
H
TO EXTERIOR LIGHTS (TYP)
EXTERIOR LIGHTING
WIRES
CONTROL
#14 AWG
NOT TO SCALE
FACING NORTH
2000W, 120V, ORIENTED
PHOTOELECTRIC CELL
CONTACTOR "LC" DIAGRAM
SW IN NEMA 1 ENCL
120V, COIL HAND-OFF-AUTO SEL.
MECHANICALLY HELD CONTACTS,
W/ 2EA-20A,12OV, N.O.
LIGHTING CONTRACTOR "LC"
M D
P -8
ABOVE THE DOOR TOP/ TO BE CONTROLLED BY "LC"
UNDER CANOPY/ TO BE CONTROLLED BY "LC"
REPAIR BUILDING
LED
FLUORE
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-8
ELECTRICAL
1/100
SCALE :
S S
DN
DN
SHOWER
M.TOILET/
SHOWER
W.TOILET/
J/C
MUD ROOM
MUD AREA
OFFICE
OFFICE
LAB
WASHER RM
EYE
CORRIDOR VESTVEST
CONTAINMENT FL
SECONDARY
RM
CONFERENCE
MOUNT
TV WALL
LOCKER ROOM
READY / WAITING /
ROOM
MECH/ELEC
FEC
101116
FEC
M
WP
WP
W P
TV
TV
TV
TV
C
EP EP
EP EP
W P
R
ROOM
COMM STORAGE
"P1"
P1-6
P1-8
P1-9
* ADDITIONAL LEGEND(THIS SHEET ONLY)
"WP"
TV
M
"C"
"MDP"
P1-7
EWC
NEW POWER PLAN
EP
J
SEALING FITTING (TYPICAL)
S
SCREEN CONTROLLER
P1-13
P1-14
P1-11
P1-10
P1-15 P1-16
P1-17
P1-12
P1-19
P1-18
P1-20
"P2"
NEW POWER PLAN
CIRCUIT INTERRUPTER TYPE,WEATHER PROOF
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT
GROUNDING TYPE
QUAD RECEPTACLE, 2P-3W-20A-125VAC
DUPLEX RECEPTACLE, 2P-3W-20A-125VAC
GROUNDING TYPE
DUPLEX RECEPTACLE (2P-3W-20A-125VAC,
GROUNDING TYPE) FOR NOTICE TV SET
(MH: +450mm BELOW CEILING)
DUPLEX RECEPTACLE (2P-3W-20A-125VAC)
GROUND FAULT PROTECTED
SINGLE RECEPTACLE, 2P-3W-20A-125VAC
NEMA CONFIGURATION:5-20R, W/ PLUG(5-20P)
GROUNDING TYPE FOR MICRO WAVE OVEN
GROUNDING TYPE), "EXPLOSION PROOF" COVER PLATE
SINGLE RECEPTACLE (2P-3W-20A-125VAC,
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-9
HPO
HPO
HP1
OAU
EH
HP
HP
ECH 1
ECH
HP
HP
EH
HP
HP
HP
ERV
EH
RF
RF
FEC FEC
DN
DN
1/100
SCALE :
A
A
B
ERV
J
EUH
HPO
HPO
RF-1
D
C
"MDP"
HP
AC
EUH
RF
AC
HRP
DWH
J
J
JJ
B
"P1"
J
JJ
RF
JJ
J
-2
P2-1
P2-2
JJ
RF
-1
P2-3P2-4
P2-8
P2-6
"C"C-5
D
P2-7
P2-5
D
XX
HP
P2-9 "E
P
"EP"
M A
M B
MC
MC
MA, MB
C
J
RF-2
J
RF-5
OAU
S E P C
SEALING FITTING (TYPICAL)
C
LOUVER
CONNECT TO MOTORIZED
C
S
LIGHT SWITCH
LIGHT SWITCH"EF"
P2-10
"P2"
JJ
MDP-5
MDP-4
P2-11
"M"
M-2 M-3
M-4
MECHANICAL SYSTEM
NEW POWER/CONTROL PLAN FOR
IN 53C
1#6(G)
3#1/0&
IN 35C
3#6&
1#10(G)
2#10&
IN 21C
1#10(G)
IN 53C
1#6(G)
TO M-1,
3#1&
VARIABLE REFRIGERANT FLOW HEAT PUMP-1 (OUTDOOR UNIT)
VARIABLE REFRIGERANT FLOW HEAT PUMP-2 (OUTDOOR UNIT)
82.1 AMP MCA, 208V, 3PH (MECH ITEM)
22.6 AMP MCA, 208V, 3PH (MECH ITEM)
ENERGY RECOVERY VENTILATOR-1
0.480KW, 208V, 1PH (MECH ITEM)
NON-FUSIBLE, NEMA 3R ENCL
* ADDITIONAL LEGEND(THIS SHEET ONLY)
FOR HPO-1
VARIABLE REFRIGERANT FLOW HEAT PUMP 1 THRU 6 (INDOOR UNIT)
0.030~0144KW, 208V, 1PH (MECH ITEM)
SAFETY SWITCH, 3PST, 240V, 60A
NON-FUSIBLE, NEMA 1 ENCL
SAFETY SWITCH, DPST, 240V, 30A
ABOVE CEILING FOR OAU-1 & ERV-1
FOR ERV-1,2&3 W/STEEL STRUCTURE SUPPORT
NON-FUSIBLE, NEMA 3R ENCL
SAFETY SWITCH, DPST, 240V, 30A
FOR AC-1
ROOF EXHAUST FAN-2
ROOF EXHAUST FAN-1
0.02BHP, 115V, 1 PH (MECH ITEM)
0.05BHP, 115V, 1 PH (MECH ITEM)
0.16BHP, 115V, 1 PH (MECH ITEM)
ROOF EXHAUST FAN-5 "EP" MOTOR,
0.18KW, 208V, 1PH (MECH ITEM)
OUTSIDE AIR SUPPLY UNIT-1
3.0KW, 208V, 1PH (MECH ITEM)
3.62A, 208V, 1PH (MECH ITEM)
ELECTRIC WALL HEATER-1
4.1A, 240V, 1PH (MECH ITEM)
ELECTRIC WALL HEATER-3
MAGNETIC MOTOR STARTER, 2P-120V
NEMA SIZE "00" W/O.L RELAYS,
PILOT LAMP(GREEN), AND 3-POSITION
SELECTOR SWITCH (H-O-A)
15A, 208V, 1PH (MECH ITEM)
3.0KW, 208V, 1PH (MECH ITEM)
ELECTRIC UNIT HEATER-1 (FOR ELEC/STORAGE)
83.3A, 208V, 3PH (MECH ITEM)
ELECTRIC DOMESTIC HOT WATER HEATER
DOMESTIC HOT WATER RECIR. PUMP
1/8HP, 120V, 1PH (MECH ITEM)
PILOT LAMP(GREEN), AND 3-POSITION
SELECTOR SWITCH (H-O-A)
MAGNETIC MOTOR STARTER, 2P-120V, "EXPLOSION
PROOF", NEMA SIZE "00" W/O.L RELAYS,
NEMA 1 ENCL FOR RF-5
NEMA 1 ENCL FOR RF-1, RF-2 & HRP-1
SPLIT AIR CONDITIONING INDOOR & OUTDOOR UNIT
SINGLE RECEPTACLE, 2P-3W-20A-240VAC
GROUNDING TYPE FOR HP INDOOR UNIT
3.8KW, 208V, 1PH (MECH ITEM)
ELECTRIC CEILING HEATER-1
ELECTRIC CEILING HEATER-2
W/ PLUG
EH
EH
ECH
DWH
HRP
AC
ECH
W/ FUSES (120Ax3EA), NEMA 3R ENCL
FOR HPO-2
SAFETY SWITCH, 3PST, 240V, 200A
NEW POWER/CONTROL PLAN FOR MECHANICAL SYSTEM
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-10
ELECTRICAL
EXIST/NEW POWER ONE-LINE DIAGRAM
NOT TO SCALE
400AT
400AF
100AF
3P
3P
3P 3P
100AF
CONDUCTOR, #3/0(G) IN 21C
NEW GROUNDING
EXISTING MAIN PANELBOARD
WITH NEW MAIN PANELBOARD "MDP"
CU BUS, 400A
22,000AIC SYM
G
S/NGND
REPLACE THE DETERIORATED321 5
3P
100AF
3P
FOR ABBREVIATION, LEGEND, GENERAL NOTES1.
& SCOPE OF WORK,
NOTES
"P1"
A B
EXT
HPO
EXT
SURGE SUPPRESSOR
TRANSIENT VOLTAGE
NEMA 1 ENCL
-2
HPO
-1
1WAY: SPARE W/PULL WIRE & CAP
3P
20AT
100AF
W/BUILT-IN CONTROLLER
70AT
100AF
CONNECTION (TYPICAL)
STEEL, 19diax3000LG WITH WELDING
NEW 1#3/0 "BC" IN 27C
G
VARIABLE REFRIGERANT FLOW HEAT PUMP-1 (OUTDOOR UNIT)
(UNDER MECH ITEM)
W/BUILT-IN CONTROLLER
VARIABLE REFRIGERANT FLOW HEAT PUMP-2 (OUTDOOR UNIT)
60AT
A
B
IN 53C
(UNDER MECH ITEM) (TYPICAL)
SEE SHEET NO. E-1.
* ADDITIONAL LEGEND(THIS SHEET ONLY)
NON-FUSIBLE, NEMA 3R ENCL
FOR HPO-1
EXIST/NEW POWER ONE-LINE DIAGRAM
"C"
TVSS
NEW
9 10
1P
20AT
100AF
TR TYPE, W/CT'S 400/5Ax3EA
120/208V, 60Hz SYSTEM, NEMA 3R ENCL.
AND 15MIN DEMAND REGISTER FOR 3PH, 4W,
WITH NEW ADVANCED DIGITAL WATTHOUR METER,
REPLACE THE DETERIORATED EXISTING WHM
WHM
3PH, 22.9KV-120/208V, 60HZ, 225KVA
EXIST PAD MOUNTED TRANSFORMER,
EXIST CONDUIT COUPLING (TYPICAL)
NEW CONDUIT COUPLING (TYPICAL)
SAFETY SWITCH, 3PST, 240V, 60A
SPARE
225AF
125AT
IN 35C
4#6&
1#10
IN 35C
3#4&
1#8
IN 35C
3#6&
1#10(G)
G
"P2"
1P
20AT
100AF
1P
20AT
100AF
SPARE SPARE
EXTERIOR LIGHT
70AT 60AT
"M"
IN 53C
3P
225AF
125AT
1WAY: 4-4/0 "USE"
1WAY: 4-4/0 "USE"
W/ NEW (3P-400AF-400AT)
EXIST CIRCUIT BREAKER(3P-225AF-150AT)
EXIST EXTERIOR PANELBOARD/REPLACE
E
E
EXIST ELECTRIC MANHOLE
EXISTING SEC. SERVICE LINES TO REMAIN
PVC CONDUIT (SEE EXTERIOR POWER LINE DISTRIBUTION PLAN, E-2)
1#6(G)IN 35C
3#4&
1#8
4#1/0&
1#6 3#1/0&
2SETS OF 4-4/0 & #2(G)IN 103C.
NEW U/G SEC LINE, 3WAY OF 103dia
POWER: 3PH-208V, 22.6AMP MCA
POWER: 3PH-208V, 82.1AMP MCA
W/ FUSES (120Ax3EA), NEMA 3R ENCL
FOR HPO-2
SAFETY SWITCH, 3PST, 240V, 200A
OUTDOOR
INDOOR
EXIST GROUND ROD, COPPER CLAD
NEW U/G SEC LINE 2-SETS OF 4-4/0 "USE" IN EXIST U/G 103C. DUCT WAY
NEW U/G SEC LINE 2-SETS OF 4-4/0 "USE" IN EXIST U/G 103C. DUCT WAY
1 100 10000 2#12&1#12(G)
TOTAL LOAD 17174 5710
LOAD
TOTAL
PANELBOARD "P1" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
618 20
9 10
TOTAL DEMAND LOAD ; 11,150(VA)
60HZ, SN & GND, FLUSH
4#4 & 1#8(G)
RCPTS 180VA x4EA
RCPTS 180VA x4EA
RCPTS 180VA x5EA
RCPTS 180VA x4EA
LIGHTS LED 45W x8EA,18Wx10EA, SPARE
SPARE23
24 1000
SPARE
SPACE -
2#12&1#12(G)
LIGHTS LED 50W x12EA, 18W x1EA
FANx2EA
LIGHTS LED 50W x12
LIGHTS LED 50W x9EA
25Wx6EA, 4.99Wx2EA LIGHTS LED 64Wx4EA,45Wx6EA, MICROWAVE OVEN
REF.
ELECTRIC WATER COOLER
RCPTS 180VA x5EA
EYE WASHER
RCPTS 180VA x4EA
RCPTS 180VA x4EA
RCPTS 180VA x5EA
PROJECTOR
RCPTS 180VA x4EA
RCPTS 180VA x5EA
2 100 10000 2#12&1#12(G)
TOTAL LOAD 15330 5355 4840
LOAD
TOTAL
PANELBOARD "P2" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MAIN 3P-100AF-70AT CIRCUIT BREAKER
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
348 20
141000
502 251
60HZ, SN & GND, FLUSH
4#4 & 1#8(G)
SPARE
SPARE
SPACE ---- - - --
FMCP
HEAT PUMP-2x2EA, 4x1EA, 5x1EA
HEAT PUMP-1x1EA, 3x1EA, 5x2EA
HEAT PUMP-6x1EA
ELETRIC CEILING HEATER-1
ELETRIC CEILING HEATER-2
ELETRIC WALL HEATER-1
ELETRIC WALL HEATER-2
OUTSIDE AIR SUPPLY UNIT-1
WATER HEATER
ELECTRIC DOMESTIC HOT
ELETRIC UNIT HEATER-2
ROOF FAN-1 200
29988 9996
2#12&1#12(G)
10001000
TOTAL LOAD
LOAD
TOTAL
PANELBOARD "M" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
3PHASE ,4WIRE, 120/208V,
60HZ, SN & GND, SURFACE
MTD TYPE, NEMA 1 ENCL.
CIRCUIT BREAKER
PHASE LOAD
A B PC
100 10000
AT
SIZE
AF AIC
B CA N G
REMARK
SPARE SPACE
SPACE
SPACE
SPACE
SPACE
SPARE
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE
SPARE 1000 1000 -
36388
HRP-1 200 200
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE - - - - - - - - --
100 20
12696 12496
MAIN 3P-225AF-125AT CIRCUIT BREAKER
TOTAL DEMAND LOAD ; 34888(VA)
ROOF EXHAUST FAN-5
ELETRIC WALL HEATER-2
ROOF EXHAUST FAN-1
ERV-1x1EA
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-11
ELECTRICAL
LOAD SCHEDULE
NEW PANELBOARD "P1", "P2" & "M"
23 24
SPACE
SPACE
SPACE-
-SPACE
SPACE-
LOCKING DEVICE
MAIN 3P-100AF-70AT CIRCUIT BREAKER
200 200
60 60
90 90
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
1000 1000
SPACE
SPACE
SPACE
2#10&1#10(G)
2#12&1#12(G)
SPARE
SPARE
1000 1000
1000 1000
SPACE
SPACE
1 100 20
TOTAL DEMAND LOAD ; 13,300 (VA)
3#1&1#6(G)
4#1/0 & 1#6(G)
11196
10001000
5001000
RCPT FOR CATV EQUIPMENT
TOTAL LOAD 25004500 3000
LOAD
TOTAL
PANELBOARD "C" LOAD SCHEDULE
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
3PHASE ,4WIRE, 120/208V,
60HZ, SN & GND, SURFACE
MTD TYPE, NEMA 1 ENCL.
CIRCUIT BREAKER
1000 1000 1
PHASE LOAD
A B PC
20100 10000
AT
SIZE
AF AIC
B CA N G
REMARK
2#12&1#12(G)
TVSS
11000
3000 1500
COMM RACK
RCPT FOR TTB
RCPT FOR CATV EQUIPMENT
SPARE
MAIN 3P-100AF-60AT CIRCUIT BREAKER
4#10&1#10(G)
SPACE
SPACESPACE
SPACESPACE
SPARE
TVSS
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
SPACE - - - - - - - - -
- - - - 3 30
SPARE 1000 1000 -
4#6 & 1#10(G)
TOTAL DEMAND LOAD ; 4500(VA)
OUTDOOR & INDOOR UNIT
SPLIT AIR CONDITIONING
10000
3 100 22000
TOTAL LOAD
LOAD
TOTAL
LOAD DESCRIPTION
NO.
CKT
GND
S/N
DIAGRAM
CONNECTION
CIRCUIT BREAKER
PHASE LOAD
A B PC AT
SIZE
AF AIC
B CA N G
REMARK
MTD TYPE, NEMA 1 ENCL.
3PHASE ,4WIRE, 120/208V,
PANELBOARD "P1"
PANELBOARD "P2"
PANELBOARD "C"
HEAT PUMP-1 (OUTDOOR UNIT)
HEAT PUMP-2 (OUTDOOR UNIT)
1000 1000
60HZ, SN & GND, SURFACEPANELBOARD "MDP" LOAD SCHEDULE
62776 59818 58836
MAIN 3P-400AF-400AT CIRCUIT BREAKER
4#4&1#8(G)
225 125
4#4&1#8(G)
3#6&1#10(G)
1000 1000
1000 1000
2#12&1#12(G)
27122712 2712
SPARE
SPACE
SPACE -
TOTAL DEMAND LOAD ; 152725 (VA)
PANELBOARD "M"
985229556 125
10001000
SPARE
180780
SPACE
SPACE
SPACE
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-12
ELECTRICAL
EXTERIOR LIGHTS 22Wx11EA
SPARE
LOAD SCHEDULE
NEW PANELBOARD "C" & "MDP"
17174 571059465518
15330 5355 48405135
36388 12696 12496 11196
25004500 300010000
9852 9852
12 1000
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPACE
SPARE
SPARE
SPACE
SPACE
201001
3#1/0&1#6(G)
REPAIR BUILDING
4#1/0&1#6(G)
4#6&1#10(G)
2SET OF 4#4/0 & 1#2(G)
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-13
S S
DN
DN
SHOWER
M.TOILET/
SHOWER
W.TOILET/
J/C
MUD ROOM
MUD AREA
OFFICE
OFFICE
LAB
WASHER RM
EYE
CORRIDOR VESTVEST
CONTAINMENT FL
SECONDARY
RM
CONFERENCE
MOUNT
TV WALL
LOCKER ROOM
READY / WAITING /
ROOM
MECH/ELEC
FEC
101116
ROOM
COMM
STORAGE
FF
M F
W
PM
F
W P
FMCPFTR AMBER STROBE SHALL BE DE-RATED AS REQUIRED)
+ MNS-AMBER STROBE W/WORDS "ALERT")
WITH COMBO.(FA-CLEAR STROBE W/WORD "FIRE"
WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)
"WP" TYPE, WALL MOUNTED TYPE,
MASS NOTIFICATION SPEAKER
(WATTAGE AS REQ'D)
WP
ADDRESSABLE MANUAL PULL STATIONF
M F
VISUAL SIGNAL STROBES (15 or 75 CANDELA MINIMUM, FMCP
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES AS REQ'D,
(AS REQ'D) & MICROPHONE. NEMA 1 ENCL
DIGITAL VOICE PANEL W/AMPLIFIER & BACK UP AMPLIFIER
BATTERY CHAREGER, POWER MODULES PANEL (AS REQ'D) AND
SYNCHRONIZATION CONTROL MODULE, POWER SUPPLY,
PROGRAMMABLE MODULE & RELAYS, LCD ANNUNCIATOR,
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL (FMCP),
COMBINED ADDRESSABLE
DIGITAL VOICE MODULE, MICROPHONE, BATTERY,
ADDRESSABLE SMOKE
DETECTOR
FTR
(PROGRAM OF D-21 MONACO
BT-XM AT LEAST 16 ZONES)
W/BATTERY & BATTERY
CHARGER, NEMA 1 ENCL
LEGEND
NEW FIRE ALARM BUILDING TRANSMITTER
DETECTOR
ADDRESSABLE HEAT
F
FMCPTO
FMCPTO
SCALE : 1/100
NOTIFICATION SYSTEM PLAN
NEW FIRE ALARM AND MASS
NEW FIRE ALARM AND MASS NOTIFICATION SYSTEM PLAN
F
F
F
F
F
F
F
F
F
F
F
FF
F
F
F
F
F
F/MF/M
F/M
F /M
F /M
F /M
F/M
F/M F/M F/M
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-14
NOTES:
NFPA 72, 2013 EDITION.
PRERECORDED MESSAGES ARE IN ENGLISH AND HANGUL AT
CONTRACTOR SUBMITS SHOP DRAWINGS.
THE VOLTAGE DROP AND POWER SUPPLY CALCULATION
SHALL BE PROVIDED BY THE CONTRACTOR WHEN THE
4.
(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.
ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mmTHE FIRE ALARM SYSTEM IS CONCEPTUAL. THE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
MANUFACTURER'S LISTED INSTALLATION
2.
CONTRACTOR SHALL COMPLETE DESIGN AND INSTALL
13.
12.
11.
9.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
AND THE MASS MESSAGE NEEDS TO HAVE PRE ALERT
PATTERN IS REQUIRED FOR FIRE ALARM EVACUATION
VOICE EVACUATION SYSTEM IN LIEU OF TEMPORAL
ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED
ELECTRICAL AND MECHANICAL SYSTEM EQUIPMENT
COORDINATE THE EXACT DEVICE LOCATIONS WITH
SWITCHES AND NON-ADDRESSABLE INITIATION
ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE
PROHIBITED FOR ALL IDC, NAC AND SLC.
ALL CLASS "B" EXCEPTIONS IN NFPA 72, 23.4.2.2 ARE8.
7. CLASS "B" RACEWAY OF FA SYSTEM SHALL BE
SEPARATED BY A MINIMUM OF 1220mm HORIZONTAL
10. COAXIAL CABLE SHALL BE ONE PIECE BETWEEN
3.
5.
6. THE POWER CIRCUIT NUMBER DEDICATED TO FIRE
ALARM CIRCUIT AND ROOM LOCATION OF PANEL
LETTER "FIRE ALARM CIRCUIT" ON THE DEDICATED
FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED
THE FIRE ALARM/MASS NOTIFICATION SYSTEM
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING
FIRE ALARM INTELLIGIBILITY/AUDIBILITY CALCULATION,
WIRE SIZE, CONDUIT SIZE, NO. OF WIRES FOR THE FIRE
POWER CIRCUIT BREAKER AND/OR DISCONNECT SWITCH.
SHALL BE INDICATED ON THE FIRE ALARM/MASS
BUILDING TRANSMITTER AND ANTENNA.
AND 305mm VERTICALLY.
DEVICES SHALL BE PROVIDED WITH CLASS "B"
THE SYSTEM FOR READY TO USE. THE NUMBER OF
DEVICES SHOWN IS THE MINIMUM REQUIRED AND THE
FINAL QUANTITY SHALL BE IN ACCORDANCE WITH THE
DEVICE LOCATIONS IN ACCORDANCE WITH THE
AND BUILDING ARCHITECTURAL FEATURES.
OR FM APPROVED.
SPECIFICATION SECTION 28.31.76.00.31 (FA) AND
HAVE PRE ALERT TEMPORAL PATTERN MIN 2 CYCLES
PROVIDE ADDITIONAL RELAYS AS REQUIRED.14.
18.
19.
20.
PER UFC 4-021-01.
17. THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE
NUMBER OF DEVICES SHOWN IS THE MINIMUM REQUIRED
AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE
MANUFACTURER'S EQUIPMENT LISTING.
SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION
THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT
LEAST FOR THE FOLLOWING ITEMS.
FOR ABBREVIATION, LEGEND, AND GENERAL NOTES
STROBES FOR MASS NOTIFICATION SHALL BE MARKED
STROBES FOR FIRE ALARM SHALL BE MARKED "FIRE"
"ALERT" IN RED LETTER AND W/AMBER LENS.
SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH
1.
AND W/CLEAR LENS.
15.
CONTINUOUS 3-10 SECOND TONE, NFPA 72, 24.4.1.2.2
& 24.4.1.8.2.
THE MASS SYSTEM ACTIVATION MUST OVERRIDE THE FIRE
ALARM NOTIFICATION APPLIANCES THE MASS SYSTEM
ON THE PANEL BY SWITCH.
THIS SEQUENCE IS REQUIRED FOR BOTH PRE-RECORDED
MASS MESSAGE IS REQUIRED TO BE ANNOUNCED
IMMEDIATELY UNTIL SHUTDOWN MANUALLY.
SPECIFICATION SECTION 28.31.76.00.31 (MNS)
THE CONTRACTOR SHALL PROVIDE THE REQUIRED
TESTING TO ACHIEVE A MINIMUM CIS SCORE 0.8 AS
16.
DEVICE LOCATIONS IN ACCORDANCE WITH THE
MANUFACTURER'S LISTED INSTALLATION
AND NFPA 72, 2013 EDITION.
APPLIANCES UNTIL MASS ALERT IS CANCELED MANUALLY
ACTIVATION MUST OVERRIDE THE FIRE ALARM NOTIFICATION
MESSAGES AND MANUAL MICROPHONE INITIATED MESSAGES.
ARE IDENTICAL TO FIRE ALARM VISUAL APPLIANCES.
23.
MASS VISUAL APPLIANCE LOCATION REQUIREMENTS
AS SHOP DRAWING SUBMITTALS.
CONTRACT DRAWINGS SHALL NOT BE SUBMITTED
ARMY AND AIR FORCE PROJECTS.
WITH ANY FIRE ALARM VISUAL APPLIANCES ON
MASS VISUAL APPLIANCES SHALL NOT BE COMBINED24.
25.
22. FIRE ALARM SYMBOLS FROM NEPA 170 SHALL BE
AND ALL VISUAL APPLIANCES WITHIN THE SAME ROOM
ALL AUDIBLE APPLIANCES WITHIN THE BUILDING21.
SHALL BE SYNCHRONIZED.
VOICE EVACUATION SPEAKERS, NEPA 72.
AUDIBLE APPLIANCES SHALL PROVIDE THE STANDARD
TEMPORAL PATTERN UNLESS NFPA 101 REQUIRES
USED.
26. SHOW WEATHERPROOF EXTERIOR SPEAKERS AT ALL
EXTERIOR DOORS OR EXTERIOR GATHERING AREAS.
SHALL BE UL LISTED OFF-THE-SHELF-EQUIPMENT AND
ALL BACK-UP AMPLIFIERS WIRING AND ARRANGEMENT27.
SHALL BE TESTED TO THE STANDARDS OF UL OR RM AS
REQUIRED BY UFC 4-21-01, PARAGRAPH 4-4.3.
BOTH KOREAN AND ENGLISH.
THE MAN SHALL HAVE PRERECORDED MASSAGES IN28.
APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
ALARM AND DETECTION SYSTEM.
NOTIFICATION CONTROL PANEL COVER.
MODULES.
SYSTEM. VOICE EVACUATION MESSAGE NEEDS TO
REQUIRED.
WITH THE APPLICABLE CODE, SPECIFICATIONS AND
REQUIREMENTS AND WIRE COUNT.
OF 20% SPARE ADDRESSES FOR FUTURE USE.
FIRE ALARM SYSTEM OF EACH SLC TO HAVE A MINIMUM29.
SEE SHEET NO. E-1.
2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING
1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING
3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING
6) "ALL CLEAR" MESSAGE
TEST8)
THE BUILDING
CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND 7)
THE LOCAL AREA
5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR
NORMAL MAIN ENTRANCE/EXIT
4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE
FIRE ALARM/MASS NOTIFICATION
CONTROL PANEL (FMCP)
FTR
16#14 IN 21C(FOR SIGNAL)
2#12 IN 16C(FOR POWER)
#6 "BC" IN 21C
GROUND CONDUCTOR
COAXIAL CABLE
W/CONNECTORS IN 16C
OMNI-DIRECTION TYPE
FIRE ALARM ANTENNA
W/MOUNTING BRACKET
GROUND ROD, COPPER CLAD
WITH WELDING CONNECTION
STEEL, 19mmdia x 3000mmLG
SG
G ~
G
CONTROL PANEL & BOOSTER PANEL)
(INSTALLED BESIDE FIRE ALARM
(RATED AS REQ'D) (TYPICAL)
SURGE PROTECTOR
2#12 & 1#12(G) IN 16C
GROUND ROD, COPPER CLAD
GROUNDING SYSTEM #6, "BC" IN 21C
CONN TO BLDG ELECTRODE
STEEL, 19mmdiax3000mmLG
WITH WELDING CONNECTION AND
ENCLOSURE
LIGHTNING ARRESTER
W/WEATHER-PROOF
ADDRESSABLE MANUAL
PULL STATION (TYPICAL)
WALL MOUNTED "WP" TYPE,
NOTIFICATION SPEAKER
FIRE ALARM/MASS
(WATTAGE AS REQ'D) (TYPICAL)
ADDRESSABLE SMOKE
DETECTOR
NOT TO SCALE
ELECTRICAL
W/WORDS "FIRE" + MNS-AMBER STROBE
W/WORDS "ALERT") VISUAL SIGNAL STROBES
AS REQ'D)/COMBO. (FA-CLEAR STROBE
WALL MOUNTED SPEAKER (WATTAGE
SHALL BE DE-RATED AS REQUIRED) (TYPICAL)
(15 or 75 CANDELA MINIMUM, AMBER STROBE
SURFACE MOUNTED BUILDING
TRANSMITTER W/BATTERY &
BATTERY CHARGER, RELAY
FROM MNS NEMA 1 ENCL
BOARD W/CONTROLWIRING
BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)
SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE
FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,
24VDC, BUILT-IN ADDRESSABLE POINTS MODULES
AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,
POWER MODULE AS REQ.D LCD ANNUNCIATOR,
MODULE, POWER SUPPLY, MICROPHONE, BATTERY,
AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL
SEMI FLUSH MOUNTED COMBINED ADDRESSABLE
NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM
SYSTEM DIAGRAM
NEW FIRE ALARM/MASS NOTIFICATION
F M
WP
EXT114 114 116 111 112115
103 104 106 F
M
WP
EXT 102
115 114 114 113 112 111 116 F
107104103116102
ADDRESSABLE HEAT
F
TO FIRE ALARM CIRCUITS "P1-21"
F
106 108
109 107 108
DETECTOR (TYPICAL)
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-15
S S
DN
DN
FEC
SHOWER
M.TOILET/
SHOWER
W.TOILET/
J/C
MUD ROOM
MUD AREA
OFFICE
OFFICE
LAB
WASHER RM
EYE
CORRIDOR
VEST
VEST
CONTAINMENT FL
SECONDARY
RM
CONFERENCE
MOUNT
TV WALL
LOCKER ROOM
READY / WAITING /
ROOM
MECH/ELEC
FEC
103104
FEC
ROOM
COMM
STORAGE
LAN
T T B
SCALE : 1/100
NEW LAN/TEL PLAN
NEW LAN/TEL PLAN
T
T
T
T
T
T
T
T
T
T T
T
T
T
T
EQUIPMENT RACK (1-DATA & 1-TEL) (TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
2-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
EQUIPMENT RACK (2-DATA & 2-TEL) (TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
4-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
EQUIPMENT RACK (3-DATA & 3-TEL)(TYPICAL)
TO BE TERMINATED AT PATCH PANELS IN
6-AWG#24, CAT6, LAN CABLE IN 27mm dia C.
CABLE TRAY 300mm(W)x(150(H)
LENGTH AS REQUIRED
(1WAY FOR DATA, 1WAY FOR TEL.)
CAT6 CABLES IN 2-WAY 103mm C.
NEW TELEPHONE TERMINAL BOARD
NEW EQUIPMENT RACK
SEE NEW LAN/TEL SYSTEM DIAGRAM
SEE NEW LAN/TEL SYSTEM DIAGRAM
EXOTHERMIC WELDING, LISTED COMPRESSION TWO-
1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR
TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE
HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE
1#6 "BC" IN 21C
CONN TO MAIN PANELBOARD
NOT TO SCALE
STAMP FACING OUT" TO ENSURE THAT THEY CAN BE
3. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT
REVISION OF THE ANSI/TIA/EIA-568.
4. LABEL ALL DROPS IAW TIA/EIA-606-A.
5. LABEL ALL GROUNDS IAW I3A.
LUGS ARE PREFERRED.
FIELD VERIFIED.
TO TELEPHONE PATCH PANEL
TGB
CONN TO TMGB
1#6 "BC" IN 27C
(100mm x 450mmLG x 6.4mmTHK)
GROUND BUS BAR(TGB)
TMGB
G
(TYPICAL)
CABLE SUPPORT
G
110TYPE TERMINAL BLOCK
(TYPICAL)
CROSS CONNECTION CORD AS REQ'D
PLUS 25% SPARES TO BE FURNISHED BY THE
1#6 "BC" IN 16C
G
FOR TELEPHONE
1-48PORT PATCH PANEL
AS REQ'D
PROVIDE PATCH CORDS
HUB(N.I.C)
1-48PORT PATCH PANEL
W/ RACK MOUNTED 6-SINGLE
REAR RECEPTACLE, ON-OFF
SWITCH & CORD, 2P-3W-20A-125V
GROUND BUS BAR(TGB)
TELECOMMUNICATION
TELECOMMUNICATION MAIN
PTB
CONTRACTOR
RECEPTACLES
(1-25PAIR)
ENTRANCE TERMINAL BLOCK
110 TYPE PROTECTED
G
2. "PLYWOOD WILL BE INSTALLED WITH FIRE RATED
NOTE.
SHALL BE COORDINATED WITH BASE SIGNAL COMPANY.
SYSTEM AND WIRING FOR GOVERNMENT APPROVAL. TELECOMMUNCATION WORK
6. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAILED TELECOMMUNICATION
1-12CORE, FIBER OPTIC CABLE IN 103C.
PATCH PANEL W/"SC" CONNECTOR
1-24 STRAND FIBER OPTIC
QUAD-PLEX RECEPTACLE
2P-3W-125V-20A GND TYPE
WITH DEDICATED CIRCUIT
(24"(W)x72"(H)x36"(D)
POWER SURGE PROTECTION
COMM RM
1-25PAIR, #24AWG TEL CABLE IN 103C.
TO EACH TEL OUTLET AS REQ'D VIA CABLE TRAY
1,800(W)x2,400(H) FIRE RATED PLTWOOD
TELEPHONE TERMINAL BOARD ("TTB"),
G
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
E-16
ELECTRICAL
(100PAIR) FOR TEL
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO EACH DATA OUTLET AS REQ'D VIA CABLE TRAY
G
TO BE TERMINATED AT FIBER OPTIC PATCH PANEL
LENGTH AS REQUIRED
CABLE TRAY 300mm(W)x(150(H)
G
G
G
"MDP" GROUNDING BUS BAR
FOR DATA
(TYPICAL)
NEW LAN/TEL SYSTEM DIAGRAM
TO PNLBD C-1
TO PNLBD C-2
EQUIPMENT CABINET
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
E-17
S S
ROOM
COMM
DN
DN
SHOWER
M.TOILET/
SHOWER
W.TOILET/
J/C
MUD ROOM
MUD AREA
OFFICE
OFFICE
LAB
WASHER RM
EYE
CORRIDOR
VEST
VEST
CONTAINMENT FL
SECONDARY
RM
CONFERENCE
MOUNT
TV WALL
LOCKER ROOM
READY / WAITING /
ROOM
MECH/ELEC
FEC
103104
ROOM
COMM STORAGE
TV
TV
TV
TV
TV
TV
CTC
1/100
SCALE :
NEW CATV PLAN
NEW CATV PLAN
T V
T V
TV
TV
T V
T V
WALL MOUNTED TYPE
TV OUTLET
TYPE CONNECTOR
W/"0.0"dB LOSS FACE
PLATE & F-81 BARREL
CEILING) (TYPICAL)
(MH:+450mm BELOW
PULL BOX (300 x 300 x 200D)
W/ 8-WAY TAP-OFF AND LOCKING
DEVICE ABOVE CEILING
(5-1000MHZ)
COAXIAL CABLE
RG 11/U IN 21C
(TYPICAL)
EXTERIOR
NEW U/G RG-11/U CATV CABLE
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
CAPABILITIES, LOCKING DEVICE AND
AIR VENTS SHALL BE INSTALLED
ON CATV CABINET TO ENSURE
ADEQUATE VENTILATION IN COMM RM
NEMA 1 ENCL
INCLUDING NEW 3-WAY SPLITTER,
NEW CATV DISTRIBUTION CABINET
COAXIAL CABLE
RG 6/U IN 16C
(TYPICAL)
G
T
V
AMP
ROOF
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
NOT TO SCALE
E-18
TV
TV
TV
TV
TV
114114 115
TV
NEW CATV DIAGRAM
NEW CATV DIAGRAM
1st FL COMM RM
COAXIAL CABLE
RG 6/U IN 16C
(TYPICAL)
PULL BOX (300 x 300 x 200D)
W/ 8-WAY TAP-OFF AND LOCKING
DEVICE ABOVE CORRIDOR CEILING
(5-1000MHZ) (TYPICAL)
ROOM NO WHERE
DEVICE IS LOCATED
(TYPICAL)
WALL MOUNTED TYPE
TV OUTLET
TYPE CONNECTOR
W/"0.0"dB LOSS FACE
PLATE & F-81 BARREL
CEILING) (TYPICAL)
(MH:+450mm BELOW
GROUNDING TYPE)
(2P-3W-20A-125VAC,
NEW DUPLEX RECEPTACLE
NEW SINGLE RECEPTACLE
(2P-3W-20A-250VAC,
GROUNDING TYPE)
FOR CATV AMPLIFIER
FOR CATV AMPLIFIER
TO PNLBD "C-3"
TO PNLBD "C-4"
INCLUDING NEW 2-WAY SPLITTER,
TRUNK BRIDGE AMPLIFIERS W/RETURN PATH
CAPABILITIES, LOCKING DEVICE AND
AIR VENTS SHALL BE INSTALLED
ON CATV CABINET TO ENSURE
ADEQUATE VENTILATION IN COMM RM
NEMA 1 ENCL
NEW GROUNDING WIRE
RG 11/U IN 21C
COAXIAL CABLE
NEW CATV DISTRIBUTION CABINET
EXTERIOR
NEW U/G RG-11/U CATV CABLE
RG 11/U IN 21C
COAXIAL CABLE
(TYPICAL)
| E-1 |
| E-2 |
| E-3 |
| E-4 |
| E-5 |
| E-6 |
| E-7 |
| E-8 |
| E-9 |
| E-10 |
| E-11 |
| E-12 |
| E-13 |
| E-14 |
| E-15 |
| E-16 |
| E-17 |
| E-18 |