HS-00554-5J
HGFEDCBA
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
D - 19 - 17
29 JUL 19
E-09
CAMP CARROLL
KIM, CK
HVAC CONTROL PLAN - 1ST FLOOR
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
- E09
P-1
SCALE : 1 /100
"L1A" "L1B"
C
CC
C
C
CC
C
C
C C
C
C
C
C
CCCCC
C
123124125126127
129 130 131 132 135 136
VELVE
120A
120B
114 113 112 111
109A 107106105104103
ELEC
MECH
COMM
108134
C C C
C
C
CC
C C
C
C
C
C
C
C C
C C
C C C C C
CCC
C
C
CCC
C
C
HVAC CONTROL PLAN1 - 1ST FLOOR
J J J J J
J
J J J J
J
J
JJJJJ
J J
J
JJJ JJ
J
J
J
J
(MECH. ITEM)
NEW THERMOSTAT W/ CONTROLLER
J J J
JJJ
J J J
C C C
CC
C
IN RM 120A
TO "CC-2"
IN RM 120A
TO "CC-1"
IN RM 120A
TO "CC-4"
IN RM 120A
TO "CC-7"
IN RM 120A
TO "CC-8"
"CC-1"~"CC-9"
(MECH. ITEM, TYP. OF 9EA)
"CC-1" THRU "CC-9"
CENTRAL CONTROLLER W/ EMERGENCY SHUT-OFF
IN RM 120A
TO "CC-5"
IN RM 120A
TO "CC-3"
IN RM 120A
TO "CC-6" IN RM 120A
TO "CC-9"
NOTES FOR HVAC CONTROL
SEE DRAWING M-11 AND M-12 FOR HEAT PUMP UNIT AND ERV CONTROL SCHEMATIC DIAGRAM
C C
1.
UP UP
UP
4 -1 4 -2
56 -1 6 -2
4 -3 3 -1 3 -2 3 -3
C C
Tch Tch Tch Tch Tch Tch
Tch
Tch
TchTchTchTchTchTchTch Tch
Tch
Tch Tch Tch Tch
TchTch Tch
Tch Tch
Tc
Tch
T
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
D - 19 - 17
29 JUL 19
E-10
CAMP CARROLL
KIM, CK
SCALE : 1 /100- E10
P-1
SCALE : 1 /100- E10
P-2
HVAC CONTROL PLAN1 - 2ND FLOOR
HVAC CONTROL PLAN1 - 3RD FLOOR
3RD FLOOR
HVAC CONTROL PLAN1 - 2ND FLOOR
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
224223222
204 206205
207A
207B
209B
209C
210A 209A
210B
210C 211B
211A
213214A
214B
216A
216C
216B
215A
215C 214C
215B
"L2A" "L2B" J
C
C
C C
C
C C C
C
C C
C
C
C
C
C
C
C
C
C C
C
C C
C
C C
C
C
C
C
C
C
C
C
C
TO OUTDOOR UNIT "4-2"
C
TO OUTDOOR UNIT "5"
C
C
C
C
C
C
C
C C
C
C
C
C
C
C C
C
C
C
CC
C C
C
C
C
C
TO OUTDOOR UNIT "3-2"
C
C
C
CC
C
C
UNIT
TO 1ST FLJ J
J
J
J
J
J
J
J
J
J
J J J
J J
JJ
J J
J J
J
J
J
J
J
J
JJJ
JJ
JJJ
J
311D
311A 311C
311B
308A
309 308B
319B
319C318317
316A
316B
319A
304A
305B
304B 305A
307C 307B
307A
"L3B""L3A"
J
C
C C
C C C
C
C
C
C
C
C C
C
C
C C
C C
C
TO OUTDOOR UNIT "4-3"
C
C
TO OUTDOOR UNIT "6-2"
C
C
C
C C
C
C
C
C C
C
C
C C
C
C
C
C
C
C
C C C
C
C
C
C
C
C
C
C
C C
C
C
TO OUTDOOR UNIT "3-3"
C
CUNIT
TO 1ST FL
J
J
J
J
J J
J J
J
J J
J
J
J
J J
J
J
J
J
JJJ
J
J
J
J
J J
J
J
J
311E
C
C
C
1.
NOTES FOR HVAC CONTROL
SEE DRAWING M-11 AND M-12 FOR HEAT PUMP UNIT AND ERV CONTROL SCHEMATIC DIAGRAM
Tch
Tch
Tch
Tch Tch Tch Tch
Tch Tch Tch
TchTch
Tch
Tch Tch Tch
Tch Tc Tch Tch Tch
Tch
Tch
TchTchTchTch
Tch
TchTch
Tch
UP DN UPDN
DN UP
COMM
DN DN
DN
Tch
Tch
TchTch
Tch
Tch
Tch
Tch
Tch
Tch
Tc
Tch
Tch
Tch
TchTchTch
Tch
Tch
Tch
Tch
Tch
Tch
TchTch
Tch
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
D - 19 - 17
29 JUL 19
E-11
CAMP CARROLL
KIM, CK
- E11
P-1
SCALE : 1 /100
HVAC CONTROL PLAN2 - 1ST FLOOR
HVAC CONTROL PLAN2 - 1ST FLOOR
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
C
IN RM 120A
TO "CC-1"
C
C C
IN RM 120A
TO "CC-2"
C
C
C
IN RM 120A
TO "CC-3"
C
C
C
C C
- E11
P-1
SCALE : 1 /100
122123124125126127
129 130 131 132 135 136
VELVE
120A
120B
114 113
109A107106105104
ELEC
MECH
COMM
HVAC CONTROL PLAN2 - 1ST FLOOR
"CC-1"~"CC-9"
J
JJ
J
J
(MECH. ITEM, TYP. OF 9EA)
"CC-1" THRU "CC-9"
CENTRAL CONTROLLER W/ EMERGENCY SHUT-OFF
(MECH. ITEM)
NEW VENTILATOR CONTROLLER
1.
NOTES FOR HVAC CONTROL
SEE DRAWING M-11 AND M-12 FOR HEAT PUMP UNIT AND ERV CONTROL SCHEMATIC DIAGRAM
UP UP
UP
C C
VC
VC
VC
VC
VC
VC
OA
EA
SA
RA
OA
EA
SA
RA
O A
E A
S A
R A
O A
E A
S A
R A
OA
EA
SA
RA
O A
E A
S A
R A
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
29 JUL 19
66 E-12
CAMP CARROLL
KIM, CK
3RD FLOOR
HVAC CONTROL PLAN2 - 2ND FLOOR
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
D - 19 - 17
C
C
IN RM 120A
TO "CC-4"C
219218 224223222
204 206205
207A
207B
209B
209C
210A 209A
210B
210C211B212
211A
213214A
214B
216A
216C
216B
215A
215C 214C
215B
C
C
C C IN RM 120A
TO "CC-5"
C
IN RM 120A
TO "CC-6"
IN RM 120A
TO "CC-7"
C
C
C
C
CC
C
IN RM 120A
TO "CC-8"
C
C
C
C
C
C
C
C
C
IN RM 120A
TO "CC-9"
SCALE : 1 /100- E12
P-1 HVAC CONTROL PLAN2 - 2ND FLOOR
SCALE : 1 /100- E12
P-2 HVAC CONTROL PLAN2 - 3RD FLOOR
311D
311E
311B
310 308A
309 308B
319B
318317
316A
319A
303 304A
305B
304B
307C
307A
307B
305A
316B 319C
311A
311C
J
J
J
J
J
J
J
JJ
J
J
J
1.
NOTES FOR HVAC CONTROL
SEE DRAWING M-11 AND M-12 FOR HEAT PUMP UNIT AND ERV CONTROL SCHEMATIC DIAGRAM
UP DN UPDN
DN UP
DN DN
DN
VC
VC VC
VC
VC
VC
VC
VC VC
VC
VC
VC
OA
EA
SA
RA
OA
EA
SA
RA
O A
E A
S A
R A
O A
E A
S A
R A
OA
EA
SA
RA
OA
EA
SA
RA
O
A
E A
S A
R A
OA
EA
SA
RA
O A
E A
S A
R A
O A
E A
S A
R A
O A
E A
S A
R A
OA
EA
SA
RA
COMM
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
D - 19 - 17
29 JUL 19
E-13
CAMP CARROLL
KIM, CK
SCALE : 1 /100- E13
P-1
COMM
C R
T T
B
122123124125126127
129 130 131 132 133 134 135 136
VELVE
120A
120B
114 113 112 111
109A108107106105104
ELEC
MECH
EXST NEW
LEGEND FOR COMMUNICATION
QUADPLEX OUTLET, TYPE ’B’
CR CR COMMUNICATION RACK
TTB TTB TELEPHONE TERMINAL BOARD
TTC
104MM CONDUIT
CABLE AND 1-12 STRAND SINGLE-MODE FOC IN
EXISTING 1-100PAIR, #24AWG TELECOMMUNICATION
EXISTING EXTERIOR PULLBOX, 600MM W X 600MM X 150MM T
CABLE IN 104MM CONDUIT FROM EXISTING "TTC"
EXTEND NEW 1-200PAIR, #24AWG TELECOMMUNICATION
EXISTING TELEPHONE TEMINAL CABINET "TTC"
EXISTING 1-300PAIR, #24AWG TELECOMMUNICATION CABLE
COMMUNICATION PLAN - 1ST FLOOR
L L
L
L L
L L
L
L
L
LL L L
L L
L
L
L
L
L
L
L
L L
L
L
L
L
L
L
L
LL
L
L
L
L
COMMUNICATION PLAN - 1ST FLOOR
LL 2W - CAT-6, 4PAIR, #24AWG IN 27MM RMC
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
UP UP
UP
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
D - 19 - 17
29 JUL 19
E-14
CAMP CARROLL
KIM, CK
219218 224223222221220
204 206205
207A
207B
209B
209C
210A 209A
210B
210C211B212
211A
213214A
214B215B
215C 214C
216A 215A
216C
216B
COMM
314 313 312
311D
311E
311A
311C
311B
310 308A
309 308B
319B
319C
318317
316A
316B
319A
303 304A
305B
304B
305A
307C
307A
307B
SCALE : 1 /100
SCALE : 1 /100- E14
P-2
- E14
P-1
COMM
COMMUNICATION PLAN - 2ND FLOOR
COMMUNICATION PLAN - 3RD FLOOR
L
L
L
L
L
L
L
L
L L
L
L
L
L L L
L L
L
L
L L
L
L L
L L
L
L
L
L
L
L L
L L
L
L
L
L
L
L L
L
L
L
L
L
L
L
L L L L
L
L L
L L
L
L
L L
L
L
L
L
L L
L
L
L L
L
L
L
L
L
L
L
L
L
L
L
L L
L
L
L
L
L L
L
LL
L L
L L L L
L
L
L L
L
L
L
L
L
L
L L
L L
L
L L
L
L
L
L L
L
L L L L
L
L
L
L
L
L
L
L
L
L
L
L
L L
L
L L
L
L L
L
L L L
L L
L
L
L
L
L
L
L
LL
L
L
L
L
LL
L
L
L
L
L L
L
L
L L
L
L
L
L
L
L
L L L
L
L L
L
L
L
L
L
L
LL
L L
3RD FLOOR
COMMUNICATION PLAN - 2ND FLOOR,
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230
COMM
UP DN UPDN
DN UP
DN DN
DN
DESIGNED BY
CHECKED BY
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :SAFETY REP
SIGNAL REP
FES
FORCE PROTECTION
CHIEF,
DESIGN & TECH. REVIEW Br.
O & M
HOUSING DIV.
REVIEWED BY
SYMBOL BY CHK.ZONE DATE APVD.
R E V I S I O N S
DESCRIPTION
UNITED STATES ARMY GARRISON DAEGU
DIRECTORATE OF PUBLIC WORK
ENGINEERING DIVISION, DESIGN & TECHNICAL REVIEW Br
UNIT #15746, APO AP 96218-5746
DATE:
SIN, YS
SHEET OFAS SHOWN
ELECTRICAL
HS-00557-7J D - 19 - 17
29 JUL 19
CAMP CARROLL
KIM, CK
E-15
- E15
D-2
SCALE : NONE
COMMUNICATION SYSTEM DIAGRAM - 2ND FLOOR
3M LENTH MIN
SERVICE LOOP,
1-#6 AWG "BC"
NEW GROUNDING WIRE,
"BC" IN 22 MM RMC.
NEW GROUNDING WIRE,1-#3/ 0 AWG
GROUNDING LUG (TYPICAL)
NEW UL LISTED TWO HOLE
FIRE RATED PLYWOOD 5EA
1200MM W X 2400MM H X 20MM THK,
NEW TELEPHONE TERMINAL BOARD(TTB)
(100mm(W) X 6.4mm(T) X 300mm(L)
GROUNDING BUSBAR (TMGB)
NEW TELECOMMUNICATION MAIN
FIBER OPTIC CABLE
EXISTING 1-12 STRAND SINGLE MODE
EXISTING 1-300PAIR, #24AWG TEL CABLE
EXISTING 1-100PAIR, #24AWG TEL CABLE
G
G
G
G
G
G
G
FIBER OPTIC CABLE
NEW 1-12 STRAND SINGLE MODE
COM. RM
TO 2ND FLOOR
COM. RM
TO 3RD FLOOR
OPTIC CABLE
EXISTING 1-12STRAND SINGLE MODE FIBER
EXISTING 1-100PAIR, #24AWG TEL CABLE AND
104MM CONDUIT
G
G
3M LENTH MIN
SERVICE LOOP,
FIBER OPTIC CABLE
EXISTING 1-12 STRAND SINGLE MODE
NEW 1-50PAIR, #24AWG TEL CABLE
(TYP. OF 1EA AND 4EA)
110 TYPE TERMINAL BLOCK
NEW 50PAIR BACKBOARD MOUNTED
COM. RM
TO 3RD FLOOR
COM. RM
FLOOR
FROM 1ST
COM. RM
FLOOR
FROM 1ST
G
G
1-#1/ 0 AWG "BC"
NEW GROUNDING WIRE,
FIBER OPTIC CABLE IN 104MM CONDUIT
AND NEW 1-12 STRAND SINGLE MODE
NEW 1-50PAIR, #24AWG TEL CABLE
FIRE RATED PLYWOOD 2EA
1200MM W X 2400MM H X 20MM THK,
NEW TELEPHONE TERMINAL BOARD(TTB)
NEW GROUNDING WIRE,1-#3/ 0 AWG "BC"
NEW GROUNDING WIRE, 1-#6 AWG "BC"
WITH QUAD COVER PLATE (TYP. OF 40EA)
CAT-6, 8-PIN (RJ45 TYPE)
NEW DUAL MODULAR JACK
- E15
D-1
SCALE : NONE
COMMUNICATION SYSTEM DIAGRAM - 1ST FLOOR
WITH QUAD COVER PLATE (TYP. OF 105EA)
CAT-6, 8-PIN (RJ45 TYPE)
NEW DUAL MODULAR JACK
1ST FLOOR AND 2ND FLOOR
COMMUNICATION SYSTEM DIAGRAM -
EQUIVALENT)
MANUFACTURE: CIRCA ENT. INC. OR
(MODEL NO. 1880ENA1/NSC-100,
ENTRANCE TERMINAL BLOCK 110 TYPE
NEW 1EA OF 100PAIR PROTECTED
BAR IN MAIN PANEL "MDP"
CONNECT TO MAIN GROUND
L
L
L
L
L
L
L
L
L
DEDICATED CIRCUIT OF "LT-3" (TYP. OF 1EA)
2P-3W-125V-20A, GROUNDING TYPE WITH
NEW SURGE SUPPRESSION TYPE DUPLEX RECEPTACLE,
2100MM H X 475MM W
FLOOR MOUNTED RACK,
PATCH PANEL W/6-PIN MOD CONNECTORS
NEW 6EA-24PORTS RACK MOUNTED, CAT 6
CAT 6 PATCH CORDS, 105EA
PORTS AS REQUIRED (GFM)
FIBER OPTIC SWITCH, NUMBER OF
FIBER OPTIC PATCH CORD, 1-SINGLE MODE
PRODUCED PIG TAIL
INCL. FUSION SPLICE FACTORY
12 PORTS, RACK MOUNTED TYPE,
NEW FIBER OPTIC DISTRIBUTION FRAME,
NEW CAT 6 PATCH CORDS, 48EA
VOICE PATCH PANEL, CAT-6
NEW 6EA-24PORTS RACK MOUNTED
WITH DEDICATED CIRCUIT OF "LT-3" (TYP. OF 1EA)
MIN 6 RECEPTACLES, 2P-3W-125V-20A, GROUNDING TYPE
NEW RACK MOUNTED OUTLETS, SURGE SUPPRESSION TYPE
(480mm(W) X 13mm(T) X 50mm(L)
GROUNDING BUSBAR (TMGB)
NEW TELECOMMUNICATION MAIN
NEW CABLE TRAY 200MM W X 100MM H (TYPICAL)
NEW CAT 6 PATCH CORDS, 48EA
CAT 6, 4PAIR, #24AWG (TYP. OF 220EA)
(TYP. OF 1EA AND 4EA)
110 TYPE TERMINAL BLOCK
NEW 50PAIR BACKBOARD MOUNTED
DEDICATED CIRCUIT OF "LT-3" (TYP. OF 1EA)
2P-3W-125V-20A, GROUNDING TYPE WITH
NEW SURGE SUPPRESSION TYPE DUPLEX RECEPTACLE,
2100MM H X 475MM W
FLOOR MOUNTED RACK,
PATCH PANEL W/6-PIN MOD CONNECTORS
NEW 6EA-24PORTS RACK MOUNTED, CAT 6
CAT 6 PATCH CORDS, 105EA
PORTS AS REQUIRED (GFM)
FIBER OPTIC SWITCH, NUMBER OF
FIBER OPTIC PATCH CORD, 1-SINGLE MODE
PRODUCED PIG TAIL
INCL. FUSION SPLICE FACTORY
12 PORTS, RACK MOUNTED TYPE,
NEW FIBER OPTIC DISTRIBUTION FRAME,
NEW CAT 6 PATCH CORDS, 50EA
VOICE PATCH PANEL, CAT-6
NEW 6EA-24PORTS RACK MOUNTED
WITH DEDICATED CIRCUIT OF "LT-3" (TYP. OF 1EA)
MIN 6 RECEPTACLES, 2P-3W-125V-20A, GROUNDING TYPE
NEW RACK MOUNTED OUTLETS, SURGE SUPPRESSION TYPE
(480mm(W) X 13mm(T) X 50mm(L)
GROUNDING BUSBAR (TMGB)
NEW TELECOMMUNICATION MAIN
NEW CABLE TRAY 200MM W X 100MM H (TYPICAL)
NEW CAT 6 PATCH CORDS, 48EA
CAT 6, 4PAIR, #24AWG (TYP. OF 80EA)
IN COMM. RM (TYPICAL)
PANEL ON COMMUNICATION RACK
WIRE TO CONNECTED TO PATCH
NEW 2W - CAT-6, 4PAIR, #24AWG IN 27MM RMC
IN COMM. RM (TYPICAL)
PANEL ON COMMUNICATION RACK
WIRE TO CONNECTED TO PATCH
NEW 2W - CAT-6, 4PAIR, #24AWG IN 27MM RMC
(2-1 ADA, HQ)
REPAIR BUILDING NO. S-230