GENERAL NOTES

1.

2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE

NOTED ON THE DRAWING.

LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE

PANELBOARD SEE SPECIFICATION

SAFETY SWITCH 1524mm TO CENTER OF THE ENCL

RECEPTACLE,TELEPHONE OUTLET 305mm TO CENTER OF THE ENCL

MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL

1676mm TO CENTER OF THE ENCL

2286mm TO CENTER OF BELL

3.

4.

6.THE SOIL RESISTANCE TO GROUND FOR THE ELECTRICAL AND COMMMUNICATION

SYSTEMS SHALL BE 25 OHMS OR LESS. THE SOIL RESISTANCE TEST SHALL BE

7.

COORDINATED WITH THE CENTRAL FIRE DEPARTMENT SO THAT

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

ON CEILINGDETECTOR

1372mm TO CENTER OF STATIONMANUAL PULL STATION

5.

CONDUCTED BY THE CONTRACTOR TO OBTAIN THE REQUIRED SOIL RESISTANCE.

INDICATEDS 2 #12AWG IN 16C

INDICATEDS 3 #12AWG IN 16C

INDICATEDS 4 #12AWG IN 16C

A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;

1219mm TO CENTER OF THE ENCLWALL SWTICH

CONDUIT UNLESS OTHERWISE INDICATED.

ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C

AND LOCATION OF THE F/A ANTENNA WITH THE CENTRAL FIRE DEPARTMENT

THE CONTRACTOR SHALL SUBMIT THE SHOP DRAWING FOR THE MOUNTING

TO TRANSMIT THE ALARM RADIO SIGNAL WAVE WITHOUT ANY OBSTRUCTION.

DETAIL OF THE F/A ANTENNA, AND COORDINATE THE MOUNTING HEIGHT

F/A EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE EQUIPMENT SHOULD BE COMPATIBLE WITH THE MAIN EXISTING

1.

SCOPE OF WORK

F/A & MNS EQUIPMENT IN THE CENTRAL FIRE DEPARTMENT.

THE MANUFACTURER AND MODEL OF NEW F/A& MNS EQUIPMENT SHALL BE

F/A &MNS CONTROL

COMBO. SPEAKER & STROBE

8.

SINGLE POLE TOGGLE SWITCH, 15A-125V

L E G E N D

FLEXIBLE CONDUIT W/CONNECTORS

LIGHTING

WIRING

POWER

INTERIOR

S

SYMBOL DESCRIPTION

DESCRIPTION

DESCRIPTION

T

J

THERMOSTAT (UNDER MECH. ITEM)

JUNCTION BOX

SYMBOL

SYMBOL

SAFETY SWITCH

C CONTROL CIRCUIT

AND GOVERNMENT INSTALLED

GOVERNMENT FURNISHED

GFGI

WEATHERPROOFWP

LA LIGHTNING ARRESTER

EXPLOSIONPROOFEP

DISTRIBUTIONDIST

GROUND FAULT PROTECTIONGFP

A AMPERE

AC ALTERNATING CURRENT

AF/AT AMPERE FRAME/AMPERE TRIP

AWG AMERICAN WIRE GAUGE

BC BARE COPPER

BLDG BUILDING

BRKR BREAKER

C CONDUIT

CB CIRCUIT BREAKER

CKT CIRCUIT

CONN CONNECTION

CT CURRENT TRANSFORMER

DET(S) DETAIL(S)

DIAG DIAGRAM

DISC DISCONNECT

DWG(S) DRAWING(S)

EA EACH

EM EMERGENCY

ENCL ENCLOSURE

EXST EXISTING

F/A FIRE ALARM

FL FLOOR

FLUOR FLUORESCENT

FXTR FIXTURE

GEN GENERATOR

GND GROUND

HP HORSE POWER

HZ HERTZ

INCAND INCANDESCENT

INSTL INSTALLATION

J-BOX JUNCTION BOX

K KILO

KV KILO VOLT

KVA KILO VOLT AMPERE

LTG LIGHTING

MAG MAGNETIC

MAX MAXIMUM

MIN MINIMUM OR MINUTE

MTG MOUNTING

NO NUMBER

O/H OVER HEAD

PH PHASE

PNLBD PANELBOARD

PRIM PRIMARY

PWR POWER

Q'TY QUANTITY

RCPT RECEPTACLE

REQ'D REQUIRED

SCHED SCHEDULE

SEC SECONDARY

SPEC SPECIFICATION

STD STANDARD

SW SWITCH

TEL TELEPHONE

TYP TYPICAL

U/G UNDERGROUND

V VOLT

VA VOLT AMPERE

W WATT

W/ WITH

XFMR TRANSFORMER

& AND

CABNET TYPE, RATED WATT ON LTG SCHEDULE

LED LIGHTING FIXTURE, WALL MOUNTED OR UNDER

ON LTG SCHEDULE, WET LOCATION

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

HOMERUN CIRCUIT TO PANELBOARD

TYPE OF MTG ON LTG SCHEDULE

EXTERIOR LED LIGHTING FIXTURE, RATED WATT &

TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING

ABBREVIATION

THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM

IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE

MECHANICAL DRAWINGS.

ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG

WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.

THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR

ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.

FMCP

FTR

ANTENNA

AUXILIARY

DESCRIPTION

F

TELEPHONE OUTLET

SYMBOL

CTC CATV SYSTEM CABINET

CATV OUTLET

ADDRESSABLE FA MANUAL PULL STATION

WP

F M

TTC

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL

MOUNTED TYPE

F/A & MASS NOTIFICATION SPEAKER "WP" WALL

STROBES

WALL MOUNTED SPEAKER /COMBO. (FA+MNS)VISUAL

CONNECTION

BUILDING TRANSMITTER UNIT FOR FIRE ALARM

SYSTEM

F

WIRING FOR TELEPHONE LINET

BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL

WIRING CONCEALED IN THE CEILING AND WALL

F/M

L

WP

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-30A-125/250V, GROUNDING

TYPE WITH PLUG

SINGLE RECEPTACLE, 3P-4W-50A-125/250V, GROUNDING

L

W/EMERGENCY UNIT

WIRING TO UPSTAIR OR DOWNSTAIR

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

L

L

THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE

WIDTH OF DUCT EXCAVATION.

AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.

TO THEIR ORIGINAL CONDITION AND OPERATION DURING

ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES

THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING

CIRCUIT INTERRUPTER TYPE,WEATHER PROOF

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

CIRCUIT INTERRUPTER TYPE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

EXIT LIGHT, SINGLE FACE, WALL MOUNTED TYPE

(CEILING MOUNTED TYPE W/ARROW)

L

TELEPHONE TERMINAL CABINET

STEEL CONDUIT

FIRE ALARM SYSTEM CIRCUIT, FACTORY PAINTED RED

TYPE

SINGLE RECEPTACLE, 2P-3W-20A-125V, GROUNDING

MAGNETIC MOTOR STARTER

FAN MOTOR (UNDER MECH. ITEM)

M MOTOR (UNDER MECH. ITEM)

UH

S

WHM

MANUAL MOTOR STARTER W/PILOT LAMP

WATTHOUR METER

SAFETY SWITCH

S

TS TAMPER SWITCH (UNDER MECH. ITEM)

FS FLOW SWITCH (UNDER MECH. ITEM)

F

MANUAL MOTOR STARTER W/PILOT LAMP AND

3-POSITION SELECTOR SWITCH(H-O-A)

PANELBOARD OR LOADCENTER

TV

3 & 4-WAY SWITCH, 15A-125V

L

L

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

L

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

W/EMERGENCY BATTERY UNIT

ON LTG SCHEDULE

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

ELECTRIC UNIT HEATER

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

SCOPE OF WORKS

LEGEND, GENERAL NOTES AND

E-1

2.

12.

13.

14.

5.

A. REPAIR/MAINTENANCE ( K )

10.

11.

9.

15.

CEILING.

ALL WIRING SHALL BE CONCEALED ABOVE CEILING WHEN THE ROOM HAS

CATV BEFORE CONSTRUCTION.

CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,

AND GOVERNMENT ACCEPTANCE.

PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION

CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO

FIRE CODE AND SPECIFICATIONS.

OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,

ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS

OR RENOVATION.

CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION

THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING

FIXTURE A MINIMUM DISTANCE OF 458mm.

FIRE ALARM DETECTORS SHALL BE LOCATED TO CLEAR ANY LIGHTING

UNITS.

CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER

CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY

16.

4.

7.

6.

NEW.

W/COVER PLATES AND ASSOCIATED WIRING & CONDUIT WITH

REPLACE EXISTING CATV CABINETS & PULLBOXES, OUTLETS

WIRING AND CONDUIT.

REQ'D) DEVICE, LOCAL OPERATING CONSOLE AND ASSOCIATED

VISUAL SIGNAL STROBES, MICROPHONE, SPEAKER (WATTAGE AS

DETECTOR & RELAY MODULE, BUILDING TRANSMITTER, ANTENNA,

NOTIFICATION SYSTEM PANEL, MANUAL PULL STATION, SMOKE

NEW ADDRESSABLE FIRE ALARM CONTROL AND MASS

REPLACE DETERIORATED FIRE ALARM CONTROL SYSTEM WITH

3.

SYSTEM WITH ASSOCIATED WIRING AND CONDUIT.

REMOVE AND REINSTALL EXISTING CCTV CAMERAS & MONITORING

3S 4S

WITH NEW.

CONTROLLED LIGHTING CONTACTOR, WIRES AND CONDUITS

LIGHTS, EXTERIOR LIGHTS, LIGHT SWITCHES, PHOTOCELL

REPLACE DETERIORATED EXISTING LIGHTING FIXTURES, EXIT

WITH NEW.

BREAKERS INDICATED IN DRAWING, POWER WIRING & CONDUITS

REPLACE EXISTING RECEPTACLES AND COVER PLATES, CIRCUIT

SYSTEM WITH NEW.

CONTROL SYSTEM, WIRES AND CONDUITS FOR MECHANICAL

MANUAL MOTOR STARTERS, JUNCTION BOXES, SAFETY SWITCHES,

REPLACE DETERIORATED EXISTING MAGNETIC MOTOR STARTERS,

PLATES AND ASSOCIATED WIRING AND CONDUIT WITH NEW.

EQUIPMENT RACK AND ACCESSORIES, OUTLETS W/ COVER

REPLACE DETERIORATED EXISTING TELEPHONE TERMINAL BOARD,

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

L

ON LTG SCHEDULE, DOWN LIGHT

LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG

D SINGLE POLE DIMMING SWITCH, 1000W-125V

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-2

NEW 1ST & 2ND FLOOR LIGHTING PLAN

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-3UP

FEC

(GFGI)

OVEN

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

LAUNDRY

STAIR-1

BALCONY

TV/LOUNGE ROOM

STORAGE

BULK

L

S

FEC

W W

W W

W W

W

D

D

D

D

D

D

D

UP

STAIR-2

UP

"RB1"

"RB2"

"RB3"

"RB4"

"RB5"

"RB6" "RB8"

"RB7"

"RB10"

"RB9"

"RB12"

"RB11"

"RB14"

"RB13"

"RB16"

"RB15"

S

S

MP2A-1

MP1A-8MP1A-7

J

"MP2A""MP2"

L

L

L

L

L L L L L L L L L L L L

L

L

LLLLLLLLLLLL

L

L

L

L

L L

L L

S

L

L

L

S

L

L

L L

L L

S

S

SCALE: 1 : 100

NEW 1ST FLOOR LIGHTING PLAN

SCALE: 1 : 100

NEW 2ND FLOOR LIGHTING PLAN

OLCP

UP

FEC

UP

FEC

107108

STORAGE

111112

125124

STAIR-2

STAIR-1

139138

MECH ROOM

VEST-2

VEST-1

OFFICE

SUPPLY ROOM

TEL/COMM ROOM

LOBBY

CORRIDOR-1 CORRIDOR-2

W. TOILET M. TOILET

BALCONY

BALCONY

JANITOR

FEC

CONFERENCE

EOC

SEC VAULT

COMM/

OFFICE

OFFICE

WAR ROOM

ROKA-2

S-3 OFFICES-6 OFFICE

OFFICE

CHAPLAIN

ASST OFFICE

CHAPLAIN

S-4 OFFICE

S-2 OFFICE

ROKA-1

UP

FEC

129127

OFFICE

COMMANDING

VEST-3

VAULT

CRYPTO

STAIR-3

SGT MAJ

COMMANDING

OFFICE

XO OFFICE

OFFICE OFFICE

S-1 OFFICE

STORAGE

ROOM

WAITING

TOILET

L L

L

L

L

L L L L L L L L L L

L

L

LLLLLLLLLLL

"MP1"

"MP1A"

S

MP1-3

MP1-1,3

MP1A-1,3

MP1A-3

PL1-5

PL1-9 /////////

///PL1-11,13PL1-13

MP1-7

P

S

3S

S

S

S

S S

S

S

S

S

3S

3S

3S

SS

3S

S

S

S

3S

SS

S

S

PL1-3,5

S

PL1-1

PL1-7,9

MP1-5,7

S

F F

JJ

S S

S

SS

L

L L

L

L L

L L L L L L L

L

L L L L

L

L L L L

LLL

L L L

L

LL L

L L L L L

L L L

L L

LL

LLL

L L

L

L L

L

L L

L L

LL

LL

LL

L

L L

L

L

L

L

L

LL

L

L

L

L

L

L

L

L

L L

LL

L

L

L L

L

L

L

L LL

L

L L

L L L L

L L L

L

L L L L L L L LL L L L L L L L L L L L

L

L L

L

S

L

S

L

S

LL

S

S

S

L

L

S

LL

L L

"PL1"

SS

S

S

S

S

S

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "A" LIGHTING PLAN

ON DWG E-3

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "B" LIGHTING PLAN

ON DWG E-3

L L

L

L L

L

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

PULL BOX

L

L

L

(TYPICAL)

2-#10 AWG "TH" & 1-#10(G) IN EXIST CODUIT.

(TYPICAL)

2-#10 AWG "TH" & 1-#10(G) IN EXIST CODUIT.

TO RELOCATED LIGHTING CONTROL PANEL

PROVIDE ASSOCIATED WIRING AND COUDUIT

DIAGRAM ON DWG E-5/CONTRACTOR SHALL

SEE EXTERIOR LIGHTING CONTROL

NEW EXTERIOR LIGHTING CONTROL PANEL

D

FEC

N

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-1

STORAGE

BULK

GAME ROOM

BALCONY

STORAGE

BULK

FEC

FEC

(GFGI)

OVEN

(GFGI)

MACHINE

ICE MAKE338

STAIR-2

UP

REF(GFGI)

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-3

UP

S

S

S S

S

S

S

S

"Rx1"

"Rx2"

JF

FJ

SLEEPING RM

LIVING/

SERVICE AREA

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

S

S S

S

S

S

S

S

SLEEPING RM

LIVING/

FJ

F J

S

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SERVICE AREA

SSSS

S S

S S

S

S S

S

S S S

S S

S

S S

SSS

S

2 3

"Rx15"

"Rx16"

Rx16-1

Rx15-1 Rx1-1

Rx2-1

S3 S3S3

S3

S3 S3S3 S3

L L

L

L

L LL L

L

L

L L

L L

L L

L L

L L

L L

L L L L

L L

L L

L L

L L

L L

L L L

L L

L

L

L

LL

L L

L

L L

L

EXIST LOADCENTER

EXIST LOADCENTER

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-3

LOCATED ON THE ROOF

CONTROL,1-PHASE,120VAC,1KW (MAX.),

PHOTOCELL FOR EXTERIOR LIGHT

"RC2"

"RC1" "RC3"

"RC4"

"RC5"

"RC6" "RC8"

"RC7"

"RC10"

"RC9"

"RC12"

"RC11"

"RC14"

"RC13"

"RC16"

"RC15"

LL

LL

L

L

L L L

L L L

L

L

L L L L L L L L L L L L

L

L

LLLLLLLLLLLL

L

L

L

EXIST PNLBD MP3, MP3A

S

MP3A-1

"MP3A""MP3" MP3A-2

S

3//// ////

CONDUIT DOWN TO 1ST FL

S S

MP1A-10

MP1A-9

(TYPICAL)

EXST EXTERIOR LIGHTING CIRCUIT

S

SCALE: 1 : 100

NEW 3RD FLOOR LIGHTING PLAN

L

TYPICAL "A" MODULE LIGHTING PLAN TYPICAL "B" MODULE LIGHTING PLAN

ON THIS DWG

UNIT MODULE "B" LIGHTING PLAN

SEE TYPICAL LIVING / SLEEPING ROOM

ON THIS DWG

UNIT MODULE "A" LIGHTING PLAN

SEE TYPICAL LIVING / SLEEPING ROOM

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

MODULE LIGHTING PLAN

NEW 3RD FLOOR LIGHTING PLAN &

(TYPICAL)

2-#10 AWG "TH" & 1-#10(G) IN EXIST CODUIT.

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

4 1220

DIODE(LED) EXIT LIGHT FIXTURE, 1PH, 120V,

WALL OR CEILING SURFACE MOUNTED LIGHT EMITTING

SINGLE FACE 4.99W(MAX INPUT) (NS-3a) OR DOUBLE

FACE 7.22W(MAX INPUT) (NS-3b), BATTERY BACK-UP

WITH BATTERY CHARGER

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER &

CEILING RECESSED LIGHT EMITTING DIODE (LED)

143.9mm

.3 m m

210mm

245mm

254mm

100 WALL

222mm

CAST ALUMINUM HOUSING AND CLEAR PRISMATIC LENS

LIGHTING FIXTURE, WEATHER/INSECT PROOF TYPE,

m m

NS-4a & NS-4bNS-3a & NS-3b NS-5a & NS-5b NS-6a & NS-6b

NS-7 NS-8 NS-9 NS-10

NS-11a & NS-11b

E-4

LIGHTING FIXTURE DETAILS

FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH CONVERTER &

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

(NS-11b) ACCESSORIES AS REQUIRED, (NS-11a) & WITH EM UNIT

FIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES

WALL SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

AS REQUIRED, UL LISTED POWER UNITFIXTURE, 1PH, 120V, 18W, WITH CONVERTER & ACCESSORIES, CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)

WET LOCATION SHOWER LIGHT TRIM, UL LISTED POWER UNIT

ACCESSORIES AS REQUIRED, UL LISTED POWER UNIT

CEILING SURFACE/PENDANT MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER AND

ACCESSORIES AS REQUIRED, (NS-6a) & EM UNIT(NS-6b)

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 45W, UL LISTED, WITH CONVERTER &

ACCESSORIES AS REQUIRED, (NS-5a) & WITH EM UNIT (NS-5b)

FIXTURE, 1PH, 120V, 25W, UL LISTED, WITH CONVERTER &

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

ACCESSORIES AS REQUIRED, (NS-4a) & WITH EM UNIT (NS-4b)

CEILING SURFACE MOUNTE DLIGHT EMITTING DIODE (LED)

1PH-120V-22W, HEAVY DUTY CORROSION RESISTANT

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

NS-12a & NS-12b

CEILING RECESSED MOUNTED LIGHT EMITTING DIODE (LED)

FIXTURE, 1PH, 120V, 50W, UL LISTED, WITH DIMMING CONTROL,

EM UNIT (NS-11b) CONVERTER & ACCESSORIES AS REQUIRED, (NS-11a) & WITH

N

R

7 8 9 10 f c b e d a

FOR 1ST FLOOR LFET SIDE

FOR 2ND FLOOR RIGHT SIDE

FOR 3RD FLOOR LEFT SIDE

FOR 1ST FLOOR RIGHT SIDE

FOR 2ND FLOOR LEFT SIDE

FOR 3RD FLOOR RIGHT SIDE

NOT TO SCALE

5 6

H O A

3-POSITION (AUTO-OFF-HAND)

SELECTOR SWITCH

BALCONY LIGHTING CONTROL PANEL, NEMA 1 ENCL.

PHOTOCELL FOR EXTERIOR LIGHT

CONTROL,1-PHASE,120VAC,1KW (MAX.),

LOCATED ON THE ROOFLOCATED ON 1ST FLOOR

PANELBOARD "MP-1A"

COIL VOLTAGE ; 120VOLT

CONTACT AMPERE RATING; 20AMP

120V,60HZ, 6 POLES,

MULTIPOLE LIGHTING CONTACTOR

NEW EXTERIOR LIGHTING CONTROL DIAGRAM

(TYPICAL OF 15 EACH)

22 WATTS, 120V, 60HZ

LED LIGHTING,

EXTRIOR LIGHTING ;

ROOM NAME

WATTS TYPE SHT NO

REMARKSLAMP TYPE

QTY (EA)

MOUNTING METHOD

ROOM NO

CEILING RECESSED

CEILING RECESSED

NS-11a

CEILING RECESSED

CEILING RECESSED

CEILING SURFACE6NS-9

CEILING RECESSED

STORAGE

1ST FL

NS-6b

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

O&MA STD. DET. 40-06-04

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

LED

LED

LED

LED

LED

NS-11b

LED

LED

CEILING RECESSED350LED

18 NS-8

EMERGENCY UNIT

NS-11a

45LED

LED

LED

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

45 NS-6b

NS-6a ---

EMERGENCY UNIT

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED 45

45 NS-5a

NS-5b ---

--- 2

EMERGENCY UNIT

CEILING RECESSED

CEILING RECESSED

4LED ---

--- CEILING SURFACE

CEILING SURFACE

EMERGENCY UNIT

45 1

NS-6a

NS-6b ---

EMERGENCY UNIT

NS-5b ---

25 NS-4b

NS-4a ---

45 ---

NS-6a

NS-6b

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

LIGHTING FIXTURE SCHEDULE

TOILET104

SUPPLY ROOM

TEL/COMM ROOM

VEST-3

VEST-1,VEST-2,

JANITOR

MECH ROOM

CORRIDOR-2

CORRIDOR-1,

ROOM

SGT MAJ, WAITING

OFFICE, COMMANDING101, 102, 103

OFFICE, XO OFFICE

COMMANDING105, 106

EOC, ROKA-1, ROKA-2107, 108, 109

115, 116, 117, VAULT

OFFICE, COMM/SEC

WAR ROOM, S-6 OFFICE,

OFFICE

S-3 OFFICE, OFFICE,119, 120, 121

122, 123

124, 125 W. TOILET, M. TOILET

126, 127, 129, OFFICE, S-1 OFFICE

S-2 OFFICE, OFFICE,

128,130

STORAGE

CRYPTO VAULT,

LOBBY

132, 133, 134

138,139

ROOM NAME

WATTS TYPE SHT NO

REMARKSLAMP TYPE

QTY (EA)

MOUNTING METHOD

ROOM NO

CEILING RECESSEDLIVING/SLEEPING ROOM

SERVICE AREA

CEILING RECESSED

NS-5a

NS-8

WALK-IN CLOSET

LED 1/22

1/4

WALL MOUNTED

CEILING SURFACE

NS-9

EXIT SIGN NS-3 ---

CEILING SURFACE

WALL MOUNTED

CEILING SURFACE/

2ND FL 3RD FL

PLAN

MODULE UNIT

BED ROOM

BULK STORAGE

TV / LOUNGE ROOM 4

CEILING RECESSED

2 CEILING RECESSED

GAME ROOM

30 30

2 2

O&MA STD. DET. 40-06-04

NS-7

LAUNDRY

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

CEILING RECESSED

LED

LED

LED

LED

LED

NS-5b

201-232, 301-332

LED

LED

CEILING RECESSED32 3245LED

18 NS-7

EMERGENCY UNIT

EMERGENCY UNIT

CEILING RECESSED

NS-5b

18 NS-7

LED

LED

LED

LED

LED

LED

LED

LED

LED

LED

NS-6a

NS-6b ---

--- CEILING SURFACE

CEILING SURFACE

EMERGENCY UNIT

NS-6b ---

50 ---

NS-11b

50 NS-11b

NS-5b

NS-5b

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

EMERGENCY UNIT

LIGHTING FIXTURE SCHEDULE

EXTERIOR LIGHT NS-10

ROOM

TOILET / SHOWER

236, 334, 336

LED

NS-11b

NS-11a

NS-11b

NS-6a

CEILING RECESSED

EMERGENCY UNIT

CEILING SURFACE

CEILING RECESSED

EMERGENCY UNIT

CEILING RECESSED

CEILING SURFACE

CEILING SURFACE

50 NS-11a

NS-11b50

50 NS-11b

NS-11a

NS-11a

NS-11b50

NS-7

50 NS-11b

NS-11a

CEILING SURFACE

CEILING RECESSED

CEILING RECESSED

7 CEILING SURFACE

CEILING SURFACE

NS-11a

NS-11b

235 STAIR WAY-1

STAIR WAY-1

NS-11a

NS-5a

CEILING SURFACE

NS-11a

EXTERIOR LIGHT LED 1/22 NS-10 --- 30 CEILING SURFACE

1/4EXIT SIGN NS-3 --- WALL MOUNTED

CEILING SURFACE/

5LED

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

EXTERIOR LIGHTING CONTROL DIAGRAM

LIGHTING FIXTURE SCHEDULE & NEW

CEILING RECESSED

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

E-5

111, 113, 114

CONFERENCE RM,112

OFFICE

OFFICE, CHAPLAIN

S-4, CHAPLAIN ASST

CEILING RECESSED

CEILING RECESSEDLED

LED

EMERGENCY UNIT

50 NS-12a

NS-12b50

DIMMING CONTROL

DIMMING CONTROL

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-6

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-3

UP

FEC

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

LAUNDRY

STAIR-1

BALCONY

TV/LOUNGE ROOM

STORAGE

BULK

L

S

FEC

W W

W W

W W

W

D

D

D

D

D

D

D

UP

STAIR-2

UP

"RB1"

"RB2"

"RB3"

"RB4"

"RB5"

"RB6" "RB8"

"RB7"

"RB10"

"RB9"

"RB12"

"RB11"

"RB14"

"RB13"

"RB16"

"RB15"

MP2A-5

MP2A-4

MP2A-6

M

RH

PL2-10

MP2A-3

REF

ICE

IN 1 "C

3-#8 "THW" & 1-#10 "THW"(G)

SCALE: 1 : 100

NEW 1ST FLOOR POWER PLAN

SCALE: 1 : 100

NEW 2ND FLOOR POWER PLAN

UP

FEC

FEC

108110

STORAGE

111112

125124

STAIR-2

STAIR-1

139138

MECH ROOM

VEST-2

VEST-1

OFFICE

SUPPLY ROOM

TEL/COMM ROOM

LOBBY

CORRIDOR-1

CORRIDOR-2

W. TOILET M. TOILET

BALCONY

BALCONY

JANITOR

FEC

CONFERENCE

EOC

SEC VAULT

COMM/

OFFICE

OFFICE

WAR ROOM

ROKA-2

S-3 OFFICES-6 OFFICE

OFFICE

CHAPLAIN

ASST OFFICE

CHAPLAIN

S-4 OFFICE

S-2 OFFICE

ROKA-1

UP

FEC

129127

OFFICE

COMMANDING

VEST-3

STAIR-3

SGT MAJ

COMMANDING

OFFICEXO OFFICE

OFFICE OFFICE

S-1 OFFICE

ROOM

WAITING

TOILET

UP

MP1-24

LP1-25

LP1-23,25

LP1-24

PL1-17

PL1-16

PL1-14,16

PL1-12

PL1-8

PL1-4

"PL1"

"MP1A"

"MP1"

PL1-2,4

MP1-6

MP1-16

PL1-20

PL1-18,20

LP1-21

LP1-22,24

MP1-15

MP1-19

MP1-17,19

MP1-18

MP1-20,22,24

MP1-14

MP1-13

MP1-11,13

MP1-9,11,13MP1-10

MP1-21

FOR PROJECTOR

CEILING MOUNTED RECEPTACLE

MP1-12,14

MP1-8,10

PL1-18,20

LP1-19,21

PL1-15,17

PL1-6,8

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "A" POWER PLAN

ON DWG E-7

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "B" POWER PLAN

ON DWG E-7

MP2A-8

"MP2A""MP2"

NEW 1ST & 2ND FLOOR POWER PLAN

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

MP1-2

N

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-1

STORAGE

BULK

GAME ROOM

BALCONY

STORAGE

BULK

FEC

FEC

(GFGI)

OVEN

STAIR-2

UP

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

BED ROOM

STAIR-3

UP

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-7

MP3A-4

MP3-18

MP3A-6

MP3A-8

ICE

RH

M

REF

MP3A-2

MP3A-3

IN 1 "C

3-#8 "THW" & 1-#10 "THW"(G)

"MP3A""MP3"

"RC2"

"RC1" "RC3"

"RC4"

"RC5"

"RC6" "RC8"

"RC7"

"RC10"

"RC9"

"RC12"

"RC11"

"RC14"

"RC13"

"RC16"

"RC15"

RH

REF

ICE

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING TYPE,

FOR RANGE HOOD, MOUNTED IN RANGE HOOD CABINET.

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING TYPE,

FOR REFRIGERATOR, MH 305mm FROM FLOOR.

DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

CIRCUIT INTERRUPTER TYPE FOR ICE MAKER, MH 305mm

FROM FLOOR.

M DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUND FAULT

CIRCUIT INTERRUPTER TYPE FOR MICROWAVE OVEN

MOUNTED IN MICROWAVE OVEN SHELVE. (SEE ARCH DRAWING)

SERVICE AREA "Rx2"

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SERVICE AREA

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SLEEPING RM

LIVING/

SERVICE AREA

M R

M R R M

R M

Rx2-3Rx2-2

RC2-10

Rx2-6

Rx2-9

Rx1-9

Rx1-6"Rx1"

Rx1-10

Rx1-3 Rx1-2

"Rx15"

"Rx16"

Rx15-3

Rx15-6

Rx15-9

Rx16-3Rx16-2

Rx16-10 Rx16-6

Rx16-9

Rx15-10

Rx15-2

2 3

1 : 100SCALE:

1 : 100SCALE:

SCALE: 1 : 100

NEW 3RD FLOOR POWER PLAN

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "B" POWER PLAN

ON THIS DWG

SEE TYPICAL LIVING / SLEEPING ROOM

UNIT MODULE "A" POWER PLAN

ON THIS DWG

TYPICAL "A" MODULE POWER PLAN TYPICAL "B" MODULE POWER PLAN

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

MODULE POWER PLAN

NEW 3RD FLOOR POWER PLAN &

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-8

203 204 205 206 207

210211212

STAIR-3

UP

FEC

225 226 227 228 229

231 232 201 202 203

214215

216217 218219

221222223

LAUNDRY

STAIR-1

BALCONY

TV/LOUNGE ROOM

STORAGE

BULK

L

S

FEC

W W

W W

W W

W

D

D

D

D

D

D

D

UP

STAIR-2

UP

RB3-8

C

C

TC H TC H

C

C

TC H TC H

C

C

TC H TC H

C

C

TC H TC H

C C

TC HTC H

C C

TC HTC H

C

TC HTC H

C C

TC HTC H

C

RB2-8 RB4-8 RB6-8 RB10-8 RB12-8 RB14-8

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

RB16-8

RB15-8RB13-8

RB11-8

RB9-8

MP2A-2

"MP2""MP2A"

"PL2"

THC

CRB8-8

RB7-8

RB5-8RB1-8

SCALE: 1 : 100

NEW 2ND FLOOR FAN COIL UNIT POWER/CONTROL PLAN

SCALE: 1 : 100

NEW 1ST FLOOR FAN COIL UNIT POWER/CONTROL PLAN

FAN COIL UNIT, 1PH, 120VAC,

(UNDER MECH ITEM, TYPICAL)

UP

FEC

UP

FEC

108110

STORAGE

111112

115 116 117

125124

STAIR-2

STAIR-1

139138

MECH ROOM

VEST-2

VEST-1

OFFICE

SUPPLY ROOM

TEL/COMM ROOM

LOBBY

CORRIDOR-1 CORRIDOR-2

W. TOILET M. TOILET

BALCONY

BALCONY

JANITOR

FEC

CONFERENCE

EOC

SEC VAULT

COMM/

OFFICE

OFFICE

WAR ROOM

ROKA-2

S-3 OFFICES-6 OFFICE

OFFICE

CHAPLAIN

ASST OFFICE

CHAPLAIN

S-4 OFFICE

S-2 OFFICE

ROKA-1

UP

FEC

129127

OFFICE

COMMANDING

VEST-3

VAULT

CRYPTO

STAIR-3

SGT MAJ

COMMANDING

OFFICE

XO OFFICE

OFFICE OFFICE

S-1 OFFICE

STORAGE

ROOM

WAITING

TOILET

C

TC H

C

C

PL1-28

C

TC H

C

TC H

C

TC H

TC H

C

"PL1"

PL1-26

C

TC H

PL1-27

PL1-30

C

TC H

TC H

C

TC H C

C

C

TC HTC H

C

C

PL1-31

TC H

C

PL1-29

C

TC H

C

C

TC H

C

TC H

TC H

C

TC H

C

C

C

C

TCH

C

TC H

TC H

C

TC H

PL1-27

SPLIT AIR CONDITIONING UNIT

1PH, 120V, 1KW (MECH ITEM)

NON-FUDIBLE, NEMA 3R ENCL.

SAFETY SWITCH, DPST, 30A, 120VFAN COIL UNIT, 1PH, 120VAC,

(UNDER MECH ITEM, TYPICAL)

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

POWER/CONTROL PLAN

NEW 1ST & 2ND FLOOR FAN COIL UNIT

C

"RB1"

"RB2"

"RB3"

"RB4"

"RB5"

"RB6" "RB8"

"RB7"

"RB10"

"RB9"

"RB12"

"RB11"

"RB14"

"RB13"

"RB16"

"RB15"

N

325 326 327 328 329

331 332

301 302

315316317318319320321322323324

STAIR-1

STORAGE

BULK

GAME ROOM

BALCONY

STORAGE

BULK

FEC

FEC

STAIR-2

UP

304 305 306 307 308

309310312 311313314

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-9

RC1-8 RC3-8 RC5-8 RC7-8 RB9-8

RB11-8 RB13-8 RB15-8

C

C

TC H TC H

C

C

TC H TC H

C

C

TC H TC H

C

C

TC H TC H

C C

TC HTC H

C C

TC HTC H

C

C

TC HTC H

C C

TC HTC H

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

C

C

TC HHTC

RB16-8RB14-8RB12-8RB10-8

H

"MP3""MP3A"

MP3A-7

RC8-8RC6-8RC4-8RC2-8

SCALE: 1 : 100

NEW 3RD FLOOR FAN COIL UNIT POWER/CONTROL PLAN

FAN COIL UNIT, 1PH, 120VAC,

(UNDER MECH ITEM, TYPICAL)

C

TH

C

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

POWER/CONTROL PLAN

NEW 3RD FLOOR FAN COIL UNIT

"RC2"

"RC1" "RC3"

"RC4"

"RC5"

"RC6" "RC8"

"RC7"

"RC10"

"RC9"

"RC12"

"RC11"

"RC14"

"RC13"

"RC16"

"RC15"

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

SCALE: 1 : 25

SCALE: 1 : 50

J

DWH

J

P-3

B

UHJ

J

P-1

J

P-2

J

P-4

EF-1

J

(MECH ITEM)

THERMOSTAT FOR COOL

(MECH ITEM)

THERMOSTAT FOR HEAT

4-#8AWG "THW" IN 1" CONDUIT

MMS-3

MMS-3

PM-9

PM-10

MDP-7

T

PM-6

PM-2

T2

PM-7

C

T1

C

MMS-1

PM-5

"PM"

"MDP"

J

C

D

D

D

D

D

D

W

W

W

W

W

SINK

D

"PL2"

PL2-6

PL2-13

PL2-12

PL2-9

PL2-8

PL2-2

PL2-4

PL2-14

PL2-15

PL2-3

LAUNDRY ROOM ENLARGED PLAN (2nd FLOOR)

MECH ROOM ENLARGED PLAN

T EF-2

J

MMS-1

COIL VOLTAGE 120V, NEMA1 ENCL.

NEMA SIZE "00", "H-O-A SWITCH, PILOT LAMP,

NEW MAGNETIC MOTOR STARTER, 2P-115VAC,

MMS-2

* ADDITIONAL LEGEND (THIS SHEET ONLY)

MMS-1

MMS-3

MMS-2

MMS-1

IN 16 diaC (TYP OF 7)

3-#10AWG & 1-#10AWG(G)

P-2

B

UH

DWH

EF-2

P-3

P-4

EF-1

P-1

(UNDER MECH ITEM)

CHILLED WATER CIRC. PUMP, 200V/3PH, 5HP,

(UNDER MECH ITEM)

HOT WATER CIRC. PUMP, 200V/3PH, 5HP

(UNDER MECH ITEM)

DOMESTIC HOT WATER CIRC. PUMP, 115V/1PH, 1/2HP

(UNDER MECH ITEM)

DOMESTIC HOT WATER RE-CIRC. PUMP, 200V/3PH, 2HP

(UNDER MECH ITEM)

EXHAUST FAN, 120V/1PH, 1/3HP

E-10

PL2-11

EXIST PNLBD "PM"

EXIST PNLBD "MDP"

& 1- 1/0 AWG(G) IN 103 C

NEMA1 ENCL.

"H-O-A SWITCH, PILOT LAMP, COIL VOLTAGE 120V,

CICUIT BREAKER TYPE(3P-40AT), 3P-250VAC, NEMA SIZE "1",

NEW COMBINATION TYPE MAGNETIC MOTOR STARTER,

NEMA1 ENCL.

"H-O-A SWITCH, PILOT LAMP, COIL VOLTAGE 120V,

CICUIT BREAKER TYPE(3P-20AT), 3P-250VAC, NEMA SIZE "0",

NEW COMBINATION TYPE MAGNETIC MOTOR STARTER,

M

T

EXIST PNLBD "PL2"

W

W

PL2-1

PL2-17

PL2-7

PL2-5

LIQUID CHILLER

EXIST AIR - COOLED

NOT FUSIBLE, NEMA 3R ENCL.

NEW SAFETY SWITCH 3PST-240V-600A,

WATER HEATER, 120V/1PH, 8OW/UNIT

EXIST NATURAL GAS FIRED DOMESTIC HOT

120V/1PH, 380W/UNIT

EXIST NATURAL GAS FIRED HOT WATER BOILER,

WHM

PM-11PM-3

T T

ENLARGED PLAN

MECH ROOM, 2ND FL LAUNDRY ROOM

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

(UNDER MECH ITEM)

EHAUST FAN, 120V/1PH, 1/20HP

(UNDER MECH ITEM)

ELECTRIC UNIT HEATER, 120V/1PH, 3KW

EXIST U/G 4-400MCM "THW"

EXIST WATT HOUR METER

ELECTRICAL

1 2

3 4

A

5 6

7 8

9 10

11 12

LIGHTING RECEPTACLE

RECEPTACLE

REFRIGERATOR

MICROWAVE OVEN

SPARESPARE

SPARE

SPARE

SPARE FAN COIL UNIT

RECEPTACLE

S N

G R D

BALCONY LIGHTING

BALCONY LIGHTING

BALCONY LIGHTING

LIGHTING

LIGHTING RECEPTACLE

RECEPTACLE

BALCONY LIGHTING

BALCONY LIGHTING

BALCONY LIGHTING

S N

G R D

A C

SPARE

5 6

SPACE

SPACE

SPACE

S N

G R D

DOMESTIC HW HEATER

DOMESTIC HW CIRC PUMP

HOT WATER CIRC PUMP

LIGHTING, RECEPTACLE

DOMESTIC HW RECIRC PUMP

HW BOILER

WALL VENTILATION

CHILLED WATER CIRC PUMP

A C

NOT TO SCALE

NOT TO SCALE

EXIST PNLBD "MP1A" CONN DIAGRAM

IN 16C

2-AWG #12& 1-#12 (G)

NOT TO SCALE

EXIST PNLBD "PL1" CONN DIAGRAM

NOT TO SCALE

EXIST PNLBD "PM" CONN DIAGRAM

IN 16C

2-AWG #10& 1-#10 (G)

FIRE ALARM CONTROL/MNS

FA/MNS BOOSTER PANEL#1 FA/MNS BOOSTER PANEL#2

IN 16C

2-AWG #12& 1-#12 (G)

SPACE

13 14

100A

EXIT MAIN LUGS;

LUGS ONLY

EXIST 100A MAIN

LUGS

EXIST 100A MAIN

E-11

EXIST PANELBOARD CONN DIAGRAMS-1

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 22C

NEW 3-AWG #12& 1-#12 (G)

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 22C

NEW 3-AWG #10& 1-#10 (G)

IN 22C

NEW 3-AWG #10& 1-#10 (G)

* NEW AFCI TYPE CIRCUIT BREAKER (TYPICAL)

CIRCUIT BREAKER (TYPICAL)

CIRCUIT INTERRUPTER(AFCI) TYPE

CIRCUIT BREAKER W/ NEW ARC FAULT

REPLACE EXISTING 1P-100AF-20AT

SPACE

SPACE

IN 16C

2-AWG #12& 1-#12 (G)

CIRCUIT BREAKER

REPLACE W/NEW 2P-100AF-20AT

CONN DIAGRAM (TYPICAL)

EXIST LOADCENTER "RB1~16", "RC1~16"

G R D

S N

23 24

25 26

SPACE

SPACE

SPACE

A C

LIGHTS

SPARE

SPARE

SPARE

LUGS

EXIST 400A MAIN

30 MP1A

RECEPTACLE

LIGHTS

LIGHTS

LIGHTS

RECEPTACLE

RECEPTACLE

RECEPTACLE RECEPTACLE

RECEPTACLE RECEPTACLE

RECEPTACLE RECEPTACLE

RECEPTACLEPROJECTOR

RECEPTACLERECEPTACLE

RECEPTACLE RECEPTACLE

RECEPTACLE

RECEPTACLE

VENDING MACHINE

LAN SYSTEM

TELPHONE SYSTEM

GAS LEAK DETECTOR

ELECTRIC UNIT HEATER

NOT TO SCALE

EXIST PNLBD "MP1" CONN DIAGRAM

G R D

S N

A C

LUGS

EXIST 200A MAIN

IN 16C

NEW 2-AWG #12& 1-#12 (G)

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

LIGHTS RECEPTACLE

RECEPTACLE RECEPTACLE

RECEPTACLERECEPTACLE

RECEPTACLERECEPTACLE

RECEPTACLERECEPTACLE

RECEPTACLERECEPTACLE

FAN COIL UNIT FAN COIL UNIT

FAN COIL UNITFAN COIL UNIT

FAN COIL UNIT FAN COIL UNIT

RECEPTACLE

IN 16C

NEW 2-AWG #12& 1-#12 (G)

SPLIT AIR CONDITIONING UNIT

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

SPARE

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

S N

G R D

S N

G R D

SPACE

A C

A C

LIGHTING

RECEPTACLE

RECEPTACLE

FAN COIL UNIT

REFRIGERATOR

ICE MAKER

LIGHTING

RECEPTACLE

LIGHTING

FAN COIL UNIT

RECEPTACLE

ICE MAKER

REFRIGERATOR

SPACE

SPACE

DRYER

SPARE

WASHER

WASHER

DRYER

DRYER

DRYER

WASHER

DRYER

DRYER

SPARE

WASHER

DRYER

SPARE

SPARE

WASHER

RECEPTACLE AND WALL VENT

S N

G R D

A C

NOT TO SCALE

EXIST PNLBD "MP2A" CONN DIAGRAM

NOT TO SCALE

EXIST PNLBD "MP3A" CONN DIAGRAM

NOT TO SCALE

EXIST PNLBD "PL2" CONN DIAGRAM

IN 16C

2-AWG #12& 1-#12 (G)

SPARE

CATV CABINET

CATV CABINET

100A

EXIT MAIN LUGS;

100A

EXIT MAIN LUGS;

LUGS

EXIST 200A MAIN

DRYER

CIRCUIT BREAKER W/ NEW 2P-100AF-20AT

REPLACE EXISTING 1P-100AF-20AT

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 16C

NEW 2-AWG #12& 1-#12 (G)

IN 22C

NEW 2-AWG #10& 1-#10 (G)

IN 22C

NEW 2-AWG #10& 1-#10 (G)

IN 16C

NEW 2-AWG #12& 1-#12 (G)

RANGE HOOD

RANGE HOOD

EXIST PNLBD CONN DIAGRAMS-2

E-12

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

SCALE: 1 : 100

NEW 2ND FLOOR FIRE ALARM CONTROL/MASS NOTIFICATION SYSTEM PLAN

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-13

BED ROOM

204 205 206 207 208

209210211212213214

STAIR-3

UP

FEC

225 226 227 228 229 230 231 232 201 202 203

214215216217218219220221222223224

L

S

FEC

W W

W W

W W

W

D

D

D

D

D

D

D

UP

STAIR-2

UP

SCALE: 1 : 100

NEW 1ST FLOOR FIRE ALARM CONTROL/MASS NOTIFICATION SYSTEM PLAN

COMBINED ADDRESSABLE FIRE ALARM/

FTR BUILDING TRANSMITTER W/BATTERY &

BATTERY CHARGER, NEMA 1 ENCL

W/MOUNTING BARCKET

OMNI-DIRECTION TYPE

FIRE ALARM ANTENNA

DIGITAL VOICE PANEL W/AMPLIFIER & BACK

SYNCHRONIZATION CONTROL MODULE,

24VDC, BUILT-IN ADDRESSABLE POINTS

UP AMPLIFIER (AS REQ'D) & MICROPHONE,

POWER MODULES PANEL(AS REQ'D) AND

MICROPHONE, BATTERY, BATTERY CHAREGER,

MODULE & RELAYS LCD ANNUNCIATOR,

MODULES AS REQ'D, PROGRAMMABLE

MASS NOTIFICATION CONTROL PANEL,

POWER SUPPLY, DIGITAL VOICE MODULE,

FMCP

W/WORDS "FIRE" + MNS-AMBER STROBE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

M F

WP

F ADDRESSABLE MANUAL PULL STATION

SPEAKER (WATTAGE AS REQ'D)

FIRE ALARM/MASS NOTIFICATION

WALL MOUNTED "WP" TYPE,

NEMA 1 ENCL

(15 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

SHALL BE DE-RATED AS REQUIRED)

INCLUDING MICROPHONE &

LOCAL OPERATING CONSOLE(LOC)LOC

PUSH BUTTONS, etc.

* ADDITIONAL LEGEND (THIS SHEET ONLY)

F

WP

ADDRESSABLE MANUAL PULL STATION "WP" TYPE

FMBP BOOSTER PANEL, 1PH, 120VAC

INPUT, 6A(MAX)@24VDC OUTPUT W/CLASS

"A" AS REQ'D WITHSLC MODULE AS REQ'D,

POWER MODULE PANEL (AS REQ'D)AMPLIFIER

GROUND LOOP ISOLATION AND TRANSIENT

PROTECTION BATTERY & BATTERY CHARGER,

NEMA 1 ENCL (TYPICAL)

(AS REQ'D) CONFIGURATION PROGRAMMABLE

R ADDRESSABLE RELAY MODULE

TS

J

J

PS

FS

J

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

FLOW SWITCH W/ADDRESSABLE

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

TEMPER SWITCH W/ADDRESSABLE

PRESSURE SWITCH W/ADDRESSABLE

ADDRESSABLE CARBON MONOXIDE GAS DETECTORCO

UP

FEC

UP

FEC

107108110

STORAGE

111112

125124

STAIR-2

STAIR-1

139138

MECH ROOM

VEST-2

VEST-1

OFFICE SUPPLY ROOM

TEL/COMM ROOM

LOBBY

CORRIDOR-1 CORRIDOR-2

W. TOILET M. TOILET

BALCONY

BALCONY

JANITOR

FEC

CONFERENCE EOC

SEC VAULT

COMM/

OFFICE

OFFICE

WAR ROOM

ROKA-2

S-3 OFFICE

S-6 OFFICE

OFFICE

CHAPLAIN

ASST OFFICE

CHAPLAIN

S-4 OFFICE

S-2 OFFICE

ROKA-1

UP

FEC

129127

OFFICE

COMMANDING

VEST-3

VAULT

CRYPTO

STAIR-3

SGT MAJ

COMMANDING

OFFICE

XO OFFICE

OFFICE OFFICE

S-1 OFFICE

STORAGE

ROOM

WAITING

TOILET

F

WP

M

F

WP

F

M

F

MF

F/M

F

F

F M

WP

WP

F

M

F/M

F/M

F F

F/M F/M

F

M

F

F M

WP

WP

F

M F

F/M

FF

F

F/M

J J

FS TS

FF

F M

C P

F T

R

F

F

F

J JJ JCO

TS PSTS TS

F

F/M

F

M F

WP

WP

F/M

F

F

M

F

F

WP

M F

WP

F

F

M

F

F M

WP

WP

F

M

F

F M

WP

WP

F

M

F/M

F

F

M

F

WP

M

F

WP

F

M

FF

F

F/M

SB SB SB SB SB SB SB SB

F F F F F F

F

F

M WP

WP

F

M

F

M

F/MF/MF/M

F

M

F M

WP

WPF

F

M

F/M

F

M

F/M

F

M

SBSB

F

F

F

F

WP

WP

M

F

SBF

M

F

SB

F

F/M

SBSB

FF

F/M F/M

F

WP

WP

M

F

F F

SB

F

M

F

M

F/M

SB

FF

F/M

FMBPTO

F M

B P

FMBPTO

FS TS

J J

FMCP

TO

L O

C

SEE FIRE ALARM CONTROL/MNS DIAGRAM E-15

BOOSTER PANEL-1, 1PH, 120VAC INPUT, 6A(MAX)

F

F

F

SBSBSBSBSBSBSBSB

FFFFFF F

M

F

M

F

F

WP

WP

M

F

FF

F

M

F

WP

WP

M

F

F

M

F

F/MF/MF/MF/MF/MF/M

FMBPTO

F

F

M

SB

F

F

M

F/M

F

F

M

SB

F

F/M F/M

F

M

F

M WP

WPF

SB SB SB

F F

SB SB SB

F F

F

F

M WP

F WP

F

M

F

M

F/M F/M F

M

F/MF/M

F/MF/M

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

SYSTEM PLAN

CONTROL/MASS NOTIFICATION

NEW 1ST & 2ND FLOOR FIRE ALARM

N

325 326 327 328 329 330

331 332

301 302 303

BED ROOM

BED ROOM

315316317318319320321322323324

FEC

FEC

STAIR-2

UP

303 304 305 306 307 308

309310312 311313314

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-14

SCALE: 1 : 100

NEW 3RD FLOOR FIRE ALARM CONTROL/MASS NOTIFICATION SYSTEM PLAN

W/WORDS "FIRE" + MNS-AMBER STROBE

AS REQ'D)/COMBO. (FA-CLEAR STROBE

WALL MOUNTED SPEAKER (WATTAGE

M F

WP

F ADDRESSABLE MANUAL PULL STATION

SPEAKER (WATTAGE AS REQ'D)

FIRE ALARM/MASS NOTIFICATION

WALL MOUNTED "WP" TYPE,

(15 CANDELA MINIMUM, AMBER STROBE

W/WORDS "ALERT") VISUAL SIGNAL STROBES

SHALL BE DE-RATED AS REQUIRED)

INCLUDING MICROPHONE &

LOCAL OPERATING CONSOLE(LOC)LOC

PUSH BUTTONS, etc.

* ADDITIONAL LEGEND (THIS SHEET ONLY)

FMBP

BOOSTER PANEL, 1PH, 120VAC

NEMA 1 ENCL (TYPICAL)

R ADDRESSABLE RELAY MODULE

"A" AS REQ'D WITHSLC MODULE AS REQ'D,

POWER MODULE PANEL (AS REQ'D)AMPLIFIER

GROUND LOOP ISOLATION AND TRANSIENT

PROTECTION BATTERY & BATTERY CHARGER,

(AS REQ'D) CONFIGURATION PROGRAMMABLE

INPUT, 6A(MAX)@24VDC OUTPUT W/CLASS

ADDRESSABLE MANUAL PULL STATION "WP" TYPEF

WP

FS

J

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

FLOW SWITCH W/ADDRESSABLE

TS

J

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

TEMPER SWITCH W/ADDRESSABLE

SB SB SB SB SB SB SB SB

F F F F F F

F

F

M WP

WP

F

M

F

M

F/MF/MF/M

F

M

F M

WP

WPF

F

M

F/M

F

M

F/M

F

M

SBSB

F

F

F

F

WP

WP

M

F

SBF

M

F

SB

F

F/M

SBSB

FF

F/M F/M

F

WP

WP

M

F

F F

SB

F

M

F

M

F/M

SB

FF

F/M

FMBPTO

F M

B P

FMBPTO

FS TS

J J

FMCP

TO

L O

C

SEE FIRE ALARM CONTROL/MNS DIAGRAM E-15

BOOSTER PANEL-2, 1PH, 120VAC INPUT, 6A(MAX)

F

F

F

SBSBSBSBSBSBSBSB

FFFFFF F

M

F

M

F

F

WP

WP

M

F

FF

F

M

F

WP

WP

M

F

F

M

F

F/MF/MF/MF/MF/MF/M

FMBPTO

F

F

M

SB

F

F

M

F/M

F

F

M

SB

F

F/M F/M

F

M

F

M WP

WPF

SB SB SB

F F

SB SB SB

F F

F

F

M WP

F WP

F

M

F

M

F/M F/M

F

M

F/MF/M

F/MF/M

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

MASS NOTIFICATION SYSTEM PLAN

NEW 3RD FLOOR FIRE ALARM CONTROL/

2#12 IN 16C(FOR POWER)

12#14 IN 21C(FOR SIGNAL)

(TYPICAL)

SEE NOTE 2. BELOW

FOR NO & SIZE OF WIRE

WHICH DEVICE IS LOCATED

(TYPICAL)

ROOM NUMBER

SG

6#14 IN 16C

BOOSTER PANEL#1 (FMBP)

BATTERY CHARGER, POWER MODULE PANEL(AS REQ'D)

SYNCHRONIZATION CONTROL MODULE, DIGITAL VOICE

FIRE ALARM/MASS NOTIFICATION CONTROL PANEL,

24VDC, BUILT-IN ADDRESSABLE POINTS MODULES

AS REQUIRED, PROGRAMMABLE MODULE & RELAYS,

POWER MODULE AS REQ.D LCD ANNUNCIATOR,

NEW FIRE ALARM/MASS NOTIFICATION SYSTEM DIAGRAM

NOT TO SCALE

(TYPICAL)

BATTERY & BATTERY CHARGER, etc. NEMA 1 ENCL

GROUND LOOP ISOLATION AND TRANSIENT PROTECTION

BOOSTER PANEL, 1PH, 120VAC INPUT, 6A(MAX)

@24VDC OUTPUT W/CLASS"A" AS REQ'D WITH

SLC MODULE AS REQ'D, POWER MODULE PANEL (AS REQ'D)

AMPLIFIER(AS REQ'D) CONFIGURATION PROGRAMMABLE RELAYS,

(TYPICAL)

W/MOUNTING BRACKET

LIGHTNING ARRESTER

OMNI-DIRECTION TYPE

W/CONNECTORS IN 16C

COAXIAL CABLE

GROUND CONDUCTOR

#6 "BC" IN 21C

W/WEATHER-PROOF ENCLOSURE

WITH WELDING CONNECTION

GROUND ROD, COPPER CLAD

STEEL, 19mmdia x 3000mmLG

BUILDING

TRANSMITTER

G ~

GROUND ROD, COPPER CLAD

#6, "BC" IN 21C

GROUNDING SYSTEM

CONN TO BLDG ELECTRODE

STEEL, 19mmdiax3000mmLG

WITH WELDING CONNECTION AND

2#12 & 1#12(G) IN 16C

G

SG

CONTROL PANEL (FMCP)

COMBINED FIRE ALARM/

ROOF

3rd FLOOR

1st FLOOR

FIRE ALARM/MASS NOTIFICATION

BOOSTER PANEL#2 (FMBP)

2#12 & 1#12(G) IN 16C

SG

SURGE PROTECTOR

(RATED AS REQ'D)

(TYPICAL)

SURFACE MOUNTED COMBINED ADDRESSABLE

MODULE, POWER SUPPLY, MICROPHONE, BATTERY,

AND AMPLIFIER(AS REQ'D), NEMA 1 ENCL

MASS NOTIFICATION

FIRE ALARM/MASS NOTIFICATION

15.

"FIRE" AND W/CLEAR LENS.

1.

"ALERT" IN RED LETTER AND W/AMBER LENS.

SAFE PATH FACILITY COMMUNICATIONS OR APPROVED EQUAL.

STROBES FOR FIRE ALARM SHALL BE MARKED

STROBES FOR MASS NOTIFICATION SHALL BE MARKED

FOR ABBREVIATION, LEGEND, AND GENERAL NOTES

MASS NOTIFICATION SYSTEM SHALL BE SIMILAR TO WHEELOCK10.

5) EMERGENCY WEATHER CONDITIONS APPROPRIATE FOR THE LOCAL AREA

4) EVACUATION OF THE BUILDING USING EXITS OTHER THAN THE NORMAL MAIN ENTRANCE/EXIT

2) INTRUDER/HOSTILE PERSON SIGHTED WITHIN/AROUND THE BUILDING

1) BOMB THREAT OR ACTUAL BOMB WITHIN/AROUND THE BUILDING

ARE IN ENGLISH AND HANGUL AT LEAST FOR THE FOLLOWING ITEMS.

THE MASS NOTIFICATION SYSTEM SHALL BE ENSURED THAT PRERECORDED MESSAGES

WITH THE MANUFACTURER'S LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE LOCATIONS IN ACCORDANCE

THE APPLICABLE CODE, SPECIFICATIONS AND MANUFACTURER'S EQUIPMENT LISTING.

IS THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE IN ACCORDANCE WITH

THE MASS NOTIFICATION SYSTEM IS CONCEPTUAL. THE NUMBER OF DEVICES SHOWN17.

3) OCCUPANTS DIRECTED TO TAKE COVER WITHIN THE BUILDING

6) "ALL CLEAR" MESSAGE

PER DRAFT UFC 4-021-01.

16.

19.

18.

14. ADDITIONAL RELAY IS PROVIDED AS REQUIRED.

SYNCHRONIZED. AUDIBLE APPLIANCES SHALL PROVIDE THE

APPROVED.

ARCHITECTURAL FEATURES.

LOCATIONS IN ACCORDANCE WITH THE MANUFACTURER'S

IN ACCORDANCE WITH THE APPLICABLE CODE, SPECIFICATIONS

THE MINIMUM REQUIRED AND THE FINAL QUANTITY SHALL BE

AND READY TO USE. THE NUMBER OF DEVICES SHOWN IS

BE PROVIDED WITH CLASS "A" MODULES

HORIZONTAL AND 305mm VERTICALLY.

TRANSMITTER AND ANTENNA.

PANEL COVER.

BREAKER AND/OR DISCONNECT SWITCH.

FOR THE FIRE ALARM AND DETECTION SYSTEM.

AUDIBILITY CALCULATION, WIRE SIZE, NO. OF WIRES

NOTES:

SHALL BE RESPONSIBLE FOR PROVIDING FIRE ALARM

THE FIRE ALARM/MASS NOTIFICATION SYSTEM CONTRACTOR

FIRE ALARM CIRCUIT SHALL BE IDENTIFIED BY A RED LETTER

"FIRE ALARM CIRCUIT" ON THE DEDICATED POWER CIRCUIT

CIRCUIT SHALL BE INDICATED ON THE FIRE ALARM CONTROL

THE POWER CIRCUIT NUMBER DEDICATED TO FIRE ALARM4.

3.

2.

COAXIAL CABLE SHALL BE ONE PIECE BETWEEN BUILDING5.

SYSTEM SHALL BE SEPARATED BY A MINIMUM OF 1220mm

INCOMING AND OUTGOING CLASS "A" RACEWAY OF FA6.

7.

PROHIBITED FOR ALL IDC, NAC AND SLC.

ALL TAMPER SWITCHES, FLOW SWITCHES, PRESSURE

SWITCHES AND NON-ADDRESSABLE INITIATION DEVICES SHALL

COORDINATE THE EXACT DEVICE LOCATIONS WITH ELECTRICAL

AND MECHANICAL SYSTEM EQUIPMENT AND BUILDING

ALL DEVICES AND EQUIPMENT SHALL BE UL LISTED OR FM

ALL AUDIBLE APPLIANCES WITHIN THE BUILDING AND ALL

VISUAL APPLIANCES WITHIN THE SAME ROOM SHALL BE

STANDARD TEMPORAL PATTERN, NFPA 72.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

9.

11.

12.

13.

SHALL COMPLETE THE DESIGN AND INSTALL THE SYSTEM

8.

LISTED INSTALLATION REQUIREMENTS AND WIRE COUNT.

SHOP SUBMITTAL TO SHOW DETAILED INSTALLATION DEVICE

AND MANUFACTURER'S EQUIPMENT LISTING.

THE FIRE ALARM SYSTEM IS CONCEPTUAL. THE CONTRACTOR

ALSO CONDUITS SHALL BE RUN AWAY AT LEAST 900mm

(3-FEET) FROM HVAC, HOT & COLD WATER PIPING.

NEMA 1 ENCL

SURFACE MOUNTED BUILDING

BATTERY CHARGER

F

(MNS) AND NFPA 72.

FA SYSTEM SHALL OVERRIDE THE MASS NOTIFICATION SYSTEM.

2#12 & 1#12(G) IN 16C2nd FLOOR

(WATTAGE AS REQ'D)

(TYPICAL)

"WP" WALL MOUNTED TYPE

F/A & MASS NOTIFICATION SPEAKER

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

FLOW SWITCH W/ADDRESSABLE

SB

WALL MOUNTED SPEAKER (WATTAGE AS REQ'D)

/COMBO. (FA+MNS) VISUAL STROBES

(CANDELA AS REQ'D) (TYPICAL)

FIRE ALARM ADDRESSABLE

W/SOUNDER BASE (TYPICAL)

SMOKE DETECTOR

ADDRESSABLE PHOTOELECTRIC

SEE SHEET NO E-1.

TO FMCP (TYPICAL)

LOC

LOC

(TYPICAL)DETECTOR

ADDRESSABLE SMOKE

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

F F

FFF

FF

F F

TS

J

137 137

J

PS

J

TSTS

J

F

SBSB SB SB SB SB

F

SB SB

SB SB

F

SB SB SB SB

F

SB SBSBSB

F

SB SBSBSBSB

F

SB

SB

F

SB

F

SB SBSBSB SB SB

F

WP

F

M WPF

M

EXT

EXT

WPF

M

EXT

WP

F

M

EXT

WP

F

M

WP

F

M

EXT

WPF

M

EXT

WP

F

M

WP

F

M

WP

F

M EXT

WPF

M

EXT

WPF

M

EXT

WPF

M

EXT

WP

F

M

EXT

WP

EXT

F M

208207

210 209EXT

SB

F

SBSB SB SB SB SB

F

SB SB

FFFF

SB

F

SB

F

SB SBSBSB SB SB

F

WP

F

M

WP

F

M

WPF

M EXT

WP

F

M

EXT

WP

F

M EXT

WP

F

M EXT

WP

F

M

EXT

WP

EXT

F

M

308307

310 309EXT

SB SB SB SB SB SB SB SBSBSB

F

SB SBSBSBSB

F

SB

139131

101102

129127

105106

128126

135 125136

138108

123 122

114113 112

115 116 117 118 119

216 215 214 213 212 211 210 209

208207206205204203

204 205 206203202201

216 215 214 213 212 211

202201232231230

232231

234217218

230229

229228

228227

220221222

226225

223224

324 323 322 321 320 319 317

324 323

325 326

320 319

329 330

316 315

333 335 301 302 303

314 313

304 305 306

311312

309310311312313314315316

316317318

331 332

325 326 327 328 329 330 331 332 301 302 303 304 305 306 307 308

EXT

WP

EXT

WP

EXT

WPWP

EXT

EXT

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

226225

224 223 222 221 220 219 217

WP

EXT

WP

EXT

WP

EXT

WP

EXT

236235233

EXT

WP

EXT

WP

EXT

WP

EXT

WP

EXT

TO MP1A-11

TO MP1A-13

TO TO MP1A-14

FS

J J

TS335 335

FS

J J

TS

235 235

FS

J J

TS

136 136

MANUAL PULL STATION

FIRE ALARM ADDRESSABLE

EXT

WP

EXT

WP

EXT

WP

EXT

WP

"WP"TYPE(TYPICAL)

MANUAL PULL STATION

FIRE ALARM ADDRESSABLE

(TYPICAL)

(UNDER MECH ITEM)

MODULE FOR SPRINKLER SYSTEM

PRESSURE SWITCH W/ADDRESSABLE

TRANSMITTER "BT-XM" W/BATTERY &

MODULE FOR SPRINKLER SYSTEM

(UNDER MECH ITEM)

TEMPER SWITCH W/ADDRESSABLE

CO

7) CARBON MONOXIDE GAS DETECTION MESSAGE WITHIN/AROUND THE BUILDING

E-15

SYSTEM DIAGRAM

NEW FIRE ALARM/MASS NOTIFICATION

MANUAL PULL STATION, WEATHER PROOF

105133

120 121

WP

F

M

EXT 109

F

F

F

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

TAK, YS

131420

SPECIFICATION AND NFPA 72.

SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH SPECIFICATION

ALL CLASS "A" EXCEPTIONS IN NFPA 72 ARE

333336

UP

FEC

137107108

STORAGE

111112

115 116

125124

STAIR-2

STAIR-1

139138

MECH ROOM

VEST-2

VEST-1

OFFICE

SUPPLY ROOM

TEL/COMM ROOM

LOBBY

CORRIDOR-1

CORRIDOR-2

W. TOILET M. TOILET

BALCONY

BALCONY

JANITOR

FEC

CONFERENCE EOC

SEC VAULT

COMM/

OFFICE

OFFICE

WAR ROOM

ROKA-2

S-3 OFFICES-6 OFFICE

OFFICE

CHAPLAIN

ASST OFFICE

CHAPLAIN

S-4 OFFICE

S-2 OFFICE

ROKA-1

UP

FEC

128 130

129127

OFFICE

COMMANDING

VEST-3

VAULT

CRYPTO

STAIR-3

SGT MAJ

COMMANDING

OFFICE

XO OFFICE

OFFICE OFFICE

S-1 OFFICE

STORAGE

ROOM

WAITING

TOILET

RJ-45, DUAL TYPE (TYP)

TEL & LAN OUTLET, CAT 6

CABLE TRAY, 100 X 50 MM

T T T

T

T

T

T T

T

T

T

T

T

TT T

T

T

T

T

T

T

T

T T

T

T

T

T

T T

T

TTTT

T

TTT

T

T

TT

TT

T

TTTT

T

TT

T T

T T

T T

T

T

T

T

T

T

T

T

T

T

T T

T

T

TTT

T T

T

T

TT

T

TT

TTB

TELEPHONE TERMINAL BOARD (TTB)

SEE DIAGRAM

84.58"(H)"x24"(W)x34.67"(D)

NEW EQUIPMENT RACK

LAN

E-16

T

DOUBLE GANG ELECTRICAL

BOX AND FACE PLATE FOR

8-PIN (RJ45 TYPE) WITH

DUAL CAT-6 MODULAR JACK

"1-TEL/1-DATA" (TYPICAL)

AT PATCH PANEL (TYPICAL)

WIRE IN 27C TO BE TERMINATED

2-4PAIR, #24AWG, CAT-6

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

SCALE:

NEW 1ST FLOOR LAN/TEL PLAN

1 : 100

NEW 1ST FLOOR LAN/TEL PLAN

A

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

SYSTEM, S-1974, CP CASEY

REPAIR BUILDING AND INSTALL SPRINKLER

B C D

E F G H

SYMBOL BY

DESIGNED BY

ENERGY MANAGER

SUBMITTED BY

USING AGENCY

APPROVED BY

PROJECT NO. DRAWING NO. REF NO.

SCALE :

ZONE DATE APVD.

UTILITIES

SHEET OF

REVIEWED BY

DESCRIPTION

BLDGS & GROUNDS

CHIEF, ENGR'G DIV

DES

CHK'D

REVISIONS

IMCOM

FIRE & EMERGENCY SVC

SAFETY

ENVIRONMENT

UNIT #15707, APO AP 96258-5707

ENGINEERING DIVISON, DPW, USAG-RED CLOUD

HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD

US ARMY INSTALLATION MANAGEMENT COMMAND

DEPARTMENT OF THE ARMY

ELECTRICAL

E-17

(TYPICAL)

CABLE SUPPORT

EXOTHERMIC WELDING, LISTED COMPRESSION TWO-

1. THE CONNECTIONS OF THE BONDING CONDUCTOR FOR

TELECOMMUNITIONS TO THE TMGB SHALL UTILIZE

HOLE LUGS, SUITABLE AND EQUIVALENT TWO-HOLE

NOTES:

CROSS CONNECTING

PATCH CORD AS REQ'D

(1-100PAIR) (TYPICAL)

110 TYPE TERMINAL BLOCK

G

NEW TELEPHONE TERMINAL BOARD (TTB)

G

GROUNDING BUSBAR (TMGB)

(100mm(W) x6.4mm(D) x450mmLG)

GROUND WIRE

NEW TELECOMMUNICATION MAIN

CONDUCTOR #6AWG

RACK TYPE 1-48 PORT

PATCH PANEL "DATA"

NEW GROUND BONDING

RACK TYPE 1-48 PORT

(TYPICAL)

PATCH PANEL "DATA"

6 METER (20FEET) SLACK

W/"SC" TYPE CONNECTIONS

HUB (N.I.C)

MODE FIBER OPTIC CABLE

(TYPICAL)

SEE NOTE 2 BELOW.

SURGE SUPPRESSION TYPE

QUAD-PLEX RECEPTACLE

2P-3W-125V-20A

GROUNDING TYPE WITH

DEDICATED CIRCUIT

3000mmx2400mmx19mmTHK PLYWOODx1EA

CONDUIT COUPLING

(TYPICAL)

NEW CONDUIT STUB-UP W/SEALING

(150mm AFF) (TYPICAL)

84.58"(H)"x24"(W)x34.67"(D)

(100mm(W) x6.4mm(D) x300mmLG)

NEW TELECOMMUNICATION

GROUNDING BUSBAR (TGB)

G

(TYPE NEMA 5-20R)

POWER RECEPTACLES

(TYPICAL)

RACK TYPE 1-48 PORT

RACK TYPE 1-12 PORT

PATCH PANEL "TEL"

CONN TO NEW MAIN PANEL

GROUNDING SYSTEM

1#6 "BC" IN 27C

G

G

EQUIPMENT RACK

ENTRANCE TERMINAL BLOCK (100PAIRS)

NEW 110 TYPE PROTECTED

PTB

G

NOT TO SCALE

TELECOMMUNICATION SYSTEM DIAGRAM FOR 1ST FLOOR

FINISHED FLOOR AND SHALL BE PLACED WITHIN 75mm

3. ENTRANCE CONDUITS SHALL EXTEND 150mm ABOVE

STAMP FACING OUT" TO ENSURE THAT THEY CAN BE

"PLYWOOD WILL BE INSTALLED WITH FIRE RATED

4. TEST RESULTS WILL BE PROVIDED IAW THE MOST RECENT

REVISION OF THE ANSI/TIA/EIA-568.

5. LABEL ALL DROPS IAW TIA/EIA-606-A.

6. LABEL ALL GROUNDS IAW I3A.

LUGS ARE PREFERRED.

FIELD VERIFIED.

OF A WALL.

2. PLYWOOD SHALL BE FIRE-RATED.

7. CONTRACTOR SHALL SUBMIT SHOP DRAWING FOR DETAIL

EQUIPMENT RACK AND TELEPHONE TERMINAL BOARD FOR

GOVENRMENT APPROVAL PRIOR TO CONSTRUCTION.

(TYPICAL)

END BLANKS

D

T

D

T

D

T

113 111 109

ROOM NUMBER

WHICH DEVICE IS LOCATED

(TYPICAL)

1-4PAIR, #24AWG, CAT-6

FOR TEL IN 27C

CONN TO NEW PATCH PANEL

VIA CABLE TRAY

SOLID BOTTOM TYPE CABLE TRAY

ABOVE THE CEILING

(STEEL, 300mmW x 150mm H x LENGTH

AS REQ'D) W/O COVER

WITH SUPPORTER EVERY 3000mm

TO BE TERMINATED AT PATCH

TEL/DATA WIRE IN 27C

2-4PAIR, #24AWG, CAT-6

PANEL VIA CABLE TRAY

(TYPICAL)

D

T

D

T

D

T

D

T

D

T

D

T

115…