Drawing_files___109375___Bldg55___ELEC.PDF
PDF 569 KB Posted
- Attached to
- Repair bunkers, CRC
- Solicitation number
- W91QVN-18-R-0048
About this file
bldg. 55 Elec
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GENERAL NOTES SCOPE OF WORK
E-1
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
A. REPAIR/MAINTENANCE ( K )
2.
SCOPE OF WORK
LEGEND, GENERAL NOTES AND
SINGLE POLE TOGGLE SWITCH, 15A-125V
L E G E N D
FLEXIBLE CONDUIT W/CONNECTORS
LIGHTING
WIRING
POWER
INTERIOR
S
SYMBOL DESCRIPTION
DESCRIPTION
DESCRIPTION
J JUNCTION BOX
SYMBOL
SYMBOL
F FAN MOTOR (UNDER MECH. ITEM)
C CONTROL CIRCUIT
AND GOVERNMENT INSTALLED
GOVERNMENT FURNISHED
GFGI
WEATHERPROOFWP
LA LIGHTNING ARRESTER
EXPLOSIONPROOFEP
DISTRIBUTIONDIST
GROUND FAULT PROTECTIONGFP
A AMPERE
AC ALTERNATING CURRENT
AF/AT AMPERE FRAME/AMPERE TRIP
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BLDG BUILDING
BRKR BREAKER
C CONDUIT
CB CIRCUIT BREAKER
CKT CIRCUIT
CONN CONNECTION
CT CURRENT TRANSFORMER
DET(S) DETAIL(S)
DIAG DIAGRAM
DISC DISCONNECT
DWG(S) DRAWING(S)
EA EACH
EM EMERGENCY
ENCL ENCLOSURE
EXST EXISTING
F/A FIRE ALARM
FL FLOOR
FLUOR FLUORESCENT
FXTR FIXTURE
GEN GENERATOR
GND GROUND
HP HORSE POWER
HZ HERTZ
INCAND INCANDESCENT
INSTL INSTALLATION
J-BOX JUNCTION BOX
K KILO
KV KILO VOLT
KVA KILO VOLT AMPERE
LTG LIGHTING
MAG MAGNETIC
MAX MAXIMUM
MIN MINIMUM OR MINUTE
MTG MOUNTING
NO NUMBER
O/H OVER HEAD
PH PHASE
PNLBD PANELBOARD
PRIM PRIMARY
PWR POWER
Q'TY QUANTITY
RCPT RECEPTACLE
REQ'D REQUIRED
SCHED SCHEDULE
SEC SECONDARY
SPEC SPECIFICATION
STD STANDARD
SW SWITCH
TEL TELEPHONE
TYP TYPICAL
U/G UNDERGROUND
V VOLT
VA VOLT AMPERE
W WATT
W/ WITH
XFMR TRANSFORMER
& AND
PANELBOARD
HOMERUN CIRCUIT TO PANELBOARD
TYPE OF MTG ON LTG SCHEDULE
EXTERIOR LED LIGHTING FIXTURE, RATED WATT &
TYPE
DUPLEX RECEPTACLE, 2P-3W-20A-125V, GROUNDING
ABBREVIATION
AUXILIARY
DESCRIPTIONSYMBOL
BRANCH CIRCUIT, EXPOSED ON CEILING OR WALL
L
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
ON LTG SCHEDULE
LED LIGHTING FIXTURE, RATED WATT & TYPE OF MTG
W/EMERGENCY BATTERY UNIT
L
1.
2.MOUNTING HEIGHTS ABOVE FLOOR SHALL BE AS FOLLOW UNLESS OTHERWISE
NOTED ON THE DRAWING.
LIGHTING FIXTURE SEE LIGHTING FIXTURE SCHEDULE
PANELBOARD SEE SPECIFICATION
SAFETY SWITCH 1524mm TO CENTER OF THE ENCL
305mm TO CENTER OF THE ENCL
MOTOR CONTROLLER 1524mm TO CENTER OF THE ENCL
3.
4.
5.
INDICATEDS 2 #12AWG IN 16C
INDICATEDS 3 #12AWG IN 16C
INDICATEDS 4 #12AWG IN 16C
A GREATER NUMBER OF WIRES ARE INDICATED AS FOLLOWS;
1219mm TO CENTER OF THE ENCLWALL SWTICH
CONDUIT UNLESS OTHERWISE INDICATED.
ALL EQUIPMENT CONTROL WIRING SHALL BE #14 AWG. "TW" IN 16C
10.
11.
THE COTNRACTOR SHALL SUBMIT A SHOP DRAWING OF HVAC SYSTEM
IN ACCORDANCE WITH SEQUENCE OF OPERATION INDICATED ON THE
MECHANICAL DRAWINGS.
ANY CIRCUIT WITHOUT FURTHER DESIGNATION INDICATES 2-#12AWG
WIRES IN 16C CONDUIT UNLESS OTHERWISE INDICATED.
THE GROUNDING CONDUCTORS SHALL BE SEPARATELY PROVIDED FOR
ELECTRICAL EQUIPMENT UNLESS OTHERWISE INDICATED ON THE DRAWING.
CATV BEFORE CONSTRUCTION.
CONTRACTOR SHALL COORDINATE WITH AREA MP, DO IMO, SIGNAL BRIGADE,
AND GOVERNMENT ACCEPTANCE.
PANELBOARD DOOR, REQUIRED BEFORE FINAL BUILDING INSPECTION
CONTRACTOR SHALL MAKE CIRCUIT CHARTS AND ATTACH THEM TO
FIRE CODE AND SPECIFICATIONS.
OF THE NATIONAL ELECTRICAL CODE, NATIONAL ELECTRICAL SAFETY CODE,
ALL ELECTRICAL WORK SHALL CONFORM TO THE CURRENT REQUIREMENTS
OR RENOVATION.
CONDITION AND DIMENSIONS PRIOR TO COMMENCING ANY CONSTRUCTION
THE CONTRACTOR SHALL BE RESPONSIBLE IN VERIFING ALL EXISTING
UNITS.
CERTIFICATE FROM MANUFACTURER FOR LED LIGHTING FIXTURES AND POWER
CONTRACTOR SHALL BE RESPONSIBLE TO PROVIDE 10YEARS WARRANTY
THE GRADING LINE OF NEW DUCTS WILL BE LIMITED TO THE
WIDTH OF DUCT EXCAVATION.
AND AFTER INSTALLATION OF ELECTRICAL SYSTEM.
TO THEIR ORIGINAL CONDITION AND OPERATION DURING
ALL DAMAGED AREA INCLUDING SODDING, UTILITIES, STRUCTURES
THE CONTRACTOR SHALL BE RESPONSIBLE FOR RESTORING
RECEPTACLE
5.
PLATES AND ASSOCIATED WIRING & CONDUITS WITH NEW.
REPLACE EXISTING PANELBOARD, RECEPTACLES W/COVER
6.
7.
8.
9.
6.
1.
12.
WITH CONDUIT PLUG.
CONDUIT WHERE ELECTRIC DEVICES ARE REMOVED SHALL BE BLOCKED UP
T TELEPHONE LINE
WITH NEW.
REPLACE EXISTING EXTERIOR POWER DISTRIBUTION LINE
RESTORE EXISTING EXTERIOR TELEPHONE LINE WITH NEW.
3.
& CONDUITS WITH NEW.
MAIN ENCLOSED CIRCUIT BREAKER, AND ASSOCIATED WIRING
RESTRORE AUTOMATIC TRANSFER SWITCH, GENERATOR SETS,
4.
WALL FAN AND UNIT HEATER WITH NEW.
JUNCTION BOXES, CONTROL/POWER WIRES AND CONDUITS,
REPLACE DETERIORATED EXISTING MOTOR CONTROLLER,
7.
INTERIOR COMMUNICATION CABLE.
TRAY, PANELBOARD, TELEPHONE TERMINAL CABINETS,
REMOVE ABANDONED ELECTRICAL DEVICES INCLUDING CABLE
AND CONDUITS WITH NEW.
EXTERIOR LIGHT, STREET LIGHTS, TOGGLE SWITCHES, WIRES
REPLACE DETERIORATED EXISTING LIGHTING FIXTURES,
CAMP RED CLOUD
(BLDG S-55)
REPAIR BUILDING S-294, S-50 & S-55
TAK, YS
109375
W A
L L
B U
N K
E R S
U N
D E
R G
R O
U N
D
S
SHED
3PH-22.9KV-120/208V-225KVA
EXISTING PAD MOUNTED TYPE TRANSFORMER,
SECONDARY LINES W/ASSOCIATED ACCESSORIES.
CONTRACTOR SHALL BE RESPONSIBLE TO CONNECT NEW
EXISTING PRIMARY/SECONDARY CONCRETE POLE/
EXISTING MAIN PANELBOARD "MP"
SEC RACK(4 SPOOLS)
REMOVE ENTRANCE CAP(4 HOLES) AND
4-AWG#4 "WP"
REMOVE NEW OVERHEAD SECONDARY WIRE,
G E
N
A T S
S
E
E E
E
E
E
E
E
O/H O/H
O
H
O
H
O
H
U/ G
U
G
U /G
TT
C
T
U/ G
NEW ENGINE DRIVEN, DIESEL FUELED,
LIQUID COOLED GENERATOR,
W/BUILT-IN CONTROLLER, INCLUDING
NECESSARY DAYTANK, BATTERY CHARGER,
JACKET WATER HEATER & CIRCUIT BREAKER
WEATHER PROTECTIVE HOUSING W/SILENCER.
BUT EXIST CONCRETE PAD TO REMAIN
NEW U/G SEC LINE
E-2
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
REMOVE EXIST WIRE
T
T
T
U
G
U
G
EXIST TELEPHONE PEDESTAL
NEW TELEPHONE TERMINAL CABINET
EXIST O/H SEC LINE
S
O
H
O
H
NEW O/H SEC LINE 4-AWG#1/0
SEC RACK(4 SPOOLS)
NEW ENTRANCE CAP(4 HOLES) AND
WALL MOUNTED AUTOMATIC TRANSFER
SWITCH ("ATS"), 4POLE, 4W, 120/208V, 60HZ, 150A,
SWITCH NEMA 1 ENCL
W/LOCKING DEVICE, ISOLATION/BYPASS TRANSFER
NEW MAIN ENCLOSED CIRCUIT
BREAKER "MCB" (3P-225AF-150AT,
240VAC, 10,000AIC SYM)
W/LOCKING DEVICE,
NEMA 1 ENCL
P1
P2
P3
O/H
O/H O/H
UL LISTED. (TYPICAL OF 4EA)
SURGE PROTECTION DEVICE, BUILT-IN PHOTOCELL,
NEW EXTERIOR LED STREET LIGHT, 100W, 120V, 1PH,
ACCESSORIES.(TYPICAL)
SECONDARY LINES W/ASSOCIATED
RESPONSIBLE TO CONNECT NEW
EXIST POLE/CONTRACTOR SHALL BE
1/250SCALE :
EXIST/NEW EXTERIOR POWER DISTRIBUTION PLAN
NEW 4-AWG#1/0 IN 53dia CONDUIT
CAMP RED CLOUD
(BLDG S-55)
REPAIR BUILDING S-294, S-50 & S-55
TAK, YS
109375
PLAN
EXIST/NEW EXTERIOR POWER DISTRIBUTION
REPLACE W/NEW O/H SEC LINE 4-AWG#3/0
3PH, 4W, 120/208V, 60HZ, 62.5KVA
4-AWG#1/0 & 1#4(G) IN 53dia CONDUIT
UG
INDOOR
OUTDOOR
EXISTING UNDERGROUND PRIMARY LINE
EXIST PANELBOARD "EM"
EM
U
G
SEC:120/208V-225KVA
TRANSFORMER, 3PH-PRI.:22.9KV
EXISTING PAD MOUNTED TYPE
SUG
P
P
EXISTING OVERHEAD PRIMARY LINE
W/ ASSOCIATED ACCESSORIES
CONNECT TO NEW SECONDARY WIRE
EXISTING PRI/SEC RISER POLE/
S
GENERATOR RM
A T S
NEW ENGINE DRIVEN, DIESEL FUELED,
LIQUID COOLED GENERATOR,
W/BUILT-IN CONTROLLER, INCLUDING
NECESSARY DAYTANK(250GAL), BATTERY CHARGER,
WALL MOUNTED AUTOMATIC TRANSFER
SWITCH ("ATS"), 4POLE, 4W, 120/208V, 60HZ, 150A,
SCALE :
P
U
G
E-3
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
ELECTRICAL
NEW PULL BOX
TO EXIST PANELBOARD "MP" AT BUILDING S-50
J
J
G E
C
G
NEW MAIN ENCLOSED CIRCUIT
BREAKER "MCB" (3P-225AF-150AT,
240VAC, 10,000AIC SYM)
W/LOCKING DEVICE,
G
TRANSFER SWITCH (ATS)
NEW WALL MOUNTED AUTOMATIC
NEW WIRE,
NEW GENERATOR CONTROL LINE
IN 27dia PVC CONDUIT
NEW GROUND WIRE,
#6 "BC"
CONNECTION(TYPICAL)
COPPER CLAD STEEL
19dia x 3000LG WITH WELDING
NEW GROUND ROD
NEW ENGINE DRIVEN, DIESEL FUELED,
LIQUID COOLED GENERATOR,
W/BUILT-IN CONTROLLER, INCLUDING
JACKET WATER HEATER & CIRCUIT BREAKER
NEMA 1 ENCL
NEW WIRE,
BLDG S-55
BLDG S-55
BLDG S-55
NEW #2 "BC" IN 27C
NEW O/H SEC LINE
P
BLDG S-55
EXIST WIRING TO REMAIN
4-AWG#1/0 & 1#4(G) IN 54C
BLDG S-55
NEW PANELBOARD "P"
BLDG S-50
BLDG S-50
BLDG S-50
W/SILENCER.
NECESSARY DAYTANK(250GAL), BATTERY CHARGER,
NEW SEC LINE
W/LOCKING DEVICE, ISOLATION/BYPASS
TRANSFER SWITCH, NEMA 1 ENCL
4POLE, 4W, 120/208V, 60HZ, 150A,
MP
EXIST PANELBOARD "MP",
1-#2 AWG "BC" IN 16mm dia C.
EXIST GROUNDING WIRE,
CONNECTION
EXIST GROUND ROD, COPPER CLAD
SEC RACK(4 SPOOLS)
NEW ENTRANCE CAP(4 HOLES) AND
NEW PULL BOX
SWITCH NEMA 1 ENCL
W/LOCKING DEVICE, ISOLATION/BYPASS TRANSFER
CIRCUIT BREAKER W/SILENCER
1/50
NEW GENERATOR & ATS LAYOUT PLAN
NOT TO SCALE
POWER SINGLE LINE DIAGRAM
EXISTING PRI./SEC. LINE
P1
P2
P3
4-AWG#3/0
CONDUIT
4-AWG#1/0 & 1#4(G) IN 54C
4-AWG#1/0 "WP"
W/ ASSOCIATED ACCESSORIES
EXISTING POLE/ CONNECT TO NEW SECONDARY WIRE
"P"
P-6
P-5
NEW PANELBOARD "P"
NEW MAIN ENCLOSED CIRCUIT
BREAKER "MCB" (3P-225AF-150AT,
240VAC, 10,000AIC SYM)
W/LOCKING DEVICE,
NEMA 1 ENCL
NEW SECONDARY LINE, 4-AWG#1/0 IN 53C.
NEW SECONDARY LINE, 4-AWG#1/0 IN 53C.
POWER SINGLE LINE DIAGRAM
NEW GENERATOR & ATS LAYOUT PLAN &
CAMP RED CLOUD
(BLDG S-55)
REPAIR BUILDING S-294, S-50 & S-55
TAK, YS
109375
3PH, 4W, 120/208V, 60HZ, 62.5KVA
3PH, 4W, 120/208V, 60HZ, 62.5KVA
4-1/0 & 1#4(G) IN 53dia
IN 54mm dia C.
NEW U/G 4-AWG#1/0 AND 1-#4(G)
NEW UNDERGROUND SECONDARY LINE, 4-AWG#1/0 & 1#4(g) IN 53C.
IN 54mm dia C.
NEW 4-AWG#1/0 AND 1-#4(G)
REPACE WITH NEW O/H SEC LINE
GENERATOR RM
E-4
A
B C D
E F G H
SYMBOL BY
DESIGNED BY
ENERGY MANAGER
SUBMITTED BY
USING AGENCY
APPROVED BY
PROJECT NO. DRAWING NO. REF NO.
SCALE :
ZONE DATE APVD.
UTILITIES
SHEET OF
REVIEWED BY
DESCRIPTION
BLDGS & GROUNDS
CHIEF, ENGR'G DIV
DES
CHK'D
REVISIONS
IMCOM
FIRE & EMERGENCY SVC
SAFETY
ENVIRONMENT
UNIT #15707, APO AP 96258-5707
ENGINEERING DIVISON, DPW, USAG-RED CLOUD
HEADQUARTERS, UNITED STATES ARMY GARRISON, RED CLOUD
US ARMY INSTALLATION MANAGEMENT COMMAND
DEPARTMENT OF THE ARMY
L L
L L
SS
J
T
NS-3a & NS-3b
CEILING SURFACE MOUNTED LIGHT EMITTING DIODE (LED)
FIXTURE, 1PH, 120V, 50~54W, WITH CONVERTER & ACCESSORIES
(NS-3a) & WITH EM UNIT (NS-3b) AS REQUIRED
NS-4
WALL/CIELING MOUNTED LED LIGHT FIXTURE,
1PH, 120V, 22W LED LAMP, WITH CONVERTER &
ACCESSORIES AS REQUIRED (WET LOCATION TYPE)
SCALE :
NEW GROUND FLOOR ELECTRICAL PLAN
GROUNDING TYPE (TYPCIAL)
DUPLEX RECEPTACLE, 2P-20A, 120VAC,
F J
S
SCREEN, PREFABRICATED ROOF CURB
BY MFG FIELD INSTALLED, W/BACKDRFT DAMPER, BIRD
DISCONNECT SWITCH, EQUIPMENT SUPPORT PROVIDED
115/1PH/60HZ, 1/4HP, AIR CAP: 849.3(LPS), ESP:93.4, RPM:989,
WALL MOUNTED FAN, BELT DRIVE CENTRIFUGAL
THERMOSTAT
W/UNIT MOUNTED DISCONNECT SWITCH AND
ELECTRIC UNIT HEATER, 208V, 1PH, 60HZ, 3KW,
P-1
P-2
P-3
P-4
"P"
AND ACCESSORIES AS REQUIRED TYPE, "NS-3b"
120/277VAC, 1PH, 50 WATT, CONVERTER W/EMERGENCY UNIT
LED LIGHTING FIXTURE, CEILING SURFACE MOUNTED,
PHOTOCELL, AND ACCESSORIES AS REQUIRED TYPE, "NS-4"
120/277VAC, 1PH, 22 WATT, CONVERTER W/BUILT-IN
LED LIGHTING FIXTURE, WALL MOUNTED, OUTDOOR TYPE,
PILOT LIGHT, NEMA 1 ENCL.
MANUAL MOTOR STARTER, 1PH, 120VAC, (1HP MAX.)
PANELBOARD "P"
ACCESSORIES AS REQUIRED TYPE, "NS-3a"(TYPICAL)
120/277VAC, 1PH, 50 WATT, CONVERTER AND
LED LIGHTING FIXTURE, CEILING SURFACE MOUNTED,
LIGHTING1
A
T O T A L
NO.
CKT
DESCRIPTION
LOAD(VA)
TOTAL PHASE LOAD BREAKER SIZE
CONNECTION DIAGRAM
F TB C
S N
1 2
A B C
GRD
N
SURFACE MOUNTED, NEMA 1 ENCL
3PH-4W-120/208V-60HZ, W/ SN & GRD, 10,000AIC
RECEPTACLE 4EA-180 VA
1 100 20
1,000
NEW PANELBOARD "P" LOAD SCHEDULE
ELECTRIC UNIT HEAER 3KW
4EA-50W, 1EA-22W
FAN 1/4HP
1,000W
1,000W
SPARE 1,000W
1,000
1,000
1500 1500
GENERATER BATTERY CHARGER
GENRATOR ENGINE BLOCK HEATER
SPARE 1,000W
SPARE 1,000W
1,000
1,000
2942 3750 25009192
100AF-50AT
MAIN CB
TOTAL DEMAND LOAD ; 6404 ( VA ) DEMAND FACTOR ; 69.7 ( % )
SPACESPACE
SPACE SPACE
SPACE SPACE
SPACE SPACE
LIGHTING FIXTURE SCHEDULE
LED
LED
NS-3a
NS-3b
LED 22
NO.
ROOM
ROOM NAME
EXT
TYPE
LAMP
TYPE WATTS SHT.NO.
QTY
CEILING SURFACE
CEILING SURFACE
STD.DET.NO. 40-06-04
MOUNTING TYPE REMARK
W/"EM" UNIT
GENERATOR RM
NS-4 WALL MOUNTED
1/50
LIGHTING FIXTURE DETAILS & SCHEDULE
NEW PANELBOARD "P" LOAD SCHEDULE
NEW GROUND FLOOR ELECTRICAL PLAN,
ELECTRICAL
CAMP RED CLOUD
(BLDG S-55)
REPAIR BUILDING S-294, S-50 & S-55
TAK, YS
109375
| E-1 |
| E-2 |
| E-3 |
| E-4 |
File details come from the government source that posted it.