Addendum U0004 is issued prior to receipt of the bids and does hereby become a part of the contract documents and in case of conflict it shall supersede original project manual and drawings. Each bidder shall be responsible for issuing information contained herein to sub-contractors and suppliers to ensure that his/her proposal covers all work required by the contract documents including this addendum. Each bidder shall acknowledge receipt of this addendum on the proposal form where indicated.
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
F8N3CE0173A003 SZCQ089023
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER (Type or print)
30-105-04EXCEPTION TO SF 30
APPROVED BY OIRM 11-84
STANDARD FORM 30 (Rev. 10-83)
Prescribed by GSA
FAR (48 CFR) 53.243
Addendum U0004 is issued prior to receipt of the bids and does hereby become a part of the contract documents, and in case of conflict, it shall supersede original project manual and draw ings.
Each bidder shall be responsible for issuing information contained herein to sub-contractors and suppliers to ensure that his/her proposal covers all w ork required by the contract documents including this addendum.
Each bidder shall acknow ledge receipt of this addendum on the proposal form w here indicated.
1. CONTRACT ID CODE PAGE OF PAGES
J 1 21
16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)
16C. DATE SIGNED
BY 14-Apr-2011
16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR
(Signature of Contracting Officer)(Signature of person authorized to sign)
8. NAME AND ADDRESS OF CONTRACTOR (No., Street, County, State and Zip Code) X W912TF-11-R-0502
X 9B. DATED (SEE ITEM 11)
09-Mar-2011
10B. DATED (SEE ITEM 13)
9A. AMENDMENT OF SOLICITATION NO.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer is extended, X is not extended.
Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:
(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;
or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE
RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN
REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
12. ACCOUNTING AND APPROPRIATION DATA (If required)
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE
CONTRACT ORDER NO. IN ITEM 10A.
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER (Specify type of modification and authority)
E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.
14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
10A. MOD. OF CONTRACT/ORDER NO.
2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)
6. ISSUED BY
3. EFFECTIVE DATE
14-Apr-2011
CODE
FA6291 NEW HAMPSHIRE AIR NATIONAL GUARD
NGNH-PFO-PC JOINT CONTRACTING
302 NEWMARKET ST
PEASE ANGB
NEWINGTON NH 03803-0157
W912TF 7. ADMINISTERED BY (If other than item 6)
4. REQUISITION/PURCHASE REQ. NO.
CODE
See Item 6
FACILITY CODECODE
EMAIL:TEL:
W912TF-11-R-0502
SECTION SF 30 BLOCK 14 CONTINUATION PAGE
SUMMARY OF CHANGES
SECTION SF 30 - BLOCK 14 CONTINUATION PAGE
The following have been added by full text:
AMENDMENT U0004
RESPONSES TO RFI QUESTIONS
1. Spec section 283176 1.4 System description A. Scope states “complete zoned fire alarm and mass notification system” and drawing FA501 shows a conventional zoned system. Is an addressable fire alarm and Mass Notification System acceptable?
Response 1: Provide a zoned system as indicated in the drawings and specifications.
A. If so, drawing FA501 note 12 states “Provide six (6) spare zones”. Will 6 spare addresses be an acceptable substitute?
Response 1, A: Provide six (6) spare zones.
B. If not, please provide a model/make of a UL listed conventional zoned FACP with mass notification?
Response 1, B: It is not necessary for the fire alarm control panel to be the same panel as the mass notification panel (they can be two separate panels). The fire alarm control panel(s) and mass notification panel(s) shall be connected together to form a complete, operational fire alarm and mass notification system.
2. Section 102220 Para 2.12 A. 3- Circuit 3hot/3 neutral/1 ground/1 isolated ground electrical system called out for systems furniture. Is 4 hot/2 neutral/2 ground acceptable?
Response 2: Yes, 4 hot/2 neutral /2 ground rated at 20 amps; (8) 12-gauge copper wires, is acceptable. The neutral and ground conductors shall not be shared between 2 circuits fed from the same whip.
3. Section 102219 Para 2.4 A. Describes FSC wood requirements. Is FSC wood required for all veneer on Demountable partitions where veneer is used?
Response 3: Yes, FSC wood and veneer is required.
4. Section 102219 Para 2.2 I. 3. Describes Extrusion of sliding door frames to be rectilinear. Should all demountable wall trim be rectilinear or is curvilinear acceptable as well?
Response 4: Extrusion of sliding door frames shall be manufacturer’s standard to match adjacent profiles. See change to Specification Section 102219 listed further below. Wall trim shall be manufacturer’s standard (rectilinear or curvilinear).
5. IF601 drawing Workstations General Notes says panel/frame shall have open base (exposed foot) with a utility beltline below the worksurface. Does this mean all panels/frames shall have exposed foot and not have closed kick plates with power at base and anywhere power is need in panels it will be located immediately below the worksurface?
Response 5: Yes, see Specification Section 102220 paragraph 2.3, D.
6. IF601 Workstation Finish & Material Schedule A Frameless Screen/Fin calls out for Frosted Glass. In the Workstations General Notes: 3. immediately below if calls out for the glass screen to be translucent. Should the screens be clear or frosted/opaque?
Response 6: Screens should be frosted glass, per schedule. On sheet IF601, Schedules & Details, Workstations General Note 3, change “TRANSLUCENT” to “AS NOTED IN WORKSTATIONS FINISH
AND MATERIAL SCHEDULE”.
7. (Question separated into subsections for clarity by A/E)
A. There seems to be some contradiction relative to flashing in SS042113. Para 3.9 B 4&5 reference ribbed sheets while the other references seem to be to smooth sheets? Which is required? Within those paragraphs, there is also a reference to an interlocking hemmed edge system and also a reference to flexible flashing short of the veneer face and adhering to the drip edge. What system is to be used?
Response 7, A: Provide stainless steel smooth sheets. Delete references to ribbed sheet and flexible flashing from specification. See changes to Specification Section 042113 listed further below.
B. At the cavity side of the corbelled bricks, they are shown flush with the standard brick courses. Wall sections on 1/AE301 and 2&3/AE302 show some type of brick in-fill while details on AE604 show a custom size brick? Does this space need to be in-filled on the cavity side of the brick? If so what is the method that is to be used?
Response 7, B: Delete the infill and custom sized brick. Provide mortar behind the corbelled brick
(a regular sized brick) to provide a drainage plane even to the courses above and below.
C. What is the specific color and texture of the permeable pavers, seating wall cap and the mortar for the seat wall as color has a cost impact?
Response 7, C: Per the specifications, provide the following:
Permeable Pavers: Per Specification Section 321443, 2.1, C, 4: “Color: As selected by
Contracting Officer from manufacturer's range of colors with a Solar Reflectance Index (SRI) of at least 29.
Seating Wall Cap: Per Specification Section 047200, 2.2, I: “Color and Texture: Provide units with fine-grained texture and warm gray color resembling building face brick (Brick 2) with
Indiana limestone texture.” Mortar is to match building brick veneer mortar. Note: Wall cap sample should be submitted with or after Brick 2 sample submittal.
8. Re Steel finish: the exterior canopies SF 403 and pavilion framing SF106 look to be galvanized on struc drawings and spec, but arch drawings AE522 and AE109 indicate to be painted. Please clarify
Response 8: Exterior exposed galvanized steel is to be painted. Apply per manufacturer’s written instruction. Submit Product data for each type of product. Include preparation requirements and application instructions. Examine substrates and conditions, with Applicator present, for conditions affecting performance of the Work. Verify suitability of substrates, including surface conditions.
Proceed with coating application only after unsatisfactory conditions have been corrected. Remove grease and oil residue from galvanized sheet metal by mechanical methods to produce clean, lightly etched surfaces that promote adhesion of subsequently applied paints. Paint using a latex system consisting of the following:
1. Prime Coat: Primer, galvanized metal, as recommended in writing by topcoat manufacturer for exterior use on galvanized-metal substrates with topcoat indicated.
2. Intermediate Coat: Latex, exterior, matching topcoat
3. Topcoat: Latex, exterior, low sheen (Gloss Level 3-4), MPI #15.
9. Please submit the following RFI questions as they relate to Division 8 Openings -specification sections: 081113 (Hollow Metal Doors and Frames); 083473 (Sound Control Assemblies); 087100 (Door Hardware):
A. Does the DoD Minimum Antiterrorism standards - UFC 4-010-01: Do these standards apply to this building? We were unable to find any reference in the bid documents.
Response 9, A: Yes, the UFC 4-010-01 standards apply to the building. The level of protection is
“low.” See site plan for stand-off distances.
B. Door Rating "S"; please confirm doors with these ratings are smoke barrier doors. If so, these are essentially the same as 20Min rated fire doors, based upon paragraph 13 of the Steel Door Institute (SDI publication 118-01. These doors will require smoke seal.
Response 9, B: Doors indicated within the Door Schedule, Fire Rate column, as “Smoke” are doors within a smoke barrier. These doors require a smoke gasketing and a self-closing or automatic closing device. Doors within the smoke barrier for this project are not required to have a fire rating.
C. Hardware Sets at doors where noted;
a. HW#1 - Pairs Doors 101 and 103: Electrified hardware required per Remark P (Doors with Intercom; let in by buzzer) is not specified. Should the Electronic Lockset listed for HW#2 be intended for HW#1? HW#2 calls for exit device function "F14" which is non-locking.
Response 9, C, a: Doors 101 and 103 are to be provided with Hardware Set 1 as indicated.
Doors 102A and 102B are the electrified doors and are to be provided with Hardware Set 2 as indicated. On Sheet AE601, DOOR SCHEDULE AND DETAILS, delete Remark “P” from doors
101 and 103 and add Remark “P” to 102A and 102B.
b. HW#2 - Pairs Doors 102A, 102B: "S" Smoke rating listed for these openings is not available for Aluminum Storefront. Please verify doors are rated. If rated, should openings be changed to hollow metal type storefront?
Response 9, C, b: No, doors are not fire rated.
c. HW#3: Listed for doors 105, 130B, 174, A103 specifies concealed vertical devices for single doors. Rim devices can be used, as they are for HW#4B and 5, rather than the concealed vertical type which are a nuisance to keep adjusting. Please confirm.
Response 9, C, c: Door Hardware Set No. 3: provide rim exit device (no change in function) in lieu of concealed vertical device.
d. HW#4 - Door 107B: Door is Storefront. Confirm HW#3 should be used?
Response 9, C, d: Yes, provide Hardware Set #3 at Door 107B, not #4.
e. HW#4A - Door A110: Since this is the entry door to Storage A110 should exterior trim/cylinder be provided; "Exit Only" is specified?
Response 9, C, e: No, provide Hardware Set #4B at door A110.
f. HW#7B - Pairs Doors 129, 130C: "S" Smoke rating listed for these openings is not available for Aluminum Storefront. Please verify doors are rated. If rated, should openings be changed to hollow metal type storefront? Specified hardware is not correct for pairs rated doors. Both leaves must be self- closing/latching. Please confirm.
Response 9, C, f: Doors are not rated. Both leaves are to be self-closing/latching.
g. HW#7C - STC50 Pair Wood Sound Doors 127A: Concealed vertical devices cannot be used for sound doors. Devices should be changed to surface vertical devices x less bottom rods. Hinges should be provided as part of the sound door assembly. Please confirm.
Response 9, C, g: Yes, provide hinges as part of the sound door assembly at doors indicated as sound control assembly (Doors 106A, 127A, 169, 171, 173, 219A, and 219B). At Door 127A provide surface vertical devices in lieu of concealed vertical devices.
h. HW#8 - Rated Doors A104A, A104B, A104C: Doors require door closers - not specified.
Please confirm.
Response 9, C, h: Yes, provide door closers at Doors A104A, A104B, and A104C.
i. HW#8 - Wood STC50 Sound Doors 219A, 219B: Hinges should be provided as part of the sound door assembly. Please confirm.
Response 9, C, i: Yes, provide hinges as part of the sound door assembly at doors indicated as sound control assembly (Doors 106A, 127A, 169, 171, 173, 219A, and 219B).
j. HW#9A, 9B - Doors 108, 109B, 111, 112,113A, 113B, 163: Rim devices can be used at single doors, rather than concealed vertical devices which are a nuisance to keep adjusting. Please confirm.
Response 9, C, j: Door Hardware Set No. 9A and 9B: provide rim exit device (passage function F01) in lieu of concealed vertical device.
k. HW#9A - STC Wood Sound Doors 169,171 (Both Inswinging); Specified concealed vertical exit devices are not correct for Wood STC doors, or for inswinging doors.
Devices should be changed to Entry Locksets 1000-F05. Hinges should be provided as part of the sound door assembly. Please confirm.
Response 9, C, k: Doors 169 and 171: in lieu of Door Hardware Set No. 9A, provide Door
Hardware Set No. 9C. See changes to Specification Section 087100 listed further below.
l. HW#9A - Door 131A: Door is inswinging to storage. We suggest HW#11A is more appropriate. Please confirm.
Response 9, C, l: Door131A: in lieu of Door Hardware Set No. 9A, provide Door Hardware
Set No. 9C except delete viewers and door is not a sound door. See changes to Specification
Section 087100 listed further below.
m. HW#11 - STC Wood Sound Door 173: Hinges should be provided as part of the sound door assembly. Please confirm.
Response 9, C, m: Yes, provide hinges as part of the sound door assembly at doors indicated as sound control assembly (Doors 106A, 127A, 169, 171, 173, 219A, and 219B).
n. HW#13 - Rated Doors 116, 117B, 117C, 118: Rated doors must be self-latching.
Push/Pulls should be changed to passage locksets 1000-F01; smoke gasket is required.
Please confirm
Response 9, C, n: Doors 116, 117B, 117C and 118 are not rated but part of smoke partitions.
Doors located in smoke partitions are required to be self-closing and self-latching. At doors
116, 117B, 117C and 118, in lieu of push/pull hardware, provide passage locksets. Provide smoke gasketing.
o. HW#15 - Rated Doors to Sleep Rooms: Smoke gasket is required. Please confirm.
Response 9, C, o: Yes, Add smoke gasketing to Hardware Set #15.
p. HW#16 - Doors 104B, 104C, 109A, 109C, 117A, A102B: Doors are "Interior to Interior
Vestibules"
1. Is specified weatherstripping required?
Response 9, C, p, 1: Yes, provide weather stripping at interior vestibule doors.
2. Thresholds are specified, but there is not sill detail. Are they needed?
Response 9, C, p, 2: Yes, provide thresholds.
3. Rim devices can be used in lieu of concealed vertical devices. Please confirm for all.
Response 9, C, p, 3: Door Hardware Set No. 16: provide rim exit device (Function F09) in lieu of concealed vertical device.
q. HW#16 - Single Storefront Door 130 (Inswinging): "S" Smoke rating listed for this opening is not available for Aluminum Storefront:
1. Please verify door is rated. If rated, should openings be changed to hollow metal type storefront?
Response 9, C, q, 1: No, door is not a rated door assembly. Door is to be self-closing/latching.
2. Rim devices can be used in lieu of concealed vertical devices. Please confirm for all.
Response 9, C, q, 2: Door Hardware Set No. 16: provide rim exit device (no change in function) in lieu of concealed vertical device.
r. HW#18 - Rated Door 157: Requires smoke gasket for 20Min door. Please confirm.
Response 9, C, r: Yes, provide smoke gasketing at door 157.
s. HW#18 - Storefront Door 202:
1. Verify specified mortise passage 1000- F01 is correct for a storefront door;
or should a push/pull bar set J501 x J501 be used?
Response 9, C, s, 1: Yes, provide push/pull bar set. Change Door 202 hardware set to 3 hinges, push/pull bar set, surface-mounted closer, 1 kick plate, and 1 door stop at wall.
2. Confirm a door closer is not required.
Response 9, C, s, 2: Provide a door closer at Door 202. See response above.
t. HW#19: Hollow Metal Security Door A116:
1. Heavy duty hinges (A8111) should be used.
Response 9, C, t, 1: Yes, provide heavy duty hinges door A116, Hardware Set
#19.
2. A door closer is needed for a 45Min rated door. Please confirm for all.
Response 9, C, t, 2: Yes, provide door closers at fire rated doors.
u. HW#21 - Pocket Door 131B:
1. Heavy Duty Track, Hangers, Floor Guides and Rollers should be specified for this oversized door.
Response 9, C, u, 1: Yes, Hardware Set #21 for sliding door is to include heavy duty track, hangers, floor guides, and rollers, bumper, and 1 lockset.
2. Lockset F29 will not work with a sliding pocket door. If there is a jamb at the leading edge of the door, a hook-bolt deadlock can be used (Adamsrite MS1850ANSI-505). If no jamb, a vertical concealed edge lock (Adamsrite MSI 877 x Centerline of Cylinder 36" AFF) Please confirm for all.
Response 9, C, u, 2: There is no jamb at the sliding pocket door at the locking side. In lieu of lockset F29, provide a vertical concealed edge lock type
(Adamsrite MS877 or approved equivalent). Install centerline of cylinder at 36-inch AFF.
v. HW#23 - Glass Doors 220A and 220B: Is hardware for these doors to be provided by section 087100? Or is it provided as part of the glass door assemblies? Please reply.
Response 9, C, v: Glass door hardware is to be provided by Section 87100, Door Hardware.
Provide Hardware set No. 23 at doors 220A and 220B.
D. Door Closers:
a. Specification paragraph 2.22.B.1 requires closers to be non-handed. However, the LCN closer series 4010 listed in paragraph 2.22.A.1 is a handed closer. The correct LCN series would be 4041. Please confirm.
Response 9, D, a: Yes, provide handed closer. Delete “non-handed” from Section 087100, paragraph 2.22, B, 1.
b. Specification paragraph 2.22.B.1 requires closers to have metal covers, whereas paragraph 2.22.C.4 requires aluminum covers. Closer manufacturers offer standard plastic covers which comply with A156.15. Please confirm that plastic covers are acceptable. We do not know of any manufacturer offering aluminum covers.
Response 9, D, b: Plastic covers are acceptable. Delete “full metal” from Section 087100, paragraph 2.22, B, 1.
E. Electro-Magnetic Door Holders: Floor mounted unit are specified in paragraph 2.25. These will not work with Double Egress Pairs Doors. Please confirm that wall mounted types are correct at these locations.
Response 9, E: Electro-magnetic door holders at Hardware Set #7A to be wall mounted types.
Those at Hardware Set #7B to be floor mounted holders.
F. Door Gasketing: Specification paragraph 2.26.C references "Housed" gasketing. Is this meant to describe the weatherstripping listed in hardware groups?
Response 9, F: Door gasketing listed in 2.26C applies to weatherstripping and smoke gasketing.
Gasketing should not be of the press-on adhesive type. Sound gasketing to be included as part of the sound control door assembly.
G. Buy America Provisions: Many of the manufacturers of hinges listed in the specifications only offer hinges made in China. Is it the intent to bypass the Buy America requirements and allow hinges made in China? Those companies are: Stanley, Cal-Royal, Ives, Mckinney, and PBB.
Please advise.
Response 9, G: Provide equivalent product to comply with the Buy America Provisions.
H. Access Control Section - Division 28 Coordinated with Door Hardware Section 087100:
a. Electrified Hinges are referenced in paragraph 2.2. F, but are not specified in any hardware groups. Please confirm none are required.
Response 9, H, a: Electrified hinges are not required. Delete Section 087100, paragraph
2.2, F in its entirety.
b. Electric Strikes are referenced in paragraph 2.8, however, none are specified in hardware groups. Please confirm none are required.
Response 9, H, b: Provide electric strikes at doors with card readers.
c. Electro-Magnetic Locks are referenced in paragraph 2.9 and are also referenced as Door
Schedule General Note 5 on drawing AE601 - "Exterior Door Hardware Shall Have Electromagnetic Locks." However, none are specified in hardware groups.
1. Please confirm none are required.
Response 9, H, c, 1: Electro-magnetic locks are not required. Delete Section
087100, paragraph 2.9 in its entirety.
2. Or, advise if they are required for use on exterior doors to be coordinated with the balance of hardware specified at each affected opening.
Response 9, H, c, 2: Electro-magnetic locks are not required.
d. Auxiliary Electrified Door Hardware - Specification Paragraph 2.32:
1. Boxed Power Supplies are referenced in sub-paragraph 2.32.B, but are not listed in hardware groups. Are these provided by Division 28? Please confirm.
Response 9, H, d, 1: Boxed power supplies are to be provided by Division 08, not Division 28. Each door with an electric strike is to receive power. Specific number is to be determined; see changes to Specification Section 087100 listed further below.
2. Monitor Strikes are referenced in sub-paragraph 2.32.C, but are not listed in hardware groups. Confirm none are required.
Response 9, H, d, 2: No monitor strikes are required. Delete Section 087100, paragraph 2.32, C.
3. Door Position Switches are referenced in sub-paragraph 2.32.D, but are not indicated in hardware groups or on the door schedule. Should they be provided for all of the exterior doors? Please confirm.
Response 9, H, d, 3: Provide door position switch at Door A116.
J. Masterkey System: Paragraph 2.17 identified that the existing base keying system is "Best".
There are, however, other manufactures that can provide permanent cylinder cores master-keyed into an existing "Best" system, provided that we know what "Keyway" and “Bitting System" is being used.
a. Please advise the "Keyway": A, B, C, D, E, F, etc.
b. Please advise the "Bitting System"; Standard, A4 etc.
Response 9, J, a and b: Per the specifications, provide “Best Access System” which is the existing base keying system. Contact Best for information regarding Keyway and Bitting
System.
10. Lobby 102: Please identify pattern showing where the aluminum tile goes.
Response 10: See 1/AE641 and response to question 22, B below.
11. Room 127: Please clarify the location for broadloom carpet. Is there carpet under the seats or just on the stairs, aisles, and front floor space?
Response 11: Carpet is to be provided throughout the room (except at raised platform) including under the seats. See 2/AE402.
12. The spec [Section 105626] in 2.5.B.3 calls out for 48" widths on the shelving. Since this is an industrial application, wouldn't the use of Industrial Wide Span, possibly using 2-72" wide versus 3-
48” wide to make up the 12 length per carriage, be more end-user friendly? This would eliminate the extra limitation (obstruction) of the added uprights.
Response 12: Provide 48-inches deep by 72-Inches wide shelf units with no closed backs or dividers. Each shelf is to have a capacity of 500 pounds. See changes to Specification Section
105626 listed further below.
13. The spec [Section 105626] in 2.5.B.5 calls out for a 24" depth shelf. Since the carriages are drawn as
48" depth, this would seem to mean that the 24" depth will be placed back to back on the 48" carriage. With the application being totally industrial, with bulk storage, is there a need for 24" depth shelving, versus using a full 48" depth thru shelf?
Response 13: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
14. The spec [Section 105626] in 2.5.B.6 calls out for adjustable dividers on 30% of the shelving, with five dividers per shelf. Since this is industrial storage, were adjustable dividers needed in this system?
Response 14: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
15. The spec [Section 105626] in 2.5.E called out for Closed Backs. With the need for thru shelving storage capability, where would these closed backs be needed?
Response 15: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
16. The spec [Section 105626] in 2.5 F calls out for Center Dividers. These are typically needed of the shelves are to be 24/24 back to back and controlled separation is needed between the shelves.
Should these be provided since end users seem to prefer all thru shelving capabilities?
Response 16: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
17. The spec [Section 105626] in 2.5.H.1 calls out for a minimum of 3/4 high shelf supports. Will this meet the end users need for minimum load tolerances? I recall there were applications in the dept.
where possible loads of 400 Lbs. per shelf were expected.
Response 17: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
18. The drawing shows one of the Stationary Platforms located nearest the exit door. It also shows three small cabinets with doors backed up against this Stationary Platform. Is this where the Closed
Backs were needed, on one the platform side butting up against the three cabinets?
Response 18: Both end units can remain stationary. Closed backs are not required.
19. Mobile Storage Shelving Questions (Section 105626, 2.5):
A. Shelf total discrepancy: In Paragraph 105626, 2.5, B, subsection 6a and 6b, it states there are a total of (224) shelves. If there are (5) 24"D x 48"W shelves per section, (8) 48"W sections per carriage, and (7) double-faced ranges, I come up with (280) shelves, not including canopy tops. Is this correct?
Response 19, A: Provide maximum number of shelves per unit to comply with the specifications. See changes to Specification Section 105626 listed further below.
B. Adjustable partitions: Also, it calls for adjustable dividers at 30 percent of the shelves. If there are (280) total shelves (not including canopy tops), than dividers are required at (84) shelves.
On each of the (80) shelves, it seems to be calling for (5) dividers per shelf, for a total of (400) dividers. Is this correct?
Response 19, B: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
C. Closed backs: Each carriage is 48" deep, comprised of back-to-back shelving ranges that are
24" deep. Paragraph E seems to call for closed backs, which could be interpreted to mean the
(2) 24" deep shelving ranges should be divided by full height closed backs. In essence, this would make each 24" deep x 48" wide shelving unit a closed cabinet. Is this correct?
Response 19, C: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or dividers. Each shelf is to have a capacity of 500 pounds. See changes to Specification
Section 105626 listed further below.
D. Stationary shelving range near wall: It appears that one of the stationary shelving units is adjacent to a wall on one side of its full length. If there are closed backs, or center dividers for adjustable partitions / dividers, on this stationary shelving range, it would restrict access to the side of the unit closest to the wall. Should this unit be mobile, instead of stationary?
Response 19, D: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or dividers. Each shelf is to have a capacity of 500 pounds. See changes to Specification
Section 105626 listed further below.
E. Center dividers: For the adjustable partitions to function, slotted center dividers are needed.
So, for the 30 percent of shelves that have adjustable dividers, the center dividers are necessary. Are the center dividers required for the other 70% of the shelves?
Response 19, E: Provide 48-inches deep by 72-inches wide shelf units with no closed backs or
105626 listed further below.
20. Please provide a mechanical schedule for Unit Heaters.
Response 20: Unit heater schedule can be found on Sheet M704, SCHEDULES AND CONTROL
SEQUENCES.
21. Please reference Drawings M-108 and P-108. Please clarify the reference to Bid Option No.1 piping indicated on these drawings.
Response 21: There is no sheet M-108 as part of the drawing set. There are no references to Bid
Option No.1 on sheet P-108.
22. Re: Floor Covering
A. Where is the cork being used?
Response 22, A: Cork is to be provided on the south wall of the OG Conference Room (Room
219). See Room Finish Schedule on AE640 and detail 14/AE743.
B. Is there a pattern for the AlumaFloor and what sizes are being used?
Response 22, B: See detail 1/AE641. Design intent is to use manufacturer’s standard sizes.
For example, the northern most east-west running stripe that is shown to be 2 inches to 6 inches wide would be made from a series of AlumaFloor’s standard 24-inch by 48-inch tiles combined with their standard 6-inch by 24-inch tiles in the pattern shown. The two triangular sections to the east and west of the circular piece may be split as necessary in order to utilize manufacturer’s standard tile sizes.
23. The Furniture CAD Drawings provided in Addendum #2 are missing xref drawings and can not be reproduced with out the missing xref drawings. Can the furniture drawings provided in addendum
#2 be provided in PDF?
Response 23: The drawings will be re-posted in both corrected .dwg and .pdf format.
24. Will the Owner be performing any testing of construction materials or are these all the responsibility of the General Contractor to hire an independent testing company?
Response 24: The General Contractor is responsible for testing as required by the specifications.
The Government reserves the right to perform testing as it feels is required outside the specifications.
25. Can the project Superintendent also act as any of the other required personnel listed in the specifications such as the Safety Officer or LEED coordinator or should General Contractors include the cost for separate personnel for each position mentioned?
Response25: See Section 014510, Contractor Quality Control, paragraph 3.2 for limitations regarding personnel roles (Example: per 3.2, C, 4, Project Superintendent may not also be the CQC manager). Project Superintendant may also be the Safety Officer and/or LEED coordinator if they are (per Section 018113.13, Sustainable Design Requirements - LEED for New Construction and
Major Renovations, paragraph 1.13, B) “an experienced LEED-Accredited Professional. LEED coordinator may also serve as waste management coordinator.
26. Is the Fall Protection Equipment at the roof to be included in the base bid or does it just apply to bid option #3?
Response 26: Fall protection equipment at the roof applies to bid option #3 and should not be included in the base bid.
27. The Fall Protection specifications do not specify how many users the system is to be designed for to use at one time. Please clarify
Response 27: Design the system to support two (2) workers at any one time.
28. Reference 1/AE108: At the Loading Dock there is a section 4/AE302 shown. This section is not shown on AE302. Please provide.
Response 28: The correct section is 3/AE302.
29. Reference Part II General Conditions Item 12 Utilities and Services. Line A.4 states the utility rates will be stated at the pre-solicitation meeting. Were these rates for utilities ever released? Also please verify that the General Contractor is responsible to include in their bids any and all cost of utilities (water, electricity, etc…) required for the project. The wording in this section is a bit confusing when referring to reimbursement.
Response 29: See Amendment 1, posted Mar 22, 2011, “Amendment U0001 Specifications” section, item 3, for clarifications to the reimbursement procedure. The Government will bill the contractor $.12/KWH for electricity. Water rates will be set by the City of Portsmouth. Natural Gas rates will set by the gas utility company.
30. Is any of the exposed Structural Steel such as the pieces shown at the bridge or at any of the windows to be considered Architecturally Exposed Structural Steel and require any special shop preparation or finishes?
Response 30: Exposed structural steel shall be shop primed for painting in the field. Grind exposed welds smooth. Remove erection bolts, etc. and plug weld holes.
31. Reference Drawing C001 Note 9: Has the Asbestos Containing Pipe Insulation mentioned in this note been quantified and is there a report available? It does not seem to be mentioned in the report all ready provided in the Division 2 specifications.
Response 31: See Amendment 1, posted Mar 22, 2011, “Drawings” section, item 2, b for revisions to the note.
32. Is a temporary construction fence around the project perimeter required?
Response 32: See 1/CD101 for location of required temporary Foreign Object Damage (FOD) fence.
Specification Section Part II - General Conditions, Section 23, provides further direction.
33. Most specification sections are calling for mock ups of their respective items. Are in place Mock
Ups that can become part of the completed work acceptable or does the Owner want all Mock Ups to be performed separately and placed in a particular area on the site?
Response 33: Unless otherwise specified, mockups are to be performed separately, located on-site where directed by the Contracting Officer. Where possible, mockups of separate building systems shall be combined.
34. Reference 3/SF105: It appears that this is a mezzanine area above rooms A105, 106, 107, 108 and
113. There’s no reference to this mezzanine on the Architectural drawings and there is also no access shown for this area. Please clarify.
Response 34: Structural details are correct as shown. Access to this space shall not be provided as part of this contract.
35. Please clarify the extent of the Wire Mesh Partition at Room 108. It appears that a floor to deck wire mesh partition is required along the south wall of room A109. The wall turns north towards room A108 and continues above the mezzanine deck and appears to terminate near Column Line E-
3. Is this correct?
Response 35: Provide a wire mesh partition at the south and west walls of room 109. To the south of the column at E-3, the wire mesh partition is to go from the floor slab to the deck structure above. To the north of the column at E-3, the wire mesh partition is to go from the slab above room A108 to the deck structure above. See 4/AE203 and 5/AE203.
36. Detail 6/AE502 states Bid Option 1. What in this detail is part of Bid Option 1 which is the
Demountable Partitions and System Furniture?
Response 36: Delete “- BID OPTION #1” from the title of detail 6/AE502. Detail 6/AE502 is part of base bid work.
SPECIFICATIONS
1. SECTION 018113.13, SUSTAINABLE DESIGN REQUIREMENTS – LEED FOR NEW CONSTRUCTION AND
MAJOR RENOVATIONS
a. LEED for New Construction v2.2 Registered Project Checklist; Innovation & Design Process
Section:
1. Credit 1.1: Add the following title: “Non-Toxic Landscape Maintenance.”
2. Credit 1.2: Add the following title: “Interior Furniture & Furnishings.”
3. Credit 1.3: Add the following title: “Transformer Insulating Liquid.”
2. SECTION 042113, BRICK MASONRY
a. Paragraph 3.9, B: Delete paragraphs 4, 5, 6, 7, and 8 in their entirety.
3. SECTION 087100, DOOR HARDWARE
a. Paragraph 1.7, D: After “power supplies” add “, access control system.”
b. Add paragraph 2.32, B, 1 to read as follows: “Locate power supplies adjacent to security panel.”
c. Add paragraph 2.32, B, 2 to read as follows: “Provide the least number of power supplies required to adequately serve doors with electrified door hardware.”
d. Paragraph 3.8, B, Door Hardware Set No. 2 (Aluminum Double Door – Interior): Change
“Function 14” to “Function 09.”
e. Paragraph 3.8, B: Add “Door Hardware Set No. 9C (Interior Door – Man Trap w/ No Delayed
Egress)” to consist of the following:
1. 3 Hinges A8112 (Hinges are to be provided as part of the sound control door assembly).
2. 1 Electronic Lockset with Cardreader F05.
3. 1 Closer C02021.
4. 2 Viewers One mounted at ADA compliant height.
5. 1 set Gasketing.
f. Paragraph 3.8, B, Door Hardware Set No. 19 (Steel Security Door):
1. Add an electric strike.
2. Add a door position switch.
g. Paragraph 3.8, B, Door Hardware Set No. 23 (Glass Single Door): Delete “1 Door Pull, J501” from Overhead Closer description line.
h. Paragraph 3.8, B, Door Hardware Set No. 24 (Double Door):
1. Add an astragal.
2. Add two (2) closers.
4. SECTION 102219, DEMOUNTABLE PARTITIONS (BID OPTION #1)
a. Paragraph 2.2, I, 3: Delete “Rectilinear.”
5. SECTION 105626, MOBILE STORAGE SHELVING
a. Delete paragraph 2.1, B. List of manufacturers is to remain.
b. Paragraph 2.5, B, 1: Insert “at 24 inches” after “stationary ranges” and “at 48 inches” after
“mobile ranges.”
c. Paragraph 2.5, B, 3: Change “1219 mm (48 inches)” to “1829 mm (72 inches).”
d. Paragraph 2.5, B, 5 Change “610 mm (24 inches)” to “1219 mm (48 inches).”
e. Delete paragraph 2.5, B, 6 in its entirety.
f. Add paragraph 2.5, B, 6 to read as follows: “Load Capacity: 227 kilograms (500 pounds) per shelf.”
g. Delete paragraph 2.5, E and F in their entirety.
6. SECTION 220719, PLUMBING PIPING INSULATION
a. Paragraph 2.1, F, 2: change to read as follows: “Type I, 454 Deg C (850 Deg F) Materials:
Mineral or glass fibers bonded with a thermosetting resin. Comply with ASTM C 547, Type I, Grade A, with factory-applied ASJ or FSK.”
b. Add paragraph 3.10, C to read as follows: “Provide PVC jacket covers on fittings and accessories. On exposed piping, also provide PVC pipe jacket up to 8 feet above floor.”
c. Paragraph 3.11, B, 1, a: after “Type I” add the following: “minimum thickness in accordance with ASHRAE 90.1 or the manufacturer’s recommendations, whichever is greater.
Coordinate with pipe safety marking requirements in Division 22 section “Heat Tracing for
Plumbing Piping.””
d. Paragraph 3.11, C, 1: after “following” add the following: “horizontal piping only.”
7. Section 230719, HVAC PIPING INSULATION
a. Paragraph 3.13, A, 1: Delete “and Smaller:”
b. Add paragraph 3.13, C, to read as follows: “A.C. Condensate:”
c. Add paragraph 3.13, C, 1 to read as follows: “Flexible Unicellular, 1/2 inch thick minimum, sealed vapor tight. Seal with two coats of manufacturer-recommended paint where exposed to sunlight.”
d. Paragraph 3.14, B, 1: Change “None” to “Fittings and accessories only.”
e. Delete paragraph 3.14, C, 1.
f. Paragraph 3.14, C, 2: Change to 3.14, C, 1 and after “accessories” add the following: “and on piping up to 8 feet above finished floor.”
DRAWINGS
1. SHEET AE108, PARTIAL FIRST FLOOR PLAN AND RCP – AFE WING
a. Keynote 7: Change “BE” to “STRUCTURE ABOVE.”
2. SHEET AE601, DOOR SCHEDULE AND DETAILS
a. Door Schedule: Delete Door 104C.
3. SHEET M601, MECHANICAL SCHEDULES (SHEET 1 OF 2)
a. Energy/Heat Recovery Unit Schedule SI (IPS) Supply and Exhaust Fans columns: change “PA” to “KPA.”
b. Energy/Heat Recovery Unit Schedule SI (IPS): change data as follows
1. ERV-1 Supply fan ESP: Change “.700 *2.75+” to “.311 *1.25+.”
2. ERV-1 Exhaust Fan ESP: Change “.440 *1.75+” to “.311 *1.25+.”
3. ERV-2 Supply fan ESP: Change “.700 *2.75+” to “.498 *2.00+.”
4. ERV-2 Exhaust Fan ESP: Change “.440 *1.75+” to “.436 *1.75+.”
5. ERV-3 Supply fan ESP: Change “.750 *2.75+” to “.199 *0.80+.”
6. ERV-3 Exhaust Fan ESP: Change “.700 *2.75+” to “.199 *0.80+.”
4. SHEET M701, MECHANICAL CONTROL SEQUENCES
a. Detail 1, Under ERV-1 AND ERV-2 SEQUENCE OF OPERATION:
1. In paragraph beginning with “ERV-1:” add “BY INTERNAL CONTROLLER” after
“MAINTAIN.”
2. After “SAFETIES” paragraph add a paragraph to read as follows: “ERV-1 AND ERV-2
SHALL HAVE FACTORY-MOUNTED CONTROLLERS WHICH REDUCE WHEEL SPEED ON
SENSING WHEEL FROSTING.”
b. Detail 1, Under ERV-3 AND HC-3 SEQUENCE OF OPERATION:
1. In paragraph beginning with “ERV-2 DEFROST” change “ERV-2” to “ERV-3.”
c. Detail 1, ERV-1, 2, AND 3 POINTS LIST:
1. Change “HEAT EXCHANGE WHEEL SPEED” to “ERV-2 WHEEL SPEED.”
2. Delete note 4 from ERV-2 WHEEL SPEED.
5. SHEET EY102, FIRST FLOOR SECURITY PLAN – NORTH AND MATRIX
a. Keynote 1: Change “MAGNETIC LOCKS” to “ELECTRIFIED DOORS.”
6. SHEET E001, ELECTRICAL SYMBOLS, ABBREVIATIONS, AND GEN NOTES
a. Add Electrical General Note 17 to read as follows: “INSTALL DOOR POWER SUPPLIES
FURNISHED WITH THE DOOR HARDWARE. PROVIDE CONDUIT AND WIRING. PROVIDE
POWER AND CONTROL TO ELECTRIFIED DOORS FROM ADVANTOR SECURITY SYSTEM.”
- END OF ADDENDUM NO. 6 -
AMENDMENT U0004 ATTACHMENTS
Posted on www.FBO.gov
CAD drawings:
IF001, IF101, IF102, IF103, IF201, IF501, IF502, IF503, IF601
(End of Summary of Changes) http://www.fbo.gov/