ABBREVIATIONS
A OR AMP
AC
AC
AF
AFF
AFG
AHU
AIC
AL
ARU
ASYM
AT
ATS
AUTO
AWG
BCW
BFF
BFG
BLDG
C
CAT
CB
CCTV
CFCI
CKT
CLF
CM
CMH
CPT
CT
CU
D
DC
DF
DISC
DOAS
DPST
DPDT
DSCU
DSS
EC
EF
ELEC
EMH
EMT
E or EMER
EQUIP
ERV
EXIST or EX
EUH
EWC
EWH
F
FACP
FCU
FLEX
FWE
G OR GND
GFGI
GFI
GRS
GWH
H or HT
HOA
HP
HP
AMPERE(S)
ALTERNATING CURRENT
AIR COMPRESSOR / AIR CURTAIN
AMP FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CAPACITY
ALUMINUM
AIR TURNOVER UNIT
ASYMMETRICAL
AMP TRIP
AUTOMATIC TRANSFER SWITCH
AUTOMATIC
AMERICAN WIRE GAUGE
BARE COPPER WIRE
BELOW FINISHED FLOOR
BELOW FINISHED GRADE
BUILDING
CONDUIT
CATEGORY
CIRCUIT BREAKER
CLOSED CIRCUIT TELEVISION
CONTRACTOR FURNISHED CONTRACTOR INSTALLED
CIRCUIT
CURRENT LIMITING FUSE
CONTROL MODULE
COMMUNICATIONS MANHOLE
CONTROL POWER TRANSFORMER
CURRENT TRANSFORMER
COPPER OR CONDENSING UNIT
DEPTH
DIRECT CURRENT
DESTRATIFICATION FAN
DISCONNECT SWITCH
DEDICATED OUTSIDE AIR SYSTEM (UNIT)
DOUBLE POLE SINGLE THROW
DOUBLE POLE DOUBLE THROW
DUCTLESS SPLIT CONDENSING UNIT (POWERS THE DSS INDOOR UNIT)
DUCTLESS SPLIT SYSTEM (INDOOR UNIT)
EMPTY CONDUIT
EXHAUST FAN
ELECTRICAL
ELECTRICAL MANHOLE
ELECTRICAL METALLIC TUBING
EMERGENCY
EQUIPMENT
ENERGY RECOVERY VENTILATOR (INCLUDES ENERGY WHEEL AND FANS ONLY)
EXISTING
ELECTRIC UNIT HEATER
ELECTRIC WATER COOLER
ELECTRIC WATER HEATER (STORAGE AND INSTANTANEOUS)
FUSE
FIRE ALARM CONTROL PANEL
FAN COIL UNIT
FLEXIBLE
FURNISHED WITH EQUIPMENT
GROUND
GOVERNMENT FURNISHED GOVERNMENT INSTALLED
GROUND FAULT INTERRUPTER
GALVANIZED RIGID STEEL CONDUIT
GAS WATER HEATER
HEIGHT
HAND-OFF AUTOMATIC
HORSE POWER
HEAT PUMP (OUTDOOR PORTION OF SPLIT SYSTEM HEAT PUMP, USE CU FOR
STANDARD DX OUTDOOR UNIT)
HT
HWRP
HZ
IDS
IMC
IRH
J OR JB
K
KAIC
KCM OR KCMIL
KV
KVA
KW
KWHR
L
LA
LAN
LM
LOC
LTG
MAX
MCA
MCB or MB
MGB
MH
MIN
MLO
MM
MOD
MT or MTD
MRS
N
NEC
NEMA
NFPA
NI-CAD
NC
NESC
NO
NTS
P
PA
PF
PH
PMT
PNL
PVC
RECEPT or RECP
RMC
RMS
SA
SCCR
SE
S/N
SP
SPD
SPDT
SPEC
SPST
SQ
SWBD
TMGB
TOL
TP
TYP
U
UG
UIO
UL
UTP
V
VA
VAV
W
WHDM
WP
XFMR
Z
HEAT TRACKING
HOT WATER RECIRCULATION PUMP
HERTZ
INTRUSION DETECTION SYSTEM
INTERMEDIATE METAL CONDUIT
INFRARED HEATER
JUNCTION BOX
KILO
THOUSAND AMPERE INTERRUPTING CAPACITY
THOUSAND OF CIRCULAR MILS
KILOVOLT
KILOVOLT-AMPERES
KILOWATT
KILOWATT-HOUR
LENGTH
LIGHTNING ARRESTOR
LOCAL AREA NETWORK
LUMENS
LOCAL OPERATOR CONSOLE
LIGHTING
MAXIMUM
MINIMUM CIRCUIT AMPACITY
MAIN CIRCUIT BREAKER
MAIN GROUND BAR
METAL HALIDE or MANHOLE or MOUNTING HEIGHT
MINIMUM
MAIN LUGS ONLY
MONITORING MODULE OR MULTIMODE
MOTOR OPERATED DAMPER
MOUNT or MOUNTED
MOTOR RATED SWITCH
NEUTRAL
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NATIONAL FIRE PROTECTION ASSOCIATION
NICKEL CADMIUM
NORMALLY CLOSED
NATIONAL ELECTRICAL SAFETY CODE
NORMALLY OPEN
NOT TO SCALE
POLE(S) or PUMP
PUBLIC ADDRESS
POWER FACTOR
PHASE
PAD MOUNTED TRANSFORMER
PANEL OR PANELBOARD
POLYVINYL CHLORIDE
RECEPTACLE
RIGID METAL CONDUIT
ROOT MEAN SQUARE
SURGE ARRESTOR
SHORT CIRCUIT CURRENT RATING
SERVICE ENTRANCE
SOLID NEUTRAL
SUMP PUMP
SURGE PROTECTIVE DEVICE
SINGLE POLE DOUBLE THROW
SPECIFICATIONS
SINGLE POLE SINGLE THROW
SQUARE
SWITCHBOARD
TELECOMMUNICATIONS MAIN GROUNDING BUSBAR
THERMAL OVERLOAD
TWISTED PAIR
TYPICAL
URINAL
UNDERGROUND
UNLESS INDICATED OTHERWISE
UNDERWRITERS LABORATORY
UNSHIELDED TWISTED PAIR
VOLTS
VOLT AMPERES
VAV TERMINAL UNIT (WITHOUT A FAN)
WATTS or WIRE or WIDTH
WATTHOUR DEMAND METER
WEATHERPROOF
TRANSFORMER
IMPEDANCE
GENERAL NOTES:
THE WORK SHALL CONFORM WITH ALL REQUIREMENTS OF:
(A) NFPA 70-2017 (NATIONAL ELECTRICAL CODE)
(B) NFPA 70E-2015 (NATIONAL ELECTRICAL SAFETY CODE)
(C) APPLICABLE LOCAL CODES AND FEDERAL AND STATE LAWS.
MINIMUM RACEWAY SIZE SHALL BE 3/4". INCREASE RACEWAY SIZE AS REQUIRED TO LIMIT
RACEWAY FILL RATIO TO LESS THAN 40% FULL.
CONTRACTOR SHALL CAREFULLY COORDINATE WORK WITH OTHER TRADES THROUGH THE
GENERAL CONTRACTOR AND SHALL BE RESPONSIBLE FOR SECURING SPACE REQUIREMENTS
FOR ELECTRICAL EQUIPMENT CLEARANCE FOR RECESSED LIGHTING FIXTURES AND
CORRECT ROUGH-IN LOCATIONS OF ELECTRICAL CONNECTIONS.
CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING CATALOG NUMBERS ON THESE
DRAWINGS TO MATCH WITH MATERIAL DESCRIPTIONS INDICATED.
VERIFY EXACT HEIGHT OF EACH COUNTERTOP AND BACKSPLASH ON ARCHITECTURAL
DETAILS AND/OR CASE WORK SHOP DRAWINGS AND ADJUST SPECIFIED MOUNTING HEIGHT OF
WALL OUTLETS TO LOCATE BOTTOM OF OUTLET BOX 4" ABOVE TOP OF BACKSPLASH. IF NO
BACKSPLASH IS USED, LOCATE BOTTOM OF OUTLET BOX 6" ABOVE COUNTERTOP.
VERIFY DOOR SWINGS WITH ARCHITECTURAL DRAWINGS BEFORE ROUGHING IN WALL
SWITCHES. SWITCHES IN THE SAME LOCATION SHALL BE GANGED TOGETHER IN ONE
COMMON BACKBOX AND SHALL HAVE ONE COMMON FACE PLATE.
ALL FEEDERS AND BRANCH CIRCUITS SHALL INCLUDE A GREEN INSULATED GROUND
CONDUCTOR, SIZE PER NATIONAL ELECTRICAL CODE, OR AS SHOWN, CONNECTED TO EACH
DEVICE AND OUTLET BOX ON THE CIRCUIT AND TO THE PANELBOARD GROUND BUS. PROVIDE
A DEDICATED NEUTRAL CONDUCTOR FOR EACH BRANCH CIRCUIT. MULTIPLE BRANCH
CIRCUITS IN ONE RACEWAY REQUIRE ONLY ONE GROUND CONDUCTOR. GROUNDING BUSHING
AT OUTLET BOX AND RACEWAY TERMINATION SHALL BE PROVIDED.
VERIFY LUMINAIRE, CEILING MOUNTED SMOKE DETECTOR LOCATIONS WITH ARCHITECTURAL
REFLECTED CEILING PLANS FOR EXACT LOCATIONS AND DIMENSIONS PRIOR TO
INSTALLATION. VERIFY EXACT LOCATIONS OF MOTORS AND EQUIPMENT BEFORE ROUGHING-
IN.
REFER TO ONE-LINE DIAGRAMS, SCHEDULES AND RISER DIAGRAMS FOR CONDUCTOR AND
CONDUIT SIZES NOT SHOWN ON PLANS.
PROVIDE IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE
ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO STORE, FURNISH,
INSTALL, MOUNT, CONNECT, CONTROL AND POWER EQUIPMENT INDICATED, AS WELL AS ALL
APPURTENANCES REQUIRED TO MAKE TELECOMMUNICATIONS SYSTEM OPERATE AS
INDICATED WTIHIN THESE DRAWINGS AND SPECIFICATIONS AND TO FULFILL THE SCOPE OF
WORK.
DEMOLISH IS AN INCLUSIVE TERM USED TO DESCRIBE ASPECTS OF THE WORK TO BE
ACCOMPLISHED, AND IS HEREBY DEFINED TO REQUIRE CONTRACTOR TO DISCONNECT
EQUIPMENT FROM ALL CONNECTIONS, REMOVE FROM THE OWNER'S SITE, AND DISPOSE OF
IN ACCORDANCE WITH FEDERAL, STATE AND LOCAL LAWS AND ORDINANCES. COST OF
DISPOSAL IS ENTIRELY THE CONTRACTOR'S RESPONSIBILITY.
EMT: COMPLY WITH ANSI C80.3 AND UL 797. ALL EMT SHALL BE FACTORY PAINTED. PROVIDE
THE FOLLOWING COLOR FOR EACH SYSTEM:
1. FIRE ALARM - RED
2. TELECOMMUNICATIONS - ORANGE
3. 480/277V POWER - YELLOW
4. 208/120V POWER - BLUE
5. SECURITY - PURPLE
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-001
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
G E
N E
R A
L N
O T
E S
A N
D A
B B
R E
V
IA
T
IO
N S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 58 FT.
PROVIDE 2#12 & 1#12G-3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 92 FT. AND
GREATER THAN OR EQUAL TO 58 FT. PROVIDE 2#10 & 1#10G-3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 147 FT.
AND GREATER THAN OR EQUAL TO 92 FT. PROVIDE 2#8 & 1#8G-
3/4"C.
FOR ALL ONE-WAY CIRCUITS OF LENGTH OF LESS THAN 229 FT.
AND GREATER THAN OR EQUAL TO 147 FT. PROVIDE 2#6 & 1#6G-
3/4"C.
WIRE SIZING FOR ALL 20A 120V CIRCUITS, UIO:
50902 05/11/19 parkerm Image
SYMBOL DESCRIPTION
PANELBOARD, SEE SCHEDULES
EQUIPMENT AS INDICATED
MOTOR, HORSEPOWER AS INDICATED
1/2
MOTORIZED DAMPER
3-POLE COMBINATION MAGNETIC MOTOR STARTER/ DISCONNECT
(NEMA SIZE/ FUSE SIZE/ NEMA ENCLOSURE) NF = NONFUSED
DISCONNECT SWITCH, (SWITCH AMPS/ FUSE SIZE/ POLES/ NEMA
ENCLOSURE) NF = NON-FUSED
INDIVIDUALLY MOUNTED CIRCUIT BREAKER, (CB SIZE/ POLES/
NEMA ENCLOSURE)
DRY TYPE TRANSFORMER, KVA AS INDICATED
METER
ELECTRONIC METER
DISTRIBUTION PANELBOARD
CEILING OR WALL MOUNTED JUNCTION BOX
PULL OR JUNCTION BOX
M
MOD
2/60/40/1
60/40/3/3R
40/3/3R
CB
T
M
EM
J J
J
EQUIPMENT
GROUND CONNECTION
3/4" x 10'-0" COPPERCLAD
GROUND ROD, 18" BFG.
LIGHTNING PROTECTION
SYSTEM AIR TERMINAL
BARE COPPER GROUND
CONDUCTOR, 1/0 UIO.
4/0 BARE COPPER GROUND
CONDUCTOR
G
G4
LIGHTNING PROTECTION
ROOF CONDUCTOR
LP
LIGHTNING PROTECTION
ELECTRICAL CONNECTION
SYMBOL
FLUORESCENT LUMINAIRE AND OUTLET BOX. LETTER INDICATES
LUMINARE TYPE. SEE LIGHTING FIXTURE SCHEDULE.
FLUORESCENT LUMINAIRE AND OUTLET BOX, WITH PROVISIONS FOR
EMERGENCY LIGHTING. LETTER INDICATES LUMINAIRE TYPE. SEE
LIGHTING FIXTURE SCHEDULE.
WALL MOUNTED FLUORESCENT LUMINAIRE AND OUTLET BOX.
LETTER INDICATES LUMINAIRE TYPE. SEE LIGHTING FIXTURE
SCHEDULE.
CEILING OR WALL MOUNTED EXIT SIGN AND OUTLET BOX. PROVIDE
NUMBER OF ARROWS AND FACES INDICATED. LETTER INDICATES
LUMINAIRE TYPE. SEE LIGHTING FIXTURE SCHEDULE. WALL MT AT 96" AFF.
RECESSED OR PENDANT MOUNTED LUMINAIRE AND OUTLET
BOX. LETTER INDICATES LUMINAIRE TYPE. SEE LIGHTING FIXTURE SCHEDULE.
WALL MOUNTED LUMINARE AND OUTLET BOX. LETTER
INDICATES LUMINAIRE TYPE. SEE LIGHTING FIXTURE SCHEDULE.
DESCRIPTION
A
AE
M
X X
C
D a b
FLUORESCENT LUMINAIRE AND OUTLET BOX WIRED FOR
MULTILEVEL SWITCHING, LOWER CASE LETTER INDICATES
SWITCHLEG DESTINATION.
CEILING OR WALL MOUNTED LUMINAIRE AND OUTLET BOX
WITH PROVISIONS FOR EMERGENCY LIGHTING.
LUMINAIRES
GROUND
GROUND ROD
TRANSFORMER
CURRENT TRANSFORMER
FUSE
ELECTRICAL CONNECTION
CIRCUIT BREAKER
SWITCH
SURGE ARRESTORS
SEPARABLE CONNECTION
DRY TYPE TRANSFORMER, K-13
RATED, KVA AS INDICATED45
ONE-LINE SYMBOLS
SYMBOL
CIRCUIT HOMERUN TO PANELBOARD, LA-1,3,5 ADJACENT TO
ARROW INDICATES HOMERUN OF CIRCUITS, 1,3,5 TO PANEL LA.
MARKS ACROSS RACEWAY INDICATE THE NUMBER OF PHASE
CONDUCTORS AND NEUTRAL IN RACEWAY. GROUND
CONDUCTORS ARE INDICATED BY LONGER HASHMARKS. NO
MARKS ACROSS RACEWAY INDICATES 2#12 CONDUCTORS AND
1#12 GROUND CONDUCTOR. CONDUCTOR SIZE #12 UNLESS
INDICATED OTHERWISE. MINIMUM RACEWAY SIZE SHALL BE 3/4"
RACEWAY EXPOSED TO VIEW
CONCEALED RACEWAY, LOCATED IN WALL OR ABOVE
FINISHED CEILING
DESCRIPTION
UNDERGROUND RACEWAY, LOCATED BELOW
GRADE OR CONCRETE SLAB
FLEXIBLE RACEWAY
RACEWAY TURNED TOWARD VIEWER
RACEWAY TURNED AWAY FROM VIEWER
RACEWAY TERMINATION, STUB-OUT AND CAP
LA-1,3,5
PLUG-IN BUSWAY, UIO
SURFACE METAL RACEWAY OR MULTIOUTLET
ASSEMBLY AS INDICATED
CABLE TRAY (SIZE AS INDICATED ON PLAN)
WIRING
DUCTBANK, TEXT INDICATES QUANTITY AND SIZE OF DUCTS
(I.E. 2W4" = TWO 4" DUCTS)
2W4"
WIRING DEVICES
SYMBOL DESCRIPTION
MOTOR RATED DISCONNECT SWITCH WITH THERMAL
OVERLOADS, SPST, MT. ON UNIT, UIO.
WALL SWITCH, AC TYPE, SPST, MOUNT 48" AFF
3-WAY WALL SWITCH, MOUNT 48" AFF
4-WAY WALL SWITCH, MOUNT 48" AFF
SLIDE DIMMER, MT 48" AFF
CEILING MOUNTED OCCUPANCY SENSOR
CEILING MOUNTED DAYLIGHT SENSOR
PHOTOELECTRIC CELL
D
M
OS
DS
PE
DUPLEX RECEPTACLE NEMA 5-20R,
MT 18" AFF, UIO
DUPLEX RECEPTACLE, NEMA 5-20R, MT 48" AFF
OR ABOVE COUNTER TOP/BACKSPLASH
DOUBLE-DUPLEX RECEPTACLE NEMA 5-20R,
MT 18" AFF, UIO
WP = WEATHER PROOF; TP = TAMPER PROOF; TV = MOUNT AT 60" AFFRECEPTACLE
SUBSCRIPTS
FLOOR BOX WITH DUPLEX RECEPTACLE NEMA 5-20R
SPECIAL RECEPTACLE, NEMA TYPE AS INDICATED,
MT 18" AFF UIO
CEILING BOX WITH DUPLEX RECEPTACLE, NEMA 5-20R
MULTI-COMPARTMENT FLOOR BOX WITH FOUR DUPLEX
RECEPTACLES AND FOUR DATA JACKS.
5-30R
DUPLEX GFI RECEPTACLE, NEMA 5-20R, MOUNTED
CONCEALED BEHIND ELECTRIC WATER COOLER
EWC
DUPLEX GFI RECEPTACLE NEMA 5-20R,
MT 18" AFF, UIO
DUPLEX GFI RECEPTACLE NEMA 5-20R, MT 48"
AFF OR ABOVE COUNTER TOP/BACKSPLASH
SIMPLEX RECEPTACLE NEMA 5-20R,
MT 18" AFF, UIO
3/4" x 10'-0" COPPERCLAD
STATIC GROUND ROD, 18" BFG.
SEE DETAIL A1/E-501.
S
3/4" x 10'-0" COPPERCLAD
GROUND ROD GROUND WELL,
18" BFG. SEE DETAIL D3/E-501.
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-002
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L S
Y M
B O
L S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
50902 05/11/19
REF.
FD
O
O O
O
3Da
3Da
O
O O
OS
OS
OS
OS
OS
OS
OS
3Db
3Db
DS
J
J
J
OS OS
NCOIC
HANGAR BAY
LOAD
STANDARDIZATION
CREW OFFICE
WEAPONS STORAGE
116COMM.
WEAPONS EQUIP.
STORAGE
HEF
MECH.
ELEC.
CLASSROOM
WOMEN'S
MEN'S
JAN.
CORRIDOR
VEST.
AE AE AE AE
AEAEAEAE
AE AE AE AE
AEAEAEAE
B
BE
B
B BE
B
B
BE
B
BBEB
B
B
CE
C
C
CE
CE C
C CE C CE C
C
CE
C
C
DE
DDE
D D
F a b ba b b
GE
G G
GE
GE
H H
H
GE
GE
D
DE
X
X
X
X
X
X X
X
DE
D
DE
F
D
LA-2
LA-1
LA-10
LA-8
LA-5
FA-2
LA-3
LA-4
D
FIRE PUMP HOUSE
JE
JE JE
JE
FP-8
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-101
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
L
IG
H T
IN
G
P L A
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 8 168
1/8"
SCALE: 1/8" = 1'-0"A2
LIGHTING FLOOR PLAN
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
SEE SHEET E-602 FOR LIGHTING FIXTURE SCHEDULE.
GENERAL NOTES:
1.
2.
SCALE: 1/8" = 1'-0"E2
LIGHTING FLOOR PLAN - FIRE PUMP HOUSE
PROVIDE STRIP LIGHTS WITH WIRE GUARD.
CONTROL LIGHTS VIA DAYLIGHT HARVESTING. WIRE ALL EXIT SIGNS
AHEAD OF LOCAL SWITCHING. LIGHTS SHALL TURN OFF WHEN
DAYLIGHTING MEASURES 50 FC.
PROVIDE MANUAL OVERRIDE TO DAYLIGHT HARVESTING SYSTEM.
CONTROL EXTERIOR LIGHTS VIA PHOTOCELL/BUILDING AUTOMATION
SYSTEM. PROVIDE 4 POLE CONTACTOR WITH HOA SWITCH WITH
ETHERNET.
HANGAR LIGHTING CONTROL CABINET. SEE B3/E-602 AND B5-E602 FOR
DETAILS. SEE D1/E-602 FOR HANGAR LIGHTING CONTROL DIAGRAM.
BLUE ROTATING BEACON. REFER TO FA-101 FOR EXACT LOCATIONS.
KEY NOTES:
2 2
N
50902 05/11/19
M
J
J
J
J
M M
M M
MM
MM
J
J
M
J
J
J
E-401
C1
DBA C
3.6
DDC
TV
WP WP
WP
WP
FMCP
WP
WP
WP
WP
60"
18"
RA-1
RA-3
RA-5
RA-7
EWC
RA-9
RA-11
RA-13
RA-15
RA-23
RA-21
RA-19RA-17
RA-25
RA-27
RA-29
FA-1
RA-2,4
RA-6,8
RA-10,12
RA-14,16
COMM.
ELEC.
MECH.
NCOIC
LOAD
STANDARDIZATION
CREW OFFICE
HANGAR BAY
WOMEN'S
MEN'S
CLASSROOM
WEAPONS STORAGE
WEAPONS EQUIP.
STORAGE
HEF
E-401
C3
MDP-8,10,12
RA-18
RA-20
RA-22
RA-24
RA-26
HEF PANEL
FA-3
LA-6
WP
FP
FP-1
FIRE PUMP HOUSE
JOCKEY PUMP
CONTROLLER
FIRE PUMP
CONTROLLER
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-111
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
P O
W E
R P
L A
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: 1/8" = 1'-0"A2
POWER FLOOR PLAN
SCALE: = 1'-0"
0 8 168
1/8"
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
SEE SHEET E-601 FOR ONE LINE DIAGRAM.
GENERAL NOTES:
1.
2.
PROVIDE 100A 480V 3 PH. FUSIBLE DISCONNECT SWITCH IN HANGAR
FOR 400 HZ CONVERTERS.
ALL HANGAR RECEPTACLES SHALL BE GFI AND MOUNTED AT 48" AFF.
CEILING MOUNTED RECEPTACLE FOR PROJECTOR.
FABRIC HANGAR DOOR MOTOR.
WIREWAY FOR FIRE PUMP.
400A SERVICE ENTRANCE DISCONNECT SWITCH. WIREWAY SHALL BE
PROVIDED BELOW DISCONNECT SWITCH.
400A MANUAL TRANSFER SWITCH. WIREWAY SHALL BE PROVIDED
BELOW DISCONNECT SWITCH.
TEMPORARY GENERATOR CONNECTION POINTS.
30A, SERVICE ENTRANCE RATED, DISCONNECT SWITCH FOR FABRIC
HANGAR DOOR.
PROVIDE JUNCTION BOX WITH 1"C WITH PULLSTRING FROM 18"
JUNCTION BOX TO 60" JUNCTION BOX.
MOTOR OPERATED OVERHEAD DOOR. MOTORIZED SWITCHES SHALL
BE CONNECTED TO THE BMS.
HAND DRYER
HANGAR DOOR SWITCH SHALL BE CONNECTED TO THE BMS.
POWER FOR GARBAGE DISPOSAL.
POWER FOR FLUSH VALVES AND AUTOMATIC FAUCETS.
INVERTER FOR HANGAR LIGHTING. WALL MOUNT ABOVE 24" AFF.
MANUAL TRANSFER SWITCH FOR FABRIC DOOR.
KEY NOTES:
SCALE: 1/8" = 1'-0"E2
POWER FLOOR PLAN - FIRE PUMP HOUSE
11 11
N
50902 05/11/19
REF.REF.
SM
SM
SM
SM
SM
SM
SM SM
SM
SM
SM SM
SM
SM
SM
J
J
J
J
J
JFD
FD
FDFD FD FD
FD
FD
FD
SM
SM
DBA C
3.6
FCU-2
HWRP-1
ERV-1
DOAS-1
FCU-1
IRH-1
IRH-3
IRH-2
FCU-3
DF-1
EUH-2
90"
ARU-1
RB-1,3
RB-5,7
RB-9,11
RB-2,4,6
RB-20
RB-8,10
RB-16,18
RB-12
RB-14
RB-26
RB-22
RB-24
RB-15,17,19
RB-28
WEAPONS EQUIP.
STORAGE
WEAPONS STORAGE
HANGAR BAY
CLASSROOM
WOMEN'S
MEN'S
LOAD
STANDARDIZATION
CREW OFFICE
CORRIDOR
ELEC.
COMM.
VEST.
NCOIC
MECH.
HEF
IT1-2,4
EF-1
GWH-1
RB-13
EUH-3
DSCU-1
DSS-1
RB-23,25
EUH-4
EUH-5
RB-27,29
RB-31,33
RB-30
RB-32
RB-34
RB-36
DOAS-HP-1
HP-1
EUH-1
FIRE PUMP HOUSE
FP-2,4,6
FP-3,5
EF-2
FP-10
FP-7,9,11
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-121
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
M E
C H
A N
IC
A
L P
O W
E R
P L A
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 8 168
1/8"
SCALE: 1/8" = 1'-0"A2
MECHANICAL POWER PLAN
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
SEE SHEET E-603 FOR MECHANICAL EQUIPMENT SCHEDULE.
GENERAL NOTES:
1.
2.
GWH-1 ON MOTION SENSOR. TIE INTO DDC SYSTEM.
PROVIDE INTERLOCK SO THAT WHEN DOORS ARE OPEN, INFRARED
HEATERS SHALL BE LOCKED OFF.
RECEPTACLE FOR SPOT COOLER. MOUNT RECEPTACLE AT 48" AFF.
JUNCTION BOX FOR MOD'S.
KEY NOTES:
SCALE: 1/8" = 1'-0"E2
MECHANICAL POWER PLAN - FIRE PUMP HOUSE
N
3 3
50902 05/11/19
LP LP
LP
LP LP LP LP
LP
LP
LP
LP
LP
LPLPLPLP
LP
LP
LP
LP
LP
LP
LP
LP
LP
DBA C
3.6
G4
G4 G4
G4 G4
LP
LP
LP
LP
A1
E-502
D1
E-502
D1
E-502
A1
E-502
LP
LP LP
LP
G4
G4
D1
E-502
A1
E-502
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-131
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
L
IG
H T
N
IN
G P
R O
T E
C T
IO
N
P L A
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 8 168
1/8"
SCALE: 1/8" = 1'-0"A2
LIGHTNING PROTECTION SYSTEM PLAN
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
REFER TO SHEET E-502 FOR LIGHTNING PROTECTION DETAILS.
PROVIDE CLASS 1 LIGHTNING PROTECTION MATERIALS.
THE COMPLETED LIGHTNING PROTECTION INSTALLATION SHALL MEET
THE REQUIREMENTS OF THE NATIONAL FIRE PROTECTION CODE, NFPA
780, STANDARD FOR THE INSTALLATION OF LIGHTNING PROTECTION
SYSTEMS AND AFI 32-1065. SYSTEM SHALL BE INSPECTED AND
CERTIFIED BY LPI.
A COPPER LIGHTNING PROTECTION SYSTEM OR ANY COPPER
COMPONENTS SHALL NOT BE MOUNTED ON AN ALUMINUM SURFACE. TO
AVOID GALVANIC CORROSION, USE ALUMINUM COMPONENTS ON
ALUMINUM SURFACES.
ANY GROUNDED METALLIC BODY WITHIN THE DISTANCE SPECIFIED BY
NFPA 780, PARAGRAPH 3-24.2 SHALL BE BONDED TO THE LIGHTNING
PROTECTION SYSTEM.
METALLIC UNDERGROUND PIPING ENTERING THE STRUCTURE SHALL BE
BONDED TO THE LIGHTNING PROTECTION SYSTEM AT ITS NEAREST
POINT.
THE ADHESIVE REQUIRED FOR ADHESIVE MOUNTED BASES AND CABLE
FASTENERS SHALL BE COMPATIBLE WITH THE ROOFING MATERIAL.
VERIFY THE COMPATIBILITY WITH THE ROOFING MANUFACTURER.
AIR TERMINALS MUST BE LOCATED ON ALL ROOF TOP EQUIPMENT AS
SPECIFIED IN THE NFPA CODE. ANY OBJECT WITH A METAL THICKNESS
OF 3/16" OR GREATER NEED NOT HAVE AN AIR TERMINAL IF THE OBJECT
IS PROPERLY BONDED TO THE LIGHTNING PROTECTION SYSTEM.
DESIGNS SHOWN ARE DIAGRAMMATIC AND INTENDED TO SHOW THE
BASIC LIGHTNING PROTECTION SYSTEM. THE CONTRACTOR MUST
VERIFY THE DIMENSIONS AND SITE CONDITIONS AND INSTALL A
LIGHTNING PROTECTION SYSTEM THAT COMPLIES WITH THE NFPA 780
CODE REQUIREMENTS.
GENERAL NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
SCALE: 1/8" = 1'-0"E2
LIGHTNING PROTECTION SYSTEM PLAN - FIRE PUMP HOUSE
REFER TO SHEET E-141 FOR THE GROUNDING PLAN.
KEY NOTES:
N
50902 05/11/19
G4
G4
DBA C
3.6
G4
G4
G4
G4
S S G4
S S G4
G4 G4
G4
G4
G4
G
TMGB
EGB
G4
G4
G4 G4
G4
G4 G4
G4
G4
G4
G4 G4
G4
G4
EGB
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-141
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
G R
O U
N D
IN
G
P L A
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 8 168
1/8"
SCALE: 1/8" = 1'-0"A2
GROUNDING PLAN
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
GROUND LOOP SHALL BE A MINIMUM OF 10' FROM OUTSIDE FACE OF
FOUNDATION.
SEE SHEET E-131 FOR LIGHTNING PROTECTION SYSTEM PLAN.
GENERAL NOTES:
1.
2.
3.
SEE DETAIL A1/E-501.
REFER TO SHEET E-131 FOR THE LIGHTNING PROTECTION SYSTEM PLAN.
SEE DETAIL D3/E-501.
KEY NOTES:
1 1
2 2
N
50902 05/11/19
DBA C
3.6
NCOIC
HANGAR BAY
LOAD
STANDARDIZATION
CREW OFFICE
WEAPONS STORAGE
COMM.
WEAPONS EQUIP.
STORAGE
115 HEF
MECH.
ELEC.
CLASSROOM
WOMEN'S
MEN'S
JAN.
CORRIDOR
VEST.
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:4
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-151
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
H A
Z A
R D
O U
S C
L A
S S
IF
IC
A T
IO
N
P L A
N A
N D
D E
T A
IL
S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 8 168
1/8"
SCALE: 1/8" = 1'-0"B2
HAZARDOUS CLASSIFICATION PLAN
GENERAL NOTES:
SEE E-001 AND E-002 FOR GENERAL NOTES,
ABBREVIATIONS AND SYMBOLS.
ALL ELECTRICAL WORK IN HAZARDOUS AREAS SHALL BE
IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE
ARTICLE 501 FOR CLASSIFICATION INDICATED.
CLASSIFICATION APPLIES TO ENTIRE VOLUME OF ROOM.
DIVISION 2 AREA IS 3 FEET RADIUS AT DOORS.
VICINITY OF AIRCRAFT: THE AREA WITHIN 5 FEET
HORIZONTALLY FROM AIRCRAFT POWER PLANTS OR
AIRCRAFT FUEL TANK SHALL BE CLASSIFIED AS A CLASS 1,
DIVISION 2 LOCATION THAT SHALL EXTEND UPWARD FROM
FLOOR TO A LEVEL 5 FEET ABOVE THE UPPER SURFACE
OF THE WINGS AND OF ENGINE ENCLOSURES.
CLASS 1 DIVISION 2 AREA
SEE NOTES
N
CLASS 1 DIVISION 2 AREA,
18" AFF & BELOW 1.
2.
3.
4.
50902 05/11/19
J
MDP LA
RARB
T1
T2
EGB
SPD
FA
IT1
IT1-1
IT1-5
IT1-3
TMGB
LADDER TYPE CABLE TRAY
TELECOMMUNICATIONS RACK (TYP.)
TELECOMMUNICATIONS BACKBOARD
ON THREE WALLS
IT1-7
IT1-9,11
IT1-15,17
IT1-13
JUNCTION BOX FOR GIANT VOICE SYSTEM
IT1-6
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-401
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E N
L A
R G
E D
E L E
C T
R
IC
A L
T E
L E
C O
M R
O O
M S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: = 1'-0"
0 2 42
1/2"
SCALE: 1/2" = 1'-0"C1
ENLARGED PLAN - ELECTRICAL RM
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS AND
ELECTRICAL SYMBOLS.
SEE SHEET E-601 FOR ONE LINE DIAGRAM.
GENERAL NOTES:
1.
2.
DISCONNECT SWITCH FOR PANEL IT1.
MOUNT RECEPTACLES TO CABLE TRAY.
KEY NOTES:
SCALE: 1/2" = 1'-0"C3
ENLARGED PLAN - COMM RM
50902
05/11/19
82,000 GAL. TANK
LP
LP
LP
LP
LP
LP
LP
LP
FP-18
FP-12,14,16
G G
G
G
M
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-402
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
W A
T E
R S
T O
R A
G E
T A
N K
D E
T A
IL
P
O W
E R
A N
D L
IG
H
T N
IN
G
P R
O T
E C
T
IO
N
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
D e s ig n e r
A u th o r
C h e c k e r
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.B2
WATER STORAGE TANK DETAIL POWER AND LIGHTNING PROTECTION
SEE SHEET E-001 AND E-002 FOR GENERAL NOTES, ABBREVIATIONS
AND ELECTRICAL SYMBOLS.
GENERAL NOTES:
1.
POWER FOR HOT BOX. COORDINATE EXACT LOCATION WITH
MANUFACTURER.
60/NF/3/13R DISCONNECT SWITCH FOR 10KW WATER TANK HEATER.
COORDINATE EXACT LOCATION WITH MANUFACTURER.
KEY NOTES:
50902 05/11/19
COPPER BAR,
SIZE AS SPECIFIED
HOLES (PLAIN OR TAPPED) AS SPECIFIED
2700 VOLT INSULATORS
STEEL BRACKETS
SEE E-601 FOR
ADDITIONAL INFORMATION.
#10 BRASS BALL CHAIN
FINISHED HANGAR FLOOR
OR APRON PAVEMENT
3/4" N.C. THREAD
INSTALL BELOW CONCRETE SLAB.
EXOTHERMIC BONDING.
IN HANGARS, MAX,
RESISTANCE TO
GROUND SHALL BE 25
OHMS FROM ANY
GROUND ROD
BRASS PIN
CAST BRONZE
HOUSING
GROUND
PLAN
PAINT YELLOW
PAINT RED
PAINT THE WORD "GROUND"
IN 1" BLACK LETTERS AND
THE DATE TESTED IN 1/2"
BLACK LETTER
GROUND RECEPTACLE
SET IN FLOOR
ELEVATION
2" 18" DIA. 2"
2-3/4" DIA.
-7
/8
R E
F U
E L
IN
G S
Y S
T E
M
M
IN
F
O R
H A
N G
A R
S
M
IN
F
O R
H Y
D R
A N
T
/4
CAST BRONZE
COVER,
FRICTION FIT
INSTALL PIGTAIL TO CONNECT TO
FACILITY GROUND GRID; DO NOT CUT
GROUND GRID WIRES.
EPOXY OR SPOT WELD THREAD
COUPLING AFTER COMPLETING
ALIGNMENT WITH HANGAR FLOOR,
INCLUDING COVER ALIGNMENT.
NOTE:
1. PAINT COLORS ASSOCIATED WITH STATIC GROUNDING SERVICES VARY WITH
APPLICATION AND SERVICE. THE PAINT IS APPLIED DIRECTLY TO THE
HANGAR FLOOR OR APRON PAVEMENT, AND IS NOT APPLIED TO THE
RECEPTACLE.
2. DIRECTED BY THE USING ACTIVITY, RECEPTACLE COVERS WITH BRASS BALL
CHAIN.
TO IMPROVE SYSTEM RESISTANCE, ERICO GEM MAY BE USED
AS A BACKFILL MATERIAL IN AN AUGURED HOLE. PROVIDE
GROUND RODS TO ACHIEVE MAXIMUM 10 OHMS RESISTANCE.
1"x4" SLOT IN
12" PVC PIPE
GROUND CONDUCTOR, SIZE
AS NOTED ON PLANS
DRIVEN COPPER CLAD
GROUND ROD 5/8" x 10'
(SEE NOTE)
NOTE:
TEST WELL AND COVER
CADWELD TYPE GT
CLEAN SAND FILL
#2 AWG BCW TINNED PIGTAIL
24"
30" MIN
2"
2"
12" MIN
FINISHED GRADE
PROVIDE UTILITY
MARKER TAPE
BURIED 12" BELOW
FINISHED GRADE
COMPACTED
SAND
PVC DUCT (SEE PLAN
FOR QUANTITY & SIZE)
3"
LOOSE FILL
15"
N O
M
IN
A L
10"
CONCRETE RING
AROUND BOX
BOX AND
COVER
CRUSHED ROCK
COMPACTED EARTH
STAINLESS STEEL HEX
BOLT AND WASHER
PULL SLOT
SKID RESISTANT
SURFACE
SECTIONAL BOX
WHEN REQUIRED
TYPE HANDHOLE SIZING
5 12" X 12" X 24" DEEP
6 12" X 18" X 24" DEEP
7 12" X 24" X 24" DEEP
8 24" X 36" X 24" DEEP
9 30" X 48" X 24" DEEP
HANDHOLE REQUIREMENT
1. HOUSING SHALL BE A POLYMER CONCRETE REINFORCED WITH A HEAVY WEAVE FIBERGLASS
REINFORCING WITH COMPRESSIVE STRENGTH OF NO LESS THAN 10,000 psi.
2. COVER SHALL WITHSTAND A SERVICE LOAD OF NO LESS THAN 15,000 LBS OVER A 10" x 10" AREA.
3. PROVIDE STAINLESS STEEL BOLTS AND INSERTS.
4. PROVIDE WITH (2) 2 1/2" MOUSEHOLES.
5. PROVIDE LABEL "ELECTRICAL" FOR POWER HANDHOLES OR "COMMUNICATIONS" FOR COMMUNICATIONS
HANDHOLES, OR AS INDICATED.
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-501
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L D
E T
A
IL
S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.D1
GROUND BAR
SCALE: N.T.S.A1
STATIC GROUNDING RECEPTACLE DETAIL
SCALE: N.T.S.D3
GROUND ROD INSPECTION WELL DETAIL
SCALE: N.T.S.D5
ELEC - 2W DUCTBANK LOOSE FILL
SCALE: N.T.S.A4
HANDHOLE DETAIL
50902 05/11/19
NOT ACCEPTABLEACCEPTABLE NOT ACCEPTABLE
.0
0°
.0
0°
90.00°
8" 8"
8"
CABLE
PARALLEL COMBINATION
CABLE SPLICER
CABLE
ALUMINUM CLAMP;
ATTACH TO ROOF SEAM
STANDING SEAM ROOF
ATTACH TO SURFACE
OF ROOF CLAMP
(SHOWN BELOW)
M
IN
ROOF CONDUCTOR (ALUMINUM). ATTACH
TO ROOF EVERY 3' MINIMUM
REQUIREMENTS
THE UNIT SHALL CONSIST OF SOLID STATE ELECTRONIC
COMPONENTS AND SHALL BE COMPLETELY SELF-CONTAINED WITH
A NICKEL CADMIUM BATTERY AND ENCAPSULATED
INVERTER/CHARGER HOUSED IN A SINGLE ENCLOSURE. IT SHALL
BE PACKAGED FOR FIELD OR FACTORY INSTALLATION.
OPERATION - THE UNIT SHALL AUTOMATICALLY SUPPLY POWER
FOR THE ILLUMINATION OF ONE LAMP IN THE EVENT OF FAILURE
OF NORMAL POWER. WHEN NORMAL SUPPLY RETURNS, THE
UNIT SHALL AUTOMATICALLY RECHARGE, FROM FULL
DISCHARGE, IN 24 HOURS. DURING NORMAL CONDITIONS THE
BATTERY CHARGER SHALL TRICKLE CHARGE THE BATTERY
FROM AN UNSWITCHED CIRCUIT TO MAINTAIN FULL CHARGE
CONDITION. A FULLY CHARGED CONDITION SHALL BE INDICATED
BY A LIGHT-EMITTING DIODE.
TEST SWITCH, CONVENIENTLY LOCATED.
VOLTAGE - 120 OR 277 VOLTS, TO MATCH CIRCUIT.
LIFE - THE UNIT SHALL HAVE A MAINTENANCE-FREE LIFE OF 7 YEARS
MINIMUM.
THE UNIT SHALL MEET OR EXCEED THE NATIONAL ELECTRICAL CODE,
NFPA 70 TIME AND VOLTAGE REQUIREMENTS AND SHALL PROVIDE A
MINIMUM OF 1100 LUMENS OF INITIAL EMERGENCY ILLUMINATION.
THE UNIT SHALL CONFORM TO UL 924.
1.
2.
3.
4.
5.
6.
7.
LUMINAIRE REQUIREMENTS:
13"
NOMINAL
9"
NOMINAL
1. HOUSING - DIE-CAST ALUMINUM OR HIGH-IMPACT, UV-STABILIZED, INJECTION-MOLDED
THERMOPLASTIC. SINGLE OR DOUBLE-FACED AS INDICATED.
2. FINISH (ON CAST ALUMINUM HOUSING ONLY) - TEXTURED POWDER COAT FINISH
OPTIONS INCLUDE WHITE, WHITE WITH BRUSHED ALUMINUM FACE, BLACK, OR BLACK
WITH BRUSHED ALUMINUM FACE.
3. LETTERS/CHEVRONS - MINIMUM 6" HIGH WITH 3/4" STROKE. RED OR GREEN LETTERS
AS INDICATED. PROVIDE CHEVRONS AS INDICATED EITHER LEFT, RIGHT OR BOTH
DIRECTIONS AS INDICATED. CHEVRONS PUNCHED OUT THROUGH HOUSING AS
REQUIRED.
4. EMERGENCY PACK - SOLID-STATE, CONSTANT-CURRENT TYPE BATTERY CHARGER
WITH MAINTENANCE-FREE, NICKEL-CADMIUM BATTERY, AC-ON INDICATOR LAMP AND
TEST SWITCH.
5. MOUNTING - UNIVERSAL MOUNTING KIT FOR CEILING, WALL OR END-OF-FIXTURE
MOUNTING.
6. ILLUMINATION - PROVIDED BY RED, GREEN OR WHITE HIGH-OUTPUT LEDS INSIDE OF
FIXTURE HOUSING. PROVIDE POLYSTYRENE DIFFUSER IN COLOR INDICATED WITH
FREQUENCY-MATCHED SILKSCREEN COATING FOR MAXIMUM LED LIGHT OUTPUT.
7. CERTIFICATION - UL LISTED AND CERTIFIED FOR DAMP LOCATIONS.
GRADE
FINISHED FLOOR
DOWN CONDUCTOR 1" PVC BUILDING WALL
OR COLUMN
3/4" x 10'-0"
GROUND ROD
EXOTHERMIC WELD
BARE COPPER
GROUND RING
FINISHED ROOF
WALL OR COLUMN
DUCT SEAL
M
IN
MIN
3 FEET
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-502
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L D
E T
A
IL
S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.D2
CABLE BENDING DETAIL
SCALE: N.T.S.D5
CABLE SPLICE
SCALE: N.T.S.D1
AIR TERMINAL CLAMP
SCALE: N.T.S.A3
EMERGENCY BALLAST
SCALE: N.T.S.B5
LED EXIT SIGN
SCALE: N.T.S.A1
DOWN CONDUCTOR DETAIL
50902 05/11/19
HOUSING - DIE CAST ALUMINUM WITH INTEGRAL HEAT SINKS
FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT
FINISHED WITH HIGH REFLECTANCE (MINIMUM 85%), BAKED WHITE
ENAMEL FINISH.
LENS - POLYCARBONATE
LAMPS - HIGH OUTPUT LEDS WITH WIDE DISTRIBUTION.
MOUNTING - UNIVERSAL HANGER FOR CHAIN, TONG OR CRADLE
SYSTEM.
ELECTRICAL - HIGH POWER FACTOR ELECTRONIC INTEGRAL LED
DRIVERS. DIMMING DRIVER STANDARD.
CERTIFICATION - UL LISTED AND LABELED.
MANUFACTURER'S WARRANTY - MINIMUM 10 YEAR
RATED FOR USE AT 55 DEGREES C.
LUMINAIRE REQUIREMENTS:
1.
2.
3.
4.
5.
6.
7.
8.
9.
14" - 24" NOMINAL
N O
M
IN
A L
4' NOMINAL
LUMINAIRE REQUIREMENTS:
NOMINAL
5"
HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY. ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. FIXTURE SHALL NOT
PERMANENTLY DEFORM OUT OF "SQUARE" WHEN PICKED UP FROM ANY CORNER.
FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH HIGH
REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
LENS - 100% ACRYLIC
LAMPS - LED. PROVIDE WATTAGE AND TYPE AS SPECIFIED IN LIGHTING FIXTURE SCHEDULE.
DRIVER - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR (≥ .95),
ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR LIGHTING FIXTURE
SCHEDULE FOR BALLAST OPTIONS AND SPECIFICS.
CERTIFICATION - UL LISTED AND LABELED.
1.
2.
4.
5.
6.
LUMINAIRE REQUIREMENTS:
1. HOUSING - DIE-FORMED, COLD-ROLLED STEEL, WITH REINFORCEMENT RIBS FOR
RIGIDITY. ENDCAPS SECURED WITH TABS, SCREWS OR RIVETS. FIXTURE SHALL
NOT PERMANENTLY DEFORM OUT OF "SQUARE" WHEN PICKED UP FROM ANY
CORNER.
2. FINISH - MULTI-STAGE PHOSPHATE BONDING TREATMENT FINISHED WITH
HIGH REFLECTANCE (MINIMUM 85%), BAKED WHITE ENAMEL FINISH.
3. LAMPHOLDERS- PRESSURE-LOCKED TYPE ENCLOSED IN TURRET HOUSING.
4. REFLECTOR - DIE-FORMED, COLD-ROLLED STEEL WITH TRANSVERSE RIBS FOR
RIGIDITY. SOLID, 10% UPLIGHT APERATURE OR 20% UPLIGHT APERATURE AS
INDICATED IN LIGHTING FIXTURE SCHEDULE.
5. LAMPS - LED, TYPICALLY WITH WATTAGES AS INDICATED.
SEE LIGHTING FIXTURE SCHEDULE.
6. BALLAST - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR ( ≥ .95),
ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION OR LIGHTING
FIXTURE SCHEDULE FOR BALLAST OPTIONS AND SPECIFICS.
7. CERTIFICATION - UL LISTED AND LABELED.
8. OPTIONS - CHAIN HANGER AND PLATED STEEL WIRE GUARD.
9. PHOTOMETRICS - MINIMUM VALUE OF COEFFICIENT OF UTILIZATION (CU) AND
EFFICIENCY, GIVEN INTERIOR CAVITY REFLECTANCES OF 80-50-20:
1. HOUSING - ONE-PIECE, DIE-STAMPED, COLD ROLLED STEEL OR ACRYLIC-ENAMELED ALUMINUM.
PROVIDE WITH PRE-WIRED JUNCTION BOX HAVING SNAP-ON ACCESS COVER. ACCESS TO
JUNCTION BOX FROM BELOW CEILING SHALL BE PROVIDED THROUGH FIXTURE AFTER REMOVAL
OF REFLECTOR.
2. REFLECTOR AND TRIM - ONE-PIECE, CLEAR, SPUN ALUMINUM, IRIDESCENCE- SUPRESSED, WITH PAINTED WHITE SELF TRIM. OTHER FINISHES AND TYPES AVAILABLE. SEE LIGHTING FIXTURE
SCHEDULE.
3. BALLAST - CLASS P, MULTI-VOLT (120V-277V INPUT), HIGH POWER FACTOR ( ≥ .95), PROGRAMMED RAPID START ELECTRONIC TYPE WITH ≤ 10% TOTAL HARMONIC DISTORTION. BALLAST SHALL BE
CAPABLE OF UNIVERSALLY OPERATING 26W, 32W, OR 42 WATT LAMPS.
4. LAMPS - LED. PROVIDE WATTAGES AS INDICATED. SEE LIGHTING FIXTURE SCHEDULE..
5. CERTIFICATION - UL LISTED AND LABELED.
6. MANUFACTURER'S WARRANTY - MINIMUM 10 YEAR.
7. OPTIONS -
REFLECTOR TYPE - DIRECT DOWNLIGHT OR WALL WASH; SEMI-SPECULAR OR SPECULAR.
REFLECTOR COLOR - CLEAR, CHAMPAGNE, PEWTER, WHEAT, GOLD OR BRONZE
TRIM - OPEN REFLECTOR, STEPPED WHITE OR BLACK BAFFLE
LUMINAIRE REQUIREMENTS:
6" or 8"
NOMINAL
6" NOMINAL
HOUSING - DIE-CAST SINGLE PIECE ALUMINUM, DIE CAST DOORFRAME
WITH A 1/8" THICK TEMPERED GLASS LENS. DOORFRAME FULLY
GASKETED WITH ONE PIECE SOLID SILICONE.
REFLECTOR - SEGMENTED REFLECTOR.
BALLAST - ELECTRONIC HIGH FREQUENCY BALLAST.
WIRING - FIXTURE SHALL HAVE INTERNAL GREEN GROUNDING SCREW.
NO INTERNAL WIRING SHALL BE EXPOSED.
SOCKET: FOUR PIN POSITIVE LATCHING THERMOPLASTIC.
FINISH: TEXTURED DARK BRONZE, WITH ENHANCED CORROSION
RESISTANCE POLYESTER POWDER FINISH.
LAMPS - PROVIDE WATTAGE AND TYPE AS SPECIFIED IN LIGHTING
FIXTURE SCHEDULE.
LENS - IMPACT RESISTANT GLASS.
CONCEALED MOUNTING HARDWARE (ALL HARDWARE CORROSION
RESISTANT).
UL 1572 LISTED - SUITABLE FOR OUTDOOR WET LOCATIONS.
PROVIDE FULL CUTOFF OPTICS.
PROVIDE EMERGENCY LED SECONDARY SOURCE (TWO MODULES)
BATTERY PACK.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
LUMINAIRE REQUIREMENTS:
LUMINAIRE REQUIREMENTS:
1. HOUSING - EXTRUDED ALUMINUM, FABRICATED SHEET ALUMINUM, OR A
COMBINATION OF BOTH AS INDICATED. ALL SEAMS SHALL BE SEALED
AND WELDED.
2. FINISH - MULTI-STAGE PRE-TREATMENT, FINISHED WITH BAKED-ON
POLYESTER POWDER COAT. OPTIONAL ARCHITECTURAL CLASS 1
ANODIZE FINISH AVAILABLE AS INDICATED.
3. LENS AND FRAME - EXTRUDED, ANODIZED ALUMINUM FRAME WITH ONE-
PIECE MOLDED HIGH TEMPERATURE GASKET. LENS SHALL BE TEMPERED
GLASS, FULLY GASKETED.
4. INTERNAL REFLECTOR - TWO INTERNAL LOUVERS SHALL PROVIDE
SHEILDING AND GLARE CONTROL OF BARE LAMP. FIXTURE TYPE 'OD'
SHALL INCORPORATE A THIRD LOUVER TO PROVIDE ADDITIONAL
GLARE AND SPILL LIGHT CONTROL REQUIRED TO MEET AIRPORT
DESIGN CRITERIA.
5. LAMPS - LED, WITH WATTAGES AS INDICATED. SEE LIGHTING FIXTURE
SCHEDULE.
6. BALLAST - CLASS P, THERMALLY-PROTECTED, HIGH POWER FACTOR
( ≥ .95), ELECTRONIC TYPE WITH SOUND RATING A. SEE SPECIFICATION
OR LIGHTING FIXTURE SCHEDULE FOR BALLAST OPTIONS AND SPECIFICS.
7. CERTIFICATION - UL LISTED AND CERTIFIED FOR WET LOCATIONS.
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-503
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L D
E T
A
IL
S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.C1
TYPE A AND AE FIXTURES
SCALE: N.T.S.C2
TYPE B AND BE FIXTURES
SCALE: N.T.S.C4
TYPE C AND CE FIXTURE
SCALE: N.T.S.A1
TYPE D, DE AND F FIXTURE
SCALE: N.T.S.A2
TYPE G AND GE FIXTURES
SCALE: N.T.S.A4
TYPE H FIXTURE
50902 05/11/19
FRONT VIEW
PLAN VIEW
CONCRETE ENCASED
PVC CONDUIT PRIMARY
NUMBER AND SIZE AS INDICATED
PVC CONDUIT SECONDARY
NUMBER AND SIZE AS INDICATED
RGS TO PVC COUPLING (TYP.)
3/4" X 10' GROUND ROD
(TYPICAL FOR 4) MINIMUM
FUSES
TAP CHANGER
15kV, 200A LOAD BREAK
ELBOW (TYP. FOR 3)
REINFORCING BARS
CABLE SHIELD ADAPTER (TYP.)
CABLE SHIELDS
(TYP. FOR 3)
3/4" X 10' COPPER CLAD
GROUND ROD (TYP. AT EACH
CORNER OF CONCRETE PAD)
H3A
H1A
H2A
H3B
H2B
SWITCH H1B
X0
X1
X2
X3
G4
G
G4
G
G
G
TRANSFORMER PAD
PAD DIMENSIONS AS REQUIRED
TO PROVIDE NOT LESS THAN
6" SPACING BETWEEN
TRANSFORMER & EDGE OF
PAD ON ALL SIDES
G4
G
G
G4
TRANSFORMER
SURGE ARRESTER (TYP. FOR 3)
8" THICK CONCRETE PAD
3/4" CHAMFER ALL TOP EDGES
GRADE
GROUND BUS OR PAD; ONE IN
HV & ONE IN LV COMPARTMENT
4/0 BARE COPPER GROUNDING
CONDUCTOR
WATTHOUR DEMAND METER
(CT'S & WIRING NOT SHOWN)
#4 GROUND LEAD (TYP. FOR 3)
FACTORY INSTALLED STRAP
FOUR HOLE TERMINAL AS
REQUIRED (TYP. FOR 4)
OPENINGS SIZED TO TRANSFORMER
PRIMARY & SECONDARY
COMPARTMENTS; FILL WITH GRAVEL
AROUND CONDUIT & CABLE ENTRIES
#4 REINFORCING BARS
NOT TO EXCEED 18"
SPACING BOTH WAYS
4/0 GROUND RING (TYPICAL)
EXOTHERMIC WELD (TYPICAL)
MASTIC WRAPPED RGS
PVC END BELL (TYP.)
SWITCH
EXOTHERMIC CONNECTION
(TYPICAL)
C C
24" TYP
T Y
P
M
IN
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-504
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L D
E T
A
IL
S
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
D e s ig n e r
A u th o r
C h e c k e r
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.A3
PAD MOUNTED TRANSFORMER W/GROUNDING
50902 05/11/19
A
/3 P
PNL MDP, 400A MLO, 480/277V, 3PH, 4W; 25,000 SCCR
A
/3 P
XFMR
T1
CONDUIT AND CONDUCTOR SCHEDULE:
4-600KCMIL - 4"C
4-600KCMIL & 1#2G - 4"C
NOT USED
3#10 & 1#10G - 3/4"C
4#1 & 1#8G - 2"C
3-2/0 & 1#6G - 2"C
4-3/0 & 1#6G - 2 1/2"C
3#6 & 1#10G - 3/4"C
4#4 & 1#10G - 1 1/4"C (WET LOCATION, PVC)
TRANSITION TO EMT AT 6" AFG.
3#4 & 1#10G - 1"C
4#12 & 1#12G - 3/4"C
2#12 & 1#12G - 3/4"C
NEW 500KVA PMT
12.47KV - 480/277V
4.4% Z MINIMUM
RA
200A
MCB
LA
100A
MLO
5 6
KEYED NOTES:
TEMPORARY GENERATOR CONNECTION
LIMIT DISTANCE FROM WIREWAY TO SERVICE ENTRANCE
OVERCURRENT PROTECTION TO 3'-0".
PROVIDE MINI POWER ZONE WITH 5 KVA TRANSFORMER
480-240V SINGLE PHASE WITH A 50A MCB 240V SINGLE
PHASE 6 POLE PANEL.
PROVIDE NEW 500KVA PAD MOUNTED TRANSFORMER
TO REPLACE EXISTING TRANSFORMER.
112.5KVA,3Ø
480- 208/120V
N
G
#1/0G
#1/0G
M
ELECTRONIC MULTI-
FUNCTION METER
A
/3 P
SPD
SPD
SPD
RB
200A
MCB
SPD
#4 BONDED TO TELECOM
MAIN GROUND BUS
#6 BONDED TO FACP
#1/0 BONDED TO
WATER PIPE
#1/0 BONDED TO
BUILDING STEEL
#1/0 BONDED TO
FOUNDATION REBAR
#1/0 BONDED TO
GROUND RING
GROUND BAR IN ELECTRICAL ROOM
(1/4" X 4" X 18" ON 2" STAND OFF
INSULATORS)
N E
J
M 200 HP
FIRE PUMP
FIRE PUMP
CONTROLLER
400/400/3/1 S.E. RATED
M 12.6 HP
FABRIC
DOOR
30/30/3/1 S.E. RATED
400A MTS
A
/3 P
XFMR
T2
30KVA,3Ø
480- 208/120V
#8G
IT1
100A
MLO
SPD
TO PRIMARY
DISTRIBUTION
N
E30A MTS
J
WIREWAY
100/100/3/1
A
/3 P
SPARE
A
/3 P
SPARE
M 1.5 HP
JOCKEY
PUMP
WIREWAY (3'W x 1'D)
MANHOLE
MUNITIONS LOAD CREW TRAINING BUILDING FIRE PUMP HOUSE
FP
60A
MCB
SPD
UL 1449
3RD EDITION
A
/3 P
100/100/3/1
400 HZ
EQUIPMENT
N
G
#8G
HANGAR LIGHTS
INVERTER
#1G
A
/2 P
FA
50A
MCB
#12G
XFMR
T3
#1/0 BONDED TO
WATER PIPE
#1/0 BONDED TO
BUILDING STEEL
#1/0 BONDED TO
FOUNDATION REBAR
#1/0 BONDED TO
GROUND RING
GROUND BAR IN ELECTRICAL ROOM
(1/4" X 4" X 18" ON 2" STAND OFF
INSULATORS)
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-601
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
E L E
C T
R
IC
A L O
N E
-L
IN
E D
IA
G
R A
M
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
SCALE: N.T.S.1
ELECTRICAL ONE LINE DIAGRAM
50902 05/11/19
CONTACTOR SCHEDULE
C1 - 4 POLE 20A BAY LIGHTS
C1
2" MIN.
DOOR
CONTROL ENCLOSURE
PHENOLIC TAG NOTE
TC-1
2" MIN.
SEE CONTROL SCHEMATICS, THIS SHEET.
SCHEMATICS6" TYP.
6" TYP.
2"
LABEL EACH WITH
PHENOLIC TAG. SEE
PHENOLIC TAG NOTE BELOW
(TYPICAL FOR ALL)
DIN RAIL OF SUITABLE LENGTH TO
ACCOMODATE THE REQUIRED
NUMBER OF 10A CIRCUIT BREAKERS
PHENOLIC TAG - BLACK ON WHITE WITH
MINIMUM OF 1/4" HIGH LETTERING .
PERMANENTLY ATTACH TAG TO
ENCLOSURE OR DEVICE AS REQUIRED.
SCREWS ARE NOT TO BE USED TO
ATTACH TAGS TO THE PANEL.
CA
CA - 6 POLE 20A BAY LIGHTS
OFF
AUTO
MANUAL 100%
MANUAL 50%
CONTROL CABINET DOOR PROVIDE A FOUR POSITION
SELECTOR SWITCH MOUNTED TO
THE EXTERIOR OF THE CONTROL
CABINET DOOR, DETAIL A3 THIS
SHEET, WIRED SUCH TO PROVIDE
THE FOLLOW OPTIONS:
1.
2.
3.
4.
OFF
AUTO
50%
100%
(MANUAL OVERRIDE TO
TURN THE LIGHTS OFF)
(TIMER CONTROLS THE
LIGHTS)
(MANUAL OVERRIDE TO
TURN ON LIGHTS FED
FROM CONTACTOR 1)
(MANUAL OVERRIDE TO
TURN ON ALL LIGHTS)
AUTO
100%
50%
OFF
TC-1
CA
C1
6KW LIGHTING INVERTER
CKT #5 CKT #3 CKT #4 CKT #2CKT #1
DAY LIGHT HARVESTING
W/OVERRIDE SWITCH
277V
LA-6
4 POLE LIGHTING
CONTACTOR
2 POLE LIGHTING
CONTACTOR
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-602
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
L
IG
H T
IN
G
F
IX
T U
R E
S C
H E
D U
L E
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
LIGHTING FIXTURE SCHEDULE
FIXTURE DESCRIPTION LAMP VOLTAGE MOUNTING MANUFACTURER (1)
AE HIGH BAY LED CONNECTED TO
INVERTER SYSTEM
LED
37,144 LM
277 V PENDANT AT
28'-10"
LUX DYNAMICS LED-GYM-4-UNV-840-LADC-TOP-DIR-MV-H10-18Y-EM12
B 2'X2' LED VOLUMETRIC
ARCHITECTURAL TROFFER
LED 3000 LM 277 V RECESSED TOPAZ LIGHTING F-L22-32-840-D-HP-75
BE 2'X2' LED VOLUMETRIC
ARCHITECTURAL TROFFER WITH
BATTERY BACKUP
LED 3000 LM 277 V RECESSED TOPAZ LIGHTING F-L22-32-840-D-HP-75
C 4' LED INDUSTRIAL LED
3000 LM
277 V PENDANT LITHONIA LIGHTING ZL1D L48 3000LM FST MVOLT 35K 80CRI WH WGZ48
CE 4' LED INDUSTRIAL WITH BATTERY
BACKUP
LED
3000 LM
277 V PENDANT LITHONIA LIGHTING ZL1D L48 3000LM FST MVOLT 35K 80CRI WH WGZ48 E7W
D 6' DIAMETER RECESSED LED
DOWNLIGHT LIGHT
LED
3000 LM
277 V RECESSED GOTHAM LIGHTING EVO-40-30-6AR-MD-MVOLT
DE 6' DIAMETER RECESSED LED
DOWNLIGHT WITH BATTERY BACKUP
LED
3000 LM
277 V RECESSED GOTHAM LIGHTING EVO-40-30-6AR-MD-MVOLT-EL
F 6' DIAMETER RECESSED LED LENSED
SHOWER LIGHT
LED
3000 LM
277 V RECESSED GOTHAM LIGHTING EVO-40-30-6-DFR-MVOLT
G LED QUARTERSPHERE LED
2160 LM
277 V WALL 10'-8"
AFF
LITHONIA LIGHTING WSQ LED-1-10A700/40K-SR3-277
GE LED QUARTERSPHERE WITH BATTERY
BACK UP
LED
2160 LM
277 V WALL 10'-8"
AFF
LITHONIA LIGHTING WSQ LED-1-10A700/40K-SR3-277-ELCW
H LED FLOOD LIGHT LED
18,333 LM
277 V WALL 35' AFF LITHONIA LIGHTING DSXF3 6 P2 40K FL MVOLT DDBXD
JE 4' LED INDUSTRIAL WITH BATTERY
BACKUP
LED
3000 LM
120 V PENDANT LITHONIA LIGHTING ZL1D L48 3000LM FST MVOLT 35K 80CRI WH WGZ48 E7W
X LED EXIT SIGN LED 277 V WALL LITHONIA LIGHTING LE SW 1/2 R-277 EL VR
1. BASIS OF DESIGN MANUFACTURERS ARE FOR REFERENCE ONLY. ALTERNATE FIXTURES WITH EQUIVALENT CONSTRUCTION AND PHOTOMETRIC
PERFORMANCE ARE ACCEPTABLE.
NOTE:
SCALE: N.T.S.B3
CONTROL CABINET
SCALE: N.T.S.B5
4-POSITION SELECTOR SWITCH
SCALE: N.T.S.D1
HANGAR LIGHTING CONTROL DIAGRAM
50902 05/11/19
1 2 3 4 6
A
B
C
D
SHEET OF
SHEET ID
P a rk w a y L a n e S u it e
P e a c h tr e e
C o rn e rs
G
A
P h o n e
-7
F a x
-7
S
IZ
E
A
N S
I D
F
IL
E N
A M
E
S U
B M
IT
T
E D
B Y
C H
E C
K E
D B
Y
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
IS
S
U E
D A
T E
A N
G N
O
C O
N T
R A
C T
N O
F
IL
E N
U N
B E
R
A P
P R
D
E S
C R
IP
T
IO
N
M A
R K
E
D A
T E
S B
R
Professional Certification.
I hereby certify that these documents were prepared or approved by me, and that I am a duly licensed professional engineer under the laws of the State of Maryland, License No.
Expiration Date:
/2 /2
:2
:5
P M
C R e v it L o c a l\
\1
D C
A N
G
M L C
T F
H
A N
G A
R
E L E
C
C E
N T
R A
L
R m a p
.r v t
E-603
TYPE B-3 (100%) SUBMITTAL - ISSUED FOR BID
M E
C H
A N
IC
A
L E
Q U
IP
M
E N
T S
C H
E D
U L E
M U
N
IT
IO
N
S L
O A
D C
R E
W T
R A
IN
IN
G F
A C
IL
IT
Y th
W
IN
G D
C A
N G
J O
IN
T
B A
S E
A N
D R
E W
S ,M
D
D
IS
T R
IC
T
O F
C O
L U
M B
IA
A
IR
N
A T
IO
N
A L
G U
A R
D
J O
B N
O
M A
P
M A
P
J M
S
O
C T
O B
E R
A J X
F
W
L
-1 -D
-0
X X
-X -X
X X
X
MECHANICAL EQUIPMENT SCHEDULE
ITEM VOLTAGE POLES KW HP FLA MCA MOCP FEEDER SIZE
BREAKER
AMPS
BREAKER
POLES DISC SWITCH STARTER
ARU-1 208 V 3 23.3 3#10 & 1#10G - 3/4"C 30 A 3 30/NF/3/1 BY DIV. 23
DF-1 120 V 1 1 15 2#12 & 1#12G - 3/4"C 20 A 1 MRS BY DIV. 23
DOAS-1 208 V 3 25.6 32.0 35 3#8 & 1#10G - 3/4"C 35 A 3 60/NF/3/1 BY DIV. 23
DOAS-HP-1 208 V 3 11.9 14.5 3#12 & 1#12G - 3/4"C 20 A 3 30/NF/3/3R BY DIV. 23
DSCU-1 208 V 2 13 2#12 & 1#12G - 3/4"C 15 A 2 30/NF/2/3R BY DIV. 23
DSS-1 * 208 V 2 2#12 & 1#12G - 3/4"C 15 A 2 MRS BY DIV. 23
E…