W912QR24R0009_Plans_Vol6-0000.pdf

PDF 8 MB Posted

Attached to
Solicitation W912QR24R0009 USARC Ft. Buchanan Puerto Rico
Solicitation number
W912QR24R0009
Issued by

About this file

This document provides construction plans for electrical work at the US Army Reserve Center in Fort Buchanan, Puerto Rico. Key details include specifications for lighting fixtures, panel schedules, one-line diagrams, and partial floor plans showing locations of receptacles, switches, and other electrical devices. The project involves new electrical installation throughout the facility, including in areas such as classrooms, offices, mechanical and storage rooms. Specific equipment includes lighting fixtures, receptacles, switches, communications devices, and HVAC power connections. Conduit and wiring sizes are specified along with panel schedules listing circuit information and locations supplied from relevant distribution panels.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers®

SHEET ID

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

PROJECT NO. 89301, P2# 481867

PR

O

JE

C

T N

O . 8

, P 2#

N

L

J

G

E

C

A

P

M

K

H

F

D

B

1 3 5 7 9 11 13 15 17 192 4 6 8 10 12 14 16 18 20

LOUISVILLE DISTRICT

ISSUE DATE: OCTOBER 27, 2023

CONTRACT NO.: -

SOLICITATION NO.: -

CERTIFIED FINAL SUBMITTAL

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

G-001

C O

VE

R

S H

EE

T

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

LO

U

IS

VI

LL

E D

IS

TR

IC

T

LO

U

IS

VI

LL

E, K

EN

TU

C

KY

M .B

AR

N

ET

T

K.

R

IG

G

S

A.

M

C C

O Y

O C

TO

B

ER

7, D .H

EN

SL

EY

FORT BUCHANAN, PUERTO RICO

U.S. ARMY RESERVE CENTER OPERATIONS BUILDING

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

K

ER D

.A

M N

B

A M

M

10/27/2023

07/22/202007/27/202011/6/202012-4-202005/04/202107/22/202108/25/202102/14/202202/15/202207/13/202207/21/202205/24/202310/27/202310/27/2023

10/27/2023

10/27/2023

10/27/2023

10/27/23

VOLUME 6 OF 6

W

2Q R

R

_P la ns _V ol 6-

22 November 2023

W912QR24R0009

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

SHEET ID

P R

O J E

C T

N O

P

C E

R T

IF

IE

D F

IN

A

L S

U B

M

IT

T A

L

D R

A W

IN

G

L

IS

T

U .S

A

R M

Y R

E S

E R

V E

C E

N T

E R

O P

E R

A T

IO

N

S B

U

IL

D

IN

G

F O

R T

B U

C H

A N

A N

P

U E

R T

O R

IC

O

M B

A R

N E

T T

K R

IG

G

S

A M

C C

O Y

O C

T O

B E

R

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

G-002

D H

E N

S L E

Y

SHEET LIST

SHEET NUMBER SHEET NAME

M-713 MECHANICAL CONTROLS

ELECTRICAL

E-001 ELECTRICAL LEGEND

E-002 ELECTRICAL GENERAL NOTES & ABBREVIATIONS

EL111 PARTIAL LIGHTING PLAN

EL112 PARTIAL LIGHTING PLAN

EL113 PARTIAL LIGHTING PLAN

EL601 LIGHTING DIAGRAMS

EL701 LIGHTING SCHEDULES

EP111 PARTIAL POWER PLAN

EP112 PARTIAL POWER PLAN

EP113 PARTIAL POWER PLAN

EP130 BID OPTION 0014 - ROOF PV ARRAY PLAN

EP151 PARTIAL HVAC POWER PLAN

EP152 PARTIAL HVAC POWER PLAN

EP153 PARTIAL HVAC POWER PLAN

EP410 ENLARGED POWER PLANS

EP501 ELECTRICAL DETAILS

EP601 POWER ONE LINE DIAGRAM

EP701 PANEL SCHEDULES

EP702 PANEL SCHEDULES

EP703 PANEL SCHEDULES

EP704 PANEL SCHEDULES

EP705 PANEL SCHEDULES

EY111 PARTIAL SPECIAL SYSTEMS PLAN

EY112 PARTIAL SPECIAL SYSTEMS PLAN

EY113 PARTIAL SPECIAL SYSTEMS PLAN

EY501 SPECIAL SYSTEMS DETAILS

EG130 LIGHTNING PROTECTION PLAN

EG131 BID OPTION 0014 - LIGHTNING PROTECTION PLAN

EG501 LIGHTNING PROTECTION DETAILS

EG502 GROUNDING DETAILS

EG601 GROUNDING ONE LINE DIAGRAM

TELECOMMUNICATIONS

T-001 COMMUNICATIONS LEGENDS

T-002 COMMUNICATIONS GENERAL NOTES & ABBREVIATIONS

T-111 PARTIAL COMMUNICATIONS PLAN

T-112 PARTIAL COMMUNICATIONS PLAN

T-113 PARTIAL COMMUNICATIONS PLAN

T-410 ENLARGED COMMUNICATIONS PLANS

T-501 COMMUNICATIONS DETAILS

T-502 COMMUNICATIONS DETAILS

T-601 COMMUNICATION DIAGRAMS

T-602 COMMUNICATION ROOM 147 ELEVATION DIAGRAM

T-603 COMMUNICATION ROOM 126 ELEVATION DIAGRAM

SHEET LIST

SHEET NUMBER SHEET NAME

INTERIORS

I-001 FF&E LEGEND

I-110 COMPOSITE FURNITURE PLAN

I-111 PARTIAL FURNITURE PLAN

I-112 PARTIAL FURNITURE PLAN

I-113 PARTIAL FURNITURE PLAN

LIFE SAFETY

LS001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

LS100 CODE COMPLIANCE SITE PLAN

LS110 LEVEL 1 LIFE SAFETY PLAN - COMPOSITE

FIRE PROTECTION

FP001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

FP110 LEVEL 1 FIRE PROTECTION PLAN - COMPOSITE

FP501 FIRE PROTECTION DETAILS

FP502 FIRE PROTECTION DETAILS

FIRE ALARM

FA001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

FA110 LEVEL 1 FIRE ALARM PLAN - COMPOSITE

FA501 FIRE ALARM DETAILS

FA502 FIRE ALARM DETAILS

PLUMBING

P-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

PP101 PARTIAL UNDERGROUND PLAN

PP102 PARTIAL UNDERGROUND PLAN

PP111 PARTIAL SANITARY PLAN

PP112 PARTIAL SANITARY PLAN

PP113 PARTIAL WATER PLAN

PP114 PARTIAL WATER PLAN

PP115 PARTIAL WATER PLAN

P-401 ENLARGED PLANS

P-402 ENLARGED PLANS

P-403 ENLARGED PLANS

P-404 ENLARGED PLANS

P-405 ENLARGED PLANS

P-406 ENLARGED PLANS

P-501 DETAILS

P-502 DETAILS

P-503 DETAILS

P-504 DETAILS

P-601 SCHEDULES

P-900 RISER DIAGRAMS

P-901 RISER DIAGRAMS

P-902 RISER DIAGRAMS

P-910 RISER DIAGRAMS

P-911 RISER DIAGRAMS

P-912 RISER DIAGRAMS

MECHANICAL

M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

MH111 PARTIAL FLOOR PLAN - HVAC

MH112 PARTIAL FLOOR PLAN - HVAC

MH113 PARTIAL FLOOR PLAN - HVAC

MP111 PARTIAL FLOOR PLAN - PIPING

MP112 PARTIAL FLOOR PLAN - PIPING

MP113 PARTIAL FLOOR PLAN - PIPING

M-301 SECTIONS

M-411 ENLARGED PLAN - HVAC

M-412 ENLARGED PLAN - PIPING

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-504 MECHANICAL DETAILS

M-505 MECHANICAL DETAILS

M-506 MECHANICAL DETAILS

M-507 MECHANICAL DETAILS

M-550 AIR RISER DIAGRAM

M-551 AIR RISER DIAGRAM

M-552 AIR RISER DIAGRAM

M-553 CHILLED WATER PIPING DIAGRAM

M-601 MECHANICAL SCHEDULES

M-602 MECHANICAL SCHEDULES

M-603 MECHANICAL SCHEDULES

M-701 MECHANICAL CONTROLS

M-702 MECHANICAL CONTROLS

M-703 MECHANICAL CONTROLS

M-704 MECHANICAL CONTROLS

M-705 MECHANICAL CONTROLS

M-706 MECHANICAL CONTROLS

M-707 MECHANICAL CONTROLS

M-708 MECHANICAL CONTROLS

M-709 MECHANICAL CONTROLS

M-710 MECHANICAL CONTROLS

M-711 MECHANICAL CONTROLS

M-712 MECHANICAL CONTROLS

SHEET LIST

SHEET NUMBER SHEET NAME

S-362 FRAMING SECTIONS

S-363 FRAMING SECTIONS

S-364 FRAMING SECTIONS

S-365 FRAMING SECTIONS

S-366 BID OPTION - SOLAR PANEL SUPPORT FRAMING SECTIONS

S-401 ENLARGED RAMP FOUNDATION/SLAB PLAN

S-402 RAMP SECTIONS

S-411 ENLARGED VAULT ROOF SLAB FRAMING PLAN

S-412 VAULT SECTIONS AND DETAILS

S-413 VAULT SECTIONS

S-501 TYPICAL FOUNDATION DETAILS

S-502 TYPICAL FOUNDATION DETAILS

S-503 PRECAST WALL PANEL DETAILS

S-511 TYPICAL FRAMING DETAILS

S-601 SCHEDULES

S-602 SPECIAL JOIST LOADING DIAGRAM

ARCHITECTURE

A-001 SYMBOL LEGEND

A-110 COMPOSITE FLOOR PLAN

A-111D PARTIAL DIMENSION PLAN

A-111N PARTIAL NOTE PLAN

A-112D PARTIAL DIMENSION PLAN

A-112N PARTIAL NOTE PLAN

A-113D PARTIAL DIMENSION PLAN

A-113N PARTIAL NOTE PLAN

A-130 COMPOSITE ROOF PLAN

A-140 COMPOSITE REFLECTED CEILING PLAN

A-141 PARTIAL REFLECTED CEILING PLAN

A-142 PARTIAL REFLECTED CEILING PLAN

A-143 PARTIAL REFLECTED CEILING PLAN

A-160 COMPOSITE PRECAST PANEL FLOOR PLAN

A-161 PRECAST PANEL ELEVATIONS

A-162 PRECAST PANEL DETAILS

A-181 PARTIAL SIGNAGE PLAN

A-182 PARTIAL SIGNAGE PLAN

A-183 PARTIAL SIGNAGE PLAN

A-200 COMPOSITE BUILDING ELEVATIONS

A-201 ENLARGED BUILDING ELEVATIONS

A-202 ENLARGED BUILDING ELEVATIONS

A-203 ENLARGED BUILDING ELEVATIONS

A-204 ENLARGED BUILDING ELEVATIONS

A-301 BUILDING SECTIONS

A-310 WALL SECTIONS

A-311 WALL SECTIONS

A-400 ENLARGED RESTROOM PLAN

A-401 RESTROOM DETAILS

A-402 TYPICAL RESTROOM MOUNTING HEIGHTS

A-410 RESTROOM ELEVATIONS

A-450 RAILING DETAILS

A-461 PARTIAL FINISH PLAN

A-462 PARTIAL FINISH PLAN

A-463 PARTIAL FINISH PLAN

A-500 DOOR AND FRAME TYPES AND ABA MANEUVERING

CLEARANCES

A-501 DOOR DETAILS

A-502 DOOR DETAILS

A-510 WINDOW TYPES & DETAILS

A-530 LOUVER TYPES AND DETAILS

A-540 WALL TYPES

A-541 WALL DETAILS

A-542 WALL DETAILS

A-550 COLUMN DETAILS

A-551 COLUMN DETAILS

A-560 CEILING DETAILS

A-570 ROOF DETAILS

A-571 ROOF DETAILS

A-580 MISCELLANEOUS DETAILS

A-600 DOOR SCHEDULE

A-610 FINISH SCHEDULE AND EXTERIOR FINISH KEY

A-611 FINISH KEYS & NOTES

A-620 SIGNAGE SCHEDULE

A-621 SIGNAGE DETAILS

A-700 ENLARGED VAULT DIMENSION PLAN

A-701 ENLARGED VAULT NOTED PLAN

A-710 ENLARGED CAGE PLANS

A-711 CAGE ELEVATIONS

A-712 CAGE SECTIONS AND DETAILS

A-713 CAGE DETAILS

A-800 ENLARGED KITCHEN PLAN

A-801 KITCHEN SCHEDULE

A-900 AIR BARRIER FLOOR PLAN

A-901 AIR BARRIER WALL SECTION

SHEET LIST

SHEET NUMBER SHEET NAME

GENERAL

G-001 COVER SHEET

G-002 DRAWING LIST

G-201 LOCATION AND VICINITY MAP

G-202 PROJECT AERIAL

CIVIL

V-101 OVERALL SITE SURVEY

V-111 SITE SURVEY

V-112 SITE SURVEY

B-101 OVERALL BORING PLAN

B-111 BORING PLAN

B-112 BORING PLAN

B-201 BORING LOGS

B-202 BORING LOGS

C-001 CIVIL LEGEND AND ABBREVATIONS

C-002 CIVIL GENERAL NOTES

CD101 OVERALL DEMOLITION PLAN

CD111 DEMOLITION PLAN

CD112 DEMOLITION PLAN

CG101 OVERALL GRADING AND DRAINAGE PLAN

CG111 GRADING AND DRAINAGE PLAN

CG112 GRADING AND DRAINAGE PLAN

CG201 STORM SEWER PROFILES & SCHEDULE

CG501 DRAINAGE DETAILS

CG502 DRAINAGE DETAILS

CG503 DRAINAGE DETAILS

CG701 OVERALL SEDIMENT AND EROSION CONTROL PLAN

CG711 SEDIMENT AND EROSION CONTROL PLAN

CG712 SEDIMENT AND EROSION CONTROL PLAN

CG801 SEDIMENT AND EROSION CONTROL NOTES

CG802 SEDIMENT AND EROSION CONTROL DETAILS

CG803 SEDIMENT AND EROSION CONTROL DETAILS

CG804 SEDIMENT AND EROSION CONTROL DETAILS

CG805 SEDIMENT AND EROSION CONTROL DETAILS

CG806 SEDIMENT AND EROSION CONTROL DETAILS

CS101 OVERALL SITE LAYOUT

CS111 SITE LAYOUT

CS112 SITE LAYOUT

CS401 JOINT LAYOUT PLAN

CS501 PAVEMENT DETAILS

CS502 PAVEMENT DETAILS

CS503 DESIGNATED SMOKING AREA SIGNAGE

CU101 OVERALL UTILITY PLAN

CU111 UTILITY PLAN

CU112 UTILITY PLAN

CU201 SANITARY SEWER PROFILES & SCHEDULE

CU501 SANITARY SEWER DETAILS

CU502 SANITARY SEWER DETAILS

CU511 WATER DETAILS

CU512 WATER DETAILS

LP101 OVERALL LANDSCAPE PLAN

LP111 LANDSCAPE PLAN

LP112 LANDSCAPE PLAN

ELECTRICAL

ES100 EXISTING ELECTRICAL SITE PLAN

ES101 ELECTRICAL SITE PLAN

ES501 SITE ELECTRICAL DETAILS

ES502 BID OPTION - SITE ELECTRICAL DETAILS

ES503 SITE ELECTRICAL DETAILS

TELECOMMUNICATIONS

TS101 COMMUNICATION SITE PLAN

STRUCTURAL

S-001 GENERAL STRUCTURAL NOTES AND DESIGN CRITERIA

S-002 GENERAL STRUCTURAL NOTES, DESIGN CRITERIA AND

ABBREVIATIONS

S-003 COMPONENTS AND CLADDING WIND LOAD DIAGRAM

S-111 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-112 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-113 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-114 SLAB ON GRADE CONTROL JOINT PLAN

S-131 PARTIAL ROOF FRAMING PLAN

S-132 PARTIAL ROOF FRAMING PLAN

S-133 PARTIAL ROOF FRAMING PLAN

S-141 BID OPTION - SOLAR PANEL SUPPORT FRAMING PLAN

S-200 PRECAST CONCRETE WALL ELEVATIONS KEY PLAN

S-211 CONCRETE WALL ELEVATIONS

S-212 CONCRETE WALL ELEVATIONS

S-213 CONCRETE WALL ELEVATIONS

S-251 OPERABLE PARTITION SUPPORT FRAMING ELEVATION AND

SECTION

S-301 FOUNDATION SECTIONS

S-302 FOUNDATION SECTIONS

S-361 FRAMING SECTIONS

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

K

ER D

.A

M N

B

A M

M

07/22/202007/27/202011/6/202012-4-202005/04/202107/22/202108/25/202102/14/202202/15/202207/13/202207/21/202205/24/202310/27/2023

W

2Q R

R

_P la ns _V ol 6-

INTERIOR & EXTERIOR LIGHTING FIXTURE SYMBOLS

SYMBOL DESCRIPTION

SINGLE FACE

DOUBLE FACE

TYPICAL LIGHTING FIXTURE SYMBOLS

TYPICAL LIGHTING FIXTURE SYMBOLS WITH BATTERY BACKUP OR

CONNECTED TO EMERGENCY CIRCUIT

EMERGENCY LIGHTING UNIT WITH ADJUSTABLE HEADS

CEILING FAN

LIGHTING TRACK WITH LIGHTS AS INDICATED

EXIT SIGN - PROVIDE ARROWS IF/AS INDICATED ON PLANS. SINGLE FACE =

TYPE "X1" AND DOUBLE FACE = TYPE "X2" UNLESS INDICATED OTHERWISE.

b HE

2 FILLED AREA INDICATES EMERGENCY LIGHTING (CIRCLE OR TRIANGLE)

'T' GRAPHIC ATTACHED TO SYMBOL INDICATES WALL MOUNTING

NUMBER INDICATES ASSOCIATED LIGHTING CIRCUIT

LOWER CASE LETTER INDICATES SWITCH CIRCUIT DESIGNATION IN SPACES WITH

MULTIPLE SWITCHING CIRCUITS. 'nl' INDICATES NIGHT LIGHTING UNSWITCHED FIXTURE

CAPITAL LETTER INDICATES FIXTURE TYPE. REFER TO FIXTURE SCHEDULE FOR

ADDITIONAL INFORMATION.

TYPICAL LIGHTING FIXTURE ANNOTATION

1. FIXTURE SYMBOLS ARE NOT INTENDED TO INDICATE ACTUAL PHYSICAL ATTRIBUTES OF FIXTURES.

2. REFER TO LIGHT FIXTURE SCHEDULE FOR FIXTURE DESCRIPTIONS, LUMEN AND POWER ATTRIBUTES, MOUNTING HEIGHTS AND OTHER LUMINAIRE INFORMATION.

3. EXACT LOCATION AND MOUNTING HEIGHTS OF ALL CEILING AND WALL MOUNTED FIXTURES SHALL BE

DETERMINED FROM ARCHITECTURAL RELECTED CEILING PLANS AND ELEVATIONS.

4. EMERGENCY BATTERY PACK SYSTEM ON LIGHT FIXTURES AND ALL EXIT SIGNS SHALL BE WIRED AHEAD

OF ANY SWITCH OR RELAY CONTROLLING THE CIRCUIT.

5. THE EXACT LOCATION OF ALL LIGHTING FIXTURES IN MECHANICAL SPACES SHALL BE FIELD

COORDINATED TO AVOID CONFLICT WITH THE MECHANICAL WORK.

FIXTURE ANNOTATION NOTES

SINGLE HEAD POLE MOUNTED LIGHTING FIXTURE.

DOUBLE HEAD POLE MOUNTED LIGHTING FIXTURE.

FLOOD LIGHT MOUNTED AT GRADE, ARROW INDICATES DIRECTION.

EMERGENCY EGRESS LIGHTING FIXTURE

INTERIOR LIGHTING CONTROL SYMBOLS

SYMBOL DESCRIPTION

LIGHT SWITCH OR CONTROLLER. REFER TO ROOM LIGHTING CONTROL TAG AND LIGHTING

CONTROL MATRIX FOR REQUIREMENTS.

1. REFER TO THE LIGHTING CONTROL SCHEDULE FOR SPACE LIGHTING CONTROL STRATEGIES.

2. ENSURE THAT LIGHTING CONTROL DEVICES ARE LOCATED AND INSTALLED ACCORDING TO THE MANUFACTURERS RECOMMENDATIONS TO ENSURE THAT THE CONTROL SYSTEM FUNCTIONS PER THE

LIGHTING CONTROL STRATEGY INDICATED ON THE LIGHTING CONTROL SCHEDULE AND THE

SPECIFICATIONS.

3. OCCUPANCY AND VACANCY SENSORS SHALL BE DUAL TECHNOLOGY (ULTRASONIC AND PASSIVE

INFRARED), UNLESS NOTED OTHERWISE.

LIGHTING CONTROL NOTES

LIGHTING CONTROL TAG. REFER TO LIGHTING CONTROL MATRIX.LC-XXX

DESCRIPTIONSYMBOL

MOUNTING

CEILING FLOORWALL

SUBSCRIPT INDICATES ADDITIONAL DEVICE TYPE INFORMATION. REFER

TO TYPE DESIGNATIONS FOR FURTHER INFORMATION.

NEMA 5-20R DUPLEX RECEPTACLE

NEMA 6-20R DUPLEX RECEPTACLE

NEMA 5-20R DUPLEX INTEGRAL GROUND FAULT INTERRUPT RECEPTACLE

NEMA 5-20R QUADRUPLEX RECEPTACLE

NEMA 6-20R QUADRUPLEX RECEPTACLE

NEMA L6-30R SIMPLEX RECEPTACLE

MULTI-OUTLET RACEWAY, 20A, 250V, NEMA 6-20R DUPLEX RECEPTACLE

SPACED 24" ON CENTER. PROVIDE WITH BARRIER TO SEPARATE POWER

AND TELECOM WIRING.

JUNCTION BOXJ JJ

PULL BOX: SUBSCRIPT INDICATES DIMENSIONS (L / W / D)

6/4/4

PB

DEVICE TYPE DESIGNATIONS (NOTED BY SUBSCRIPT)

AF ARC FAULT

CG CAGE MOUNTED

U UPS PROTECTED

FP FURNITURE POWER

IG ISOLATED GROUND

MGB MAIN GROUND BAR

P PILOT LIGHT

R RAISED FLOOR MOUNTED

RF FURNITURE SYSTEM POWER - RAISED FLOOR

TV TELEVISION

WP WEATHERPROOF

42" DEVICE MOUNTING HEIGHT

GROUND BAR

OPS DIGITAL OPS CLOCK

G

G GROUND BAR

SBB SECONDARY BUS BAR

NEMA 5-20R DUPLEX SWITCHED RECEPTACLE (SPLIT YOKE).

REFER TO SHEET EP501 FOR MORE INFORMATION.

NEMA 5-20R QUADRUPLEX SWITCHED RECEPTACLE (ONE

DUPLEX SWITCHED, ONE DUPLEX UNSWITCHED)

A/V AUDIO / VIDEO

POWER FLOOR BOX

POWER DEVICES

GROUNDING/LIGHTNING PROTECTION SYSTEM

SYMBOL DESCRIPTION

GROUNDING CONDUCTOR

ROOF GROUNDING CONDUCTOR

GROUNDING BOND

AIR TERMINAL (THE FOLLOW DENOTES TYPES. C: COLUMN MOUNTED, P: PARAPET

MOUNTED, S: SOLAR ARRAY MOUNTED. REFER TO SHEETS EG131 AND EG501 FOR MORE

INFORMATION.)

GROUND ROD (W: DENOTES IN WELL)W

SYMBOL DESCRIPTION

SAFETY SWITCH

NEMA ENCLOSURE RATING

SWITCH AMP RATING

30-15/3R

FUSE AMP RATING

(NF INDICATES NON-FUSED TYPE)

ENCLOSED CIRCUIT BREAKER

NEMA ENCLOSURE RATING

AIC RATING

100-22K/3R

TRIP RATING

(AMPS)(ST-SHUNT TRIP)

NEMA ENCLOSURE RATING

SWITCH AMP RATING

1/60-30/3R

TRIP RATING

(NF INDICATES NON-FUSED TYPE)

COMBINATION STARTER

ECB

NEMA STARTER SIZE

FULL VOLTAGE STARTER

MANUAL MOTOR STARTER

REDUCED VOLTAGE STARTER

VARIABLE FREQUENCY DRIVE

MISCELLANEOUS MOTOR

CONNECTION

EMERGENCY POWER OFF (EPO

SWITCH)

4NEMA ENCLOSURE RATING

NEMA ENCLOSURE

RATING

MMS

RVS

VFD

TRANSFORMER

PANELBOARDRP1PANEL NAME

TRP1XMFR NAME

ELECTRICAL EQUIPMENT / MOTOR CONNECTIONS

NEMA ENCLOSURE

RATING

NEMA ENCLOSURE

RATING

X

X-XXX

X

X-XXX

DETAIL

NOT TO SCALE

DETAIL IDENTIFICATION NUMBER

DETAIL IDENTIFICATION NUMBER

NUMBER OF SHEET ON WHICH DETAIL IS DRAWN

SYMBOL WHERE DETAIL IS TAKEN

NUMBER OF SHEET ON WHICH DETAIL IS INDICATED

DESCRIPTIONSYMBOL

SHEET NOTE1

REVISION NOTE INDICATOR1

CROSS REFERENCING SYMBOL

MISCELLANEOUS SYMBOLS

PBB PRIMARY BUS BAR

P

FB

COMBINATION POWER / COMMUNICATIONS FLOOR BOX - REFER TO

TELECOMMUNICATIONS PLANS FOR COMMUNICATIONS REQUIREMENTS.FB

SPECIAL SYSTEMS DEVICES

SYMBOL DESCRIPTION

CARD READER

BALANCED MAGNETIC SWITCH (BMS)BMS

METERWH

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

EL

EC

TR

IC

AL

L

EG

EN

D

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

E-001

D . H

EN

SL

EY

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

BUILDING GENERAL NOTES

1. REFER TO ARCHITECTURAL PLANS FOR WALL THICKNESS, HEIGHTS, TYPES, AND RATINGS.

COORDINATE ALL WALL MOUNTED WIRING DEVICES, JUNCTION BOXES, ETC., WITH THE WALL

CONSTRUCTION. VERIFY DEVICE LOCATIONS IN THE FIELD PRIOR TO ROUGH–IN.

2. COORDINATE WITH OTHER TRADES TO ENSURE THAT THE REQUIRED GROUNDING AND BONDING

CONNECTIONS TO BUILDING STEEL ARE MADE BEFORE THE STEEL IS COVERED.

3. PROVIDE ALL CONDUITS DE-BURRED AND WITH BUSHINGS TO PREVENT CABLE DAMAGE.

PROVIDE ALL CONDUIT FITTINGS WITH INSULATED THROATS.

4. ALL ELECTRICAL AND COMMUNICATIONS WORK IS NEW. PROVIDE ALL ELECTRICAL AND

COMMUNICATIONS WORK AS INDICATED AND SPECIFIED, U.N.O.

5. INSTALL ABOVE CEILING JUNCTION BOXES IN ROOMS WITH GYPSUM BOARD CEILINGS SUCH

THAT THEY ARE ACCESSIBLE. PROVIDE ACCESS PANELS IF NECESSARY TO MEET CODE

REQUIREMENTS.

6. PROVIDE PULL WIRES WITH ALL SPARE CONDUITS, DUCTS, AND INNERDUCTS.

7. PROVIDE PVC COATED RGS TYPE CONDUIT WHEN INSTALLED UNDER THE BUILDING SLAB AND

EXTENDING 5' BEYOND THE EDGE OF THE SLAB.

8. COORDINATE AND SCHEDULE THE DOWN TIMES OF THE PRIMARY ELECTRICAL SYSTEM WITH

USERS AND THE CONTRACTING OFFICER. SCHEDULE DOWN TIMES IN ADVANCE TO AVOID

INTERRUPTION OF SYSTEMS.

9. PROVIDE POWER RECEPTACLE MOUNTING HEIGHTS (TO CENTER OF DEVICE) AS FOLLOWS

U.N.O.:

- MECHANICAL ROOM RECEPTACLES - 42” A.F.F.

- EXTERIOR RECEPTACLES - 18” A.F.F.

- CAGE STORAGE (EXTERIOR TO CAGE) - 48" A.F.F.

- ABOVE COUNTER - 4” ABOVE BACKSPLASH

10. INSTALL POWER AND COMMUNICATIONS OUTLETS IN OFFICES AT 15” A.F.F. (TO BOTTOM OF

DEVICE PER ABA) TO AVOID CONFLICTS WITH FURNITURE.

11. INSTALL LIGHT SWITCHES AND WALL MOUNTED VOICE OUTLETS AT 48” A.F.F. (TO TOP OF

OUTLET PER ABA).

12. SEPARATE ELECTRICAL BOXES INSTALLED ON OPPOSITE SIDES OF A FIRE RATED WALL BY A

HORIZONTAL DISTANCE OF NOT LESS THAN 24”.

13. FIRESTOP ALL PENETRATIONS THROUGH FIRE RATED WALLS OR PARTITIONS IN ACCORDANCE WITH SPECIFICATION SECTION 07 84 00 FIRESTOPPING. REFER TO ARCHITECTURAL PLANS FOR

LOCATIONS OF FIRE RATED WALLS AND PARTITIONS.

14. ANTI-TERRORISM MEASURES: MOUNT ALL OVERHEAD UTILITIES AND OTHER FIXTURES

WEIGHING 31 POUNDS OR MORE TO MINIMIZE THE LIKELIHOOD THAT THEY WILL FALL AND

INJURE BUILDING OCCUPANTS. DESIGN ALL EQUIPMENT MOUNTINGS TO RESIST FORCES OF 0.5 TIMES THE EQUIPMENT WEIGHT IN ANY HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT

WEIGHT IN THE DOWNWARD DIRECTION. THIS REQUIREMENT IS NOT INTENDED TO APPLY TO

DISTRIBUTED SYSTEMS, SUCH AS PIPING AND CONDUIT NETWORKS.

15. DO NOT PASS CONDUIT AND WIRING NOT ASSOCIATED WITH THE TELECOMMUNICATIONS ROOMS

(TR) THROUGH THE TELECOMMUNICATIONS ROOMS. ONLY INSTALL WIRING DEDICATED TO THE

TELECOMMUNICATIONS ROOMS IN THESE ROOMS.

16. DO NOT INSTALL EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ETC) THAT DOES NOT SERVE

THE TR ABOVE, BELOW (I.E. IN OR UNDER SLAB), OR IN THESE IT SPACES. DO NOT PASS

EQUIPMENT THROUGH OR ENTER THE TRs.

17. PROVIDE A MINIMUM OF A 47" BUFFER FROM ANY WALL OF THE TR FOR ANY MOTOR,

TRANSFORMER OR OTHER ELECTRICAL DEVICE GREATER THAN 5KVA.

18. BOND EACH PRIMARY BUS-BAR (PBB) AND SECONDARY BUS-BAR (SBB) THE STEEL WITHIN THE

SAME ROOM WITH A #3/0 AWG CONDUCTOR. INSTALL BONDING CONDUCTORS IN PVC CONDUIT,

AS SHORT AND STRAIGHT AS POSSIBLE.

1. WIRE EMERGENCY FIXTURES, NOT DESIGNATED AS NIGHT LIGHTS, SUCH THAT THEY OPERATE 'ON' AND 'OFF' BY SWITCH AND IN EMERGENCY MODE UPON DISRUPTION OF NORMAL ELECTRICAL

SERVICE. EMERGENCY FIXTURES NOTED SPECIFICALLY AS 'NIGHT LIGHTS' SHALL BURN

CONTINUOUSLY.

2. PROVIDE EMERGENCY FIXTURES SUCH THAT THEY BURN UNDER LOSS OF NORMAL POWER

REGARDLESS OF MANUAL OR AUTOMATIC SWITCHING POSITION.

3. IF A SWITCHED RELAY DESIGNATION IS NOT SHOWN, LIGHT FIXTURES ARE CONTROLLED BY

SWITCHES AND RELAY IN THE ROOM IN WHICH THEY ARE LOCATED.

4. PROVIDE BI-LEVEL OR DIMMABLE LUMINAIRES FOR LIGHT FIXTURES LOCATED IN HALLWAYS, UNIT

STORAGE AREA (EXCLUDING CAGES), AND UNHEATED STORAGE AREA (EXCLUDING CAGES) TO

DIM THE LUMINARIES TO 50% OF FULL LIGHT OUTPUT, UPON SENSING VACANCY.

5. PROVIDE DIMMING BALLASTS FOR LIGHT FIXTURES CONTROLLED BY DAYLIGHT SENSORS OR

DIMMING SWITCHES.

6. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS PRIOR TO ROUGH IN. COORDINATE

LOCATION OF LIGHT FIXTURES WITH HVAC DIFFUSERS, AND OTHER EQUIPMENT.

7. EXTEND WALL SLOT FIXTURES FROM WALL TO WALL, WITH LAMPS INSTALLED IN LOCATIONS

SHOWN ON PLANS.

POWER GENERAL NOTES

1. BRANCH CIRCUIT CONDUCTOR SIZES SHOWN ON PLANS AND PANEL SCHEDULES ARE BASED ON VOLTAGE DROP CALCULATIONS USING APPROXIMATE CIRCUIT ROUTING PATHS. WHEN FIELD INSTALLED BRANCH CIRCUIT CONDUCTORS FOR 120 VOLT BRANCH CIRCUITS EXCEED 100 FEET, CONDUCTORS SHALL BE NO SMALLER THAN #10 AWG.

WHEN FIELD INSTALLED BRANCH CIRCUIT CONDUCTORS FOR 277 VOLT BRANCH CIRCUITS EXCEED 230 FEET, CONDUCTORS SHALL BE NO SMALLER THAN #10 AWG. WHEN PLANS OR PANEL SCHEDULES SHOW BRANCH CIRCUIT CONDUCTORS LARGER THAN #10 AWG, USE THE LARGER CONDUCTOR.

2. PROVIDE ELECTRICAL DISCONNECTS AS NECESSARY TO MEET NFPA 70 REQUIREMENTS. IN SOME CASES, THE DISCONNECT MAY BE PROVIDED WITH THE EQUIPMENT.

REFER TO MECHANICAL SCHEDULES FOR ADDITIONAL INFORMATION. COORDINATE ALL DISCONNECT SIZES, STARTER SIZES, WIRE SIZES, ETC., WITH MECHANICAL EQUIPMENT SUBMITTALS AS PROVIDED BY THE MECHANICAL EQUIPMENT MANUFACTURERS. MAKE ALL NECESSARY ADJUSTMENTS AT NO COST TO THE GOVERNMENT.

3. EXPOSED DISCONNECTS, ENCLOSURES, AND ELECTRICAL CONNECTIONS INSTALLED IN THE KITCHEN SHALL HAVE A NEMA 4 RATING AND SHALL BE PROTECTED FROM

SPRAYED WATER.

4. PROVIDE A DEDICATED NEUTRAL FOR ALL 120 VOLT AND 277 VOLT SINGLE PHASE CIRCUITS. MULTI-WIRE BRANCH CIRCUITS ARE NOT ALLOWED UNLESS SPECIFICALLY

NOTED OTHERWISE.

5. PLANS SHOW A SEPARATE CONDUIT FOR EACH CIRCUIT. FOR 120 AND 277 VOLT SINGLE PHASE BRANCH CIRCUITS, UP TO THREE HOME RUN CIRCUITS CAN BE COMBINED IN A SINGLE CONDUIT BACK TO THE PANEL. REDUCE THE AMPACITY OF EACH CONDUCTOR, AND SIZE THE CONDUIT PER NEC REQUIREMENTS. SIZE CONDUIT TO PROVIDE

SPARE CAPACITY FOR ONE ADDITIONAL 20 AMP CIRCUIT IN EACH CONDUIT.

6. INSTALL AN EQUIPMENT GROUNDING CONDUCTOR IN EACH CONDUIT. SIZE EQUIPMENT GROUNDING CONDUCTOR PER THE NEC FOR THE LARGEST OVERCURRENT DEVICE

PROTECTING CONDUCTORS IN THE CONDUIT.

7. PROVIDE GROUNDING PROVISIONS PER MANUFACTURER REQUIREMENTS IN TELECOMMUNICATIONS ROOMS AND OTHER ROOMS WHERE STATIC DISSIPATIVE FLOORING IS

INSTALLED.

8. COORDINATE FULLY WITH GENERAL CONTRACTOR AND WITH CONTROLS CONTRACTOR TO DETERMINE LOCATIONS WHERE ELECTRICAL POWER SOURCE IS NEEDED TO OPERATE LINE-VOLTAGE VALVES, OPERATORS AND OTHER OPERATING COMPONENTS, AND ALSO TO DETERMINE LOCATIONS OF CONTROL PANELS, SUBPANELS AND ALL OTHER ELEMENTS OF THE CONTROL SYSTEMS REQUIRING ELECTRICAL POWER. PROVIDE THE ELECTRICAL POWER NEEDED AS A PART OF THE WORK OF THIS PROJECT. AT A MINIMUM, CONTROL POWER IS EXPECTED TO BE NEEDED IN ALL MECHANICAL ROOMS, PLUS AT 1 TO 10 OR MORE LOCATIONS PER FLOOR OF THE BUILDING. CONTRACTOR SHALL OBTAIN FROM THE CONTROLS VENDOR THE EXACT COUNT, LOCATION AND ELECTRICAL CHARACTERISTICS OF POWER NEEDED FOR THE CONTROLS SYSTEMS, AND

PROVIDE ACCORDINGLY.

LIGHTING GENERAL NOTES

ELECTRICAL ABBREVIATIONS

2/C

A, AMP

AACS

ABA

AC

A/C

AF

AFC

AFF

AFG

AHU

AIC

AMP

AT

ATC

ATS

AWG

BKR

BLDG

C

CB

CLG

CW

CKT

CO

CP

CPT

CT

CU

DC

DIA

DIM

DISC

DLC

DN

DOD

DP

DT

DWG

EA

EC

ELEC

ELEV

EMER

EMT

EXH

EXT

EWC

F

FACP

FDR

FIG

FL

FLA

FLEX

FT

FU

FVNR

GF

GFCI

GFE

TWO CONDUCTOR AS IN A MULTI-CONDUCTOR CABLE

AMPERE

AUTOMATED ACCESS CONTROL SYSTEM

ARCHITECTURAL BARRIERS ACT

ALTERNATING CURRENT

AIR CONDITIONING

AMPERE FRAME

ABOVE FINISHED CEILING

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CURRENT

AMPERE

AMPERE TRIP

AUTOMATIC TEMPERATURE CONTROL

AUTOMATIC TRANSFER SWITCH

AMERICAN WIRE GAUGE

BREAKER

BUILDING

CONDUIT

CIRCUIT BREAKER

CEILING

CHILLED WATER

CIRCUIT

COPIER

CIRCULATING PUMP

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

COPPER

DIRECT CURRENT

DIAMETER

DIMENSION

DISCONNECT

DIESEL LOCOMOTIVE CABLE

DOWN

DEPARTMENT OF DEFENSE

DOUBLE POLE

DOUBLE THROW

DRAWING

EACH

EMPTY CONDUIT

ELECTRIC OR ELECTRICAL

ELEVATOR

EMERGENCY

ELECTRICAL METALLIC TUBING

EXHAUST

EXTERIOR, EXTERNAL

ELECTRIC WATER COOLER

FAX, FAHRENHEIT

FIRE ALARM CONTROL / ANNUNCIATOR PANEL

FEEDER

FIGURE

FLOOR

FULL LOAD AMPERES

FLEXIBLE

FOOT, FEET

FUSE, FUSED

FULL VOLTAGE NON-REVERSING

GROUND FAULT CIRCUIT INTERRUPTER

GOVERNMENT FURNISHED CONTRACTOR INSTALLED

GOVERNMENT FURNISHED EQUIPMENT

GFGI

GND

GRS

HH

HID

HP

HR

HTR

HVAC

Hz

HOA

ID

IN

JB

KCMIL

KO

KV

KVA

KVAR

KW

KWH

LV

LTG

M,mm,cm

MAN

MATL

MAX

MCB

MCC

MCM

MDP

MECH

MFR

MGB

MH

MIN

MISC

MLO

MT

MTD

MTG

MTL

MW

NC

NEC

NEMA

NEUT

NF

NFPA

NIC

NL

NO

NOM

NTS

OL'S

OC

OD

OH

P

PB

PBB

GOVERNMENT FURNISHED GOVERNMENT INSTALLED

GROUND

GALVANIZED RIGID STEEL

HANDHOLE

HIGH INTENSITY DISCHARGE

HORSEPOWER

HOUR

HEATER

HEATING, VENTILATING AND AIR CONDITIONING

HERTZ

HAND-OFF-AUTOMATIC SELECTOR SWITCH

INSIDE DIAMETER

INCH(ES)

JUNCTION BOX

1000 CIRCULAR MILS

KNOCK OUT

KILO VOLT

KILO VOLT-AMPERE

KILO VOLT-AMPS REACTIVE

KILOWATT

KILOWATT-HOUR

LOW VOLTAGE

LIGHTING

METER, MILLIMETER, CENTIMETER, etc.

MANUAL

MATERIAL

MAXIMUM

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

THOUSAND CIRCULAR MILS

MAIN DISTRIBUTION PANEL

MECHANICAL

MANUFACTURER

MAIN GROUNDING BUSBAR

MANHOLE, METAL HALIDE

MINIMUM, MIN

MISCELLANEOUS

MAIN LUGS ONLY

MOUNT

MOUNTED

MOUNTING

METAL

MICROWAVE

NORMALLY CLOSED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NEUTRAL

NON-FUSED

NATIONAL FIRE PROTECTION ASSOCIATION

NOT IN CONTRACT

NIGHT LIGHT - UNSWITCHED FIXTURE

NORMALLY OPEN, NUMBER

NOMINAL

NOT TO SCALE

OVERLOADS

ON CENTER

OUTSIDE DIAMETER

OVERHEAD

POLE

PULL BOX, PUSH BUTTON

PRIMARY BUS BAR

P/BD

PH

PNL

P.O.C.

PRELIM

PRESS

PR

PRI

PSI

PT

PVC

QTY

R

RAD

RCPT

REQD

REV

RF

RGS

RM

RMC

RND

RPM

S

SBB

SCHED

SD

SECT

SFCP

SF

SH

SP

SPD

SPEC

SQ

SQ FT

ST

STA

STD

STL

STRL

SW

SYM

SYS

T

TEL

TEMP

TYP

UGND

U.N.O.

UPS

UTIL

V

VA

VOL

W/ W/O

WP

WT

XFMR

PANEL BOARD

PHASE

PANEL

POINT OF CONTACT

PRELIMINARY

PRESSURE

PAIR

PRIMARY

POUNDS PER SQUARE INCH

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

QUANTITY

REFRIGERATOR

RADIUS

RECEPTACLE

REQUIRED

REVISION

RADIO FREQUENCY

RIGID GALVANIZED STEEL

ROOM

RIGID METAL CONDUIT

ROUND

REVOLUTIONS PER MINUTES

SCANNER

SECONDARY BUS BAR

SCHEDULE

STARTER DOOR

SECTION

SUB FIRE ALARM CONTROL PANEL

SYSTEM FURNITURE

SHREDDER

SINGLE POLE

SURGE PROTECTION DEVICE (TVSS)

SPECIFICATION

SQUARE

SQUARE FEET

SINGLE THROW

STATION

STANDARD

STEEL

STRUCTURAL

SWITCH

SYMMETRICAL

SYSTEM

THERMOSTAT

TELEPHONE

TEMPORARY, TEMPERATURE

TYPICAL

UNDERGROUND

UNLESS NOTED OTHERWISE

UNINTERRUPTIBLE POWER SUPPLY

UTILITY

VOLT(S)

VOLT-AMPERE

VOLUME

WITH

WITHOUT

WEATHER PROOF

WEIGHT

TRANSFORMER

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

EL

EC

TR

IC

AL

G

EN

ER

AL

N

O

TE

S

AB

BR

EV

IA

TI

O

N S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

E-002

D . H

EN

SL

EY

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

G1E

G1E

G1E

G1

G1E

G2

G2

G2

G2

G2

G2E

G2 2G2E

G2

G2E

G2

G2

G2

G2

G2E

G2

G2

G2E

G2E

G2

G2

G2

G2

G2

G2

G2

G2

G2E

G2

G2

G2E 2 G2

X1

X1

WP

WP

E1

WP

X1

G1E

G1E

G1

G1E

G1

F1E

KE

K

D

D

D

C

CE

X1

E1

E1

WP

E1

LC-CR1

LC-CR1

LC-CR1

LC-CR1

LC-MO1

LC-MO1

LC-UT1

LC-MP1

LC-MO1

LC-CN1 LC-CN2

LC-CN2LC-CN1

LC-AO1

LC-AO1

LC-AO1

LC-AO1

ASSEMBLY HALL

STORAGE

KITCHEN

SCULLERY 111

JAN

CLOSET

DRINK CLOSET

CORRIDOR

JAN

M E

N 'S

R

ES

TR

O

O M

CORRIDOR

CORRIDOR

VEST.

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CHAIR STORAGE

MECH

X1

G2

G2E

G2

G2

G2

G2

G2

G2

G2E

G2

G2E

G2

G2

G2

G2

G2

G2

G2E

CLASSROOM

CLASSROOM

LC-CN1

LC-CN1

G2

G2

E1

CE

C

C

C

C

C

C

CE

C

C

C

C

C

C

C

C

C

C

C

C

C

CE

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

C

G1E

G1

D

D

X1 4

X1

WP

KE

K

K

K

KE

K

K

K

K

K

KE

K

6 8 9 10

E

A

B

C

D

WP

WP

MATCHLINE - SEE EL113

M

AT

C H

LI

N

E -S

EE

E

L1

M

AT

C H

LI

N

E -S

EE

E

L1

B

B

B

B

B

B

B

B

DE

D

DE

DE

D

DE

D

D

6 DE

D

DE

D

D

DE

C

CE

C

C

C

C

C

C

C

CE

C

C

C

C

C

C

C

C

C

C

C

C

W O

M E

N 'S

R E

S

TR

O O

M

B

B

B

B

B

B

F1

F1E

WP

7 E1 11

F1E

LC-AO3

LC-AO3

LC-MO1

LC-UT1

MAIN T.R.

G2

G2

E1

WP

WP

E2

E1

E2

WO

E2

E2

X1

X1

X1 12

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

KEYPLAN

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

PA

R

TI

AL

L

IG

H

TI

N G

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EL111

D . H

EN

SL

EY

SCALE: 1/8" = 1'-0"

PARTIAL LIGHTING PLAN

GENERAL SHEET NOTES

1 REFER TO SHEET E-001 FOR ELECTRICAL LEGEND AND

SHEET E-002 FOR ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS.

2 REFER TO SHEET EL601 FOR LIGHTING DIAGRAMS AND

SHEET EL701 FOR LIGHT FIXTURE SCHEDULE AND

LIGHTING CONTROLS MATRIX.

3 FEED ALL FIXTURES SHOWN ON THIS PLAN FROM PANEL

'LP1'.

4 MOUNT ALL 'F1' AND 'F1E' FIXTURES SHOWN ON THIS

SHEET AT 10'-0" A.F.F., U.N.O.

5 MOUNT ALL 'C' AND 'CE' FIXTURES SHOWN ON THIS SHEET

AT 12'-0" A.F.F., U.N.O.

6 MOUNT ALL 'WP' FIXTURES SHOWN ON THIS SHEET AT

10'-0" A.F.F., U.N.O.

7 MOUNT ALL 'E1' FIXTURES SHOWN ON THIS SHEET AT 7'-6"

A.F.F., U.N.O.

SHEET KEYNOTES

1 FIXTURE SHALL ONLY OPERATE ON LOSS OF NORMAL

POWER. UPON LOSS OF NORMAL POWER, FIXTURE SHALL

OPERATE ON BATTERY BACKUP.

2 PROVIDE AN UNSWITCHED AND SWITCHED HOT FOR

CONTROLLED AND EMERGENCY CAPABILITIES FOR ALL

FIXTURES DESIGNATED AS EMERGENCY.

3 FIXTURE SHALL BE CONTROLLED SEPARATELY FROM ALL

OTHER LIGHT FIXTURES IN THIS ROOM. FIXTURE

CONTROL SHALL BE MANUAL ON, MANUAL OFF.

4 ALL WALL MOUNTED EXIT SIGNS SHALL BE MOUNTED AT

7'-6" A.F.F., U.N.O.

5 FIXTURE TO BE MOUNTED AT 8'-0" A.F.F.

6 FIXTURE TO BE MOUNTED AT 20'-0" A.F.G.

7 FIXTURE TO BE MOUNTED AT 6'-0" A.F.G.

8 FIXTURE TO BE MOUNTED AT 7'-6" A.F.G.

9 FIXTURE TO BE MOUNTED AT 2'-6" A.F.G.

10 PROVIDE CONNECTION TO DDC PANEL FOR WINDOW

SENSOR SIGNAGE. PROVIDE 120V POWER CONNECTION

FROM CIRCUIT RP7-32 WITH 2#12, 1#12G IN 3/4" C. SEE

MECHANICAL SHEET 'M-708' FOR MORE INFORMATION.

TYP1

TYP2

TYP4

TYP1

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

G1

X1

E1

WP

WP

E1

G1E

X1

X1

X1

X1

F1

F1E

F1E

F1E 12F1E

F1E

F1E

F1

F1

F1

F1

F1E

F1E

F1E

F1

F1

F1

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

X1

LC-CR1

LC-CR1

LC-UT1

LC-UT1

LC-UT1

LC-MO1

LC-MO1

CAGE STORAGE

CAGE STORAGE

MECHANICAL

CAGE STORAGE

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F1E

ELECTRICAL

E1

F1

F1E

F1

F1

F1

F1

F1E

F1

F1E

F1

F1

ARMS VAULT

F2

F2E

F2E

F2E

F2

F2

F2E

F2E

F2E

F2

F2E

F2

F2E

F2E

VE

ARMORER

F2

X1

1 2 3 4 5 6

E

A

B

C

D

3.5

MATCHLINE - SEE EL113 MATCHLINE - SEE EL113

M

AT

C H

LI

N

E -S

EE

E

L1

M

AT

C H

LI

N

E -S

EE

E

L1

F2

F2

F2E

F2

F2

F2

F2

F2E

F2E

F2E

F2

F2

F2

F2

F2 12

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

KEYPLAN

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

PA

R

TI

AL

L

IG

H

TI

N G

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EL112

D . H

EN

SL

EY

SCALE: 1/8" = 1'-0"

PARTIAL LIGHTING PLAN

GENERAL SHEET NOTES

1 REFER TO SHEET E-001 FOR ELECTRICAL LEGEND AND

SHEET E-002 FOR ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS.

2 REFER TO SHEET EL601 FOR LIGHTING DIAGRAMS AND

SHEET EL701 FOR LIGHT FIXTURE SCHEDULE AND

LIGHTING CONTROLS MATRIX.

3 FEED ALL FIXTURES SHOWN ON THIS SHEET FROM PANEL

'LP1'.

4 MOUNT ALL 'F1' AND 'F1E' FIXTURES SHOWN ON THIS

PLAN AT 11'-0" A.F.F., U.N.O.

5 MOUNT ALL 'WP' FIXTURES SHOWN ON THIS SHEET AT

10'-0" A.F.F., U.N.O.

6 MOUNT ALL 'E1' FIXTURES SHOWN ON THIS SHEET AT 7'-6"

A.F.F., U.N.O.

SHEET KEYNOTES

1 FIXTURE SHALL ONLY OPERATE ON LOSS OF NORMAL

POWER. UPON LOSS OF NORMAL POWER, FIXTURE SHALL

OPERATE ON BATTERY BACKUP.

2 PROVIDE AN UNSWITCHED AND SWITCHED HOT FOR

CONTROLLED AND EMERGENCY CAPABILITIES FOR ALL

FIXTURES DESIGNATED AS EMERGENCY.

3 ALL FIXTURES IN CAGES SHALL BE MOUNTED TO THE

UNDERSIDE OF THE CAGE. REFER TO DETAIL 1 ON SHEET

EP501 FOR MORE INFORMATION.

4 ALL FIXTURES IN CAGES SHALL BE CONTROLLED AS

LC-MO1.

6 ALL FIXTURES IN THIS ROOM SHALL BE MOUNTED AT

10'-0" A.F.F.

7 ALL WALL MOUNTED EXIT SIGNS SHALL BE MOUNTED AT

7'-6" A.F.F., U.N.O.

8 ALL FIXTURES IN THIS ROOM (EXCEPT FIXTURES

MOUNTED IN CAGES - SEE NOTE 3), SHALL BE MOUNTED

AT 11'-0" A.F.F., U.N.O.

TYP 1

TYP2

TYP4

TYP3

TYP 7

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

PC

F2

G1E

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

X1

E1

WP

WP

E1

WP

E1

E1

WP

F2

F1E 16 F1

F1E 14 F1

F1E

G1E

F1E

F1

F1E

F1

F1E

F1E

LC-UT1

LC-UT1

LC-PO1

LC-CR1

LC-MO1

CAGE STORAGE

MECHANICAL

ELEC

T.R.

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F2

F1

F1E

F1E

F1

F1E

F1E

F1

F1E

F1

F1E

F1E

F1E

F1E

F1

F1

F1E

F1E

VE

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO1

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

LC-PO2

G1 G110 10

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

G1

G1

G1E

G1

X1

WP

E1

CORRIDOR

LC-CR1

F1

F1E

F1

CAGE STORAGE

LC-CR1

WP

X1

1 2 3 4 5 6 8

E

F

G

H

J

73.5

MATCHLINE - SEE EL112 MATCHLINE - SEE EL112

M

AT

C H

LI

N

E -S

EE

E

L1

F1E 10

128A

PRINTER

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

KEYPLAN

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

PA

R

TI

AL

L

IG

H

TI

N G

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EL113

D . H

EN

SL

EY

SCALE: 1/8" = 1'-0"

PARTIAL LIGHTING PLAN

GENERAL SHEET NOTES

1 REFER TO SHEET E-001 FOR ELECTRICAL LEGEND AND

SHEET E-002 FOR ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS.

2 REFER TO SHEET EL601 FOR LIGHTING DIAGRAMS AND

SHEET EL701 FOR LIGHT FIXTURE SCHEDULE AND

LIGHTING CONTROLS MATRIX.

3 FEED ALL FIXTURES SHOWN ON THIS SHEET FROM PANEL

'LP1'.

4 MOUNT ALL 'F1' AND 'F1E' FIXTURES SHOWN ON THIS

PLAN AT 11'-0" A.F.F., U.N.O.

5 MOUNT ALL 'WP' FIXTURES SHOWN ON THIS SHEET AT

10'-0" A.F.F., U.N.O.

6 MOUNT ALL 'E1' FIXTURES SHOWN ON THIS SHEET AT 7'-6"

A.F.F., U.N.O.

SHEET KEYNOTES

1 FIXTURE SHALL ONLY OPERATE ON LOSS OF NORMAL

POWER. UPON LOSS OF NORMAL POWER, FIXTURE SHALL

OPERATE ON BATTERY BACKUP.

2 PROVIDE AN UNSWITCHED AND SWITCHED HOT FOR

CONTROLLED AND EMERGENCY CAPABILITIES FOR ALL

FIXTURES DESIGNATED AS EMERGENCY.

3 ALL FIXTURES IN CAGES SHALL BE MOUNTED TO THE

UNDERSIDE OF THE CAGE. REFER TO DETAIL 1 ON SHEET

EP501 FOR MORE INFORMATION.

4 ALL FIXTURES IN CAGES SHALL BE CONTROLLED AS

LC-MO1.

5 PROVIDE PHOTO CELL AND INSTALL PER

MANUFACTURERS RECOMMENDATIONS.

6 ALL WALL MOUNTED EXIT SIGNS SHALL BE MOUNTED AT

7'-6" A.F.F., U.N.O.

7 ALL FIXTURES IN THIS ROOM SHALL BE MOUNTED AT

10'-0" A.F.F., U.N.O.

TYP1

TYP2 TYP3TYP4

TYP6

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

LIGHTING

CONTROL PANEL

BY LIGHTING

CONTROLS

VENDOR

EXTERIOR LIGHTING POWER PACK(S)

NOTES:

1. COORDINATE CONTROLS REQUIREMENTS AND QUANTITIES WITH LIGHTING CONTROL VENDOR.

2. EXTERIOR LIGHTING CIRCUITS SHALL TURN OFF VIA TIMECLOCK AT MIDNIGHT AND TURN ON VIA

TIMECLOCK AT 4 AM.

3. EXTERIOR LIGHTING CIRCUITS SHALL TURN ON VIA PHOTOCELL WHEN SUFFICIENT DAYLIGHTING IS NOT

AVAILABLE AND TURN OFF VIA PHOTOCELL WHEN SUFFICIENT DAYLIGHTING IS AVAILABLE.

4. PROVIDE SCHEDULE OVERRIDE FOR SPECIAL BUILDING OCCUPANCY EVENTS.

SEE PANEL SCHEDULES FOR ADDITIONAL CIRCUITING INFORMATION.

CAT 6

CABLING

LINE VOLTAGE TO

EXTERIOR LIGHTING

FIXTURES

LINE VOLTAGE FROM

PANEL LP1

CAT 6

CABLING

CAT 6

CABLING

INPUT FROM PHOTOCELL

INPUT FROM TIMECLOCK

DIGITAL ROOM

CONTROLLER

ON/OFF/DIM

DIGITAL WALL

DEVICES

DIGITAL OCCUPANCY/VACANCY

AND/OR

PHOTOSENSORS

ALL CONNECTIONS BETWEEN CONTROL DEVICES SHALL BE LMRJ CABLES

LIGHTING

LOAD

LINE VOLTAGE

0-10V CONTROL WIRING

OTHER LIGHTING LOADS

LINE VOLTAGE

INTEGRAL

EM DRIVER

EM LIGHTING

LOAD

LINE VOLTAGE

0-10V CONTROL WIRING

OUTPUTS TO ROOM PLUGLOAD CONTROLLERS

AND HVAC CONTROLS, AS NECESSARY

NOTES:

1. PROVIDE ADDITIONAL POWER, DEVICES, CABLES, PROGRAMMING, ETC AS NEEDED TO MEET ALL

REQUIREMENTS OF SYSTEM MANUFACTURER.

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

LI

G

H

TI

N G

D

IA

G R

AM

S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EL601

D . H

EN

SL

EY

EXTERIOR LIGHTING CONTROL DIAGRAM

LIGHTING CONTROL DIAGRAM

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

LI

G

H

TI

N G

S C

H

ED

U

LE

S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EL701

D . H

EN

SL

EY

1. PROVIDE ALL REQUIRED EQUIPMENT, CABLES, AND PROGRAMMING, INCLUDING, BUT NOT LIMITED TO, CONTROL PANELS, POWER PACKS, SENSORS, ROOM CONTROLLERS, LOCAL WALL STATIONS, ETC. AS NEEDED TO PROVIDE THE CONTROL SCENARIOS DESCRIBED ABOVE. REFER TO SPECIFICATION 26 51 00 INTERIOR LIGHTING FOR ADDITIONAL INFORMATION.

2. LOCATE AND INSTALL LIGHTING CONTROL DEVICES PER MANUFACTURERS RECOMMENDATIONS TO ENSURE THAT LIGHTING SYSTEM OPERATES AS SPECIFIED.

3. ALL CEILING MOUNTED LIGHTING CONTROL DEVICES SHALL BE PROVIDED IN THEIR OWN CEILING TILE. COORDINATE LOCATIONS WITH ARCHITECTURAL REFLECTED CEILING PLAN.

4. REFER TO LIGHTING CONTROL DIAGRAM FOR TYPICAL CONNECTIONS.

5. TIMEOUT FOR VACANCY SENSING SHALL BE 15 MINUTES.

6. PROVIDE PASSIVE OCCUPANCY/VACANCY SENSORS IN ALL CIRCULATION SPACES, AND STORAGE/JANITOR ROOMS. PROVIDE DUAL TECHNOLOGY OCCUPANCY/VACANCY SENSORS IN ALL OTHER AREAS.

7. FOR SPACES LESS THAN OR EQUAL TO 10,000 SF, LOCAL CONTROL DEVICES CANNOT CONTROL MORE THAN 2500 SF.

8. FOR SPACES LARGER THAN 10,000 SF, LOCAL CONTROL DEVICES CANNOT CONTROL MORE THAN 10,000 SF.

9. WHERE BI-LEVEL SWITCHING OR A PERCENTAGE ON OR OFF IS INDICATED, FIXTURES SHALL BE DIMMED BY THE PERCENTAGE SHOWN. INDIVIDUAL FIXTURES SHALL NOIT BE TURNED OFF TO MEET THIS REQUIREMENT.

10. WHERE MORE THAN ONE SWITCH IS SHOWN IN THE SAME ROOM, EACH SWITCH SHALL BE CAPABLE OF PROVIDING THE INDICATED CONTROL UNLESS OTHERWISE NOTED.

11. ALL SPACES WITH EMERGENCY FIXTURES SHALL INCLUDE UL924 LIGHTING RELAY OPERATION IN THE LIGHTING CONTROL SEQUENCE.

12. SCHEDULED SHUTOFF SHALL BE BASED ON BUILDING OCCUPANCY SCHEDULE.

NOTES:

LIGHTING CONTROL MATRIX

LIGHTING

CONTROL TAG

MANUAL-

ON

MANUAL-ON

50%

AUTO-ON

100%

AUTO-ON

50%

MANUAL

DIMMING

MANUAL-

OFF

AUTO-OFF

100%

AUTO-OFF 50% W/

SCHEDULED SHUTOFF ROOM TYPES (NOT ALL ROOM TYPES ARE LISTED) NOTES

AO1 X X X DINING, LOUNGE, OR BREAKROOM

AO3 X X RESTROOMS

CN1 X X X CONFERENCE ROOMS

CN2 X X X X CONFERENCE ROOMS WHERE DAYLIGHTING RESPONSE IS

REQUIRED

CR1 X X CORRIDORS, STAIRS PROVIDE SCHEDULED SHUTOFF BASED ON BUILDING OCCUPANCY SCHEDULE.

MO1 X X JANITOR, STORAGE, CAGES

MP1 X X X X MULTIPURPOSE ROOM

PROVIDE PRESET MANUAL SCENE SYSTEM WITH USER CONFIGURABLE SCENES.

PROVIDE INTERFACE FOR INTEGRATION WITH A/V CONTROLLER. ALL LIGHTING

CONTROL SENSORS SHALL BE DISABLED DURING A/V PRESENTATION MODE.

PO1 X X X PRIVATE OFFICE, OPEN OFFICE, WORKROOMS

PO2 X X X X PRIVATE OFFICE, OPEN OFFICE WHERE DAYLIGHTING

RESPONSE IS REQUIRED

UT1 X X ELECTRICAL, MECHANICAL, TELECOMMUNICATIONS ROOMS.

PROVIDE LINE VOLTAGE SWITCHING.

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION LAMP WATTAGE VOLTAGE

LUMEN

OUTPUT

EMERGENCY

LUMEN

OUTPUT MOUNTING FIXTURE SPECIFICATIONS REMARKS

MOUNTING

HEIGHT

B ARCHITECTURAL PERIMETER LED 14 W 277 V 1600 - RECESSED PROVIDE HOUSING CONSTRUCTED OF 24 GUAGE STEEL OR BETTER AND A 18 GUAGE REAR SUPPORT CHANNEL WITH CAPTIVE LEVELING SCREWS. PROVIDE EXTRUDED WHITE

ALUMINUM MOUNTING RAILS. REFLECTOR SHEILDS MAY BE STEEL OR ALUMINUM AND SHALL HAVE A WHITE FINISH. ALL STEEL PARTS SHALL BE PAINTED WITH A HIGH GLOSS

BAKED WHITE ENAMEL.

8' - 0"

C 4' ARCHITECTURAL PENDANT LED 25 W 277 V 3200 - PENDANT FIXTURE SHALL PRODUCE 100% DOWNLIGHT. FIXTURE BODY SHALL BE ONE 4'-PIECE CHANNEL COMPOSED OF EXTRUDED ALUMINUM. TRANSLUCENT LOUVERS ALONG REFLECTOR EDGE FOR AESTHETICS. FINISH SHALL BE A MATTE, STAIN WHITE POLYESTER POWDER COAT. EXTRUDED ALUMINUM CHANNEL, END CAPS, AND PERFORATED STEEL SHIELDS ARE PAINTED. PROVIDE DIE-FORMED STEEL INTERNAL COUPLE WHICH MECHANICALLY FASTENS TO ADJOINING FIXTURE, FORMING HAIRLINE JOINT. FIXTURE

SHALL BE MOUNTED WITH STAINLESS STEEL AIRFCRAFT CABLE.

SEE PLANS FOR

MOUNTING HEIGHTS.

CE 4' ARCHITECTURAL PENDANT LED 25 W 277 V 3200 1000 PENDANT FIXTURE SHALL PRODUCE 100% DOWNLIGHT. FIXTURE BODY SHALL BE ONE 4'-PIECE CHANNEL COMPOSED OF EXTRUDED ALUMINUM. TRANSLUCENT LOUVERS ALONG REFLECTOR EDGE FOR AESTHETICS. FINISH SHALL BE A MATTE, STAIN WHITE POLYESTER POWDER COAT. EXTRUDED ALUMINUM CHANNEL, END CAPS, AND PERFORATED STEEL SHIELDS ARE PAINTED. PROVIDE DIE-FORMED STEEL INTERNAL COUPLE WHICH MECHANICALLY FASTENS TO ADJOINING FIXTURE, FORMING HAIRLINE JOINT. FIXTURE

SHALL BE MOUNTED WITH STAINLESS STEEL AIRFCRAFT CABLE.

SEE PLANS FOR

MOUNTING HEIGHTS.

D 6" RECESSED DOWNLIGHT LED 18 W 277 V 1000 - RECESSED SELF-FLANGED SEMI-SPECULAR, MATTE-DIFFUSE OR SPECULAR LOWER RELFECTOR. 16-GAUGE GALVANIZED STEEL CONSTRUCTION, MAXIMUM 1-1/2" CEILING THICKNESS.

LIGHT ENGINE AND DRIVER ACCESSIBLE THROUGH APERTURE.

9' - 0"

DE 6" RECESSED DOWNLIGHT LED 18 W 277 V 1000 1000 RECESSED SELF-FLANGED SEMI-SPECULAR, MATTE-DIFFUSE OR SPECULAR LOWER RELFECTOR. 16-GAUGE GALVANIZED STEEL CONSTRUCTION, MAXIMUM 1-1/2" CEILING THICKNESS.

LIGHT ENGINE AND DRIVER ACCESSIBLE THROUGH APERTURE.

9' - 0"

E1 EGRESS (REMOTE HEAD) LED 12 W 277 V - - WALL COMPACT, LOW-PROFILE REMOTE, WEATHERPROOF, EMERGENCY EGRESS FIXTURE. FIXTURE AND BATTERY SHALL BE UL LISTED FOR WET LOCATIONS AND BALLAST SHALL BE LISTED FOR COLD WEATHER AND SHALL MEET OR EXCEED UL 924, NFPA, AND OSHA STANDARDS. FORWARD THROW CONFIGURATION.

SEE PLANS FOR

MOUNTING HEIGHTS.

E2 EGRESS (REMOTE HEAD) LED 12 W 277 V - - WALL COMPACT, LOW-PROFILE REMOTE, WEATHERPROOF, EMERGENCY EGRESS FIXTURE. FIXTURE AND BATTERY SHALL BE UL LISTED FOR WET LOCATIONS AND BALLAST SHALL BE LISTED FOR COLD WEATHER AND SHALL MEET OR EXCEED UL 924, NFPA, AND OSHA STANDARDS. WIDE THROW CONFIGURATION.

SEE PLANS FOR

MOUNTING HEIGHTS.

F1 4' INDUSTRIAL STRIP LED 35 W 277 V 5000 - SURFACE CONSTRUCTED HOUSING OF COLD-ROLLED STEEL WITH A HEAVY-DUTY 20-GAUGE CHANNEL. ALL METAL PARTS SHALL RECEIVE A RUST INHIBITIVE COATING BEFORE APPLICATION OF THE FINISH COAT. END PLATES SHALL BE SECURED BY SCREWS. PROVIDE WIRE LAMP GUARD FOR ALL F FIXTURES.

SEE PLANS FOR

MOUNTING HEIGHTS.

F1E 4' INDUSTRIAL STRIP LED 35 W 277 V 5000 700 SURFACE CONSTRUCTED HOUSING OF COLD-ROLLED STEEL WITH A HEAVY-DUTY 20-GAUGE CHANNEL. ALL METAL PARTS SHALL RECEIVE A RUST INHIBITIVE COATING BEFORE APPLICATION OF THE FINISH COAT. END PLATES SHALL BE SECURED BY SCREWS. PROVIDE WIRE LAMP GUARD FOR ALL F FIXTURES.

SEE PLANS FOR

MOUNTING HEIGHTS.

F2 4' INDUSTRIAL STRIP W/ WIRE GUARD LED 35 W 277 V 5000 - SURFACE CONSTRUCTED HOUSING OF COLD-ROLLED STEEL WITH A HEAVY-DUTY 20-GAUGE CHANNEL. ALL METAL PARTS SHALL RECEIVE A RUST INHIBITIVE COATING BEFORE APPLICATION OF THE FINISH COAT. END PLATES SHALL BE SECURED BY SCREWS. PROVIDE WIRE LAMP GUARD FOR ALL F FIXTURES.

SEE PLANS FOR

MOUNTING HEIGHTS.

F2E 4' INDUSTRIAL STRIP W/ WIRE GUARD LED 35 W 277 V 5000 700 SURFACE CONSTRUCTED HOUSING OF COLD-ROLLED STEEL WITH A HEAVY-DUTY 20-GAUGE CHANNEL. ALL METAL PARTS SHALL RECEIVE A RUST INHIBITIVE COATING BEFORE APPLICATION OF THE FINISH COAT. END PLATES SHALL BE SECURED BY SCREWS. PROVIDE WIRE LAMP GUARD FOR ALL F FIXTURES.

11' - 0"

G1 2'X2' VOLUMETRIC TROFFER LED 30 W 277 V 3300 - RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

G1E 2'X2' VOLUMETRIC TROFFER LED 30 W 277 V 3300 1325 RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

G2 2'X2' VOLUMETRIC TROFFER LED 36 W 277 V 4000 - RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

G2E 2'X2' VOLUMETRIC TROFFER LED 36 W 277 V 4000 RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

K 2'X2' KITCHEN TROFFER LED 33 W 277 V 4563 - RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

KE 2'X2' KITCHEN TROFFER LED 33 W 277 V 4563 1723 RECESSED 2' X 2' HIGHLY ENERGY EFFICIENT LED TROFFER FIXTURE FOR GENERAL VOLUMETRIC SPACE. PROVIDE COLD ROLLED STEEL HOUSING COMPLETE WITH INTEGRAL SIDE TRIM FLANGES, INTEGRAL T-BAR SAFETY CLIPS, AND SPRING LOADED LATCHES. INCLUDE INTEGRAL GALVANIZED BALLAST BOX AND ENDPLATES. FINISH FIXTURE HOUSING AND TRIM WITH EITHER POLYESTER POWDER PAINT OR BAKED ENAMEL APPLIED AFTER FABRICATION.

9' - 0"

VE VANDAL RESISTANT LED 82 W 277 V 6150 1400 WALL HOUSING MADE FROM HEAVY-DUTY, 16-GUAGE COLD-ROLLED STEEL. POLYCARBONATE LENS GASKETED AGAINST MOISTURE

AND CONTAMINANTS. LENS IS SECURED TO HOUSING WITH TAMPER-RESISTANT SCREWS.

8' - 0"

WO WINDOW SENSOR SIGNAGE LED 2 W 120 V - - WALL PROVIDE AN TRANSLUCENT BLACK ACRYLIC PANEL WITH REVERSE STENCIL-CUT BLACK VINYL MESSAGE. MESSAGE SHALL SAY 'WINDOW OPEN' AND DISPLAY IN RED LED. 8' - 0" WP WALL PACK FIXTURE LED 66 W 277 V 6340 - WALL RUGGED CAST ALUMINUM FIXTURE WITH INTEGRAL, WEATHERTIGHT LED DRIVER COMPARTMENTS AND HIGH PERFORMANCE ALUMINUM HEATSINKS SPECIFICALLY DESIGNED

FOR LED APPLICATIONS. TYPE 4 DISTRIBUTION.

X1 SINGLE FACE EXIT SIGN LED 3 W 277 V - - WALL /

SURFACE

PROVIDE AN IMPACT-RESISTANT, SCRATCH-RESISTANT, AND CORROSION-PROOF THERMOPLASTIC HOUSING. FACE PLATE SHALL INCLUDE UNIVERSAL DIRECTIONAL CHEVRON INSERTS THAT ARE EASILY REMOVED AND REINSERTED. THE BATTERY SHALL BE SEALED, MAINTENANCE-FREE AND NICKEL-CADMIUM. THE CHARGER SHALL BE SOLID STATE AND SHALL PROVIDE A CONTINUOUS, VARIABLE, CURRENT LIMITED, FILTERED AND REGULATED CHARGE RATE. EQUIP WITH A PUSH-TO-TEST SWITCH.

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FBFB

J

J

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FB

FBFBFBFB

J

FBFBFB

FB

FB

FB

FB

FB

FB

FB

FB

J J

J

J

WP

WP

WP

42"

WP 34

WP

EP410

18 18

31 31

23 24

28 28

D R

IN

K

C

LO

SE

T

SCULLERY

CORRIDOR

ASSEMBLY HALL

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

CORRIDOR

JAN

KITCHEN

C

LO

SE

T

STORAGE

VEST.

CORRIDOR

MECH114

CHAIR STORAGE

31 31 72" 72"

4 25 26 6

29 30

23 24

CLASSROOM

CLASSROOM

6 4

72"

24 23

26 25

12 10 8

17 13

19 15 11

24 16 22 20 14 18

25 23 25 25 23

6 8 9 10

E

A

B

C

D

JAN

MAIN T.R.

W O

M E

N 'S

R E

S

TR

O O

M

M E

N 'S

R

ES

TR

O

O M

42"

42"

42"

42"

14 42"

M

AT

C H

LI

N

E -S

EE

E

P1

M

AT

C H

LI

N

E -S

EE

E

P1

MATCHLINE - SEE EP113

8 WP 4

72"

72"

72"

EP410

72"

72"

34 KP2-19,21,23

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

KEYPLAN

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

PA

R

TI

AL

P O

W

ER

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EP111

D . H

EN

SL

EY

SCALE: 1/8" = 1'-0"

PARTIAL POWER PLAN

GENERAL SHEET NOTES

1 REFER TO SHEET E-001 FOR ELECTRICAL LEGEND AND

SHEET E-002 FOR ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS.3

SHEET KEYNOTES

1 JUNCTION BOX AND DEDICATED CIRCUIT FOR PARTITION

POWER. VERIFY EXACT ELECTRICAL REQUIREMENTS

WITH MANUFACTURER PRIOR TO ROUGH-IN.

2 ALL RECEPTACLES IN THIS AREA ARE TO BE FED FROM

PANEL 'RP1'.

3 ALL RECEPTACLES IN THIS AREA ARE TO BE FED FROM

PANEL 'RP5'.

4 RECEPTACLE TO BE FED FROM PANEL 'RP6'.

5 ALL RECEPTACLES IN THIS AREA ARE TO BE FED FROM

PANEL 'RP7'.

6 RECEPTACLE TO BE FED FROM PANEL 'RP2'.

7 ALL RECEPTACLES IN THIS AREA ARE TO BE FED FROM

PANEL 'RP4'.

8 PROVIDE NEMA 4X (316 STAINLESS STEEL), 600V, 100A, 3P

FUSED DISCONNECT SWITCH WITH (3) 100A RK5 FUSES

FOR MOBILE KITCHEN TRAILER (MKT). VERIFY EXACT

REQUIREMENTS WITH EQUIPMENT MANUFACTURER.

4 4

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

A M

D J R W

BT

M

10/27/2023

W

2Q R

R

_P la ns _V ol 6-

JJ

J

J

J

WP

WP

WP 2

EP410

12 14

12 14

ELECTRICAL

CAGE STORAGE

48" 648" 6

48" 6 48" 648" 6

ARMS VAULT

MECHANICAL

48"

CG 7

CG 7

CG 7 CG 9 CG 11 CG 13 CG 15 CG 19

48" 6 48" 8

48"

WP 4

M E

N 'S

R

ES

TR

O

O M

48"

48"

48"

CG 21

CG 21

CG 21 CG 23 CG 29 CG 33 CG 33CG 29

CG 27 CG 27 CG 27 CG 37

CG 37

CG 37

CG 41

CG 41

CG 41

CG 41

CG 39

CG 39

CG 39

ARMORER

1 2 3 4 5 6

E

A

B

C

D

3.5

CG 7

CG 7

CG 9

CG 7

CG 9

CG 9

CG 9

CG 11

CG 11

CG 11

CG 13

CG 13

CG 15

CG 13

CG 15

CG 17

CG 17

CG 17

CG 19

CG 19

CG 21

CG 21

CG 23

CG 23

CG 23

CG 23

CG 25

CG 25

CG 25

CG 25

CG 29

CG 27

CG 31

CG 31

CG 31

CG 31

CG 35

CG 35

CG 35

CG 35

EP501

MATCHLINE - SEE EP113 MATCHLINE - SEE EP113

M

AT

C H

LI

N

E -S

EE

E

P1

M

AT

C H

LI

N

E -S

EE

E

P1

FA-2 FA-4

CG 39 CG 39

72"

72"

FA-6

FA-6

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

KEYPLAN

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

PA

R

TI

AL

P O

W

ER

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

J.

W

ED

EL

A.

D

AV

IS

T.

M

IZ

E

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

EP112

D . H

EN

SL

EY

SCALE: 1/8" = 1'-0"

PARTIAL POWER PLAN

GENERAL SHEET NOTES

1 REFER TO SHEET E-001 FOR ELECTRICAL LEGEND AND

SHEET E-002 FOR ELECTRICAL GENERAL NOTES AND

ABBREVIATIONS.

2 FEED ALL RECEPTACLES ON THIS SHEET FROM PANEL

'RP2' U.N.O.

SHEET KEYNOTES

1 RECEPTACLE TO BE FED FROM PANEL 'RP3'.

2 RECEPTACLE TO BE FED FROM PANEL 'RP5'.

3 ALL RECEPTACLES AND ELECTRICAL DEVICES IN…