This package includes construction plans and specifications for a U.S. Army Reserve Center Operations Building project at Fort Buchanan, Puerto Rico. The project scope involves new building construction as well as associated site work. Key details include mechanical, electrical, plumbing and architectural drawings identifying product and system requirements. The solicitation number is W912QR24R0009 and was issued by the Department of the Army Corps of Engineers Louisville District. The required construction completion date is not specified.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

US Army Corps of Engineers®

SHEET ID

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

PROJECT NO. 89301, P2# 481867

PR

O

JE

C

T N

O . 8

, P 2#

N

L

J

G

E

C

A

P

M

K

H

F

D

B

1 3 5 7 9 11 13 15 17 192 4 6 8 10 12 14 16 18 20

LOUISVILLE DISTRICT

ISSUE DATE: OCTOBER 27, 2023

CONTRACT NO.: -

SOLICITATION NO.: -

CERTIFIED FINAL SUBMITTAL

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

G-001

C O

VE

R

S H

EE

T

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

LO

U

IS

VI

LL

E D

IS

TR

IC

T

LO

U

IS

VI

LL

E, K

EN

TU

C

KY

M .B

AR

N

ET

T

K.

R

IG

G

S

A.

M

C C

O Y

O C

TO

B

ER

7, D .H

EN

SL

EY

FORT BUCHANAN, PUERTO RICO

U.S. ARMY RESERVE CENTER OPERATIONS BUILDING

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

K

ER D

.A

M N

B

A M

M

10/27/2023

07/22/202007/27/202011/6/202012-4-202005/04/202107/22/202108/25/202102/14/202202/15/202207/13/202207/21/202205/24/202310/27/202310/27/2023

10/27/2023

10/27/2023

10/27/2023

10/27/23

VOLUME 4 OF 6

W

2Q R

R

_P la ns _V ol 4-

22 November 2023

W912QR24R0009

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

SHEET ID

P R

O J E

C T

N O

P

C E

R T

IF

IE

D F

IN

A

L S

U B

M

IT

T A

L

D R

A W

IN

G

L

IS

T

U .S

A

R M

Y R

E S

E R

V E

C E

N T

E R

O P

E R

A T

IO

N

S B

U

IL

D

IN

G

F O

R T

B U

C H

A N

A N

P

U E

R T

O R

IC

O

M B

A R

N E

T T

K R

IG

G

S

A M

C C

O Y

O C

T O

B E

R

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

G-002

D H

E N

S L E

Y

SHEET LIST

SHEET NUMBER SHEET NAME

M-713 MECHANICAL CONTROLS

ELECTRICAL

E-001 ELECTRICAL LEGEND

E-002 ELECTRICAL GENERAL NOTES & ABBREVIATIONS

EL111 PARTIAL LIGHTING PLAN

EL112 PARTIAL LIGHTING PLAN

EL113 PARTIAL LIGHTING PLAN

EL601 LIGHTING DIAGRAMS

EL701 LIGHTING SCHEDULES

EP111 PARTIAL POWER PLAN

EP112 PARTIAL POWER PLAN

EP113 PARTIAL POWER PLAN

EP130 BID OPTION 0014 - ROOF PV ARRAY PLAN

EP151 PARTIAL HVAC POWER PLAN

EP152 PARTIAL HVAC POWER PLAN

EP153 PARTIAL HVAC POWER PLAN

EP410 ENLARGED POWER PLANS

EP501 ELECTRICAL DETAILS

EP601 POWER ONE LINE DIAGRAM

EP701 PANEL SCHEDULES

EP702 PANEL SCHEDULES

EP703 PANEL SCHEDULES

EP704 PANEL SCHEDULES

EP705 PANEL SCHEDULES

EY111 PARTIAL SPECIAL SYSTEMS PLAN

EY112 PARTIAL SPECIAL SYSTEMS PLAN

EY113 PARTIAL SPECIAL SYSTEMS PLAN

EY501 SPECIAL SYSTEMS DETAILS

EG130 LIGHTNING PROTECTION PLAN

EG131 BID OPTION 0014 - LIGHTNING PROTECTION PLAN

EG501 LIGHTNING PROTECTION DETAILS

EG502 GROUNDING DETAILS

EG601 GROUNDING ONE LINE DIAGRAM

TELECOMMUNICATIONS

T-001 COMMUNICATIONS LEGENDS

T-002 COMMUNICATIONS GENERAL NOTES & ABBREVIATIONS

T-111 PARTIAL COMMUNICATIONS PLAN

T-112 PARTIAL COMMUNICATIONS PLAN

T-113 PARTIAL COMMUNICATIONS PLAN

T-410 ENLARGED COMMUNICATIONS PLANS

T-501 COMMUNICATIONS DETAILS

T-502 COMMUNICATIONS DETAILS

T-601 COMMUNICATION DIAGRAMS

T-602 COMMUNICATION ROOM 147 ELEVATION DIAGRAM

T-603 COMMUNICATION ROOM 126 ELEVATION DIAGRAM

SHEET LIST

SHEET NUMBER SHEET NAME

INTERIORS

I-001 FF&E LEGEND

I-110 COMPOSITE FURNITURE PLAN

I-111 PARTIAL FURNITURE PLAN

I-112 PARTIAL FURNITURE PLAN

I-113 PARTIAL FURNITURE PLAN

LIFE SAFETY

LS001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

LS100 CODE COMPLIANCE SITE PLAN

LS110 LEVEL 1 LIFE SAFETY PLAN - COMPOSITE

FIRE PROTECTION

FP001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

FP110 LEVEL 1 FIRE PROTECTION PLAN - COMPOSITE

FP501 FIRE PROTECTION DETAILS

FP502 FIRE PROTECTION DETAILS

FIRE ALARM

FA001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

FA110 LEVEL 1 FIRE ALARM PLAN - COMPOSITE

FA501 FIRE ALARM DETAILS

FA502 FIRE ALARM DETAILS

PLUMBING

P-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

PP101 PARTIAL UNDERGROUND PLAN

PP102 PARTIAL UNDERGROUND PLAN

PP111 PARTIAL SANITARY PLAN

PP112 PARTIAL SANITARY PLAN

PP113 PARTIAL WATER PLAN

PP114 PARTIAL WATER PLAN

PP115 PARTIAL WATER PLAN

P-401 ENLARGED PLANS

P-402 ENLARGED PLANS

P-403 ENLARGED PLANS

P-404 ENLARGED PLANS

P-405 ENLARGED PLANS

P-406 ENLARGED PLANS

P-501 DETAILS

P-502 DETAILS

P-503 DETAILS

P-504 DETAILS

P-601 SCHEDULES

P-900 RISER DIAGRAMS

P-901 RISER DIAGRAMS

P-902 RISER DIAGRAMS

P-910 RISER DIAGRAMS

P-911 RISER DIAGRAMS

P-912 RISER DIAGRAMS

MECHANICAL

M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

MH111 PARTIAL FLOOR PLAN - HVAC

MH112 PARTIAL FLOOR PLAN - HVAC

MH113 PARTIAL FLOOR PLAN - HVAC

MP111 PARTIAL FLOOR PLAN - PIPING

MP112 PARTIAL FLOOR PLAN - PIPING

MP113 PARTIAL FLOOR PLAN - PIPING

M-301 SECTIONS

M-411 ENLARGED PLAN - HVAC

M-412 ENLARGED PLAN - PIPING

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-504 MECHANICAL DETAILS

M-505 MECHANICAL DETAILS

M-506 MECHANICAL DETAILS

M-507 MECHANICAL DETAILS

M-550 AIR RISER DIAGRAM

M-551 AIR RISER DIAGRAM

M-552 AIR RISER DIAGRAM

M-553 CHILLED WATER PIPING DIAGRAM

M-601 MECHANICAL SCHEDULES

M-602 MECHANICAL SCHEDULES

M-603 MECHANICAL SCHEDULES

M-701 MECHANICAL CONTROLS

M-702 MECHANICAL CONTROLS

M-703 MECHANICAL CONTROLS

M-704 MECHANICAL CONTROLS

M-705 MECHANICAL CONTROLS

M-706 MECHANICAL CONTROLS

M-707 MECHANICAL CONTROLS

M-708 MECHANICAL CONTROLS

M-709 MECHANICAL CONTROLS

M-710 MECHANICAL CONTROLS

M-711 MECHANICAL CONTROLS

M-712 MECHANICAL CONTROLS

SHEET LIST

SHEET NUMBER SHEET NAME

S-362 FRAMING SECTIONS

S-363 FRAMING SECTIONS

S-364 FRAMING SECTIONS

S-365 FRAMING SECTIONS

S-366 BID OPTION - SOLAR PANEL SUPPORT FRAMING SECTIONS

S-401 ENLARGED RAMP FOUNDATION/SLAB PLAN

S-402 RAMP SECTIONS

S-411 ENLARGED VAULT ROOF SLAB FRAMING PLAN

S-412 VAULT SECTIONS AND DETAILS

S-413 VAULT SECTIONS

S-501 TYPICAL FOUNDATION DETAILS

S-502 TYPICAL FOUNDATION DETAILS

S-503 PRECAST WALL PANEL DETAILS

S-511 TYPICAL FRAMING DETAILS

S-601 SCHEDULES

S-602 SPECIAL JOIST LOADING DIAGRAM

ARCHITECTURE

A-001 SYMBOL LEGEND

A-110 COMPOSITE FLOOR PLAN

A-111D PARTIAL DIMENSION PLAN

A-111N PARTIAL NOTE PLAN

A-112D PARTIAL DIMENSION PLAN

A-112N PARTIAL NOTE PLAN

A-113D PARTIAL DIMENSION PLAN

A-113N PARTIAL NOTE PLAN

A-130 COMPOSITE ROOF PLAN

A-140 COMPOSITE REFLECTED CEILING PLAN

A-141 PARTIAL REFLECTED CEILING PLAN

A-142 PARTIAL REFLECTED CEILING PLAN

A-143 PARTIAL REFLECTED CEILING PLAN

A-160 COMPOSITE PRECAST PANEL FLOOR PLAN

A-161 PRECAST PANEL ELEVATIONS

A-162 PRECAST PANEL DETAILS

A-181 PARTIAL SIGNAGE PLAN

A-182 PARTIAL SIGNAGE PLAN

A-183 PARTIAL SIGNAGE PLAN

A-200 COMPOSITE BUILDING ELEVATIONS

A-201 ENLARGED BUILDING ELEVATIONS

A-202 ENLARGED BUILDING ELEVATIONS

A-203 ENLARGED BUILDING ELEVATIONS

A-204 ENLARGED BUILDING ELEVATIONS

A-301 BUILDING SECTIONS

A-310 WALL SECTIONS

A-311 WALL SECTIONS

A-400 ENLARGED RESTROOM PLAN

A-401 RESTROOM DETAILS

A-402 TYPICAL RESTROOM MOUNTING HEIGHTS

A-410 RESTROOM ELEVATIONS

A-450 RAILING DETAILS

A-461 PARTIAL FINISH PLAN

A-462 PARTIAL FINISH PLAN

A-463 PARTIAL FINISH PLAN

A-500 DOOR AND FRAME TYPES AND ABA MANEUVERING

CLEARANCES

A-501 DOOR DETAILS

A-502 DOOR DETAILS

A-510 WINDOW TYPES & DETAILS

A-530 LOUVER TYPES AND DETAILS

A-540 WALL TYPES

A-541 WALL DETAILS

A-542 WALL DETAILS

A-550 COLUMN DETAILS

A-551 COLUMN DETAILS

A-560 CEILING DETAILS

A-570 ROOF DETAILS

A-571 ROOF DETAILS

A-580 MISCELLANEOUS DETAILS

A-600 DOOR SCHEDULE

A-610 FINISH SCHEDULE AND EXTERIOR FINISH KEY

A-611 FINISH KEYS & NOTES

A-620 SIGNAGE SCHEDULE

A-621 SIGNAGE DETAILS

A-700 ENLARGED VAULT DIMENSION PLAN

A-701 ENLARGED VAULT NOTED PLAN

A-710 ENLARGED CAGE PLANS

A-711 CAGE ELEVATIONS

A-712 CAGE SECTIONS AND DETAILS

A-713 CAGE DETAILS

A-800 ENLARGED KITCHEN PLAN

A-801 KITCHEN SCHEDULE

A-900 AIR BARRIER FLOOR PLAN

A-901 AIR BARRIER WALL SECTION

SHEET LIST

SHEET NUMBER SHEET NAME

GENERAL

G-001 COVER SHEET

G-002 DRAWING LIST

G-201 LOCATION AND VICINITY MAP

G-202 PROJECT AERIAL

CIVIL

V-101 OVERALL SITE SURVEY

V-111 SITE SURVEY

V-112 SITE SURVEY

B-101 OVERALL BORING PLAN

B-111 BORING PLAN

B-112 BORING PLAN

B-201 BORING LOGS

B-202 BORING LOGS

C-001 CIVIL LEGEND AND ABBREVATIONS

C-002 CIVIL GENERAL NOTES

CD101 OVERALL DEMOLITION PLAN

CD111 DEMOLITION PLAN

CD112 DEMOLITION PLAN

CG101 OVERALL GRADING AND DRAINAGE PLAN

CG111 GRADING AND DRAINAGE PLAN

CG112 GRADING AND DRAINAGE PLAN

CG201 STORM SEWER PROFILES & SCHEDULE

CG501 DRAINAGE DETAILS

CG502 DRAINAGE DETAILS

CG503 DRAINAGE DETAILS

CG701 OVERALL SEDIMENT AND EROSION CONTROL PLAN

CG711 SEDIMENT AND EROSION CONTROL PLAN

CG712 SEDIMENT AND EROSION CONTROL PLAN

CG801 SEDIMENT AND EROSION CONTROL NOTES

CG802 SEDIMENT AND EROSION CONTROL DETAILS

CG803 SEDIMENT AND EROSION CONTROL DETAILS

CG804 SEDIMENT AND EROSION CONTROL DETAILS

CG805 SEDIMENT AND EROSION CONTROL DETAILS

CG806 SEDIMENT AND EROSION CONTROL DETAILS

CS101 OVERALL SITE LAYOUT

CS111 SITE LAYOUT

CS112 SITE LAYOUT

CS401 JOINT LAYOUT PLAN

CS501 PAVEMENT DETAILS

CS502 PAVEMENT DETAILS

CS503 DESIGNATED SMOKING AREA SIGNAGE

CU101 OVERALL UTILITY PLAN

CU111 UTILITY PLAN

CU112 UTILITY PLAN

CU201 SANITARY SEWER PROFILES & SCHEDULE

CU501 SANITARY SEWER DETAILS

CU502 SANITARY SEWER DETAILS

CU511 WATER DETAILS

CU512 WATER DETAILS

LP101 OVERALL LANDSCAPE PLAN

LP111 LANDSCAPE PLAN

LP112 LANDSCAPE PLAN

ELECTRICAL

ES100 EXISTING ELECTRICAL SITE PLAN

ES101 ELECTRICAL SITE PLAN

ES501 SITE ELECTRICAL DETAILS

ES502 BID OPTION - SITE ELECTRICAL DETAILS

ES503 SITE ELECTRICAL DETAILS

TELECOMMUNICATIONS

TS101 COMMUNICATION SITE PLAN

STRUCTURAL

S-001 GENERAL STRUCTURAL NOTES AND DESIGN CRITERIA

S-002 GENERAL STRUCTURAL NOTES, DESIGN CRITERIA AND

ABBREVIATIONS

S-003 COMPONENTS AND CLADDING WIND LOAD DIAGRAM

S-111 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-112 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-113 PARTIAL FOUNDATION/FLOOR SLAB PLAN

S-114 SLAB ON GRADE CONTROL JOINT PLAN

S-131 PARTIAL ROOF FRAMING PLAN

S-132 PARTIAL ROOF FRAMING PLAN

S-133 PARTIAL ROOF FRAMING PLAN

S-141 BID OPTION - SOLAR PANEL SUPPORT FRAMING PLAN

S-200 PRECAST CONCRETE WALL ELEVATIONS KEY PLAN

S-211 CONCRETE WALL ELEVATIONS

S-212 CONCRETE WALL ELEVATIONS

S-213 CONCRETE WALL ELEVATIONS

S-251 OPERABLE PARTITION SUPPORT FRAMING ELEVATION AND

SECTION

S-301 FOUNDATION SECTIONS

S-302 FOUNDATION SECTIONS

S-361 FRAMING SECTIONS

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

K

ER D

.A

M N

B

A M

M

W

2Q R

R

_P la ns _V ol 4-

MitcheTW

OCCUPANCY SCHEDULE NUMBER

AREA OCCUPANT LOAD (PEOPLE)

EGRESS PATH TRAVEL DISTANCE (FT)

EGRESS PATH MAXIMUM ALLOWABLE TRAVEL DISTANCE (FT)

E = EXIT TRAVEL DISTANCE

C = COMMON PATH OF TRAVEL

D = DEAD END LENGTH

FE = FIRE EXTINGUISHER TRAVEL

EGRESS PATH

AREA DELINEATION, OFFSET FOR CLARITY

DOOR FIRE-RESISTANCE RATING (MINUTES), DOOR SHALL BE

SELF- OR AUTOMATIC-CLOSING

PROVIDE PANIC BAR, PRESSURE PLATE, OR OTHER APPROVED

DEVICE (WHEN LATCHING)

OBJECT NAME

EGRESS FACTOR (in/PERSON)

CALCULATED EGRESS CAPACITY (PEOPLE)EGRESS

UTILIZATION

(PEOPLE)

CLEAR WIDTH (in)

BUILDING LEVEL GROSS AREA DELINEATION

1-HOUR FIRE BARRIER

2-HOUR FIRE BARRIER

FLOOR AREA DESIGNATION

FLOOR AREA (GROSS SQUARE FT)

DOOR

33 0.20

P

XX,XXX

LEVEL X

E76.2

SMOKE PARTITION/CONSTRUCTION RESISTING

THE PASSAGE OF SMOKE

NOTE:ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN

USED ON THE PLANS. SYMBOLS NOT LISTED IN THE LEGEND

ARE IDENTIFIED WHERE THEY OCCUR.

C PROVIDE AUTOMATIC-CLOSING DOOR

FIRE EXTINGUISHER. REFER TO

ARCHITECTURAL SHEETS FOR SHEET

KEYNOTES.

K = CLASS K EXTINGUISHER FOR KITCHEN COOKING AREA

APPLICABLE CODES AND STANDARDS

UFC 1-200-01 DOD BUILDING CODE, 1 OCTOBER 2020

UFC 3-600-01 FIRE PROTECTION ENGINEERING FOR FACILITIES,

CHANGE 6, 6 MAY 2021

UFC 4-021-01 DESIGN AND O&M: MASS NOTIFICATION SYSTEMS, WITH

CHANGE 1, JANUARY 2010

ECB 2018-17 NEW REQUIREMENTS FOR VISUAL NOTIFICATION FOR

MASS NOTIFICATION SYSTEMS

IBC, INTERNATIONAL BUILDING CODE, 2018, AS REFERENCED BY UFC

1-200-01

NFPA 1, FIRE CODE, 2021

NFPA 10, STANDARD FOR PORTABLE FIRE EXTINGUISHERS, 2022

NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS,

NFPA 70, NATIONAL ELECTRIC CODE, 2020

NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE, 2019

NFPA 90A, STANDARD INSTALLATION OF AIR CONDITIONING &

VENTILATION SYSTEMS, 2021

NFPA 101, LIFE SAFETY CODE, 2021

BUILDING DESCRIPTIONS / USE AND OCCUPANCY

IBC USE AND OCCUPANCY CLASSIFICATION: SEPARATED MIXED USE

(IBC SECTION 508.4)

ASSEMBLY USE GROUP A-3 (IBC 303.4)

BUSINESS USE GROUP B (IBC 304.1)

STORAGE USE GROUP S-1 MODERATE HAZARD (IBC 311.2)

SEPARATED MIXED USE - SEPARATION REQUIRED BETWEEN A-3 &

B/ S-1 OCCUPANCIES BY A MINIMUM OF 1 HR FIRE BARRIER.

NONSEPARATION USED FOR B/S-1.

NFPA 101 OCCUPANCY CLASSIFICATION: MIXED OCCUPANCY

BUSINESS (NFPA 101 6.1.11.1)

ASSEMBLY (NFPA 101 6.1.2.1)

STORAGE (NFPA 101 6.1.13.1)

INCIDENTAL OCCUPANCIES - SMALL STORAGE OCCUPANCY AREAS

(NFPA 101 6.1.14.1.3(1))

TYPE OF CONSTRUCTION (IBC 602.2, TABLE 601)

TYPE II-B, NONCOMBUSTIBLE, UNPROTECTED

FIRE RESISTIVE REQUIREMENTS (IBC TABLE 601)

STRUCTURAL FRAME 0 HOUR RATING

EXTERIOR BEARING WALLS 0 HOUR RATING

INTERIOR BEARING WALLS 0 HOUR RATING

NONBEARING INTERIOR WALLS 0 HOUR RATING

FLOORS & SECONDARY MEMBERS 0 HOUR RATING

ROOFS & SECONDARY MEMBERS 0 HOUR RATING

HEIGHT AND AREA LIMITATIONS (IBC 504 & 506)

BUILDING IS FULLY SPRINKLERED (S & S1 VALUES USED FROM

CHAPTER 5)

ALLOWABLE HEIGHT & STORIES (IBC TABLES 504.3 & 504.4)

BUSINESS USE GROUP B: 4 STORIES, 75 FT

STORAGE USE GROUP S-1: 3 STORIES, 75 FT

ASSEMBLY USE GROUP A-3: 3 STORIES, 75 FT

ACTUAL HEIGHT: 1 STORY, 35' - 8"

ALLOWABLE BUILDING AREA WITHOUT FRONTAGE INCREASE (IBC

TABLES 506.2)

OCCUPANCY AREA

BUSINESS USE GROUP B 92,000 SQFT

STORAGE USE GROUP S-1 70,000 SQFT

ASSEMBLY USE GROUP A-3 38,000 SQFT

ACTUAL BUILDING AREA: 45,613 SQFT

ACTUAL B/S-1: 40,248 SQFT

ACTUAL A-3: 5,365

5,365 SF + 40,248 SF = 0.14 + 0.57 = .71 < 1

38,000 70,000

FIRE SEPARATIONS

SEPARATED OCCUPANCY - SEPARATIONS REQUIRED PER IBC TABLE

508.4

SEPARATED MIXED USE - SEPARATION REQUIRED BETWEEN A-3 & B/

S-1 OCCUPANCIES BY A MINIMUM OF 1 HR FIRE BARRIER. NON

SEPARATION USED BETWEEN B/S-1. MOST RESTRICTIVE BUILDING

AREA USED FOR NONSEPARATION. INCIDENTAL USES MECH, ELEC, &

JAN CLOS - AUTOMATIC SPRINKLER PROVIDED AND NO FIRE

SEPARATION REQUIRED. SMOKE PARTITION IS REQUIRED FOR THESE

SPACES. (NFPA 101 38.3.2.1, & 8.7.1.2)

CORRIDORS (NFPA 101 CHAPTERS12, 38)

CORRIDOR RATING FOR BUSINESS OCCUPANCIES SHALL BE 0 HOUR

RATING WITH SPRINKLER SYSTEM. (NFPA 101 38.3.6 CONDITION 3)

CORRIDOR RATING FOR STORAGE OCCUPANCIES DO NOT APPLY.

(NFPA 101 42.3.6). CORRIDOR RATING FOR ASSEMBLY OCCUPANCIES

SHALL BE 0 HOUR RATING WITH SPRINKLER SYSTEM. (NFPA 101 12.3.6

CONDITION 2)

AUTOMATIC SPRINKLERS AND OTHER EXTINGUISHING

EQUIPMENT

AUTOMATIC WET PIPE SPRINKLER SYSTEM PROVIDED PER UFC

3-600-01, CHANGE 6, AND NFPA 13

GENERAL PURPOSE PORTABLE FIRE EXTINGUISHERS SHALL BE

PROVIDED WHERE REQUIRED BY NFPA 101. MINIMUM 10 LB, 4-

A:80-B:C

FIRE DETECTION, ALARM AND COMMUNICATION

DETECTION ALARM AND COMMUNICATION

A COMBINATION FIRE ALARM/MASS NOTIFICATION SYSTEM IS

PROVIDED IN ACCORDANCE WITH:

UFC 3-600-01, CHANGE 6 AND UFC 4-021-01, CHANGE 1, NFPA 70

AND NFPA 72.

FIRE AND SMOKE DAMPERS

APPROVED FIRE DAMPERS SHALL BE PROVIDED IN ALL AIR

TRANSFER OPENINGS IN PARTITIONS THAT ARE REQUIRED TO

HAVE A FIRE RESISTANCE RATING AND IN WHICH OTHER

OPENINGS ARE REQUIRED TO BE PROTECTED. (NFPA 90A

SECTION 3-3.1.2). OPS HAS NO 2-HR FIRE BARRIERS. FIRE

DAMPERS NOT REQUIRED.

SMOKE DAMPERS ARE NOT REQUIRED.

INTERIOR FINISH REQUIREMENTS (NFPA 101, TABLE A.10.2.2)

EXITS: CLASS A

EXIT ACCESS CORRIDORS: CLASS A OR B

OTHER SPACES: CLASS A, B, OR C

ASSEMBLY OCCUPANCY FLOORS: CLASS I OR II (EXITS AND EXIT

ACCESS CORRIDORS)

BUSINESS/STORAGE OCCUPANCY FLOORS: CLASS I OR II (EXITS)

OCCUPANT LOADS

SEE DRAWINGS FOR SPACE FUNCTIONS AND OCCUPANT LOADS.

MEANS OF EGRESS

WHERE EXIT ACCESS FROM AN OCCUPANCY TRAVERSES

ANOTHER OCCUPANCY, THE MULTIPLE OCCUPANCY SHALL BE

TREATED AS A MIXED OCCUPANCY. (NFPA 101 SECTION

6.1.14.1.2)

EGRESS CAPACITY (NFPA 101 TABLE 7.3.1.2 AND TABLE 7.3.3.1)

ALL REQUIRED EXIT ACCESS DOORS MEET THE MINIMUM WIDTH

OF 32” PER NFPA 101 §7.2.1.2.3.2.

TOTAL BUILDING OCCUPANT LOAD AND EGRESS DOOR WIDTHS

PROVIDED ON NEXT SHEET.

CORRIDOR WIDTH REQUIRED = 44” (NFPA 101 38.2.3.2)

CORRIDOR WIDTH PROVIDED = 44” & 96"

NUMBER OF MEANS OF EGRESS (NFPA 101 SECTION 7.4.1.1)

TWO EXITS ARE REQUIRED FROM THE BUSINESS, AND STORAGE

OCCUPANCIES PER STORY.

A SINGLE EXIT IS PERMITTED FROM THE UTILITY AREAS

(ORDINARY HAZARD STORAGE)(NFPA 42.2.4.1(2))

ACTUAL NUMBER OF EXITS = 16 EXITS

ACCESSIBLE MEANS OF EGRESS (NFPA 101 SECTION 7.5.4)

COMMON PATH OF TRAVEL (NFPA 101 TABLE A.7.6, SPRINKLERED

AREAS)

BUSINESS: 100 FT

STORAGE ORDINARY HAZARD: 100 FT

ASSEMBLY: 20 FT (75 FT FOR LESS THAN 50 PEOPLE)

DEAD END LIMITS (NFPA 101 TABLE A.7.6, SPRINKLERED AREAS)

BUSINESS: 50 FT

STORAGE ORDINARY HAZARD: 100 FT

ASSEMBLY: 20 FT

LENGTH OF TRAVEL DISTANCE (NFPA 101 TABLE A.7.6,

SPRINKLERED AREAS)

BUSINESS: 300 FT

STORAGE ORDINARY HAZARD: 400 FT

ASSEMBLY: 250 FT

8.

9.

10.

11.

12.

13.

1.

2.

3.

4.

5.

6.

7.

THIS DRAWING IS NOT PART OF THE CONSTRUCTION CONTRACT. ALL

INFORMATION SHOWN ON THIS DRAWING IS SHOWN ELSEWHERE.

FOR REFERENCE ONLY

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

AB

BR

EV

IA

TI

O

N S, L

EG

E N

D A

N D

G

EN

ER

AL

N O

TE

S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

LS001

D . H

EN

SL

EY

LIFE SAFETY ABBREVIATIONS LIFE SAFETY LEGEND

LIFE SAFETY

ABBREVIATIONS SPACE FUNCTIONS

ABV ABOVE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

BEL BELOW

BLDG BUILDING

CF CUBIC FOOT (FEET)

CONT CONTINUED

DN DOWN

DWG DRAWING

FM FM GLOBAL (FACTORY MUTUAL)

FT FOOT (FEET)

IBC INTERNATIONAL BUILDING CODE

IN INCH(ES)

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NTP NOTICE TO PROCEED

NTS NOT TO SCALE

OBS OBSTRUCTION

RM ROOM

SF SQUARE FOOT (FEET)

TYP TYPICAL

U/F UNDERFLOOR

UG UNDERGROUND

UL UNDERWRITER'S LABORATORIES

UNO UNLESS NOTED OTHERWISE

W/ WITH

W/O WITHOUT

WHSE WAREHOUSE

*NOTE NOT ALL ABBREVIATIONS MAY BE USED

A-LESS ASSEMBLY: LESS CONCENTRATED (WITHOUT

FIXED SEATING)

NFPA 101

A-WAIT ASSEMBLY: WAITING SPACES NFPA 101

B-COLL BUSINESS: COLLABORATION ROOMS ≥ 450 FT² NFPA 101

B-COLS BUSINESS: COLLABORATION ROOMS ≤ 450 FT² NFPA 101

B-CON BUSINESS: CONCENTRATED NFPA 101

B-GEN BUSINESS: GENERAL NFPA 101

E-CLAS EDUCATIONAL: CLASSROOMS NFPA 101

E-LABS EDUCATIONAL: SHOPS, LABORATORIES,

VOCATIONAL ROOMS

NFPA 101

S-OTHR STORAGE: IN OTHER THAN STORAGE AND

MERCANTILE OCCUPANCIES

NFPA 101

S-STG STORAGE: IN STORAGE OCCUPANCIES (MAX

PROBABLE FOR USE, OR AS OTHER STORAGE)

NFPA 101

S/ME ACCESSORY STORAGE AND UTILITY ROOMS

(FROM 2018 IBC TABLE 1004.1.2)

NFPA 101

CONF CONFERENCE ROOMS WITH TABLES AND CHAIRS UFC 3-600-01

ITEQ IT EQUIPMENT ROOMS UFC 3-600-01

MANU MANUFACTURING AREAS UFC 3-600-01

MEP MECHANICAL, ELECTRIAL, AND OTHER BUILDING

EQUIPMENT SPACES

UFC 3-600-01

WAIT WATING SPACES, OTHER THAN THEATERS AND

SIMILAR OCCUPANCIES

UFC 3-600-01

*NOTE NOT ALL ABBREVIATIONS MAY BE USED

LIFE SAFETY CODE ANALYSIS

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-wv

EBOX

wv

EBOX

GP

ARC OPS

BUILDING

F.F.E. 64.75

USARC TRAINING BUILDING

FFE 59.0

UNHEATED

STORAGE

FFE 64.0

2.5

8"

8"

THE INTENT OF THE FIRE PROTECTION CODE SUMMARY IS TO

IDENTIFY FIRE DEPARTMENT VEHICLE ACCESS, SITE FIRE

PROTECTION FEATURES, AND HOSE LAY DISTANCES BETWEEN

HYDRANT LOCATIONS AND THE EXTERIOR OF THE BUILDING.

FIRE DEPARTMENT ACCESS

UFC 3-600-01 & NFPA 1

A. ALL FACILITIES GREATER THAN 5,000 SF OR MORE THAN

TWO STORIES IN HEIGHT MUST HAVE AT LEAST ONE MEANS

OF ALL-WEATHER GROUND ACCESS TO ALLOW EMERGENCY

VEHICLES UNIMPEDED ACCESS TO THE FACILITY.

B. ACCESS ROADS MUST BE REQUIRED TO PROVIDE ACCESS

TO THE FIRE HYDRANT FOR FACILITIES LESS THAN 5,000 SF.

FIRE HYDRANTS

UFC 3-600-01

A. HYDRANTS SHALL BE WITHIN 350 FT OF ALL PARTS OF THE

BUILDING EXTERIOR.

B. AT LEAST ONE HYDRANT SHALL BE WITHIN 150 FT OF THE

FIRE DEPARTMENT CONNECTION (FDC).

C. HYDRANTS SHALL BE INSTALLED ADJACENT TO ACCESS

ROADS AND ACCESSIBLE TO FIRE DEPARTMENT

APPARATUS. HYDRANTS SHALL BE LOCATED 3 TO 7 FEET

FROM THE ROADWAY SHOULDER OR CURB LINE.

D. HYDRANTS LOCATED ADJACENT TO PARKING AREAS OR

OTHER VEHICLE TRAFFIC AREAS, SHALL BE PROTECTED BY

BOLLARDS. THE BOLLARDS MUST BE LOCATED SO THEY ARE

NOT DIRECTLY IN FRONT OF AN OUTLET.

E. HYDRANTS SHALL BE INSTALLED WITH NOT LESS THAN 6 IN

CONNECTION TO THE SUPPLY MAIN, AND VALVED AT THE

CONNECTION. SUCTION CONNECTION SHALL BE

PERPENDICULAR TO THE STREET TO ALLOW STRAIGHT

LINED CONNECTION TO THE PUMPER.

F. HYDRANT BARRELS MUST BE LONG ENOUGH TO PERMIT AT

LEAST 18 IN CLEARANCE BETWEEN THE CENTER OF THE

SUCTION CONNECTION AND GRADE.

G. HYDRANTS SHALL BE MARKED BASED ON THE FIRE FLOW

CAPACITY. IN THE ABSENCE OF AN INSTALLATION

ESTABLISHED MARKING STANDARD THE HYDRANT BONNET

AND CAPS SHALL BE PAINTED IN ACCORDANCE WITH NFPA

291.

H. A SUFFICIENT NUMBER OF HYDRANTS MUST BE PROVIDED

SO THAT FIRE FLOW CAN BE MET WITHOUT TAKING MORE

THAN 1,250 GPM FROM ANY SINGLE HYDRANT.

FIRE DEPARTMENT CONNECTION (FDC)

UFC 3-600-01

A. FACILITIES WITH FIRE DEPARTMENT CONNECTIONS (FDC)

FOR SPRINKLER SYSTEMS SHALL BE PROVIDED WITH

SUITABLE ALL-WEATHER GROUND ACCESS SURFACE FOR

PUMPER APPARATUS WITHIN 150 FT OF SUCH FIRE

DEPARTMENT CONNECTIONS.

B. FDC MUST FACE THE ACCESS ROAD WITHOUT

OBSTRUCTIONS.

1.

2.

3.

4.

A FLOW TEST WAS CONDUCTED ON 03/01/2022.

THE TIME WAS: 1345 HRS

CONDUCTED BY: J. HOWELL TAYLOR, PE

IT REVEALED THE FOLLOWING:

TEST HYDRANT

HYDRANT: 18

STATIC PRESSURE: 43 PSI

RESIDUAL PRESSURE: 40 PSI

FLOW HYDRANT

HYDRANT: 17

FLOW: 1355 GPM

PITOT PRESSURE: 13 & 20 PSI

OUTLET SIDE: (2) 2.5 INCHES FLOWING

EXISTING FIRE PUMP PROVIDED UNDER PHASE 1:

AURORA MODEL 6-481-11 UL/FM HORIZONTAL SPLIT CASE

RATED 1000 GPM @ 40 PSIG

THIS DRAWING IS NOT PART OF THE CONSTRUCTION CONTRACT. ALL

INFORMATION SHOWN ON THIS DRAWING IS SHOWN ELSEWHERE.

FOR REFERENCE ONLY

HYDRANT DISTANCE TO BUILDING EXTERIOR

FIRE HYDRANT (FH)

POST INDICATOR

VALVE (PIV)

FIRE DEPARTMENT

CONNECTION (FDC)

177'

EXISTING HYDRANT #18

TEST HYDRANT

EXISTING HYDRANT #17

FLOW HYDRANT APPROX 470'

SOUTH OF HYDRANT #18

EXISTING FIRE

PUMP ROOM

NEW 8" SUPPLY

CONNECTING DOWNSTREAM

OF EXISTING FIRE PUMP

PROPOSED

HYDRANT

EXISTING HYDRANT

#19

EXISTING HYDRANT

UNDER PHASE 1

EXISTING HYDRANT

UNDER PHASE 1

FIRE DEPARTMENT MAIN

ENTRANCE INTO FACILITY

FIRE DEPARTMENT

CONNECTION FOR ARC OPS

FIRE ALARM REMOTE

ANNUNCIATOR FOR ARC OPS

114' - 6 23/32"

65'-6"

7'

181'-5"

FIR

E D

EPARTMENT ACCESS

FIRE DEPARTMENT ACCESS

FIRE DEPARTMENT ACCESS

WALL POST

INDICATOR VALVE (PIV)

D

AVID

SO

N

R O

AD

DEPOT R

OAD

' MINIMUM SEPARATION DISTANCE FROM

EXTERIOR WALL TO EXTERIOR WALL

IS 20' TO MEET THE FIRE SEPARATION

DISTANCE OF TABLE 602 OF THE IBC.

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

C O

D E

C O

M

PL

IA

N

C E

SI

TE

P

LA

N

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

LS100

D . H

EN

SL

EY

GENERAL NOTES

FIRE FLOW TEST

LEGEND

SCALE: 1" = 40'-0"

CODE COMPLIANCE SITE PLAN

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

40,248 SF

B/S-1

DOOR 121A

32 0.20

DOOR 107A

32 0.20

DOOR 102

32 0.20

DOOR 107B

32 0.20

DOOR 110

32 0.20

DOOR 100

32 0.20

DOOR 121B

32 0.20

DOOR 121C

32 0.20

DOOR 121D

32 0.20

DOOR 128

32 0.20

DRINK CLOSET

SCULLERY

ELEC

CORRIDOR

ASSEMBLY HALL

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MECHANICAL

T.R.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CAGE STORAGE

CORRIDOR

JAN

KITCHEN

CLOSET

STORAGE

VEST.

CORRIDOR

P

P

P

P

P

MECH

5,365 SF

A-3

1A-1

1A-2

1A-3

1A-4

1A-5

1A-6

1B-9

1B-11

DOOR 121F

32 0.20

1-1

1-2

1-4

1-5

1-6

C

C

C

CHAIR STORAGE

E300

OFFICE

OFFICE

ELECTRICAL

ARMS VAULT

ARMORER

CAGE STORAGE

1-3

JAN

M E

N 'S

R

ES

TR

O

O M

W O

M E

N 'S

R E

S

TR

O O

M

MAIN T.R.

1B-15

1A-7

1B-10

1B-12

1B-13

1B-14

1A-8

P

DOOR 124A

72 0.20

DOOR 125

32 0.20

DOOR 121

32 0.20

C100

E250

E300

C

E250

FE75

FE75

FE75

CAGE STORAGE

CAGE STORAGE

E300

E300

E300

K

117'

59'-6" > 1/3 of 117'

D50 48.75

C

C75

THIS DRAWING IS NOT PART OF THE CONSTRUCTION CONTRACT. ALL

INFORMATION SHOWN ON THIS DRAWING IS SHOWN ELSEWHERE.

FOR REFERENCE ONLY GRAPHIC SCALE: = 1'-0"

16' 08' 32' 48'16'

1/16"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

LE

VE

L

LI

FE

S

AF

ET

Y

PL

AN

C

O M

PO

SI

TE

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

LS110

D . H

EN

SL

EY

SCALE: 1/16" = 1'-0"

LIFE SAFETY PLAN - COMPOSITE

GENERAL SHEET NOTES

1 SEE SHEET LS-001 FOR GENERAL NOTES, SYMBOLS AND

LEGEND.

OCCUPANCY TABLE - LEVEL 1

NUMBER NAME

SPACE

FUNCTION AREA

AREA

FACTOR AREA TYPE

OCCUPANT

LOAD

1A-1 ASSEMBLY HALL A-FIXD 3809.97 SF NUMBER OF

SEATS

1A-2 JAN S/ME 28.70 SF 300 SF GROSS 1

1A-3 KITCHEN A-KIT 736.71 SF 100 SF GROSS 8

1A-4 STORAGE S-OTHR 163.60 SF 500 SF GROSS 1

1A-5 MECHANICAL MEP 102.32 SF 500 SF GROSS 1

1A-6 STORAGE S-OTHR 490.83 SF 500 SF GROSS 1

1A-7 CLOSET S-OTHR 28.03 SF 500 SF GROSS 1

1A-8 DRINK CLOSET S/ME 28.93 SF 300 SF GROSS 1

ASSEMBLY 262

1B-9 CLASSROOM E-CLAS 1090.80 SF 20 SF NET 55

1B-10 CORRIDOR B-GEN 1224.10 SF 150 SF GROSS 9

1B-11 CLASSROOM E-CLAS 1044.65 SF 20 SF NET 53

1B-12 TR MEP 113.98 SF 500 SF GROSS 1

1B-13 RESTROOM B-GEN 981.67 SF 150 SF GROSS 7

1B-14 JAN S/ME 64.82 SF 300 SF GROSS 1

1B-15 CLASSROOM E-CLAS 1266.55 SF 20 SF NET 64

BUSINESS 190

1-1 OFFICES B-GEN 3028.28 SF 150 SF GROSS 21

1-2 ELEC/TR MEP 158.97 SF 500 SF GROSS 1

1-3 CAGE STORAGE S-STG 25195.62 SF 500 SF GROSS 51

1-4 ARMS VAULT S-STG 3343.09 SF 500 SF GROSS 7

1-5 MECHANICAL MEP 2336.83 SF 500 SF GROSS 8

1-6 ELEC/TR MEP 292.25 SF 500 SF GROSS 1

WHSE 89

LEVEL 1 541

DOORS - LEVEL 1

NAME CLEAR WIDTH (in) EGRESS FACTOR (in/PERSON) CAPACITY (PEOPLE)

UTILIZATION

(PEOPLE)

DOOR 107A 32 0.2 160 126

DOOR 107B 32 0.2 160 127

DOOR 110 32 0.2 160 9

LEVEL A-3 480 262

DOOR 100 32 0.2 160 95

DOOR 102 32 0.2 160 95

DOOR 121 32 0.2 160 10

DOOR 121A 32 0.2 160 10

DOOR 121B 32 0.2 160 10

DOOR 121C 32 0.2 160 10

DOOR 121D 32 0.2 160 10

DOOR 121F 32 0.2 160 9

DOOR 124A 72 0.2 360 8

DOOR 125 32 0.2 160 1

DOOR 128 32 0.2 160 21

LEVEL B/S-1 1960 279

2440 541

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

ARCHITECTURAL SCALES

SCALE 1 1/2" = 1'- 0"

DETAIL

NUMBER OF SHEET ON

WHICH DETAIL IS INDICATED

(SCALE AT WHICH DETAIL IS DRAWN)

SYMBOL WHERE DETAIL IS TAKEN

NUMBER OF SHEET ON

WHICH DETAIL IS DRAWN

DETAIL IDENTIFICATION

NUMBER

DETAIL CROSS REFERENCE

FIRE SUPPRESSION LEGEND

NORTH ARROW ALWAYS

POINT TRUE NORTH

GENERAL FIRE SUPPRESSION NOTES

1. SPRINKLER AND ASSOCIATED PIPING INDICATED ON THE PLAN VIEW

DRAWINGS ARE FOR REFERENCE AND DESIGN LEVEL HYDRAULIC

CAPABILITY VERIFICATION CALCULATION ONLY. THE FIRE SPRINKLER

CONTRACTOR SHALL BE RESPONSIBLE FOR SHOP LEVEL SYSTEM

LAYOUT, DRAWINGS, AND ASSOCIATED CALCULATIONS DESIGNED AND

PREPARED IN ACCORDANCE WITH ALL APPLICABLE CODES AND

STANDARDS.

2. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF SYSTEM

REQUIREMENTS WITH ALL CONDITIONS OF THE BUILDING AND SITE

INCLUDING, BUT NOT LIMITED TO, BLIND SPACES, SHELVING, LIGHTS,

GRILLES AND DIFFUSERS, PIPING, DUCT WORK, DOORS, WINDOWS,

EQUIPMENT PLATFORMS, WALLS (FIRE RATED AND NON-FIRE-RATED),

BEAMS, JOISTS, COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS

AND EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL

CONSTRUCTION, FLOORS AND ALL CONSTRUCTION, EQUIPMENT AND

BUILDING APPURTENANCES.

3. IF DAMAGE OCCURS TO SYSTEMS OR COMPONENTS DURING RENOVATION,

THE CONTRACTOR WILL BE RESPONSIBLE FOR REPLACING AND REPAIRING

ANY DAMAGED COMPONENTS WITH LIKE MATERIALS.

4. ALL PENETRATIONS OF ELECTRICAL, TELECOM, AND SIMILAR ROOMS

SHALL BE LIMITED TO LOCATIONS ABOVE THE ACCESS DOORS TO THOSE

ROOMS TO THE MAXIMUM EXTENT POSSIBLE. IN CASES WHERE THE

PENETRATION IS NOT ABOVE THE DOOR, THE FIRE SUPPRESSION

CONTRACTOR SHALL COORDINATE THE LOCATION WITH OTHER TRADES

TO ENSURE THAT AT LEAST SIX FEET OF CLEARANCE IS PROVIDED ABOVE

ALL PANELS.

5. MECHANICAL COUPLINGS SHALL BE OF THE SAME MANUFACTURER AS

THE CONNECTED FITTINGS, OR SHALL BE SPECIFICALLY LISTED FOR

USE WITH THE CONNECTED FITTINGS.

6. FIRE SPRINKLER HANGERS SHALL BE LOCATED AND INSTALLED IN

ACCORDANCE WITH NFPA 13.

7. ALL SPRINKLERS SHALL BE INSTALLED AFTER THE PIPING HAS BEEN

INSTALLED AT ITS FINAL ELEVATION AND NOT WHILE THE PIPING IS AT

THE FLOOR LEVEL.

8. SPRINKLER GUARDS SHALL BE PROVIDED ON ALL SPRINKLERS WITHIN

7 FEET OF THE FINISHED FLOOR ELEVATION OR AS INDICATED. GUARDS

SHALL BE SPECIFICALLY LISTED FOR USE WITH THE INDICATED SPRINKLER

(BY MODEL/SIN).

9. ALL LOW POINT AREAS SHALL BE PROVIDED WITH LOW-POINT DRAIN

CONNECTIONS AND VALVES. TO THE EXTENT POSSIBLE, THESE DRAINS

SHALL BE ROUTED TO THE BUILDING EXTERIOR, OTHERWISE CAPS OR

PLUGS SHALL BE PROVIDED.

4' 02' 8' 12'4'

GRAPHIC SCALE: = 1'-0"1/4"

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8" = 1'-0"

X

X-XXX

X

X-XXX

ABV ABOVE

ABD AUTOMATIC BALL DRAIN

AFF ABOVE FINISHED FLOOR

BEL BELOW

BFP BACK FLOW PREVENTER

BLDG BUILDING

CF CUBIC FOOT (FEET)

CMDA CONTROL MODE DENSITY AREA

CONT CONTINUED

DN DOWN

DWG DRAWING

EC EXTENDED COVERAGE (SPRINKLER)

EH1 EXTRA HAZARD (GROUP 1)

EH2 EXTRA HAZARD (GROUP 2)

ELEC ELECTRIC OR ELECTRICAL

ESFR EARLY SUPPRESSION FAST RESPONSE

FAS FIRE ALARM SYSTEM

FDC FIRE DEPARTMENT CONNECTION

FHV FIRE HOSE VALVE

FM FM GLOBAL (FACTORY MUTUAL)

FP FIRE PUMP

FT FOOT (FEET)

GPM GALLONS PER MINUTE

HSW HORIZONTAL SIDEWALL (SPRINKLER)

IBC INTERNATIONAL BUILDING CODE

IFC INTERNATIONAL FIRE CODE

IN INCH(ES)

IRAS IN-RACK AUTOMATIC SPRINKLERS

ITC INSPECTORS TEST CONNECTION

JP JOCKEY (PRESSURE-MAINTENANCE) PUMP

ABBREVIATIONS

MISCELLANEOUS SYMBOLSHAZARD CLASSIFICATION

HAZARD

CATEGORY

LH

TYPE

WET PIPE

DENSITY

(gpm/SF)

0.10

0.20

NOTES

CEILING HEIGHT UP TO 30 FT

0.1GPM/SF OVER 1500SF

NFPA 13, 4.3.2, TABLE 9-3

WET PIPE

AREA

(SF)

1,500

2,500

HOSE STREAM

(gpm)

DURATION

(min)

60OH

CEILING HEIGHT UP TO 30 FT

0.2GPM/SF OVER 2500 SF

NFPA 13, 4.3.3, TABLE 9-3

LD LARGE DROP (SPRINKLER)

LH LIGHT HAZARD

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NH NATIONAL HOSE THREAD

NIC NOT IN CONTACT

N.C. NORMALLY CLOSED

N.O. NORMALLY OPEN

NTS NOT TO SCALE

OBS OBSTRUCTION

OH ORDINARY HAZARD

PIV POST INDICATING VALVE

PSI POUNDS PER SQUARE INCH

RM ROOM

SF SQUARE FOOT (FEET)

SSP STANDARD SPRAY PENDANT (SPRINKLER)

SSU STANDARD SPRAY UPRIGHT (SPRINKLER)

TYP TYPICAL

U/F UNDERFLOOR

UG UNDERGROUND

UL UNDERWRIGHTERS LABORATORIES

UNO UNLESS NOTED OTHERWISE

W/ WITH

W/O WITHOUT

*NOTE NOT ALL ABBREVIATIONS MAY BE USED

K - FACTOR

UFC 3-600-01

TABLE 9-3

5.6

8.0

0.40WET PIPE 2,000 500 120

CEILING HEIGHT UP TO 12 FT

SHELF; GROUP A PLASTICS,

NONEXPANDED, STABLE,

EXPOSED; HIGH-

TEMPERATURE.

NFPA 13, FIG. 21.3.1, TABLE

21.3.3(a)

11.2SHELF

STORAGE CMDA

EH2

WATER SUPPLY CHARATERISTICS FOR BIDDING PURPOSES

ONLY. CONTRACTOR TO PERFORM INDEPENDENT FLOW TEST:

A FLOW TEST WAS CONDUCTED ON 03/01/2022.

THE TIME WAS 1345 HRS.

CONDUCTED BY: J. HOWELL TAYLOR, PE

IT REVEALED THE FOLLOWING:

TEST HYDRANT

HYDRANT: 18

STATIC PRESSURE: 43 PSI

RESIDUAL PRESSURE: 40 PSI

FLOW HYDRANT

HYDRANT: 17

FLOW: 1355 GPM

PITOT PRESSURE: 13 & 20 PSI

OUTLET SIDE: (2) 2.5 INCHES FLOWING

EXISTING FIRE PUMP PROVIDED UNDER PHASE 1:

AURORA MODEL 6-481-11 UL/FM HORIZONTAL SPLIT CASE

RATED 1000 GPM @ 40 PSIG. EXISTING FIRE PUMP LOCATED

IN FIRE PUMP ROOM 161 OF LEVEL 1 OF EXISTING TRAINING

BUILDING. THERE ARE EXTERNAL DOUBLE EXIT DOORS TO THE

ROOM. REFER TO SHEET LS100.

SPRINKLER SYSTEM SHALL BE DESIGNED IN ACCORDANCE WITH

2019 NFPA 13. SEE SPRINKLER DESIGN SCHEDULE, THIS SHEET.

PIPING SHALL BE DESIGNED WITH SEISMIC BRACING IN

ACCORDANCE WITH 2019 NFPA 13. REFER TO STRUCTURAL

DRAWING S-001 FOR SEISMIC DESIGN CRITERIA.

PENDENT SPRINKLER, CONCEALED, QUICK RESPONSE

A

SPRINKLER SYSTEM RISER - WET

NOTE:ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE BEEN

USED ON THE PLANS. SYMBOLS NOT LISTED IN THE LEGEND

ARE IDENTIFIED WHERE THEY OCCUR.

PIPE ELBOW DOWN

PIPE TEE DOWN

PIPE ELBOW OR TEE UP

PIPE REDUCER

PIPE END CAP

PIPE COUPLING

PIPE TAP

OUTSIDE SCREW AND YOKE (OS&Y) VALVE

CHECK VALVE

FIRE DEPARTMENT CONNECTION, WALL MOUNTED, TWO INLETS

SPRINKLER DESIGN SCHEDULE AREA DESIGNATION

SPRINKLER DESIGN SCHEDULE AREA DELINEATION

PENDENT SPRINKLER, QUICK RESPONSE

UPRIGHT SPRINKLER, QUICK RESPONSE

UPRIGHT SPRINKLER ON SPRIG, QUICK RESPONSE

UFC 3-600-01_ 9-7.3.1.2: IN MIXED USE FACILITIES, MUST FOLLOW

THE MISCELLANEOUS STORAGE AND STORAGE PROVISIONS OF

NFPA 13.

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

AB

BR

EV

IA

TI

O

N S, L

EG

E N

D A

N D

G

EN

ER

AL

N O

TE

S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

FP001

D . H

EN

SL

EY

SPRINKLER SYSTEM DESIGN CRITERIA

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

FP501

FP501

DRINK CLOSET

SCULLERY

ELEC

CORRIDOR

ASSEMBLY HALL

CLASSROOM 105

CLASSROOM

CLASSROOM

CLASSROOM

MECHANICAL

T.R.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CAGE STORAGE

CORRIDOR

JAN

KITCHEN

CLOSET

STORAGE

VEST.

CORRIDOR

CORRIDOR

CAGE STORAGE

CAGE STORAGE

MECH

CHAIR STORAGE

2 3 4 5 6 8 9 10

A

G

B

D

E

H

J

K

L

C

F

F.1

E.1

2.5

E.5

ELECTRICAL

ARMORER

ARMS VAULT

ARMS VAULT

OFFICE

OFFICE

OFFICE

JAN

MEN'S RESTROOM

WOMEN'S RESTROOM

MAIN T.R.

CLASSROOM

CLASSROOM

ARMS VAULT

ARMS VAULT

GRAPHIC SCALE: = 1'-0"

16' 08' 32' 48'16'

1/16"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

SHEET ID

P R

O J E

C T

N O

P

C E

R T

IF

IE

D F

IN

A

L S

U B

M

IT

T A

L

L E

V E

L

F

IR

E P

R O

T E

C T

IO

N

P L A

N

C O

M P

O S

IT

E

U .S

A

R M

Y R

E S

E R

V E

C E

N T

E R

O P

E R

A T

IO

N

S B

U

IL

D

IN

G

F O

R T

B U

C H

A N

A N

P

U E

R T

O R

IC

O

H T

A Y

L O

R

H T

A Y

L O

R

J R

A

IN

E Y

O C

T O

B E

R

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

FP110

D H

E N

S L E

Y

SCALE: 1/16" = 1'-0"

LEVEL 1 - SPRINKLER PLAN - OVERALL

SHEET KEYNOTES

1 GUARDS SHALL BE PROVIDED FOR SPRINKLER HEADS

WITHIN THE VAULT. COORDINATE SPRINKLER DESIGN

WITH WEAPONS RACK LAYOUT.

2 UNDERGROUND FIRE SERVICE LATERAL.

3 4" FDC PIPING CONTINUE TO SPRINKLER SYSTEM

4 WALL MOUNTED FDC. EXISTING FIRE HYDRANT WITHIN

150 FT DISTANCE.

5 CHECK VALVE WITH ABD. ABD DRAIN TO DISCHARGE TO

EXTERIOR SPLASH BLOCK.

GENERAL SHEET NOTES

1 SEE SHEET FP001 FOR GENERAL NOTES, SYMBOLS AND

LEGEND.

M A

R K

D E

S C

R

IP

T

IO

N D

A T

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

2 3

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

FI

R

E

PR

O

TE

C

TI

O N

D

ET

AI

LS

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

FP501

D . H

EN

SL

EY

SHEET KEYNOTES

1 VANE TYPE WATER FLOW ALARM SWITCH

2 FIRE SPRINKLER SYSTEM RISER CHECK VALVE

ASSEMBLY

3 MAIN DRAIN VALVE (N.C.)

4 MAIN DRAIN PIPING DISCHARGED TO OUTSIDE SPLASH

BLOCK

5 8" WALL MOUNTED PIV (OS&Y VALVE) WITH TAMPER

SWITCH (N.O.)

SCALE: NTSFP501

RISER DETAIL1

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

GRADE

FOOTER

12" MIN.

FLOOR

CI FLANGE AND SPIGOT

PIECE

TO SYSTEM

RISERS

8" FIRE

SERVICE MAIN

DEPTH OF COVER

PER NFPA 24.

MECHANICAL RESTRAINTS

PER NFPA 24

PIPE SLEEVE THRU FLOOR

ALLOW 2" ANNULAR SPACE

THRUST BLOCK PER NFPA 24.

1" SPRINKLER PIPING FROM

SPRINKLER SYSTEM

PROVIDE PIPE

SUPPORT ALONG

WALL AS REQUIRED

TEST VALVE

NORMALLY

CLOSED

IDENTIFICATION SIGN

-3

/4

TO

F

IN

IS

H G

R

AD

E

NOTE:

SPRINKLER SYSTEM DESIGNER PROVIDE AS SHOWN FOR EACH SYSTEM.

PROVIDE SCH. 40 STEEL PIPE SLEEVE

WHERE PIPING PASSES THRU WALL.

CAULK ANNULAR SPACE IN A SMOKE

TIGHT MANNER.

45 DEG ELBOW

SMOOTH BORE CORROSION

RESISTANT OUTLET GIVING FLOW

EQUIVALENT TO ONE SPRINKLER

PROVIDE CONCRETE SPLASH BLOCK

TEST CONNECTION DISCHARGE

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

FI

R

E

PR

O

TE

C

TI

O N

D

ET

AI

LS

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

FP502

D . H

EN

SL

EY

SCALE: NTSFP502

FIRE SERVICE MAIN ENTRANCE1

SCALE: NTSFP502

TYPICAL INSPECTOR'S TEST CONNECTION2

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

LOCAL OPERATING CONSOLE

RADIO ALARM TRANSCEIVER

FIRE ALARM TERMINCAL CABINET

NOTIFICATION APPLIANCE POWER SUPPLY

REMOTE MICROPHONE FOR VOICE SYSTEM

FATC

LOC

NAC

ADDRESSABLE INPUT MODULE (AIM)

SPOT-TYPE HEAT DETECTOR

ADDRESSABLE OUTPUT MODULE (AOM)

H

AOM

AIM

DIGITAL ALARM COMMUNICATOR TRANSMITTER

FIRE ALARM REMOTE ANNUNCIATOR

AUTONOMOUS CONTROL UNITACU

DACT

FAA

RAT

MIC

LED-TYPE TEXT SIGNLED

FIRE/SMOKE DAMPERS

AUDIBLE/VISUAL NOTIFICATION APPLIANCE,

CEILING MOUNTED (CANDELA AS NOTED)

VISUAL NOTIFICATION APPLIANCE, CEILING MOUNTED

(CANDELA AS NOTED)

DUCT-TYPE SMOKE DETECTOR

SPOT-TYPE SMOKE DETECTOR

MANUAL FIRE ALARM BOX

VISUAL NOTIFICATION APPLIANCE, WALL

MOUNTED (CANDELA AS NOTED)

AUDIBLE/VISUAL NOTIFICATION APPLIANCE,

WALL MOUNTED (CANDELA AS NOTED)

AUDIBLE NOTIFICATION APPLIANCE, WALL MOUNTED

AUDIBLE NOTIFICATION APPLIANCE, CEILING MOUNTED

S

S

F

DH

NOTE:ALL THE SYMBOLS IN THE LEGEND MAY NOT HAVE

BEEN USED ON THE PLANS. SYMBOLS NOT LISTED IN

THE LEGEND ARE IDENTIFIED WHERE THEY OCCUR.

WATERFLOW SWITCH, VANE-TYPE, PROVIDE ASSOCIATED

INPUT MODULE

ELECTRIC WATERFLOW ALARM BELL

WF

VALVE TAMPER SWITCH, PROVIDE ASSOCIATED INPUT

MODULE

VS

POWER CIRCUIT DEDICATED TO FIRE ALARM SYSTEM

EQUIPMENT

ELECTROMAGNETIC DOOR HOLDER

WATERFLOW SWITCH, PRESSURE-TYPE, PROVIDE

ASSOCIATED INPUT MODULE

PS

REMOTE INDICATOR AND TEST SWITCH, WALL MOUNTEDRTS

FIRE ALARM LEGENDFIRE ALARM ABBREVIATIONS GENERAL FIRE ALARM/MNS NOTES INTELLIGIBILITY

REQUIREMENTS

1. VERIFY INTELLIGIBILITY BY MEASUREMENT AFTER

INSTALLATION.

2. ENSURE THAT A CIS VALUE GREATER THAN THE

REQUIRED MINIMUM VALUE IS PROVIDED IN EACH

AREA WHERE BUILDING OCCUPANTS TYPICALLY

COULD BE FOUND. THE MINIMUM REQUIRED VALUE

IS 0.8 CIS, ALTHOUGH ROUNDING IS PERMITTED

SUCH THAT A VALUE OF 0.75 MAY BE ROUNDED TO

0.8.

3. AREAS OF THE BUILDING PROVIDED WITH HARD

WALL AND CEILING SURFACES (SUCH AS METAL OR

CONCRETE) THAT ARE FOUND TO CAUSE

EXCESSIVE SOUND REFLECTIONS MAY BE

PERMITTED TO HAVE A CIS SCORE LESS THAN THE

MINIMUM REQUIRED VALUE IF APPROVED BY THE

DOD INSTALLATION, AND IF BUILDING OCCUPANTS

IN THESE AREAS CAN DETERMINE THAT A VOICE

SIGNAL IS BEING BROADCAST AND THEY MUST

WALK NO MORE THAN 33 FT (10 m) TO FIND A

LOCATION WITH AT LEAST THE MINIMUM REQUIRED

CIS VALUE WITHIN THE SAME AREA.

4. AREAS OF THE BUILDING WHERE OCCUPANTS ARE

NOT EXPECTED TO BE NORMALLY PRESENT ARE

PERMITTED TO HAVE A CIS SCORE LESS THAN THE

MINIMUM REQUIRED VALUE IF PERSONNEL CAN

DETERMINE THAT A VOICE SIGNAL IS BEING

BROADCAST AND THEY MUST WALK NO MORE THAN

50 FT (15 m) TO A LOCATION WITH AT LEAST THE

MINIMUM REQUIRED CIS VALUE WITHIN THE SAME

AREA.

5. MEASUREMENTS SHOULD BE TAKEN NEAR THE

HEAD LEVEL APPLICABLE FOR MOST PERSONNEL IN

THE SPACE UNDER NORMAL CONDITIONS (E.G.,

STANDING, SITTING, SLEEPING, AS APPROPRIATE).

6. THE DISTANCE THE OCCUPANT MUST WALK TO THE

LOCATION MEETING THE MINIMUM REQUIRED CIS

VALUE SHALL BE MEASURED ON THE FLOOR OR

OTHER WALKING SURFACE AS FOLLOWS:

• ALONG THE CENTERLINE OF THE

NATURAL PATH OF TRAVEL, STARTING

FROM ANY POINT SUBJECT TO

OCCUPANCY WITH LESS THAN THE

MINIMUM REQUIRED CIS VALUE.

• CURVING AROUND ANY CORNERS OR

OBSTRUCTIONS, WITH A 12 IN. (300 mm)

CLEARANCE THEREFROM.

• TERMINATING DIRECTLY BELOW THE

LOCATION WHERE THE MINIMUM

REQUIRED CIS VALUE HAS BEEN

OBTAINED.

7. COMMERCIALLY AVAILABLE TEST

INSTRUMENTATION SHALL BE USED TO MEASURE

INTELLIGIBILITY AS SPECIFIED BY IEC 60849 AND IEC

60268-16. THE MEAN VALUE OF AT LEAST THREE

READINGS SHALL BE USED TO COMPUTE THE

INTELLIGIBILITY SCORE AT EACH TEST LOCATION.

FIRE ALARM & MASS NOTIFICATION CONTROL UNITFMCU 1. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATION OF

SYSTEM REQUIREMENTS WITH ALL CONDITIONS OF THE

BUILDING AND SITE INCLUDING, BUT NOT LIMITED TO, BLIND

SPACES, SHELVING, LIGHTS, GRILLES AND DIFFUSERS, PIPING,

DUCT WORK, DOORS, WINDOWS, EQUIPMENT PLATFORMS,

WALLS (FIRE RATED AND NON-FIRE-RATED), BEAMS, JOISTS,

COLUMNS, HVAC EQUIPMENT, ELECTRICAL PANELS AND

EQUIPMENT, CEILINGS, AREAS WITHOUT CEILINGS, WALL

CONSTRUCTION, FLOORS AND ALL CONSTRUCTION,

EQUIPMENT AND BUILDING APPURTENANCES.

2. A.C. POWER CONDUCTORS SUPPLYING POWER TO THE FACP,

SUBPANELS, POWER EXTENDERS, ETC. SHALL BE LABELED,

MECHANICALLY SECURED, AND RED-MARKED IN ACCORDANCE

WITH NFPA 72 § 10.6.5 (2019). A MACHINE-PRODUCED LABEL

SHALL BE PROVIDED INSIDE THE DOOR OF EACH ENCLOSURE

INDICATING THE LOCATION OF THE CIRCUIT DISCONNECTING

MEANS (PANEL LOCATION, PANEL IDENTIFICATION, AND

CIRCUIT IDENTIFICATION). COORDINATE THE LOCATION AND

QUANTITY OF DEDICATED A.C. POWER CIRCUITS WITH THE

ELECTRICAL CONTRACTOR.

3. FIRE ALARM EVACUATION SIGNAL INTELLIGIBILITY SHALL BE

TESTED UTILIZING A METHOD(S) DESCRIBED IN UFC 4-021-01

(CHANGE 1 , JAN 2010) § 4-6.1.2.

4. WITH RESPECT TO BOTH VISUAL COVERAGE AND AUDIBLE

SIGNAL INTELLIGIBILITY, THE LOCATION AND QUANTITY OF

NOTIFICATION DEVICES INDICATED ON THE FIRE PROTECTION

DESIGN DRAWINGS ARE FOR SCHEMATIC / BIDDING PURPOSES

ONLY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR

ENSURING ADEQUATE COVERAGE, REGARDLESS IF

ADDITIONAL DEVICES ARE NECESSARY.

5. END-OF-LINE DEVICES ARE NOT SHOWN AND SHALL BE

PROVIDED AS REQUIRED BY THE SYSTEM MANUFACTURER.

6. AN INTELLIGENT / ANALOG FIRE ALARM SIGNALING SYSTEM

AND INTEGRATED MASS NOTIFICATION SYSTEM SHALL BE

PROVIDED AS INDICATED. THE FIRE ALARM SYSTEM SHALL BE

SITE PROGRAMMABLE. THE SYSTEM SHALL MONITOR ALL

MANUAL PULL STATION(S), SMOKE DETECTOR(S), WATER

FLOW SWITCHES, VALVE TAMPER SUPERVISORY SWITCHES,

ETC. AND PROVIDE NOTIFICATION IN ACCORDANCE WITH THE

DRAWINGS, SPECIFICATIONS, AND APPLICABLE CODES AND

STANDARDS.

7. THE FIRE ALARM SYSTEM SHALL BE UL-LISTED FOR CENTRAL

STATION SERVICE.

8. ALL INITIATING DEVICES SHALL BE INTELLIGENT / ANALOG

WHERE POSSIBLE. SEPARATE ADDRESSABLE MONITOR

MODULES SHALL BE PROVIDED FOR EACH CONVENTIONAL

INPUT DEVICE SUCH THAT EACH DEVICE IS INDIVIDUALLY

INDICATED AT THE FACP AS A DISTINCT INPUT.

9. THE CIRCUIT CONFIGURATIONS SHALL COMPLY WITH UFC

3-600-01 AND NFPA 72 REQUIREMENTS FOR THE FOLLOWING:

9.1. THE SLC SHALL BE CLASS B

9.2. THE NAC SHALL BE CLASS B

9.3. THE IDC SHALL BE CLASS B

10. THE FIRE ALARM & MASS NOTIFICATION CONTROL UNIT SHALL

BE COMPATIBLE WITH BASE FIRE-LITE ALARM SYSTEMS.

THE FMCU SHALL BE PROVIDED WITH RADIO ALARM

TRANSMITTER (AS PRIMARY METHOD) AND A DIGITAL ALARM

COMMUNICATOR TRANSMITTER (AS SECONDARY/BACKUP

METHOD) COMMUNICATOR TO TRANSMIT DISTINCT ALARM,

SUPERVISORY, AND TROUBLE SIGNALS TO THE BASE

MONITORING STATION IN ACCORDANCE WITH BASE

STANDARDS. THE RAT AND DACT SHALL BE ABLE TO

TRANSMIT BUILDING SPECIFIC SIGNALS TO THE BASE

MONITORING STATION (E.G., TROUBLE, SUPERVISORY, AND

ALARM). THE RAT AND DACT SHALL COMMUNICATE THE

INFORMATION OVER THE PUBLIC TELEPHONE NETWORK TO A

DIGITAL ALARM COMMUNICATION RECEIVER AT THE CENTRAL

STATION AND CONNECTED TO TWO TELEPHONE LINES, WHICH

ARE NOT REQUIRED TO BE "DEDICATED" TO THE FIRE ALARM.

THE RAT SHALL BE MONACO COMPATIBLE.

11. ALL WIRES SHALL BE CHECKED FOR GROUNDS, SHORTS,

OPENS, AND CORRECT RESISTANCE, CAPACITANCE, AND

OTHER APPLICABLE PARAMETERS PRIOR TO INSTALLATION OF

DEVICES AND PRIOR TO TERMINATION OF THE CIRCUITS AT

THE FACP OR SUBPANELS.

12. ALL WIRING SHALL BE IN METALLIC CONDUIT. ALL CONDUIT

SHALL BE 3/4-IN. MINIMUM. IDENTIFY ALL CONDUCTORS

INDIVIDUALLY WITH PERMANENT MARKINGS. PAINT ALL FIRE

ALARM JUNCTION BOXES AND COVERS RED IN UNFINISHED

AREAS. ALL CONDUIT SHALL HAVE 0.75-INCH WIDE PAINTED

RED BANDS AT MINIMUM 25-FOOT INTERVALS AND ON BOTH

SIDES OF FLOOR, WALL, CEILING, SLAB PENETRATIONS.

13. PULL ALL CONDUCTORS SPLICE FREE. THE USE OF WIRE NUTS,

CRIMPED CONNECTORS, OR TWISTING OF CONDUCTORS IS

PROHIBITED. ALL TERMINATIONS MUST BE AT A TERMINAL

STRIP OR DEVICE SCREW TERMINAL. RUN ALL WIRING TO

CONTROL PANELS AND OTHER CABINETS IN THE VERTICAL OR

HORIZONTAL PLANE, MAKE ALL TURNS AT 90-DEGREE ANGLES,

AND TIGHTLY BUNDLE AND WRAP ALL WIRE. ALL WIRING MUST

BE SOLID COPPER, EXCEPT FOR SPEAKER CIRCUITS OR

CIRCUITS REQUIRING SHIELDING. ALL SLC AND IDC SHALL BE

MINIMUM 16-GAUGE. UNDER NO CIRCUMSTANCES SHALL

CONDUCTORS BE SIZED SMALLER THAN THE

MANUFACTURERS' REQUIREMENTS.

14. ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES (STROBES)

SHALL BE SYNCHRONIZED ON A MINIMUM PER-FLOOR BASIS.

ALL FIRE ALARM VISUAL NOTIFICATION APPLIANCES SHALL BE

MARKED "ALERT" AND SHALL BE PROVIDED WITH CLEAR

LENSES. ANY SUSPENDED CEILING- MOUNTED NOTIFICATION

APPLIANCES SHALL BE CENTERED IN THE TILE. CEILING-

MOUNTED NOTIFICATION APPLIANCES SHALL BE UTILIZED IN

AREAS WITH SUSPENDED TILE CEILINGS, UNO.

15. MANUAL FIRE ALARM BOXES SHALL BE FLUSH-MOUNTED IN

FINISHED AREAS AND SURFACE- MOUNTED OTHERWISE.

16. FIRE ALARM SYSTEM INPUT (MONITORING) AND OUTPUT

(CONTROL) MODULES SHALL BE LOCATED WITHIN 3 FT. OF THE

MONITORED / CONTROLLED EQUIPMENT WHERE POSSIBLE.

17. COORDINATE THE LOCATION OF CEILING MOUNTED SMOKE

DETECTORS WITH HVAC DIFFUSERS. DETECTORS SHALL NOT

BE CLOSER THAN 3 FT. TO ANY AIR SUPPLY DIFFUSER OR

RETURN AIR OPENING. SUSPENDED CEILING-MOUNTED

DETECTORS SHALL BE CENTERED IN THE TILE.

18. SYSTEM SMOKE DETECTOR HEADS SHALL NOT BE INSTALLED

UNTIL AFTER FINAL CLEAN UP BY ALL TRADES. ALL SYSTEM

SMOKE DETECTORS SHALL BE PROTECTED BY DUST COVERS

UP UNTIL THE TIME OF FINAL ACCEPTANCE TESTING.

19. LOCATE THE FA/MNS NAC POWER SUPPLIES AS NEEDED,

COORDINATE THE AC POWER FOR THE NAC POWER SUPPLIES

WITH THE ELECTRICAL CONTRACTOR.

20. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR

INSTALLATION OF ANY EXTERIOR FA/MNS NOTIFICATION

APPLIANCES.

21. FOR DUCT-TYPE SMOKE DETECTION, THE DETECTOR AND

APPROPRIATE SAMPLE TUBING SHALL BE FURNISHED BY THE

FIRE ALARM CONTRACTOR, INSTALLED IN ACCORDANCE WITH

THE MANUFACTURER'S REQUIREMENTS AND LISTING BY THE

MECHANICAL CONTRACTOR, AND CONNECTED TO THE FAS BY

THE FIRE ALARM CONTRACTOR. FOR DAMPER CLOSURE

ASSOCIATED WITH THE DETECTOR, THE OUTPUT MODULE (AND

RELAY, IF NECESSARY) SHALL BE FURNISHED, INSTALLED, AND

CONNECTED TO THE FAS BY THE FIRE ALARM CONTRACTOR;

POWER SHALL BE CONNECTED BY THE ELECTRICAL

CONTRACTOR; AND DAMPER CONNECTION SHALL BE MADE BY

THE MECHANICAL CONTRACTOR. IT SHALL BE THE

RESPONSIBILITY OF THE FAS CONTRACTOR TO ENSURE THAT

THERE IS NO DAMAGE TO THE FAS AS A RESULT OF

CONNECTION TO AC POWER.

22. T-TAPPING IN SPEAKER AND STROBE CABLES IS PROHIBITED.

ALL SPEAKER AND ALL STROBE CABLES ARE TO BE PULLED,

UN-SPLICED, FROM SPEAKER/STROBE TO SPEAKER/STROBE.

23. PROVIDE AN OUTDOOR RATED SURGE PROTECTOR FOR ANY

FIRE ALARM CIRCUIT SERVING THE EXTERIOR OF THE

BUILDING. SUCH AS THE TAMPER SWITCH FOR THE POST

INDICATOR VALVE, OR EXTERIOR NAC DEVICE SUCH AS A

SPEAKER.

24. FIRE ALARM TESTING REQUIREMENTS AS PER THE FT.

BUCHANAN FIRE DEPARTMENT.

ADS NOTIFICATION

SCHEDULE

MESSAGE

INTELLIGIBILITY

REQUIRED

MESSAGE AND

TONE AUDIBILITY

REQUIRED

VISIBLE

NOTIFICATION

REQUIRED

X

X

X

X

X

X

D

C

B

A

Z

XX

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

AR

M

Y C

O R

PS

O

F

EN

G

IN

EE

R

S

D R

AW

N

B Y:

D

ES

IG

N

ED

B

Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

C H

EC

KE

D B

Y:

AN

SI

D

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

SHEET ID

PR

O

JE

C

T N

O . 8

, P 2#

C

ER

TI

FI

ED

F

IN

AL

S U

BM

IT

TA

L

AB

BR

EV

IA

TI

O

N S, L

EG

E N

D A

N D

G

EN

ER

AL

N O

TE

S

U .S

. A R

M Y

R

ES

ER

VE

C

EN

TE

R

O

PE

R

AT

IO

N

S

BU

IL

D

IN

G

FO

R

T

BU

C H

AN

AN

, P U

ER

TO

R

IC

O

H . T

AY

LO

R

H . T

AY

LO

R

J.

R

AI

N

EY

O C

TO

B

ER

7, LO

U

IS

VI

LL

E

D

IS

TR

IC

T

LO

U I S

VI

LL

E, K

EN

TU

C

KY

FA001

D . H

EN

SL

EY

AC ALTERNATING CURRENT

ACU AUTONOMOUS CONTROL UNIT

ADS ACOUSTICALLY DISTINGUISHABLE SPACES

AED AUTOMATIC EXTERNAL DEFIBRILLATOR

AFF ABOVE FINISHED FLOOR

AIM ADDRESSABLE INPUT (MONITOR) MODULE

AMP AMPERE(S)

AMP ACOUSTICALLY DISTINGUISHABLE SPACES

AOM ADDRESSABLE OUTPUT (CONTROL) MONITOR

AWG AMERICAN WIRE GAUGE

BAS BUILDING AUTOMATION SYSTEM

BEL BELOW

BLDG BUILDING

CD CANDELA

CF CUBIC FOOT (FEET)

CKT CIRCUIT

CONT CONTINUED

CU COPPER

DC DIRECT CURRENT

DN DOWN

DPDT DOUBLE POLE DOUBLE THROW

DWG DRAWING

ELEC ELECTRIC OR ELECTRICAL

EMCS EMERGENCY MANAGEMENT CONTROL SYSTEM

FA FIRE ALARM

FA/MNS COMBINATION FIRE ALARM AND MASS

NOTIFICATION SYSTEM

FAS FIRE ALARM SYSTEM

FATC FIRE ALARM TERMINAL CABINET

FM FM GLOBAL (FACTORY MUTUAL)

FMCU FIRE ALARM & MASS NOTIFICATION CONTROL

UNIT

FT FOOT (FEET)

GND GROUND

HZ HERTZ

IBC INTERNATIONAL BUILDING CODE

IDC INITIATING DEVICE CIRCUIT

IFC INTERNATIONAL FIRE CODE

IN INCH(ES)

LCD LIQUID CRYSTAL DISPLAY

LVP LOW VOLTAGE POWER

MNS MASS NOTIFICATION SYSTEM

NAC NOTIFICATION APPLIANCE CIRCUIT

NEC NATIONAL ELECTRICAL CODE

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

PRNT PRINTER

RAT RADIO ALARM TRANSMITTER

RM ROOM

SF SQUARE FOOT (FEET)

SLC SIGNALING LINE CIRCUIT

TS TAMPER SWITCH (VALVE)

U/F UNDERFLOOR

UG UNDERGROUND

UL UNDERWRITERS' LABORATORIES

UNO UNLESS NOTED OTHERWISE

UTP UNSHIELDED TWISTED PAIR

V VOLT(S)

VAC VOLTS - ALTERNATING CURRENT

VDC VOLTS - DIRECT CURRENT

W WATT(S)

W/ WITH

W/O WITHOUT

WF WATERFLOW (ALARM) SWITCH

WP WEATHERPROOF (WEATHER RATED)

*NOTE NOT ALL ABBREVIATIONS MAY BE USED

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

JH

T

JRJH

T

10/27/2023

W

2Q R

R

_P la ns _V ol 4-

B M

S B

M S

S

F

L O

C

FAA F

F

F

F

F

FMCU

F F

F F

F

F

FLOC

L O

C

LOC

L O

C

F

F

R T

S

S

LOC

LOC

FRAT

E

AOM

AOM

E E E

AOM AOMAOM

DRINK CLOSET

SCULLERY

ELEC

CLASSROOM

CLASSROOM

CLASSROOM

CLASSROOM

MECHANICAL

T.R.

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

CAGE STORAGE

CORRIDOR

KITCHEN

CLOSET

STORAGE

VEST.

CORRIDOR

CORRIDOR

WP

WP

WP

WF

VS

C

A

D

A

C

B

WP

WP

D

WP

WP

WP

WP

WP

C

CAGE STORAGE

MECH

A

C

D

JAN

C

B

C C

A

C

C

C

CHAIR STORAGE

2 3 4 5 6 8 9 10

A

G

B

D

E

H

J

K

L

C

F F.1

E.1

2.5

E.5

ARMS VAULT

ARMORER

OFFICE

OFFICE

OFFICE

MEN'S RESTROOM

MAIN T.R.

WOMEN'S RESTROOM

CLASSROOM

CLASSROOM

DH

DH

ELECTRICAL

LED

L E

D

LED

L E

DL

E

D

L E

D

L E

D

LED

L E

D

LED

AIM

AIM

A

IM

AIM

AIM

S

115 115115

30 30

30 30

30 30

4 5

110 110

95 95 95 95

95 95 95 95

95 95

7575 75

75 75

75 75 75

AIM

AIM

AIM

L E

D 8

ASSEMBLY HALL

GRAPHIC SCALE: = 1'-0"

16' 08' 32' 48'16'

1/16"GRAPHIC SCALE: = 1'-0"

N

3 5 7 9 11 13 15 17 19

L

J

G

E

C

A

2 4 6 8 10 12 14 16 18 20

P

M

K

H

F

D

B

US Army Corps of Engineers ®

U S

A R

M Y

C O

R P

S O

F E

N G

IN

E

E R

S

D R

A W

N B

Y

D E

S

IG

N E

D B

Y

S U

B M

IT

T

E D

B Y

S

IZ

E

C H

E C

K E

D B

Y

A N

S I D

IS

S

U E

D A

T E

C O

N T

R A

C T

N O

S O

L

IC

IT

A

T

IO

N N

O

SHEET ID

P R

O J E

C T

N O

P

C E

R T

IF

IE

D F

IN

A

L S

U B

M

IT

T A

L

L E

V E

L

F

IR

E A

L A

R M

P L A

N

C O

M P

O S

IT

E

U .S

A

R M

Y R

E S

E R

V E

C E

N T

E R

O P

E R

A T

IO

N

S B

U

IL

D

IN

G F

O R

T B

U C

H A

N A

N P

U E

R T

O R

IC

O

H T

A Y

L O

R

H T

A Y

L O

R

J R

A

IN

E Y

O C

T O

B E

R

L O

U

IS

V

IL

L E

D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K

E N

T U

C K

Y

FA110

D H

E N

S L E

Y

SCALE: 1/16" = 1'-0"

FIRE ALARM PLAN - COMPOSITE

GENERAL SHEET NOTES

1 SEE SHEET FA001 FOR GENERAL NOTES, SYMBOLS, AND

LEGEND.

SHEET KEYNOTES

1 AIM FOR EMERGENCY AIR DISTRIBUTION SHUTOFF

SWITCH PANEL (PROVIDED BY MECHANICAL). SEE

MECHANICAL DRAWINGS M701. SEE FIRE ALARM MATRIX

ON SHEET FA502 FOR FURTHER INFORMATION.

2 DUCT TYPE-SMOKE DETECTOR AND REMOTE TEST

STATION FOR AHU-1 SUPPLY DUCT. TEST STATION

LOCATED NO GREATER THAN 5FT AFF AND EASILY

IDENTIFIABLE.

3 FA/MNS VISUAL NOTIFICATION APPLIANCE PROVIDED TO

AVOID FEEDBACK THROUGH THE FMCU MICROPHONE.

4 FIRE-LITE COMPATIBLE FMCU WITH INTEGRAL ACU AND

INTERNAL DACT. DACT SERVES AS SECONDARY/BACKUP

MEANS OF FA/MNS COMMUNICATION WITH BASE

CENTRAL STATION.

5…