This solicitation is for the construction of an Army Reserve Center and Area Maintenance Support Activity at Wright-Patterson Air Force Base in Ohio. The project includes construction of buildings and site work such as roadways, parking areas, and utilities. The solicitation is for a design-bid-build contract awarded by the Department of the Army Corps of Engineers Engineering District Louisville. The solicitation includes specifications divided into four volumes covering procurement requirements, general construction requirements, building systems, and cybersecurity. Products and services required include general contracting work for site preparation and construction of multiple buildings, along with associated mechanical, electrical and cybersecurity systems. The response deadline is not provided in this excerpt.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Solicitation For Area Maintenance Support Activity (AMSA)/Army Reserve Center (ARC) Wright-Patterson Air Force Base, OH
P2: 478327/418158
Design-Bid-Build
Specifications Vol. 4 of 4 Certified Final Design
15 November 2023
W912QR24R0006
ARIMS: 200A Disposition: Maintain for 15yrs after construction.
W912QR24R0006_Specs_Vol4-0000
P2# 478327 AMSA / P2# 481858 ARC
Wright Patterson Air Force Base, OH
PROJECT TABLE OF CONTENTS
VOLUME ONE:
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
00 80 00.00 06 SPECIAL PROVISIONS
APPENDIX A - CONSTRUCTION PROJECT SIGN
APPENDIX B - SUBMITTAL REGISTER
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 32 01.00 06 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29.00 06 SUSTAINABILITY REPORTING
APPENDIX A - HIGH PERFORMANCE AND SUSTAINABLE BUILDING
CHECKLISTS
APPENDIX B - LEED SCORECARDS
01 35 26.00 06 GOVERNMENT SAFETY REQUIREMENTS
01 35 43 GENERAL ENVIRONMENTAL PROTECTION REQUIREMENTS (WPAFB)
APPENDIX A - STORM WATER POLLUTION PREVENTION PLAN (SWP3)
APPENDIX B - HUFFMAN RETARDING BASIN PERMIT
APPENDIX C - ENVIRONMENTAL BASELINE SURVEY
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.15 10 RESIDENT MANAGEMENT SYSTEM CONTRACTOR MODE (RMS CM)
01 45 04.10 06 CONTRACTOR QUALITY CONTROL
01 45 35 SPECIAL INSPECTIONS
APPENDIX A - STATEMENT OF SPECIAL INSPECTIONS
APPENDIX B - SCHEDULE OF SPECIAL INSPECTIONS
01 46 00.00 06 TOTAL BUILDING COMMISSIONING
APPENDIX A - (AMSA) OWNER'S PROJECT REQUIREMENTS (OPR)
APPENDIX B - (AMSA) BASIS OF DESIGN (BOD)
APPENDIX C - (AMSA) DEMAND RESPONSE ACTION PLAN
APPENDIX D - (ARC) OWNER'S PROJECT REQUIREMENTS (OPR)
APPENDIX E - (ARC) BASIS OF DESIGN (BOD)
APPENDIX F - (ARC) DEMAND RESPONSE ACTION PLAN
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
APPENDIX A - FIELD OFFICE TRAILER FOR REFERENCE ONLYH
01 74 19 CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
01 78 23 OPERATION AND MAINTENANCE DATA
VOLUME TWO:
DIVISION 02 - EXISTING CONDITIONS
02 41 00 DEMOLITION
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
03 45 00 PRECAST ARCHITECTURAL CONCRETE
DIVISION 04 - MASONRY
04 20 00 UNIT MASONRY
DIVISION 05 - METALS
PROJECT TABLE OF CONTENTS Page 1
CERTIFIED FINAL
05 12 00 STRUCTURAL STEEL
05 21 00 STEEL JOIST FRAMING
05 30 00 STEEL DECKS
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 33 METAL LADDERS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 41 16.00 10 PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
06 61 16 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 22 00 ROOF AND DECK INSULATION
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 27 19.01 SELF-ADHERING AIR BARRIERS
07 42 13 METAL WALL PANELS
07 54 19 POLYVINYL-CHLORIDE (PVC) ROOFING
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 11 16 ALUMINUM DOORS AND FRAMES
08 14 00 WOOD DOORS
08 31 00 ACCESS DOORS AND PANELS
08 33 23 OVERHEAD COILING DOORS
08 34 59 VAULT DOORS AND DAY GATES
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 44 00 CURTAIN WALL AND GLAZED ASSEMBLIES
08 51 13 ALUMINUM WINDOWS
08 60 45 INSULATED TRANSLUCENT FIBERGLASS SKYLIGHTS AND INSULATED
TRANSLUCENT FIBERGLASS WALL PANELS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 SUPPORTS FOR GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 10 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 67 23.13 STANDARD RESINOUS FLOORING & ESD RESINOUS FLOORING
09 67 23.15 FUEL RESISTIVE RESINOUS FLOORING, 3-COAT SYSTEM
09 68 00 CARPETING
09 90 00 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 11 00 VISUAL DISPLAY UNITS
PROJECT TABLE OF CONTENTS Page 2
10 12 01.00 48 RECESSED DISPLAY CASES
10 14 00.10 EXTERIOR SIGNAGE
10 14 00.20 INTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 13.00 48 WIRE MESH PARTITIONS
10 22 39 FOLDING PANEL PARTITIONS
10 26 00 WALL AND DOOR PROTECTION
10 28 00.00 48 TOILET AND SHOWER ACCESSORIES AND COAT RACKS
10 44 13.00 48 FIRE EXTINGUISHERS, CABINETS AND WALL BRACKETS
10 51 52.00 48 METAL WARDROBE LOCKERS
10 56 13.00 48 METAL STORAGE SHELVING
10 90 00.00 48 MISCELLANEOUS SPECIALTIES (PARTIAL OMAR FUNDED)
VOLUME THREE:
DIVISION 11 - EQUIPMENT
11 46 01.00 48 KITCHEN
11 46 01.01 48 APPENDIX TO FOOD SERVICE EQUIPMENT
APPENDIX A - ARMY RESERVE KITCHEN STANDARD PRODUCT DATA
DIVISION 12 - FURNISHINGS
12 24 13 ROLLER WINDOW SHADES
12 48 13 ENTRANCE FLOOR MATS AND FRAMES
DIVISION 13 - SPECIAL CONSTRUCTION
13 34 19.01 METAL BUILDING SYSTEMS (UNHEATED STORAGE BUILDING)
13 34 19.02 METAL BUILDING SYSTEMS (AMSA WASH RACK)
DIVISION 21 - FIRE SUPPRESSION
21 13 13 WET PIPE SPRINKLER SYSTEMS, FIRE PROTECTION
21 21 03.00 10 WET CHEMICAL FIRE EXTINGUISHING SYSTEM
21 30 00 FIRE PUMPS WITH FIRE PUMP ENCLOSURE
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 31 00 WATER SOFTENERS, CATION-EXCHANGE (SODIUM CYCLE)
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 03 00.00 20 BASIC MECHANICAL MATERIALS AND METHODS
23 05 93.00 06 TESTING, ADJUSTING, AND BALANCING (TAB) OF HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 00 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 INSTRUMENTATION AND CONTROL DEVICES FOR HVAC
23 09 23.02 BACNET DIRECT DIGITAL CONTROL FOR HVAC AND OTHER BUILDING
CONTROL SYSTEMS
23 11 20 FACILITY GAS PIPING
23 23 00 REFRIGERANT PIPING
23 30 00 HVAC AIR DISTRIBUTION
23 35 16.17 10 MECHANICAL ENGINE AND WELDING FUME EXHAUST SYSTEMS
23 52 00 HEATING BOILERS
23 64 10 WATER CHILLERS, VAPOR COMPRESSION TYPE
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 80 20.00 10 GAS-FIRED HEATING EQUIPMENT
PROJECT TABLE OF CONTENTS Page 3
23 81 00 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 82 00.00 20 TERMINAL HEATING UNITS
23 82 46.00 40 ELECTRIC UNIT HEATERS
VOLUME FOUR:
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.01 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - DDC
25 05 11.02 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS -
FA/MNS SYSTEM
25 05 11.03 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - IDS
25 05 11.04 CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - AMRS
SYSTEM
25 10 10 CONTROL SYSTEM (UMCS) FRONT END INTEGRATION
DIVISION 26 - ELECTRICAL
26 08 00 APPARATUS INSPECTION AND TESTING
26 12 19.10 THREE-PHASE, LIQUID-FILLED PAD-MOUNTED TRANSFORMERS
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 24 13 SWITCHBOARDS
26 27 13.10 30 ELECTRIC METERS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING
26 56 00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 05 28.36 48 CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 PUBLIC ADDRESS SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 08 10 ELECTRONIC SECURITY SYSTEM ACCEPTANCE TESTING
28 10 05 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 70 FIRE PUMP HOUSE FIRE ALARM SYSTEM, ADDRESSABLE
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM,
ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00.00 06 EARTHWORK
31 05 22.00 06 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19.61 SEALING OF JOINTS IN RIGID PAVEMENT
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE BASE COURSE
32 11 23.23 BASE COURSE DRAINAGE LAYERS
32 12 13 BITUMINOUS TACK AND PRIME COATS
32 12 16.16 ROAD-MIX ASPHALT PAVING
32 13 13.06 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR LIGHT DUTY CONCRETE
PAVEMENTS FACILITIES
32 13 14.13 CONCRETE PAVING FOR HEAVY DUTY PAVEMENTS
PROJECT TABLE OF CONTENTS Page 4
32 15 00 AGGREGATE SURFACING
32 16 19 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 17 23 PAVEMENT MARKINGS
32 31 13 CHAIN LINK FENCES AND GATES
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
APPENDIX A - WPAFB APPROVED PLANTING LIST
DIVISION 33 - UTILITIES
33 30 00 SANITARY SEWERAGE
33 40 00 STORMWATER UTILITIES
33 46 11.53 06 BIORETENTION AREAS
33 46 16 SUBDRAINAGE PIPING
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.14 BRIDGE CRANES, OVERHEAD ELECTRIC, TOP RUNNING
DIVISION 48 - ELECTRICAL POWER GENERATION
48 14 00 SOLAR PHOTOVOLTAIC SYSTEMS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 5
SECTION TABLE OF CONTENTS
DIVISION 25 - INTEGRATED AUTOMATION
SECTION 25 05 11
CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - DDC
05/21
PART 1 GENERAL
1.1 CONTROL SYSTEM APPLICABILITY
1.2 RELATED REQUIREMENTS
1.3 REFERENCES
1.4 DEFINITIONS
1.4.1 Administrator Account
1.4.2 Computer
1.4.3 Controller
1.4.4 Mission Space
1.4.5 Network
1.4.6 Network Connected
1.4.6.1 Wireless Network Connected
1.4.7 Network Media
1.4.8 User Account Support Levels
1.4.8.1 FULLY Supported
1.4.8.2 MINIMALLY Supported
1.4.8.3 NOT Supported
1.4.9 Manual Local Input
1.4.10 Card Reader
1.4.11 User Interface
1.4.11.1 Local User Interface
1.4.11.2 Remote User Interface
1.4.11.3 Types of User Interface (by capability)
1.4.11.3.1 Read-Only User Interface
1.4.11.3.2 Limited User Interface
1.4.11.3.3 Full User Interface
1.4.11.3.4 View-Only User Interface
1.4.11.4 Other User Interface Terminology
1.4.11.4.1 Writable User Interface
1.4.11.4.2 Privileged User Interface
1.4.12 Wireless Network
1.4.13 Wired Broadcast Network
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Points of Contact
1.5.2 Coordination
1.6 SUBMITTALS
1.7 QUALITY CONTROL
1.8 CYBERSECURITY DOCUMENTATION
1.8.1 Proposed STIG and SRG Applicability Report
1.8.2 Cybersecurity Interconnection Schedule
1.8.3 Network Communication Report
1.8.4 Control System Inventory Report
1.8.5 Software and Configuration Backups
1.8.6 Cybersecurity Riser Diagram
1.8.7 STIG, SRG and Vendor Guide Compliance Result Report
SECTION 25 05 11.01 Page 1
1.8.8 Control System Cybersecurity Documentation
1.8.8.1 For HVAC Control System Devices
1.8.8.1.1 HVAC Control System Devices FULLY Supporting User
Accounts
1.8.8.1.2 All Other HVAC Control System Devices
1.8.8.2 For Lighting Control System Devices
1.8.8.2.1 Lighting Control System Devices FULLY Supporting User
Accounts
1.8.8.2.2 All Other Lighting Control System Devices
1.8.8.3 Default Requirements for Control System Devices
1.9 SOFTWARE LICENSING
1.10 CYBERSECURITY DURING CONSTRUCTION
1.10.1 Contractor Computer Equipment
1.10.1.1 Operating System
1.10.1.2 Anti-Malware Software
1.10.1.3 Passwords and Passphrases
1.10.1.4 User-Based Authentication
1.10.1.5 Demonstration of Compliance
1.10.1.6 Contractor Computer Cybersecurity Compliance Statements
1.10.2 Temporary IP Networks
1.10.2.1 Network Boundaries and Connections
1.10.3 Government Access to Network
1.10.4 Passwords and Passphrases
1.10.5 Contractor Temporary Network Cybersecurity Compliance
Statements
1.11 CYBERSECURITY DURING WARRANTY PERIOD
PART 2 PRODUCTS
2.1 ETHERNET SWITCH
2.1.1 Required Functionality
2.1.2 Configuration Requirements
2.2 DAISY CHAIN IP CONTROLLERS
PART 3 EXECUTION
3.1 CYBERSECURITY HARDENING AND CONFIGURATION GUIDES
3.2 NETWORK REQUIREMENTS
3.2.1 Non-IP Control Networks
3.2.2 IP Control Networks
3.2.2.1 IP Network Routers
3.2.2.2 IP Devices With Multiple Ethernet Connection
3.2.3 Cryptographic Protection
3.2.4 Device Identification and Authentication
3.2.4.1 For HVAC Control System Devices
3.2.4.2 For Lighting Control System Devices
3.2.4.3 Default Requirements for Control System Devices
3.2.5 Cryptographic Module Authentication
3.3 ACCESS CONTROL REQUIREMENTS
3.3.1 User Accounts
3.3.1.1 Computers
3.3.1.2 Controllers
3.3.1.2.1 HVAC Control Systems
3.3.1.2.2 Lighting Control Systems
3.3.1.2.3 Electronic Security Systems (ESS)
3.3.2 Unsuccessful Logon Attempts
3.3.2.1 Devices MINIMALLY Supporting Accounts
3.3.2.2 Devices FULLY Supporting Accounts
3.3.2.3 High Availability Interfaces Exempt from Unsuccessful
SECTION 25 05 11.01 Page 2
Logon Attempts Requirements
3.3.3 System Use Notification
3.3.3.1 System Use Notification for Remote User Interfaces
3.3.3.2 System Use Notification for Local User Interfaces
3.3.4 Permitted Actions Without Identification or Authentication
3.3.5 Enclosures
3.4 USER IDENTIFICATION AND AUTHENTICATION
3.4.1 User Identification and Authentication for All System Types
3.4.2 User Identification and Authentication for Specific System
Types
3.4.2.1 HVAC Control Systems Devices
3.4.2.2 Lighting Control Systems Devices
3.4.2.3 Electronic Security System Devices
3.4.3 User Identification and Authentication for Specific Devices
3.4.4 Implementation of Identification and Authorization Requirements
3.4.5 Password-Based Authentication Requirements
3.4.5.1 Passwords for Controllers FULLY Supporting Accounts
3.4.5.2 Passwords for Devices Minimally Supporting Accounts
3.4.5.3 Password Configuration and Reporting
3.4.6 Authenticator Feedback
3.5 CYBERSECURITY AUDITING
3.5.1 Audit Events, Content of Audit Records, and Audit Generation
3.5.1.1 Computers
3.5.1.1.1 Audited Events
3.5.1.1.2 Audit Event Information To Record
3.5.1.2 For HVAC Control System Controllers
3.5.1.2.1 HVAC Control System Controllers FULLY Supporting User
Accounts
3.5.1.2.1.1 Audited Events
3.5.1.2.1.2 Audit Event Information To Record
3.5.1.2.2 Other HVAC Control System Controllers
3.5.1.3 For Lighting Control System Controller
3.5.1.3.1 Lighting Control System Controllers FULLY Supporting
User Accounts
3.5.1.3.1.1 Audited Events
3.5.1.3.1.2 Audit Event Information To Record
3.5.1.3.2 Other Lighting Control System Controllers
3.5.1.4 Default Requirements for Control System Controllers
3.5.1.4.1 Controllers Which FULLY Support Accounts
3.5.1.4.1.1 Audited Events
3.5.1.4.1.2 Audit Event Information To Record
3.5.1.4.2 Controllers Which Do Not FULLY Support Accounts
3.5.2 Audit Time Stamps
3.5.3 Auditing Front End Software
3.5.3.1 Import and Upload Requirements
3.5.3.2 Export Requirements
3.5.4 Audit Storage Capacity and Audit Upload
3.5.4.1 Device Audit Record Upload Software
3.5.5 Response to Audit Processing Failures
3.6 REQUIREMENTS FOR LEAST FUNCTIONALITY
3.6.1 Device Capabilities
3.6.2 Software
3.7 SYSTEM AND COMMUNICATION PROTECTION
3.7.1 Collaborative Computing
3.7.2 Denial of Service Protection
3.7.2.1 Default Requirements for MODERATE Impact Control Systems
3.8 SAFE MODE AND FAIL SAFE OPERATION
3.9 SYSTEM MAINTENANCE TOOL SOFTWARE
3.10 DEVICE POWER
SECTION 25 05 11.01 Page 3
3.11 VULNERABILITY SCANNING
3.11.1 Computers and Software Running on Computers
3.11.2 Controllers
3.12 FIPS 201-2 REQUIREMENT
3.13 SYSTEM AND INTEGRATION INTEGRITY
3.13.1 Malicious Code Protection
3.14 CONTROL SYSTEM CYBERSECURITY TESTING
3.14.1 Control System Cybersecurity Testing Procedures
3.14.2 Control System Cybersecurity Testing Execution
3.14.3 Control System Cybersecurity Testing Report
3.15 FIELD QUALITY CONTROL, CYBERSECURITY VALIDATION SUPPORT
3.16 CYBERSECURITY TRAINING
-- End of Section Table of Contents --
SECTION 25 05 11.01 Page 4
SECTION 25 05 11
CYBERSECURITY FOR FACILITY-RELATED CONTROL SYSTEMS - DDC
05/21
PART 1 GENERAL
Many subparts in this Section contain text in curly braces ("{" and "}") indicating which cybersecurity control and control correlation identifier (CCI) the requirements of the subpart relate to. The text inside these curly braces is for Government reference only and enables coordination of the requirements of this Section with the RMF process throughout the design and construction process. Text in curly braces are not contractor requirements.
This Section refers to Security Requirements Guide (SRGs) and Security Technical Implementation Guide (STIGs). STIGs and SRGs are available online at the Information Assurance Support Environment (IASE) website at https://public.cyber.mil/stigs/downloads/ and an SRG/STIG Applicability Guide and Collection Tool is available at https://public.cyber.mil/stigs/SCAP/ . Not all control system components have applicable STIGs or SRGs. The "Control Systems SRG" does not apply to work performed under this Section; all requirements within this section to apply applicable SRGs DO NOT include the "Control Systems SRG".
1.1 CONTROL SYSTEM APPLICABILITY
There are multiple versions of this Section associated with this project.
Different versions have requirements applicable to different control systems. This specific Section applies only to the following control systems: DDC.
1.2 RELATED REQUIREMENTS
This section does not contain sufficient requirements to procure a control system and must be used in conjunction with other Sections which specify control systems. This Section adds cybersecurity requirements to the control systems specified in other Sections, and as these requirements are conditioned on the control system being provided, there may be requirements in this Section that will not apply to this project. All Sections containing facility-related control systems or control system components are related to the requirements of this Section. Review all specification sections to determine related requirements.
In cases where a requirement is specified in both this Section and in another Section, the more stringent requirement must be met. In cases where a requirement in this Section conflicts with the requirements of another Section such that both requirements cannot be met at the same time, request direction from the Contracting Officer Representative to
SECTION 25 05 11.01 Page 5 determine which requirement applies to the project.
1.3 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING
ENGINEERS (ASHRAE)
ASHRAE 135 (2016) BACnet—A Data Communication Protocol for Building Automation and Control Networks
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 802.1x (2010) Local and Metropolitan Area Networks - Port Based Network Access Control
NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST)
NIST FIPS 140-2 (2001) Security Requirements for Cryptographic Modules
NIST FIPS 201-2 (2013) Personal Identity Verification (PIV) of Federal Employees and Contractors
U.S. DEPARTMENT OF DEFENSE (DOD)
DODI 8551.01 (2014) Ports, Protocols, and Services Management (PPSM)
DTM 08-060 (2008) Policy on Use of Department of Defense (DoD) Information Systems - Standard Consent Banner and User Agreement
1.4 DEFINITIONS
1.4.1 Administrator Account
An administrator account is an account with full permissions to a device, application, or operating system, including the ability to create and modify other user accounts.
Note that the operating system Administrator Account may be different than Administrator Accounts for applications hosted on that operating system.
Also, most controllers will not have any support for accounts and will therefore not have an 'Aministrator Account'.
1.4.2 Computer
A computer is one of the following:
a. a device running a non-embedded desktop or server version of Microsoft Windows
SECTION 25 05 11.01 Page 6
b. a device running a non-embedded version of MacOS
c. a device running a non-embedded version of Linux
d. a device running a version or derivative of the Android Operating System, where Android is considered separate from Linux
e. a device running a version of Apple iOS
Unless otherwise indicated or clear from context use of the word "device" in this Section includes computers.
1.4.3 Controller
A device other than a computer or Ethernet switch.
1.4.4 Mission Space
A device or media is in mission space if physical access to the device or media is controlled by the organization served by the device. For example, a VAV box controller in a suspended ceiling is in mission space if the VAV box serves that room; an electrical switchgear in an electrical room or an AHU in a mechanical room or on a rooftop may still be considered to be in mission space if the organization (mission) served by that switchgear or AHU controls access to the electrical room, mechanical room or rooftop.
1.4.5 Network
A network is a group of two or more devices that can communicate using a network protocol. Network protocols must provide a method for addressing devices on the network; a communication method that does not provide an addressing scheme is not a networked form of communication. Devices that communicate using a method of communication that does not support device addressing are not using a network.
1.4.6 Network Connected
A component is network connected (or "connected to a network") only when the device has a network transceiver which is directly connected to the network and implements the network protocol. A device lacking a network transceiver (and accompanying protocol implementation) can never be considered network connected. Note that (unlike many IT definitions of "Network Connected") a device connected to a non-IP network is still considered network connected (an IP connection or IP address is not required for a device to be network connected).
1.4.6.1 Wireless Network Connected
Any device that supports wireless network communication is network connected to a wireless network, regardless of whether the device is communicating using wireless. Unless physically disabled, devices with wireless transceivers support wireless, it is not sufficient to disable the wireless in software.
SECTION 25 05 11.01 Page 7
1.4.7 Network Media
The thing that provides the communication channel between the devices on a network. Typically wire, but might include wireless, fiber optic, or even power line (some network protocols allow sending network signals over power wiring).
1.4.8 User Account Support Levels
The support for user accounts is categorized in this Section as one of three levels:
1.4.8.1 FULLY Supported
Device supports configurable individual accounts. Accounts can be created, deleted, modified, etc. Privileges can be assigned to accounts.
These devices support user-based (as opposed to role-based) authentication.
1.4.8.2 MINIMALLY Supported
Device supports a small, fixed number of accounts (perhaps only one).
Accounts cannot be modified. A device with only a "User" and an "Administrator" account would fit this category. Similarly, a device with two PINs for logon - one for restricted and one for unrestricted rights would fit here (in other words, the accounts do not have to be the traditional "username and password" structure). These devices typically only support role-based authentication.
Examples of devices which MINIMALLY support accounts are a) a variable frequency drive with a single account which requires a PIN for access to configuration; and b) a room lighting control touchpad interface that has a single account.
1.4.8.3 NOT Supported
Device does not support any Access Enforcement therefore the whole concept of "account" is meaningless.
1.4.9 Manual Local Input
Manual Local Inputs are system analog or binary inputs that are adjustable by a person but are, by intrinsic hardware design, very limited in potential capabilities. Manual Local Inputs do not have touch screens or full keyboards, but may have a few buttons or dials to allow input.
Manual Local Inputs do not have full graphic screens or dot-matrix displays, but may have simple lights (LEDs) or 7-segment displays. Manual Local Inputs do not have any sort of menu structure, each button has a single well-defined function.
Examples of Manual Local Inputs are H-O-A switches, simple thermostats, and disconnect switches.
1.4.10 Card Reader
A card reader is an input/output device whose primary function is to assist in two-factor authentication. A card reader must have an interface to read data from a card and may be able to write data to a card. A card reader may have a means (such as buttons, keypad, touchscreen, etc.) for a user to input a PIN or password, as well as a limited display.
SECTION 25 05 11.01 Page 8
1.4.11 User Interface
A User Interface (UI) is something other than a Manual Local Input or Card Reader that allows a person to interact with the system or device. Note that while a Card Reader is not by itself a User Interface, a User Interface may contain a Card Reader in order for it to authenticate its user. Within control systems, there are a wide range of User Interfaces.
Two important distinctions are 1) whether the user interface is Local or Remote, and 2) the effective capabilities of the User Interface to alter data, which is the "privilege" of the user interface (where effective privilege available to a specific user at a specific user interface is the combination of the greatest privilege offered by the user interface and the specific account the user is logged into).
1.4.11.1 Local User Interface
A Local User Interface is a user interface where the physical hardware the user interacts with (keyboard, buttons, display, etc.) is physically part of the device being affected. All of the relevant characteristics of the user interface are embodied within a single device.
Note that a Local UI may be able to access data in a different device, Local versus Remote in this context refers to the user interface itself;
the capability to access data in a different device is covered under "Full User Interface".
1.4.11.2 Remote User Interface
A Remote User Interface implements a Client/Server model where the physical hardware the user interacts with (Client) is physically distinct from the device being affected (Server). Most or all of the security and functionality characteristics of the user interface are defined by the Server, not the Client. The Client and Server communicate via a network connection. A common example of a remote user interface is a web-based interface where the browser (client) is generally on different hardware than the web server (server). A Remote UI remains a Remote UI even if the user happens to be at a Client on the same hardware as the Server. What is important is that a) the Client may be on different hardware than the Server and b) the majority of the security and functional characteristics of the interface are defined at the Server.
Note that this definition of "remote" is consistent with that generally used in the control industry but is not aligned with the NIST 800-53 definition of "Remote", which refers to "outside the system". The term "Remote" here better aligns with the NIST 800-53 definition of "Network" (remote from within the system) Access.
1.4.11.3 Types of User Interface (by capability)
User interfaces are also categorized by their capabilities as being Read Only, Limited, or Full.
1.4.11.3.1 Read-Only User Interface
A Read Only User Interface (also referred to as a View-Only User Interface) is a user interface that only allows for reading data, it does
SECTION 25 05 11.01 Page 9 not allow (have the capability to) modify data. A Read Only User Interface may be either Local or Remote. A User Interface that is configured to be Read Only (by some other means than the interface itself, such as using configuration software on a laptop) is a Read-Only Interface. Note a Read Only User Interface may have buttons (or touch screen, etc.) allowing the user to navigate through the presentation of data.
Examples of a Read Only User Interfaces are a) a publicly viewable "energy dashboard" showing weather data and energy usage within a building and b) digital wayfinding signage.
1.4.11.3.2 Limited User Interface
A Limited User Interface is a user interface that - by design - can only alter information local to the user interface. Note that the determination of "alter" includes only direct interactions, it explicitly excludes interactions that might occur as secondary effects. For example, an interface changing the flow setpoint in a pump controller is a direct interaction, the subsequent change in flow (as well as any subsequent downstream changes in valve position) are not direct interactions.
Two examples of LIMITED UIs are: a) a variable speed drive has a Limited Local User Interface which allows the user to change properties within the drive, but does not allow affecting things outside the drive; and b) a typical home WiFi Router has a Limited Remote User Interface which allows configuration of the Router, but does not allow direct interaction with other devices.
1.4.11.3.3 Full User Interface
A Full User Interface can alter information in devices outside the device with the user interface. For example, a typical Local Display Panel is a Full Local User Interface while a browser-based front end is a Full Remote User Interface.
1.4.11.3.4 View-Only User Interface
See Read-Only User Interface
1.4.11.4 Other User Interface Terminology
In addition to defining whether a user interface is a Hardware Limited, Read-Only, Limited or Full, and whether it is Local or Remote, user interfaces are classified by whether they are writable or privileged.
1.4.11.4.1 Writable User Interface
Any User Interface that is not Read-Only is Writable. (Limited User Interfaces and Full User Interfaces are both writable user interfaces (as they are capable of changing a value)).
1.4.11.4.2 Privileged User Interface
A Privileged UI is a UI that has sufficient capabilities or functionality that it requires specific cybersecurity measures to be put in place to limit its unauthorized use. Ultimately, whether a specific user interface is considered a Privileged User Interface must be determined by usage.
Unless otherwise specified, user interfaces can be determined to be
SECTION 25 05 11.01 Page 10 privileged or not using the following:
a. Read-Only User Interfaces are not privileged user interfaces.
b. Full User Interfaces are privileged user interfaces.
c. User interfaces that allow for configuration of auditing or allows for modification or deletion of audit logs are privileged user interface.
d. User interfaces that allow for reprogramming a network connected device is a privileged user interface.
f. Writeable User Interfaces in Electronic Security Systems (ESS) are privileged user interfaces.
e. Except as specified above, a Limited User Interface must be determined to be privileged or not based on the specific capabilities and use case of the user interface. In general however, user interfaces that do not offer significant capabilities above and beyond those available at that location via other means (e.g. such as a disconnect switch, breaker, or hand-off-auto switch, or physical attack) are not privileged.
1.4.12 Wireless Network
Any network that communicates without using wires or fiber optics as the communication media. Wireless networks include: WiFi, Bluetooth, ZigBee, cellular, satellite, 900 MHz radio, 2.4 GHz, free space optical, point-to-point laser, and IR.
1.4.13 Wired Broadcast Network
Wired Broadcast Networks are any network, such as powerline carrier networks and modem (wired telephony), that use wire-based technologies where there is not a clearly defined boundary for signal propagation.
1.5 ADMINISTRATIVE REQUIREMENTS
1.5.1 Points of Contact
Coordinate with the following Points of Contact as indicated in this Section and as required. Not all projects will require coordination with all Points of Contact. When coordination is required and no Point of Contact is indicated, coordinate with The Contracting Office Representative (COR).
a. Government Computer Access Point of Contact: The Contracting Office Representative (COR)
b. HTTPS Certificate Point of Contact: The Contracting Office Representative (COR)
c. Email Address Point of Contact: The Contracting Office Representative
(COR)
d. Password Point of Contact: The Contracting Office Representative (COR)
SECTION 25 05 11.01 Page 11
1.5.2 Coordination
Coordinate the execution of this Section with the execution of all other Sections related to control systems as indicated in the paragraph RELATED REQUIREMENTS. Items that must be considered when coordinating project efforts include but are not limited to:
a. If requesting permission for wireless or wired broadcast communication, the Wireless and Wired Broadcast Communication Request submittal must be approved prior to control system device selection and installation.
b. If requesting permission for alternate account lock permissions, the Device Account Lock Exception Request must be approved prior to control system device selection and installation.
c. If requesting permission for the use of a device with multiple physical connections to IP networks, the Multiple IP Connection Device Request must be approved prior to control system device selection and installation.
d. Wireless testing may be required as part of the control system testing. See requirements for the Wireless Communication Test Report submittal.
e. If the Device Audit Record Upload Software is to be installed on a computer not being provided as part of the control system, coordination is required to identify the computer on which to install the software.
f. The Cybersecurity Interconnection Schedule must be coordinated with other work that will be interconnected to, and interconnections must be approved by the Government before relying on them for system functionality.
g. Cybersecurity testing support must be coordinated across control systems and with the Government cybersecurity testing schedule.
h. Passwords must be coordinated with the indicated contact for the project site.
i. If applicable, HTTPS web server certificates must be obtained from the indicated HTTPS Certificate Point of Contact.
j. Contractor Computer Cybersecurity Compliance Statements must be provided for each contractor using contractor owned computers.
1.6 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" classification are for information only. When used, a code following the "G" classification identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals Contractor Computer Cybersecurity Compliance Statements; G
SECTION 25 05 11.01 Page 12
Contractor Temporary Network Cybersecurity Compliance Statements; G
Cybersecurity Interconnection Schedule; G
Proposed STIG and SRG Applicability Report; G
SD-02 Shop Drawings
Network Communication Report; G
Cybersecurity Riser Diagram; G
SD-03 Product Data
Control System Cybersecurity Documentation; G
SD-06 Test Reports
Control System Cybersecurity Testing Procedures; G
Control System Cybersecurity Testing Report; G
SD-07 Certificates
Software Licenses; G
SD-11 Closeout Submittals
Password Change Summary Report; G
Enclosure Keys; G
Software and Configuration Backups; G
Auditing Front End Software; G
Device Audit Record Upload Software; G
System Maintenance Tool Software; G
Control System Scanning Tools; G
STIG, SRG and Vendor Guide Compliance Result Report; G
Control System Inventory Report; G
1.7 QUALITY CONTROL
1.8 CYBERSECURITY DOCUMENTATION
{For Government Reference Only: This subpart (and its subparts) relates to PL-7; CCI-003071}
SECTION 25 05 11.01 Page 13
1.8.1 Proposed STIG and SRG Applicability Report
For each model of network connected or network infrastructure device, use the DISA SRG/STIG Applicability Guide and Collection Tool (available at https://public.cyber.mil/stigs/SCAP/ to identify applicable STIGs or SRGs and provide a report indicating applicable STIGs and SRGs for each model.
1.8.2 Cybersecurity Interconnection Schedule
{For Government Reference Only: This subpart relates to CA-3(b), PL-8, SC-7(9), SC-7(11); CCI-000258, CCI-003072, CCI-003073, CCI-003075, CCI-002398, CCI-002399, CCI-002401, CCI-002402, CCI-002403.}
Provide a completed Cybersecurity Interconnection Schedule documenting network connections between the installed system and other systems.
Provide the following information for each device directly communicating between systems: Device Identifier, Device Description, Transport layer Protocol, Network Address, Port (if applicable), MAC (Layer 2) address (if applicable), Media, Application Protocol, Service (if applicable), Descriptive Purpose of communication. For communication with other authorized systems also provide the Foreign Destination and POC for Destination. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Cybersecurity Interconnection Schedule as an editable Microsoft Excel file (a template Cybersecurity Interconnection Schedule in Excel format is available at https://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/ufgs-25-05-11
1.8.3 Network Communication Report
{For Government Reference Only: This subpart (and its subparts) relates to CA-9, PL-8; CCI-003075; CCI-002102, CCI-002103, CCI-002104, CCI-002105, CCI-003072, CCI-003073, CCI-003075 and also the submittal requirements associated with CM-6, CM-7, SC-8 and SC-41 including CM-7(3), CCI-000388. }
Provide a network communication report. For each networked device, document the communication characteristics of the device including communication protocols, services used, encryption employed, and a general description of what information is communicated over the network. For each device using IP, document all TCP and UDP ports used. For non-IP communications, document communication protocol and media used. If other control system Sections used on this project include submittals documenting this information, provide copies of those submittals to meet this requirement.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Network Communication Report as an editable Microsoft Excel file.
1.8.4 Control System Inventory Report
{For Government Reference Only: This subpart (and its subparts) relates to CM-8(a), SI-17, IA-3; CCI-000389, CCI-000392, CCI-000398, CCI-002773, CCI-002774, CCI-002775, CCI-000777, CCI-000778, CCI-001958}
SECTION 25 05 11.01 Page 14
Provide a Control System Inventory report using the Inventory Spreadsheet listed under this Section at https://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/ufgs-25-05-11 documenting all devices, including networked devices, network infrastructure devices, non-networked devices, input devices (e.g.
sensors) and output devices (e.g. actuators). For each device provide all applicable information for which there is a field on the spreadsheet in accordance with the instructions on the spreadsheet.
In addition to the requirements of Section 01 33 00 SUBMITTAL PROCEDURES, provide the Control System Inventory Report as an editable Microsoft Excel file.
1.8.5 Software and Configuration Backups
{For Government Reference Only: This subpart (and its subparts) relates to CP-10; CCI-000550, CCI-000551, CCI-000552}
For each computer on which software is installed under this project, provide a recovery image of the final as-built computer. This image must allow for bare-metal restore such that restoration of the image is sufficient to restore system operation to the imaged state without the need for re-installation of software. If additional user permissions are required to meet this requirement, coordinate the creation of the image with the identified Government Computer Access Point of Contact.
For all ethernet switches provide a backup of the switch configuration.
For all controllers, provide a backup of the controller configuration and the source code for all loaded application programs (all software that is not common to every controller of the same manufacturer and model).
If any or all of these are provided under another Section, provide documentation indicating this and referencing those submittals.
1.8.6 Cybersecurity Riser Diagram
{For Government Reference Only: This subpart (and its subparts) relates to PL-2(a), PL-8; CCI-003051, CCI-003053, CCI-003072, CCI-003073, CCI-003075}
Provide a cybersecurity riser diagram of the complete control system including all network and device hardware. If the control system specifications require a riser diagram submittal, provide a copy of that submittal as the cybersecurity riser diagram. Otherwise, provide a riser diagram in one-line format.
1.8.7 STIG, SRG and Vendor Guide Compliance Result Report
For every component (device or software) with an applicable STIG or SRG in the Proposed STIG and SRG Applicability Report, provide a result report documenting compliance with the STIG or SRG requirements. For components which are scannable by the SCAP (security content automation protocol) tool (available online at https://public.cyber.mil/stigs/scap ), provide the SCAP report and raw scan results.
For every component (device or software) with manufacturer provided cybersecurity documentation, procedure, or method for secure configuration
SECTION 25 05 11.01 Page 15 or installation, provide a report documenting how the component was configured and any deviation from the manufacturer instructions.
1.8.8 Control System Cybersecurity Documentation
{For Government Reference Only: This subpart (and its subparts) relates to SA-5 (a),(b),(c); CCIs: CCI-003124, CCI-003125, CCI-003126, CCI-003127, CCI-003128, CCI-003129, CCI-003130, CCI-003131}
Provide a Control System Cybersecurity Documentation submittal containing the indicated information for each device and software application.
1.8.8.1 For HVAC Control System Devices
1.8.8.1.1 HVAC Control System Devices FULLY Supporting User Accounts
For all HVAC Control System Devices which FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device {For Government Reference Only: relates to CCI-003124}
b. Documentation that describes secure operation of the device {For Government Reference Only: relates to CCI-003124}
c. Documentation that describes effective use and maintenance of security functions or mechanisms for the device {For Government Reference Only:
relates to CCI-003127}
d. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {For Government Reference Only: relates to CCI-003128}
e. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms; or a specific indication that there are no user-accessible security functions or mechanisms in the device {For Government Reference Only: relates to CCI-003129}
f. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {For Government Reference Only: relates to CCI-003130}
1.8.8.1.2 All Other HVAC Control System Devices
For all HVAC Control System Devices which do not FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device; or a specific indication that there are no secure configuration steps that apply {For Government Reference Only: relates to CCI-003124}
b. Documentation that describes effective use and maintenance of security functions or mechanisms for the device; or a specific indication that there are no security functions or mechanisms in the device {For Government Reference Only: relates to CCI-003127}
c. For devices which include a user interface, documentation that
SECTION 25 05 11.01 Page 16 describes methods for user interaction which enables individuals to use the device in a more secure manner {For Government Reference Only:
relates to CCI-003130}
1.8.8.2 For Lighting Control System Devices
1.8.8.2.1 Lighting Control System Devices FULLY Supporting User Accounts
For all Lighting Control System Devices which FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device {For Government Reference Only: relates to CCI-003124}
b. Documentation that describes secure operation of the device {For Government Reference Only: relates to CCI-003124}
c. Documentation that describes effective use and maintenance of security functions or mechanisms for the device {For Government Reference Only:
relates to CCI-003127}
d. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {For Government Reference Only: relates to CCI-003128}
e. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms; or a specific indication that there are no user-accessible security functions or mechanisms in the device {For Government Reference Only: relates to CCI-003129}
f. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {For Government Reference Only: relates to CCI-003130}
1.8.8.2.2 All Other Lighting Control System Devices
For all Lighting Control System Devices which do not FULLY support user accounts, provide:
a. Documentation that describes secure configuration of the device; or a specific indication that there are no secure configuration steps that apply {For Government Reference Only: relates to CCI-003124}
b. Documentation that describes effective use and maintenance of security functions or mechanisms for the device; or a specific indication that there are no security functions or mechanisms in the device {For Government Reference Only: relates to CCI-003127}
c. For devices which include a user interface, documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {For Government Reference Only:
relates to CCI-003130}
1.8.8.3 Default Requirements for Control System Devices
For control system devices where Control System Cybersecurity Documentation requirements are not otherwise indicated in this Section, provide:
SECTION 25 05 11.01 Page 17
a. Documentation that describes secure configuration of the device {For Government Reference Only: relates to CCI-003124}
b. Documentation that describes secure installation of the device {For Government Reference Only: relates to CCI-003125}
c. Documentation that describes secure operation of the device {For Government Reference Only: relates to CCI-003124}
d. Documentation that describes effective use and maintenance of security functions or mechanisms for the device {For Government Reference Only:
relates to CCI-003127}
e. Documentation that describes known vulnerabilities regarding configuration and use of administrative (i.e. privileged) functions for the device {For Government Reference Only: relates to CCI-003128}
f. Documentation that describes user-accessible security functions or mechanisms in the device and how to effectively use those security functions or mechanisms {For Government Reference Only: relates to
CCI-003129}
g. Documentation that describes methods for user interaction which enables individuals to use the device in a more secure manner {For Government Reference Only: relates to CCI-003130}
h. Documentation that describes user responsibilities in maintaining the security of the device {For Government Reference Only: relates to
CCI-003131}
1.9 SOFTWARE LICENSING
{For Government Reference Only: This subpart (and its subparts) relates to SI-2(a), SI-2(c), SI-7(14); CCI-001227, CCI-002605, CCI-002737}
For all software provided that has not already been licensed to the government or project site, provide a license to the Government for a period of no less than 5 years, and the license must also include the following software updates:
a. Security and bug-fix patches issued by the software manufacturer.
b. Security patches to address any vulnerability identified in the National Vulnerability Database at http://nvd.nist.gov with a Common Vulnerability Scoring System (CVSS) severity rating of MEDIUM or higher.
Provide a single Software Licenses submittal with documentation of the software licenses for all software provided
1.10 CYBERSECURITY DURING CONSTRUCTION
{For Government Reference Only: This subpart (and its subparts) relates to
AC-18, SA-3; CCI-000258}
In addition to the control system cybersecurity requirements indicated in
SECTION 25 05 11.01 Page 18 this section, meet following requirement throughout the construction process.
1.10.1 Contractor Computer Equipment
Contractor owned computers may be used for construction. Contractor computers connected to the control system, control system network, or a control system component at any point during construction must meet the following requirements:
1.10.1.1 Operating System
The operating system must be an operating system currently supported by the manufacturer of the operating system. The operating system must be current on security patches and operating system manufacturer required updates.
1.10.1.2 Anti-Malware Software
The computer must run anti-malware software from a reputable software manufacturer. Anti-malware software must be a version currently supported by the software manufacturer, must be current on all patches and updates, and must use the latest definitions file. Computers used on this project must be scanned using the installed software at least once per day.
1.10.1.3 Passwords and Passphrases
The passwords and passphrases for computers, applications, and web-based applications supporting passwords must be changed from their default values. Passwords must be a minimum of eight characters with a minimum of one uppercase letter, one lowercase letter, one number and one special character.
1.10.1.4 User-Based Authentication
Each user must have a unique account; sharing of a single account between multiple users is prohibited.
1.10.1.5 Demonstration of Compliance
The Government has the right to require demonstration of computer compliance with these requirements at any time during the project.
1.10.1.6 Contractor Computer Cybersecurity Compliance Statements
Provide a single submittal containing completed Contractor Computer Cybersecurity Compliance Statements for each company using contractor owned computers. Contractor Computer Cybersecurity Compliance Statements must use the template published at https://www.wbdg.org/ffc/dod/unified-facilities-guide-specifications-ufgs/ufgs-25-05-11 Each Statement must be signed by a cybersecurity representative for the relevant company.
1.10.2 Temporary IP Networks
Temporary contractor-installed IP networks may be used during construction.