W912QR24R0006_Plans-0004.pdf
PDF 3 MB Posted
- Solicitation number
- W912QR24R0006
About this file
This federal solicitation is for the design and construction of an Army Reserve Center and Area Maintenance Support Activity at Wright-Patterson Air Force Base in Ohio. The estimated construction cost is between $25-100 million. The project will be awarded through a design-bid-build delivery method. The solicitation is fully open to all offerors and requires compliance with HUBZone price evaluation preferences. The selected contractor must provide all design, construction, labor, and materials for the Army Reserve Center, Area Maintenance Support Activity building, and Vehicle Maintenance Shop. The solicitation closes on December 23, 2023, with award expected in early 2024.
View the file
Other files
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
S-202 H2
L
KJD
H1 S-301
G
MH
0'
1/
2"
/8
/8
A
B E
F1 S-510
A1 S-320
F
S-401 D11
S-401 D1
8" THICK SOG
6" THICK SOG
6" THICK SOG
6" THICK SOG
MOMENT FRAME
MOMENT FRAME
S-201 H1
S-201 A1
S-202 B2
/2
163' - 1 1/2"
20' - 9" 8' - 9 7/8" 4' - 10 1/8" 19' - 9" 2' - 4 1/16" 9' - 1 5/8" 30' - 0" 32' - 0" 23' - 4" 12' - 1 13/16"
4 4 4
4 4 4
-2' - 4"
-2' - 4"
-2' - 4"
-2' - 4"
-2' - 4"
-2' - 4"
4'
3/
4"
/2
CF50 CF60 CF60
CF60
CF60
CF50
CF50
CF50
CF50 CF60 CF60 CF50
CF50
CF50
CF50
CF50
CF50
CF40
CF60
CF60x11'
CF50
CF60
CF80
CF80
CF60
CF60 CF60
CF80CF80CF60
CF30
CF30CF60x26'
CF60x26'
CF60x26'
CF60x26'
C
G1 S-320
A1 S-321
K7 S-511
K1 S-511
K13 S-511
E1 S-511
E7 S-511
E13 S-511
0.9
4.4
N
2.1
8.9
M.2
2.8
1'
9" 7'
5"
4'
5'
0" 7'
3/ 8"
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
SJ
TYP
TYP
CF30
A1 S-301
F1 S-510
L10 S-510
F1 S-510
P2 P2
P2
P1
P1
P2
P1
P1
P2
P2
P2 P2
P1
P1
P1
P1
P1
P2
P2
P2
P2
P1
P2
P2
P2
P1
P3 P4 P4 P3
P1
P2
P2
P2
P2
P3
P4 P4
P3
P1
P1
P1
P1
P1
P1
G1 S-533
TYP @ OH DOOR
8' -6
/8
8'
-5
/8
6 6
FOUNDATION PLAN NOTES
1. ELEVATIONS SHOWN ARE TO THE TOP OF THE FOUNDATIONS
AND ARE REFERENCED FORM FINISHED FIRST FLOOR
REFERENCE ELEVATION 0'-0".
2. CENTER WALL FOOTINGS ON WALL CENTERLINE UNO.
3. CENTER SPREAD FOOTINGS ON COLUMN GRID INTERSECTION
UNO.
4. SEE SHEETS S-001 AND S-002 FOR GENERAL NOTES.
5. SEE SHEETS S-501 - S-503 FOR TYPICAL FOUNDATION DETAILS.
6. SEE SHEET S-602 FOR COLUMN SCHEDULE
7. FOUNDATION SUBGRADE MUST BE PREPARED PER THE
EARTHWORK SPECIFICATIONS.
8. SLAB ON GRADE MUST BE PLACED ON A 15 MIL VAPOR BARRIER
OVER AGGREGATE CAPILLARY BREAK PER THE EARTHWORK
SPECIFICATIONS. SEE TYPICAL DETAIL K1/S-501.
9. POUR SLAB ON GRADE OVER CONCRETE FOUNDATION STEM
WALLS AT ALL EXTERIOR DOORWAYS. REINFORCE SLAB ON
GRADE AT EXTERIOR DOORWAYS PER TYPICAL DETAIL D1/S-501.
10. REINFORCE SLAB ON GRADE AT REENTRANT CORNERS PER
TYPICAL DETAIL J14/S-501
11. .IN-FLOOR RADIANT HEATING SYSTEM SHALL BE INCLUDED IN
WORKBAY SLAB AS INDICATED ON MEP DRAWINGS,
CONTRACTOR SHALL COORDINATE W/ MEP DRAWINGS.
12. 8" NON-LOADBEARING CMU WALLS NOT SHOWN, SEE ARCH,
REINF W/ #5@48" OC VERT, SEE GENERAL NOTES FOR HORIZ.
REINFORCING.
TAG NOTES
LEGEND
REENTRANT CORNER REINFORCEMENT. SEE TYPICAL DETAIL
J14/S-501
PROVIDE THICKENED SLAB AT CMU PARTITION PER TYPICAL
DETAIL L10/S-510.
SLAB REINFORCEMENT AT DISCONTINUOUS CONTROL JOINTS.
SEE TYPICAL DETAIL L13/S-503.
TRENCH DRAIN. SLOPE SLAB TO DRAIN. DET L8/S-503.
STEEL BOLLARD. SEE ARCH DRAWINGS FOR LOCATIONS AND
TYPICAL DETAIL.
RECESSED FLOOR SLAB @ ENTRY MAT LOCATIONS,
COORINATE LOCATION W/ ARCH, COORINATE RECESS DEPTH
W/ MAT SUPPLIER
PROVIDE EQUIPMENT PADS PER DETAIL F8/S-501, COORDINATE
LOCATION W/ MEP
(-2'-0")
WF25
F40
P1
ML1
ML2
EOS
SJ
SOG
TOP OF FOOTING ELEVATION.
WALL FOOTING. SEE SCHEDULE.
SPREAD FOOTING. SEE SCHEDULE.
COLUMN PIER. SEE SHEET S-502
MASONRY LINTEL 1. SEE TYPICAL DETAIL G1/S-523
MASONRY LINTEL 2. SEE TYPICAL DETAIL G1/S-523
EDGE OF SLAB.
SAWN CONTRACTION JOINT. SEE TYPICAL DETAIL 1/S-502.
SLAB ON GRADE. SEE TYPICAL DETAIL K1/S-501. SEE PLAN FOR
REINFORCEMENT.
1 1/2"X3/16" ALUMINUM BAR GRATING.
8" CMU WALL REINF W/ #5@32" OC VERT, SEE GENERAL
NOTES FOR HORIZ. REINFORCING
CONCRETE WALL. SEE PLAN FOR THICKNESS. SEE
SECTION FOR REINFORCING.
DIAGONAL BRACING. SEE FRAMING ELEVATIONS.
MARK THICKNESS REINFORCING
6" SOG 6" #4@18" OC EW
6" RECESSED SOG 6" #4@18" OC EW
8" SOG 8" #5@12" OC EW
SLAB ON GRADE SCEDULE
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IN
AL
LO
U
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
W R
IG
H
T
PA
TT
ER
SO
N
A
IR
F O
R C
E
BA
SE
, O
H
AR
EA
M
AI
N
TE
N
AN
C
E
SU
PP
O
R T
AC
TI
VI
TY
AR
M Y
R
ES
ER
VE
C
EN
TE
R
FY
, P N
4, P
(A M
SA
P N
, P
(A R
C
O C
TO
BE
R
J.
M
AC
M
IL
LA
N
N
C :\U se rs
\h 2e dc nb f\D oc um en ts \4
7_ R ev it2
0_
S_
AM
SA
_h
2e dc nb f.r vt
/2 1/
:4
1:
P M
S-111
FO
U
N D
AT
IO
N P
LA
N
N .F
IT
C
H
N .F
I T C
H
A.
D
AL
EY
AMSA
1/8" = 1'-0"A1 FOUNDATION PLAN
POL RACKS
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
N O
V
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
D
EC
W
2Q R
R
_P la ns -0
ARIMS: 200A Disposition: Maintain for 15 yrs after construction.
JOIST BEARING 1
11' - 9 3/4"
T.O.F -2' - 4"
L K J DGM H
CRANE HOOK
24' - 0"
ABEF
W14x68 COL., TYP.
STACKED
BRACE/MOMENT
FRAME
C10x25 GIRTS @
4'-0" OC MAX, TYP
HSS5X5X3/8"
COLUMN TYP
K SERIES JOIST,
SEE PLAN
BOWSTRING JOIST, TYP. SEE PLAN
BEAM SEE PLAN TYP.
W24x94 COL., TYP. @
MOMENT FRAME
HSS12X10X3/8, TYP
JOIST BEARING 2
14' - 0 3/4"
G2 S-701
CN
BARREL BEARING
33' - 4"
M.2
S-310
S-312 K1
A1 S-301
A7 S-534
C10x25 GIRTS @
TOP OF DOOR
JOIST BEARING 1
11' - 9 3/4"
T.O.F -2' - 4"
LKJD G MH
CRANE HOOK
24' - 0"
A B E F
W14x68 COL., TYP.
STACKED
BRACE/MOMENT
FRAME
C10x25 GIRTS @ 4'-0" OC MAX, TYP
HSS5X5X3/8"
COLUMN TYP
K SERIES JOIST,
SEE PLAN
BOWSTRING JOIST, TYP. SEE PLAN
BEAM SEE PLAN TYP.
W24x94 COL., TYP. @
MOMENT FRAME
HSS12X10X3/8, TYP
JOIST BEARING 2
14' - 0 3/4"
G2 S-701
C
BARREL BEARING
33' - 4"
S-310
S-312 K7
A1 S-301
C10x25 GIRTS @ TOP OF DOOR
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
W R
IG
H
T
PA
TT
ER
SO
N
A
IR
F O
R C
E
BA
SE
, O
H
AR
EA
M
AI
N
TE
N
AN
C
E
SU
PP
O
R T
AC
TI
VI
TY
AR
M Y
R
ES
ER
VE
C
EN
TE
R
FY
, P N
4, P
(A M
SA
P N
, P
(A R
C
O C
TO
BE
R
J.
M
AC
M
IL
LA
N
C :\U se rs
\h 2e dc nb f\D oc um en ts \4
7_ R ev it2
0_
S_
AM
SA
_h
2e dc nb f.r vt
/2 1/
:4
2:
P M
S-201
FR
AM
IN
G
E
LE
VA
TI
O N
S
N . F
IT
C
H
N . F
IT
C
H
A.
D
AL
EY
AMSA
H1 NORTH ELEVATION
A1 SOUTH ELEVATION
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
D
EC
W
2Q R
R
_P la ns -0
JOIST BEARING 1
11' - 9 3/4"
T.O.F -2' - 4"
259 4
OVERHEAD DOORS
16' - 0"
CRANE HOOK
24' - 0"
112 3681011
W14x68 COL., TYP.
BRACE FRAME,
TYP
C10x25 GIRTS @ 4' - 0", TYP
W FLANGE
BEAM. SEE
PLAN
BEAM SEE PLAN TYP.
CANOPY
FRAMING
JOIST BEARING 2
14' - 0 3/4"
0.94.4
BARREL BEARING
33' - 4"
2.18.9 2.8
S-310
S-310
C10x25 GIRTS @ TOP OF
DOOR
JOIST BEARING 1
11' - 9 3/4"
T.O.F -2' - 4"
2 5 94
OVERHEAD DOORS
16' - 0"
CRANE HOOK
24' - 0"
1 123 6 8 10 11
W14x68 COL., TYP.
BRACEFRAME, TYP
C10x25, @ 4'-0" OC MAX"
HSS5X5X3/8"
COLUMN TYP K SERIES JOIST,
SEE PLAN
W FLANGE BEAM,
TYP. SEE PLAN
BEAM SEE PLAN TYP.
HSS10X6X
1/4, TYP
8" CMU WALL,
SEE PLAN
JOIST BEARING 2
14' - 0 3/4"
0.9 4.4
BARREL BEARING
33' - 4"
2.1 8.92.8
S-312 K12 S-312
D1
HIGH BAY BEYOND
US Army Corps of Engineers ®
SHEET ID
U S
AR
M
Y C
O R
PS
O
F
EN
G
IN
EE
R
S
D R
AW
N
B Y:
D
ES
IG
N
ED
B
Y:
SU
BM
IT
TE
D B
Y:
SI
ZE
C H
EC
KE
D B
Y:
AN
SI
D
IS
SU
E D
AT
E:
C O
N
TR
AC
T
N O
SO
LI
C
IT
AT
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D
AT
E M
AR
K
D
ES
C R
IP
TI
O N
Fi le
P at h:
Pl ot D at e:
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C
ER
TI
FI
ED
F
IS
VI
LL
E
D
IS
TR
IC
T
D
R . M
AR
TI
N L
U
TH
ER
K
IN
G
J R
. P
LA
C E
LO
U
IS
VI
LL
E, K Y
W R
IG
H
T
PA
TT
ER
SO
N
A
IR
F O
R C
E
BA
SE
, O
H
AR
EA
M
AI
N
TE
N
AN
C
E
SU
PP
O
R T
AC
TI
VI
TY
AR
M Y
R
ES
ER
VE
C
EN
TE
R
FY
, P N
4, P
(A M
SA
P N
, P
(A R
C
O C
TO
BE
R
J.
M
AC
M
IL
LA
N
C :\U se rs
\h 2e dc nb f\D oc um en ts \4
7_ R ev it2
0_
S_
AM
SA
_h
2e dc nb f.r vt
/2 1/
:4
2:
P M
S-202
FR
AM
IN
G
E
LE
VA
TI
O N
S
N . F
IT
C
H
N . F
IT
C
H
A.
D
AL
EY
AMSA
H2 EAST ELEVATION
B2 WEST ELEVATION
R
EV
IS
ED
IN
A C
C O
R D
AN
C
E W
IT
H
A M
EN
D
M
EN
T
D
EC
W
2Q R
R
_P la ns -0
FINISH FLOOR
0' - 0"
FINISH FLOOR
0' - 0"
INSULATED
TRANSLUCENT WALL
BASE
28' - 11"
J2
A-301
MLKJHGFEDBA
CONTINUOUS PREFINISHED
METAL CLEAT COPING (X13),
TYP.
INSULATED PRECAST
CONCRETE WALL PANEL
WITH 3" RIGID INSULATION
(R-15 MIN) (X1)
PREFINISHED METAL
CONDUCTOR HEAD (X11)
AND DOWNSPOUT (X11) TO
CONCRETE SPLASH BLOCK,
TYP.
STANDING SEAM METAL
ROOF, X10
INSULATED METAL DOOR
AND FRAME (X4), TYP. OVERHEAD COILING
DOOR/INSULATED CORE
ALUMINUM UNIT, TYP. (X8)
INSULATED METAL DOOR
AND FRAME (X4), TYP.
3" (R-19 MIN.) INSULATED
METAL PANEL (X5)
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
FORMED METAL WALL
LOUVER (X7)
L3L3L4
PREFINISHED METAL 1X14
FASCIA (X13)
SNOW GUARD RAIL (X12),
TYP.
PRE-ENGINEERED
ALUMINUM CANOPY (X6)
BOLLARD, SEE CIVIL DETAILS.
C
J1
A-512
M.2
STANDING SEAM METAL ROOF
SYSTEM (X10)
WALL MOUNTED LIGHT FIXTURE,
SEE ELECTRICAL DRAWINGS
SATS CANOPY STRUCTURE (X17),
SEE STRUCTURAL
N
METAL LADDER ANCHOR
SATS CANOPY SIDEWALL;
SEE SECTION L15/A441
FINISH FLOOR
0' - 0"
INSULATED
TRANSLUCENT WALL
BASE
28' - 11"
D2
A-301
STANDING SEAM METAL
ROOF, X10
123456789101112
CONTINUOUS PREFINISHED
METAL CLEAT COPING (X13),
TYP.
STANDING SEAM METAL
ROOF SYSTEM (X10)
INSULATED TRANSLUCENT
FIBERGLASS SANDWICH
PANEL WINDOW-WALL
SYSTEM (X9)
3" (R-19 MIN.) INSULATED
METAL PANEL (X5)
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
FORMED METAL WALL
LOUVER (X7)
A1
A-441
L10 L11
SNOW GUARD RAIL (X12),
TYP.
INSULATED PRECAST
CONCRETE WALL PANEL
WITH 3" RIGID INSULATION
(R-15 MIN) (X1)
A
2' - 11"METAL LADDER ANCHOR
SATS CANOPY STRUCTURE (X17),
SEE STRUCTURAL
2.1
BOLLARD, SEE CIVIL DETAILS.
BOLLARD, SEE CIVIL DETAILS.
PREFINISHED METAL GUTTER AND
DOWNSPOUT (X11)
0.92.84.4
1. CONTRACTOR TO COORDINATE PENETRATIONS WITH MEP DRAWINGS AND
FIELD VERIFY EXACT LOCATION & SIZE OF PENETRATIONS.
2. REFERENCE EXTERIOR FINISH SCHEDULE ON SHEET A-203 FOR EXTERIOR
MATERIALS INDICATED WITH AN (X##).
3. REFER TO SHEET A-130 FOR TYPICAL EXTERIOR ROOF SYSTEMS (ER-1, ER-2,
ER-3) AND SHEET A-311 AND A-312 FOR TYPICAL EXTERIOR WALL SYSTEMS
(EW-1 AND EW-2)
4. EXTERIOR FINISH COLORS AND MATERIALS SHALL COMPLY WITH THE
WRIGHT PATTERSON AFB INSTALLATION FACILITY STANDARDS. REFER TO
STANDARD PRODUCTS AND COLORS LISTED IN THE IFS.
5. REFER TO PRECAST CONCRETE ELEVATIONS (A-210 SERIES DRAWINGS) FOR
PRECAST PANEL DIMENSIONS AND OPENING LOCATIONS.
GENERAL NOTES - ELEVATIONS
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
A
L
O
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
J J B
\D o c u m e n ts
\4 R e v it A
A
M S
A jo h n .j .b ro c k .r v t
/2 /2
:5
:3
A
M
A-201
E X
T E
R
IO
R E
L E
V A
T
IO
N S
J B
R O
C K
J B
R O
C K
L D
U N
N
AMSA
1/8" = 1'-0"A-110
A1 SOUTH EXTERIOR ELEVATION
1/8" = 1'-0"A-110
H1 EAST EXTERIOR ELEVATION
EXTERIOR FINISH SCHEDULE
MARK COMPONENT FINISH DESCRIPTION
X1 PRECAST CONCRETE PANEL BUFF ACID ETCH FINISH; MATCH
COLOR AND FINISH OF ADJACENT
MARINE CORPS RESERVE CENTER
X2 ALUMINUM ENTRANCE DOOR AND
GLAZING
COLOR: CLEAR ANODIZED
X3 ANOD. ALUMINUM WINDOW UNITS COLOR: CLEAR ANODIZED
X4 STEEL DOORS AND FRAME FACTORY FINISH, COLOR: MATCH
INSULATED METAL WALL PANEL (X5)
X5 INSULATED METAL WALL PANEL 3" ISOLEREN ML, RIBBED PANEL,
COLOR: "SANDSTONE"
X6 CANOPIES AND SUNSHADES FACTORY FINISH, COLOR:CLEAR
ANODIZED
X7 METAL WALL LOUVER COLOR:CLEAR ANODIZED
X8 O.H. SECTIONAL DOOR / INSUL. CORE
ALUM. UNIT
FACTORY FINISH, COLOR: MATCH
INSULATED METAL WALL PANEL (X5)
X9 INSULATED TRANSLUCENT FIBERGLASS
SANDWICH PANEL WINDOW-WALL
SYSTEM
FACTORY FINISH, COLOR: BONE
WHITE #21B TRIM; CRYSTAL FACE
X10 STANDING SEAM METAL ROOF FACTORY FINISH, COLOR: METALLIC
SILVER
X11 GUTTER, DOWNSPOUT, DOWNSPOUT
BOOTS, AND CONDUCTOR HEADS
FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X12 SNOW GUARD RAIL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X13 TRIM AND FLASHING FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X14 SOFFIT PANEL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X15 SNOW GUARD RAIL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X16 NOT USED NOT USED
X17 SATS CANOPY AND WASH RACK PAINTED STRUCTURAL STEEL
COLUMN. PAINT SHALL MATCH AMSA
ROOF AND TRIM COLOR.
0 8'4' 16'
0 8'4' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
N
O V
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
W
2Q R
R
_P la ns -0
FINISH FLOOR
0' - 0"
INSULATED
TRANSLUCENT WALL
BASE
28' - 11"
D2
A-301
T.O. PARAPET
16' - 8"
A
1 2 3 4 5 6 7 8 9 10 11 12
3" (R-19 MIN.) INSULATED
METAL PANEL (X5)
INSULATED PRECAST
CONCRETE WALL PANEL
WITH 3" RIGID INSULATION
(R-15 MIN) (X1)
PREFINISHED METAL
CONDUCTOR HEAD (X11)
AND DOWNSPOUT (X11) TO
CONCRETE SPLASH BLOCK,
TYP.
ALUMINUM WINDOW, FIXED
(X3), TYP.
INSULATED TRANSLUCENT
FIBERGLASS SANDWICH
PANEL WINDOW-WALL
SYSTEM (X9)
3" (R-19 MIN.) INSULATED
METAL PANEL (X5)
ALUMINUM DOOR, FULL
GLAZED, STYLE AND RAIL
(X2)
PREFINISHED METAL 1X14
FASCIA (X13)
C
SNOW GUARD RAIL (X12),
TYP.
SNOW GUARD RAIL (X12),
TYP.
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
STANDING SEAM METAL
ROOF, X10
PRE-ENGINEERED
ALUMINUM CANOPY (X6)
PREFINISHED METAL GUTTER AND
DOWNSPOUT (X11)
2.1
BOLLARD, SEE CIVIL DETAILS.
0.9 2.8 4.4
FINISH FLOOR
0' - 0"
FINISH FLOOR
0' - 0"
INSULATED
TRANSLUCENT WALL
BASE
28' - 11"
J2
A-301
T.O. PARAPET
16' - 8"
A2
A-301
INSULATED METAL DOOR
AND FRAME (X4), TYP.
INSULATED METAL DOOR
AND FRAME (X4), TYP.
M L K J H G F E D B A
STANDING SEAM METAL
ROOF, X10
OVERHEAD COILING
DOOR/INSULATED CORE
ALUMINUM UNIT, TYP. (X8)
16' - 9 1/4" 16' - 0" 8' - 0" 24' - 0" 8' - 0" 24' - 0" 12' - 10 3/16"
3" (R-19 MIN.) INSULATED
METAL PANEL (X5)
PRE-ENGINEERED
ALUMINUM CANOPY (X6)
CONTINUOUS PREFINISHED
METAL CLEAT COPING (X13),
TYP.
PREFINISHED METAL 1X14
FASCIA (X13)
PREFINISHED METAL
GUTTER AND DOWNSPOUT
(X11)
FORMED METAL WALL
LOUVER (X7)
FORMED METAL WALL
LOUVER (X7) L2
L3 L3 L1
INSULATED PRECAST
CONCRETE WALL PANEL
WITH 3" RIGID INSULATION
(R-15 MIN) (X1)
SNOW GUARD RAIL (X12),
TYP.
FORMED METAL WALL
LOUVER (X7)
L6 L5
L7
L9L13
C
J1
A-512
M.2
WALL MOUNTED LIGHT FIXTURE,
SEE ELECTRICAL DRAWINGS
BOLLARD, SEE CIVIL
DETAILS.
SATS CANOPY
STRUCTURE(X17)
N
SATS CANOPY
SIDEWALL;
SEE SECTION L15/A441
1. CONTRACTOR TO COORDINATE PENETRATIONS WITH MEP DRAWINGS AND
FIELD VERIFY EXACT LOCATION & SIZE OF PENETRATIONS.
2. REFERENCE EXTERIOR FINISH SCHEDULE ON SHEET A-203 FOR EXTERIOR
MATERIALS INDICATED WITH AN (X##).
3. REFER TO SHEET A-130 FOR TYPICAL EXTERIOR ROOF SYSTEMS (ER-1, ER-2,
ER-3) AND SHEET A-311 AND A-312 FOR TYPICAL EXTERIOR WALL SYSTEMS
(EW-1 AND EW-2)
4. EXTERIOR FINISH COLORS AND MATERIALS SHALL COMPLY WITH THE
WRIGHT PATTERSON AFB INSTALLATION FACILITY STANDARDS. REFER TO
STANDARD PRODUCTS AND COLORS LISTED IN THE IFS.
5. REFER TO PRECAST CONCRETE ELEVATIONS (A-210 SERIES DRAWINGS) FOR
PRECAST PANEL DIMENSIONS AND OPENING LOCATIONS.
GENERAL NOTES - ELEVATIONS
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
J J B
\D o c u m e n ts
\4 R e v it A
A
M S
A jo h n .j .b ro c k .r v t
/2 /2
:0
:1
A
M
A-202
E X
T E
R
IO
R E
L E
V A
T
IO
N S
J B
R O
C K
J B
R O
C K
L D
U N
N
AMSA
1/8" = 1'-0"A-110
H1 WEST EXTERIOR ELEVATION
1/8" = 1'-0"A-110
A1 NORTH EXTERIOR ELEVATION
EXTERIOR FINISH SCHEDULE
MARK COMPONENT FINISH DESCRIPTION
X1 PRECAST CONCRETE PANEL BUFF ACID ETCH FINISH; MATCH
COLOR AND FINISH OF ADJACENT
MARINE CORPS RESERVE CENTER
X2 ALUMINUM ENTRANCE DOOR AND
GLAZING
COLOR: CLEAR ANODIZED
X3 ANOD. ALUMINUM WINDOW UNITS COLOR: CLEAR ANODIZED
X4 STEEL DOORS AND FRAME FACTORY FINISH, COLOR: MATCH
INSULATED METAL WALL PANEL (X5)
X5 INSULATED METAL WALL PANEL 3" ISOLEREN ML, RIBBED PANEL,
COLOR: "SANDSTONE"
X6 CANOPIES AND SUNSHADES FACTORY FINISH, COLOR:CLEAR
ANODIZED
X7 METAL WALL LOUVER COLOR:CLEAR ANODIZED
X8 O.H. SECTIONAL DOOR / INSUL. CORE
ALUM. UNIT
FACTORY FINISH, COLOR: MATCH
INSULATED METAL WALL PANEL (X5)
X9 INSULATED TRANSLUCENT FIBERGLASS
SANDWICH PANEL WINDOW-WALL
SYSTEM
FACTORY FINISH, COLOR: BONE
WHITE #21B TRIM; CRYSTAL FACE
X10 STANDING SEAM METAL ROOF FACTORY FINISH, COLOR: METALLIC
SILVER
X11 GUTTER, DOWNSPOUT, DOWNSPOUT
BOOTS, AND CONDUCTOR HEADS
FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X12 SNOW GUARD RAIL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X13 TRIM AND FLASHING FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X14 SOFFIT PANEL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X15 SNOW GUARD RAIL FACTORY FINISH, COLOR: MATCH SS
METAL ROOF
X16 NOT USED NOT USED
X17 SATS CANOPY AND WASH RACK PAINTED STRUCTURAL STEEL
COLUMN. PAINT SHALL MATCH AMSA
ROOF AND TRIM COLOR.
0 8'4' 16'
0 8'4' 16'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
N
O V
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
W
2Q R
R
_P la ns -0
FINISHED FLOOR
FRAME TYPE A
HOLLOW METAL
FRAME TYPE B
HOLLOW METAL
FRAME TYPE C
ALUMINUM STOREFRONT
SEE SCHEDULE
2"
2"
SEE SCHEDULE
2"
2"
2" 1' - 10" 2"
FRAME TYPE D
ALUMINUM STOREFRONT
GL-1
2"
2"
2" 1' - 10" 2"
GL-2
GL-2
SEE SCHEDULE
SEE SCHEDULE
GL-1
H7D7 H7D7
FINISHED FLOOR
DOOR TYPE N
(NARROW GLAZING)
DOOR TYPE F DOOR TYPE FG
(FULL GLAZING)
DOOR TYPE OC-2
OVERHEAD COILING
(GL-5)
SEE SCHEDULE
S E
E S
C H
E D
U L E
S E
E S
C H
E D
U L E
SEE SCHEDULE
S E
E S
C H
E D
U L E
SEE SCHEDULE
7" 4"
4" 4"
16' - 0"
DOOR TYPE OC-1
OVERHEAD COILING
(GL-5)
24' - 0"
DOOR TYPE HG
(HALF GLAZING)
S E
E S
C H
E D
U L E
SEE SCHEDULE
6" 6"
GL-2
GL-1/
GL-2
GL-2/
GL-4
1. ALL EXTERIOR DOORS SHALL BE INSULATED STEEL, U.N.O.
2. REFERENCE INTERIOR DESIGN DRAWINGS FOR DOOR AND FRAME FINISH
INFORMATION.
3. REFERENCE SPEC SECTION 08 11 13 STEEL DOORS AND FRAMES FOR FURTHER
INFORMATION REGARDING STEEL DOOR AND FRAME REQUIREMENTS.
4. REFERENCE SPEC SECTION 08 14 00 WOOD DOORS FOR FURTHER INFORMATION
REGARDING WOOD DOOR REQUIREMENTS.
5. REFERENCE SPEC SECTION 08 33 23 OVERHEAD COILING DOORS FOR FURTHER
INFORMATION REGARDING OVERHEAD COILING DOOR REQUIREMENTS.
6. REFERENCE SPEC SECTION 08 41 13 ALUMINUM FRAMED ENTRANCES AND
STOREFRONTS FOR FURTHER INFORMATION REGARDING ALUMINUM FRAMED
ENTRANCES AND STOREFRONTS.
8. REFERENCE SPEC SECTION 08 71 00 DOOR HARDWARE FOR FURTHER
INFORMATION REGARDING DOOR HARDWARE REQUIREMENTS.
GENERAL NOTES - DOORS
1. REFERENCE SPEC SECTION 08 81 00 GLAZING FOR FURTHER INFORMATION
REGARDING GLAZING REQUIREMENTS.
2. REFER TO DOOR/FRAME SCHEDULE FOR GLAZING TYPE IN DOORS AND FRAMES.
3. GLAZING TYPE SHALL BE TEMPERED (SAFETY) GLAZING AT THE FOLLOWING
LOCATIONS. LOCATIONS HAVE BEEN DENOTED ON THE WINDOW, DOOR AND FRAME
TYPES DRAWINGS.
A. ALL GLAZED DOORS
B. DOOR SIDELITES LOCATED 24" OR LESS OF VERTICAL EDGE OF THE DOOR IN
THE CLOSED POSITION.
C. ALL WINDOWS WHERE BOTTOM EDGE OF GLAZING IS LESS THAN 18" ABOVE
FLOOR AND TOP EDGE OF GLAZING IS GREATER THAN 36" ABOVE THE FLOOR.
GENERAL NOTES - GLAZING
TEMPERED (SAFETY) GLAZING
LEGEND - GLAZING
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
J J B
\D o c u m e n ts
\4 R e v it A
A
M S
A jo h n .j .b ro c k .r v t
/2 /2
:5
:0
A
M
A-611
D O
O R
/F R
A M
E S
C H
E D
U L E
A N
D T
Y P
E S
J M
A C
M
IL
L A
N
J M
U S
IA
L
L D
U N
N
AMSA
DOOR SCHEDULE
DOOR
NO.
DOOR
FIRE
RATING GLAZING
FRAME
HDW SET COMMENTS:TYPE
SINGLE/P
AIR
SIZE
MATERIAL FINISH TYPE MATERIAL FINISH
DETAILS
WIDTH HEIGHT THICKNESS HEAD JAMB SILL
001 FG SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS ALUM ANOD - GL-1 D INS ALUM ANOD K1/A-612 E1/A-612 A1/A-612 AMSA-HW-7
001A FG SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS ALUM ANOD - GL-2 C INS ALUM ANOD A7/A-613 H7/D7/A-613 L7/A-613 AMSA-HW-4
002 N SINGLE 3' - 6" 7' - 0" 0' - 1 3/4" INS MTL PNT 45 MIN GL-4 B INS MTL PNT L2/A-613 H2/A-613 - AMSA-HW-8
100 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
100A N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - GL-2 A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
101 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
101A N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - GL-2 A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
101B F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
102 N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - GL-2 A HM PNT D2/A-613 A2/A-613 - AMSA-HW-1
103 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-2
104 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-13
104A - SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT H12/A-613 L12/A-613 - - CASED OPENING
105 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-2
106 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT D2/A-613 A2/A-613 - AMSA-HW-13
106A - SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" HM PNT - - A HM PNT H12/A-613 L12/A-613 - - CASED OPENING
107A N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - GL-2 A INS MTL PNT - - - AMSA-HW-5
107B N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - GL-2 A INS MTL PNT - - - AMSA-HW-5
107C F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT 45 MIN - B INS MTL PNT L2/A-613 H2/A-613 - AMSA-HW-9
108A OC-1 - 24' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
108B OC-1 - 24' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
108C OC-2 - 16' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
108D OC-2 - 16' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
108E OC-1 - 24' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
108F OC-1 - 24' - 0" 16' - 0" 0' - 2" MFR FF - GL-5 - MFR FF K14/A-612 E14/A-612 A14/A-613 AMSA-HW-14 INSULATED DOOR AND FRAME. PROVIDE POLYCARBONATE VIEWING PANES
109A N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - GL-2 A INS MTL PNT - - - AMSA-HW-5
109B N SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - GL-2 A INS MTL PNT - - - AMSA-HW-5
110A HG PAIR 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - GL-2 B INS MTL PNT L2/A-613 H2/A-613 - AMSA-HW-11
110B F PAIR 6' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-10
113 F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-5
114 F PAIR 6' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-10
115 F PAIR 6' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-10
115A F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT 90 MIN - B INS MTL PNT L2/A-613 H2/A-613 - AMSA-HW-12
116 F PAIR 6' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-10
116A F SINGLE 3' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT 45 MIN - B INS MTL PNT L2/A-613 H2/A-613 - AMSA-HW-12
117 F PAIR 6' - 0" 7' - 0" 0' - 1 3/4" INS MTL PNT - - A INS MTL PNT K8/A-612 E8/A-612 A8/A-613 AMSA-HW-10
1/4" = 1'-0"
FRAME TYPES
1/4" = 1'-0"
DOOR TYPES
GLAZING TYPES
TYPE DESCRIPTION
GL-1 EXTERIOR INSULATED GLASS
GL-2 CLEAR GLASS
GL-3 INSULATED TRANSLUCENT FIBERGLASS PANELS SANDWICH PANEL
WINDOW-WALL SYSTEM
GL-4 FIRE RATED GLASS
GL-5 MFR STANDARD INSULATED VISION PANELS
0 4'2' 8'
0 4'2' 8'
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
W
2Q R
R
_P la ns -0
FLOOR CLEAN OUT
DOMESTIC HOT WATER
WALL CLEAN OUT
DOMESTIC COLD WATER
DOMESTIC HOT WATER CIRCULATION
SANITARY SEWER
HW
WCO
CW
HWC
SS
FCO
ABBREVIATION DESCRIPTION
VENTV
CONDENSATECD
VENT THRU ROOFVTR
COMPRESSED AIRCA
FLOOR DRAIN (DESIGNATION)FD-1
DIAMETERDIA
WATER SOFTENERWS
DOMESTIC COLD WATER
DOMESTIC HOT WATER 110°F
DOMESTIC HOT WATER RETURN
VENT
SANITARY SEWER
ABBREVIATION PLAN SYMBOLDESCRIPTION
CW
HW
HWR
V
SS
INDIRECT WASTE
(CONDENSATE)
IW
COMPRESSED AIR CA
TYPICALTYP
2" CW
2" HW
2" HWC
2" V
2" SS
2" IW
2" CA
INVERT ELEVATIONI.E. / INV. ELEV.
AMERICAN SOCIETY FOR TESTING AND MATERIALSASTM
COMPRESSED AIR STATIONCAS
CHECK VALVE
GATE VALVE
BALL VALVE
DESCRIPTION PLAN SYMBOLS
GLOBE VALVE
MIXING VALVE IN CABINET
REDUCED PRESSURE
BACKFLOW PREVENTER
IN-LINE PUMP (RECIRCULATION)
3 WAY VALVE
SANITARY CLEAN OUT
EMERGENCY EYE WASH
STATION
HOSE BIBB
FLOOR DRAIN
TRENCH DRAIN
MOISTURE SEPARATOR
(COMPRESSED AIR)
ELEVATION SYMBOLS
NOT SHOWN
NOT SHOWN
NOT SHOWN
REFIRGERATED AIR DRYER -OR- RADON PIPINGRAD
DOMESTIC HOT WATER 125°F HW (125°F)
2" HW (125°F)
EXTERIOR CLEAN OUTECO
BV BALL VALVE (A.K.A. ISOLATION VALVE OR SHUTOFF VALVE)
MV-1 THERMOSTATIC MIXING VALVE (SET TO 110°F LAVS, SINKS, AND SHOWERS)
MV-2 THERMOSTATIC MIXING VALVE (SET TO 85°F FOR EMERGENCY FIXTURES)
FILTER REGULATOR LUBRICATOR ASSEMBLYFRL
FLUID DISTRIBUTION PUMPFDP
WASTE OIL / ANTIFREEZE PUMPWOP
WASTEW
SOFTENED WATERSW
GALLONS PER MINUTEGPM
GALLONS PER FLUSHGPF
ACTIVE SOIL DEPRESSURIZATIONASD
CLEAN OUTCO
GAS (NATURAL GAS)G
GATE VALVEGV
AIR COMPRESSORC
REVOLUTIONS PER MINUTERPM
REDUCED PRESSURE ZONE BACKFLOW PREVENTERRPZ BFP
1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH
PLUMBING DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL
PLUMBING DRAWINGS WILL BE SHOWN ON THE RESPECTIVE
PLUMBING DRAWING.
2. SITE UTILITIES SHOWN ON SHEETS CU-101 THROUGH CU-504.
3. SANITARY AND VENT DRAWINGS ARE SHOWN ON SHEETS P-101
AND P-103, AND P-402.
4. HOT AND COLD DOMESTIC WATER ARE SHOWN ON SHEETS P-102
AND P-401.
5. NATURAL GAS IS SHOWN ON SHEET P-103.
6. RADON MITIGATION IS SHOWN ON SHEET P-101.
7. PLUMBING DETAILS ARE SHOWN ON SHEETS P-501 THRU P-504.
8. PLUMBING EQUIPMENT SCHEDULES ARE SHOWN ON SHEET P-601, AND
DOMESTIC HOT WATER RECIRCULATING PUMP CONTROLS ARE SHOWN
ON SHEET P-701..
9. ALL WORK SHALL BE INSTALLED PER THE DETAILS PROVIDED
REGARDLESS OF WHETHER OR NOT THE DETAILS ARE CALLED OUT
ON THE PLANS.
10. PROVIDE A COMPLETE SYSTEM OF HOT AND COLD WATER, AND
WASTE AND VENT PIPING TO ALL FIXTURES WITHIN THE BUILDING.
11. THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND
APPROVAL AS REQUIRED BY CODE AND THE REQUIREMENTS OF
APPLICABLE REGULATORY AGENCIES. REQUIRED TESTS SHALL BE
PERFORMED IN THE PRESENCE OF THE GOVERNMENT UNLESS
OTHERWISE WAIVED IN WRITING.
12. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS,
LICENSES, DOCUMENTS, AND SERVICES RELATED TO INSTALLATION
OF THE WORK.
13. FURNISH ALL LABOR, INSTALL ALL MATERIALS AND EQUIPMENT,
AND INCLUDE ALL SERVICES AND INCIDENTALS PROPER TO THE
INSTALLATIONS OF WORK INVOLVED FOR A COMPLETE AND
OPERATING FACILITY.
14. WHERE TWO OR MORE PRODUCTS OF THE SAME TYPE OF
EQUIPMENT ARE REQUIRED, THE PRODUCTS OF A SINGLE
MANUFACTURER SHALL BE USED.
15. LAYOUT OF PIPING AND EQUIPMENT IS DIAGRAMMATIC. DO NOT
SCALE DRAWINGS.
16. SEAL ALL PIPE, VENT, AND CONDUIT PENETRATIONS THROUGH THE
AIR BARRIER.
17. WATER RISERS SHALL BE INSTALLED ON THE CONDITIONED SPACE
SIDE OF THE BUILDING THERMAL INSULATION.
18. RUN ALL EXPOSED PIPING AS HIGH AS POSSIBLE UNLESS
OTHERWISE NOTED. PROVIDE ANY ADDITIONAL DROPS, RISES,
OR OFFSETS REQUIRED FOR A COMPLETE INSTALLATION.
19. COORDINATE ALL WORK WITH THE OTHER TRADES AND
OBSTRUCTIONS IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT
ARISE DUE TO THE LOCATION OF EQUIPMENT OR THE USE OF
SPACE.
20. CERTAIN ITEMS SUCH AS RISES AND DROPS IN PIPING, ACCESS
DOORS, ETC., ARE INDICATED ON THE DRAWINGS FOR CLARITY
FOR A SPECIFIC LOCATION AND SHALL NOT BE INTERPRETED AS THE
EXTENT OF THE REQUIREMENTS FOR THESE TYPES OF ITEMS.
21. ROUTING OF ALL PIPING SHALL BE COORDINATED WITH OTHER
TRADES.
22. PIPE SIZES SHALL BE CONTINUED IN THE DIRECTION OF FLOW
UNTIL ANOTHER SIZE IS SHOWN.
23. ARROWS ON PIPES INDICATE DIRECTIONS OF FLOW.
24. WATER, SOIL, WASTE, AND VENT PIPING LINES SHALL BE
CONCEALED IN THE BUILDING CONSTRUCTION, EXCEPT WHERE
INDICATED. RUN ALL HORIZONTAL PIPING ABOVE CEILING UNLESS
OTHERWISE NOTED. CONCEALED PIPING IS NOT REQUIRED IN
THE MECHANICAL ROOMS.
25. CUT OPENINGS, AS REQUIRED, IN THE CONSTRUCTION FOR THE
INSTALLATION OF PIPING AND EQUIPMENT. PATCH AND REPAIR TO
MATCH THE EXISTING ADJACENT CONSTRUCTION.
26. DO NOT INSTALL EQUIPMENT OR PIPING OVER ANY ELECTRICAL
EQUIPMENT OR ELECTRICAL SERVICE SPACE.
27. COORDINATE AND PROVIDE ALL PIPING TRANSITIONS REQUIRED
FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED EQUIPMENT.
28. SERVICE WASTE & VENT ROUGH-INS INCLUDING FLOOR DRAINS
SHOWN ARE APPROXIMATE. THE CONTRACTOR SHALL COORDINATE
THE LOCATION OF ROUGH-INS WITH THE ACTUAL EQUIPMENT OR
FIXTURES INSTALLED.
29. VERIFY ACCURACY OF ALL INVERTS AND SET DRAINAGE PIPING TO
THE INDICATED INVERTS. WHEN INVERT ELEVATIONS ARE NOT
INDICATED, HORIZONTAL DRAINAGE PIPING 3 INCHES AND LARGER
SHALL PITCH 1/8 INCH PER FOOT MINIMUM AND PIPING SMALLER
THAN 3 INCHES SHALL PITCH AT ¼ INCH PER FOOT MINIMUM.
30. PROVIDE STOP VALVES AT ALL PLUMBING FIXTURES. PROVIDE
SHUT-OFF VALVES AT ALL NEW ITEMS OF EQUIPMENT. PROVIDE
MAIN AND BRANCH SHUTOFF VALVES AS INDICATED ON THE
DRAWINGS AND AS REQUIRED BY THE SPECIFICATIONS OR
INTERNATIONAL PLUMBING CODE.
31. PROVIDE DRAIN BIBBS AT ALL LOW POINTS OR TRAPPED SECTIONS
OF WATER PIPING. PROVIDE MANUAL AIR VENTS AT ALL HIGH
POINTS AND THE ENDS OF ALL PIPING LOOPS.
32. EXTEND CONDENSATE DRAIN LINES TO NEAREST FLOOR DRAIN
OR AS INDICATED. ALL CONDENSATE DRAIN PIPING SHALL BE
PITCHED DOWN IN DIRECTION OF FLOW A MINIMUM OF 1/8" PER
FOOT.
33. DRAIN PIPING IN MECHANICAL ROOMS SHALL BE ROUTED SO AS
NOT TO CREATE TRIPPING HAZARDS.
34. ALL WALL HYDRANTS AND HOSE BIBBS SHALL BE A MINIMUM OF
1’-6” ABOVE FINISHED FLOOR, EXTERIOR GRADES, OR PAVEMENTS.
PROVIDE AN ACCESSIBLE ISOLATION VALVE NEAR EACH HOSE BIBB
AND WALL HYDRANT.
35. PROVIDE NON-CONDUCTING DIELECTRIC CONNECTIONS WHEREVER
JOINING DISSIMILAR PIPE METALS.
36. LOCATE AND SIZE 4" THICK CONCRETE HOUSEKEEPING PADS AND
CURBS TO COORDINATE WITH ACTUAL EQUIPMENT PURCHASED.
EXTEND PAD BEYOND EQUIPMENT 6" IN ALL DIRECTIONS.
37. PROVIDE CLEARANCES AROUND EQUIPMENT AS RECOMMENDED
BY MANUFACTURER. INSTALL EQUIPMENT TO FACILITATE
SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF
EQUIPMENT COMPONENTS. AS MUCH AS PRACTICAL, CONNECT
EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF
INTERFERENCE WITH OTHER INSTALLATIONS.
38. PROVIDE ACCESS PANELS FOR INSTALLATION IN WALLS AND CEILINGS,
WHERE REQUIRED, TO SERVICE CONTROLS DEVICES, VALVES, AND
OTHER CONCEALED EQUIPMENT. ACCESS PANEL INSTALLATION SHALL
BE COORDINATED WITH ARCHITECTURAL WORK TO MATCH MATERIALS
AND FINISHES.
39. MAINTAIN A MINIMUM OF 6’-8” CLEARANCE TO UNDERSIDE OF PIPES,
CONDUITS, AND SUSPENDED EQUIPMENT, ETC. THROUGHOUT ACCESS
PANEL ROUTES IN MECHANICAL ROOMS.
40. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS,
FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE
EASILY ACCESSIBLE. ALL VALVES SHALL BE INSTALLED SO THAT THE
VALVE REMAINS IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT
SIDE OF VALVE IS REMOVED. ALL BALANCING VALVES AND BUTTERFLY
VALVES SHALL BE PROVIDED WITH POSITION INDICATORS AND MAXIMUM
ADJUSTABLE STOPS (AKA MEMORY STOPS). ALL VALVES (EXCEPT
CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE BEFORE
REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.
41. MAKE PROPER PIPING CONNECTIONS TO FIXTURES AND EQUIPMENT
EVEN THOUGH BRANCH MAINS, ELBOWS AND CONNECTIONS ARE NOT
SHOWN.
42. COORDINATE WITH ARCHITECTURAL DRAWINGS BEFORE
ROUGHING-IN PLUMBING FIXTURES.
43. PROTECT COPPER PIPING AGAINST CONTACT WITH MASONRY OR
DISSIMILAR METALS, HANGERS, SUPPORTS, ANCHORS AND CLIPS
SHALL BE COPPER OR COPPER PLATED.
45. PROVIDE ALL LABOR MATERIAL AND EQUIPMENT REQUIRED FOR THE
COMPLETION AND OPERATION OF ALL SYSTEMS IN THIS SECTION OF
WORK IN ACCORDANCE WITH CONTRACT PLANS, SPECIFICATIONS AND
ALL APPLICABLE STATE AND LOCAL CODES.
46. TOP SLAB-ON-GRADE FINISH FLOOR ELEVATION ARE (0' - 0")
UNLESS OTHERWISE NOTED.
47. EQUIPMENT (PIPING, DUCTWORK, ETC.) THAT DOES NOT SERVE THE TR
SHALL NOT BE INSTALLED ABOVE OR IN THESE SPACES, NOR WILL
THIS EQUIPMENT PASS THROUGH OR ENTER THE TR.
48. ALL GAS METERS, WATER METERS, AND SUBMETERS ARE TO BE
CONNECTED TO THE AMRS NETWORK. IN ADDITION, VISUAL METER
READING METHOD IS TO BE PROVIDED. SEE MECHANICAL DRAWINGS,
SHEETS M-726 AND M-727.
49. EQUIPMENT (PIPING, DUCTWORK, MACHINERY, ETC.) THAT DOES NOT
SERVE THE TELECOMMUNICATIONS ROOM (TR) SHALL NOT BE INSTALLED
ABOVE, BELOW (E.G. IN OR UNDER SLAB) OR IN THESE
TELECOMMUNICATIONS SPACES NOR WILL THIS EQUIPMENT PASS
THROUGH OR ENTER THE TR.
50. WHERE EQUIPMENT, FIXTURES, PIPING, DUCTWORK, OR OTHER
APPURTENANCES ARE MOUNTED TO, OR SUPPORTED FROM, RATED
WALLS, PROVIDE FIRESTOPPING AT ATTACHMENT PENETRATIONS TO
MAINTAIN WALL RATING IN ACCORDANCE WITH SPEC SECTION 07 84 00
FIRESTOPPING.
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
M F
C \D o c u m e n ts
\4 R e v it P
A
M S
A H
E
D D
M F
C .r v t
/2 /2
:5
:2
P
M
P-001
P L
U M
B
IN
G L
E G
E N
D
M C
A L L A
N
M C
A L L A
N
C G
R E
E N
W E
L L
AMSA
PLUMBING ABBREVIATIONS PLUMBING SYMBOL LEGEND GENERAL NOTES
PLUMBING PIPING LEGEND
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
W
2Q R
R
_P la ns -0
AIR COMPRESSOR SCHEDULE
MARK LOCATION
AIRFLOW
(ACFM)
REMARKSTYPESYSTEM
RECEIVER
TANK
(GALLONS)
MECH RM 116 COMPRESSED
AIR
ROTARY
SCREW
PRESSURE
(PSI)
HP ELECTRICAL
(V/PH/HZ)
460/3/60120 15AC-1 1-4
REFRIGERATED AIR DRYER SCHEDULE
MARK LOCATION
AIRFLOW
(CFM @
100 PSIG)
REMARKSTYPESYSTEM
MECH RM 116 COMPRESSED
AIR
ROTARY
SCREW
MAX.
PRESSURE
(PSI)
ELECTRICAL
(V/PH/HZ)
115/1/60RAD-1 1
FLUID DISTRIBUTION PUMP SCHEDULE
DESIG. TYPE TOTAL
REQ'D
SYSTEM PUMP
RATIO
MAX. AIR
SUPPLY
PRESSURE
(PSIG)
REMARKS
FDP-1.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
TRANSMISSION
FLUID (80/90)
5:1 150
FDP-2. 1
ENGINE
COOLANT
(PROP. GLYCOL
BASED)
5:1
FDP-3.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
1 DEXRON 5:1 150
FDP-4.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
15-40 ENGINE OIL
5:1
FDP-5.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
10W OIL
5:1 150
USED OILWOP-1.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
1 1:1 100
USED
ANTIFREEZE
WOP-2.
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
1 1:1 100
DUAL- DIAPHRAGM TYPE, PROVIDE WITH
PUMP STATION INCLUDING WALL MOUNT
AND START-STOP CONTROLS
DUAL- DIAPHRAGM TYPE, PROVIDE WITH
PUMP STATION INCLUDING WALL MOUNT
AND START-STOP CONTROLS
GPM
PNEUMATIC WALL
MOUNTED
POSITIVE
DISPLACEMENT
PUMP
NOTES;
1. PUMPS SHALL BE SELECTED TO MATCH THE TANK SIZE THAT THE PUMP SERVES.
275 GALLON TANK
330 GALLON TANK
275 GALLON TANK
55 GALLON DRUM
55 GALLON DRUM
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
M F
C \D o c u m e n ts
\4 R e v it P
A
M S
A H
E
D D
M F
C .r v t
/2 /2
:1
:5
P
M
P-601
P L
U M
B
IN
G S
C H
E D
U L
E S
M C
A L L A
N
M C
A L L A
N
C G
R E
E N
W E
L L
AMSA
PLUMBING FIXTURE SCHEDULE
MARK FIXTURE DESCRIPTION MOUNTING QTY
FLOW
FIXTURE FLUSH FIXTURE PIPE SIZE FIXTURE UNITS
REMARKS
MAX WATER
FLOW
MAX VOL. PER
FLUSH WASTE CW HW WASTE CW HW
P-1 WATER CLOSET WALL 1 1.28 gal 4” 1” 4 6 0 PROVIDE AN ADJUSTABLE SINGLE OR DOUBLE FLOOR-MOUNTED WALL CARRIER.
P-1A WATER CLOSET (HANDICAP) WALL 2 1.28 gal 4” 1” 4 6 0 PROVIDE AN ADJUSTABLE SINGLE OR DOUBLE FLOOR-MOUNTED WALL CARRIER.
P-2 URINAL WALL 1 0.125 gal 2” 3/4” 2 5 0
P-3 LAVATORY (COUNTERTOP) COUNTER 2 0.35 GPM 1-1/4” 1/2” 1/2” 1 1.5 1.5
P-4 SHOWER STALL FLOOR 1 1.50 GPM 2” 1/2” 1/2” 2 1 1
P-4A SHOWER STALL FLOOR 2 1.50 GPM 2” 1/2” 1/2” 2 1 1
P-5 WATER COOLER (BI-LEVEL (2 FOUNTAINS PER FIXTURE)) WALL 1 0.27 GPM 1-1/4” 1/2” 0.5 0.25 0
P-6 SERVICE SINK FLOOR 1 1.50 GPM 2” 3/4” 3/4” 2 2.25 2.25
P-7 BREAK ROOM SINK WALL 1 0.50 GPM 1-1/2” 1/2” 1/2” 2 3 3
P-8 EMERGENCY EYE RINSE BOTTLE STATION WALL 1
P-9 HOSE BIBB WALL 9
P-10 WALL HYDRANT WALL 10 0.00 GPM 3/4" 0 1.5 0 FREEZE PROOF
P-11 EMERGENCY EYEWASH/SHOWER FLOOR / WALL 5 ROOM NUMBERS 114, 115, & 117 HAVE GRATED FLOORS; MOUNT TO, OR SUPPORT FROM, WALLS/STRUCTURE AS NEEDED.
P-12 WASH SINK FLOOR 1 2 1.5 1.5
P-14 EMERGENCY EYE/FACE WASH FLOOR / WALL 1 3.00 GPM
FLOOR DRAIN SCHEDULE
ID DESCRIPTION QTY
WASTE
NOTES
PIPE
SIZE DFU
FD-1 FLOOR DRAIN 1 3" 5 1
WATER HEATER SCHEDULE
ID DESCRIPTION
LOCATION
TYPE QTY
HEAT EXCHANGER
VOLT PH FREQ REMARKS
ROOM
NUMBER ROOM NAME
GAS BURNER CAPACITY WATERSIDE
INPUT
MIN
EFF
DESIGN FLOW
LWT
DESIGN
TEMP RISE
MIN @ 75° TEMP
RISE MAX
WH-1 CONDENSING TANKLESS GAS WATER HEATER 116 MECHANICAL INSTANTANEOUS NATURAL GAS 1 199000 Btu/h 93.0% 5.0 GPM 10 GPM 125 °F 75 °F 120 V 1 60 Hz SEE NOTES 1-5
WH-2 CONDENSING TANKLESS GAS WATER HEATER 116 MECHANICAL INSTANTANEOUS NATURAL GAS 1 199000 Btu/h 93.0% 5.0 GPM 10 GPM 125 °F 75 °F 120 V 1 60 Hz SEE NOTES 1-5
WH-3 THREE PHASE ELECTRIC TANKLESS WATER HEATER 108 REPAIR BAYS INSTANTANEOUS ELECTRIC 1 20 GPM 68 °F 18 °F 460 V 3 60 Hz 54 KW HEATER, SEE NOTE 6
WH-4 THREE PHASE ELECTRIC TANKLESS WATER HEATER 108 REPAIR BAYS INSTANTANEOUS ELECTRIC 1 20 GPM 68 °F 18 °F 460 V 3 60 Hz 54 KW HEATER, SEE NOTE 6
DOMESTIC HW CIRCULATING PUMP SCHEDULE
ID TYPE
PUMP MOTOR
FLA VOLT PH FREQ REMARKSDESIGN FLOW HEAD POWER RPM
HWCP-1 IN-LINE CENTRIFUGAL 2.2 GPM 12.0 FT 0.060 hp 1440 0.55 A 115 V 1 60 Hz 1
PLUMBING EXPANSION TANK SCHEDULE
MARK LOCATION SERVICE TYPE
MINIMUM TANK MAX.
WORKING
PRESSURE
(PSIG) NOTESVOLUME
ACCEPTANCE
VOLUME
PET-1 116 MECH DOMESTIC. HOT WATER DIAPHRAM 3.4 gal 1.2 gal 60 1
NOTES:
1. WATER HEATER RUN TIMES SHALL BE MONITORED BY THE BUILDING DDC CONTROLS.
2. WATER HEATERS SHALL BE INTERCONNECTED AND COMMUNICATE TO STAGE AND MODULATE BURNERS TO MATCH THE LOAD.
3. PROVIDE GAS REGULATOR (1 PSI TO 7 IN W.C.).
4. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT.
5. MINIMUM CAPACITY TURNDOWN 10:1.
6. WATER HEATERS (WH-3 & WH-4) EACH CONNECTED TO AND SUPPLY AN EMERGENCY SHOWER/EYEWASH FIXTURE (P-11) WITH TEPID WATER (60-90 F).
WATER SOFTENER
MARK
FLOW (GAL.)
CONT./PEAK
PRESSURE
DROP (PSI)
RESIN TANK H x
DIA. (INCHES) PIPE SIZE (IN)
RESIN VOL
(FT^3)
WATER TREATED
PER CYCLE (GAL.)
BRINE TANK H x
DIA. (INCHES) GALLONS/CYCLE
DRAIN FLOW
(GPM)
ELECTRICAL
WEIGHT (LBS)VOLTS PH AMPS
WS-1 45/65 15/25 65.2"x16" 2" 4 1500 50" x 30" 6000 8 120 1 1.5 1500
WS-2 45/65 15/25 65.2"x16" 2" 4 1500 50" x 30" 6000 8 120 1 1.5 1500
NOTES:
1. PROVIDE A SHOP FABRICATED SKID WITH ALL COMPONENTS MOUNTED, PLUMBED, AND WIRED FOR A SINGLE POINT CONNECTION FOR WATER INLET, SOFT WATER OUTLET, 1-1/2" DRAIN, ELECTRICAL AND COMMUNICATIONS.
2. PROVIDE A PROGRESSIVE FLOW DUPLEX CONTROLLER TO SEQUENCE THE RESIN (BRINE) TANK VALVES.
3. PROVIDE A DDC CONTROL INTERFACE COMPATIBLE WITH THE BUILDING MANAGEMENT SYSTEM TO PROVIDE ACCESS TO ALL DATA POINTS IN THE CONTROLLERS, TIMES, AND SEQUENCERS WITH A MINIMUM OF RESIN TANK
REGENERATION, FLOW AND SYSTEM ALARMS.
NOTES:
1. ASME, PRE-CHARGED 40PSIG, 14.0" HEIGHT X 10" DIAMETER
NOTES:
1. PROVIDE TRAP GUARD FOR ALL EMERGENCY FLOOR DRAINS.
NOTES:
1. ECM MOTOR
NOTES:
1. PROVIDE WITH INTEGRATED FLOOR MOUNTED ASME RATED TANK WITH VIBRATION ISOLATION UNDER FEET.
2. PROVIDE WITH STARTER, ALTERNATOR, PRESSURE REGULATOR AND AUTOMATIC TANK, AND NO-LOSS ELECTRONIC DRAIN.
3. DDC SHALL MONITOR ON/OFF STATUS.
4. COMPRESSOR SYSTEM SHALL BE RATED FOR CONTINUOUS DUTY CYCLE
NOTES:
1. HIGH TEMPERATURE CYCLING REFRIGERATED AIR DRYER FROM THE SAME MANUFACTURER AS THE AIR COMPRESSOR MANUFACTURER.
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
R
E V
IS
E
D I
N A
C C
O R
D A
N C
E W
IT
H
A M
E N
D M
E N
T
D
E C
W
2Q R
R
_P la ns -0
REFRIGERANT LINE SET PIPINGRL
SUPPLY AIRSA
RETURN AIRRA
CEILING RETURN GRILLE
CEILING EXHAUST GRILLE
CEILING SUPPLY DIFFUSER
VOLUME DAMPER
CEILING TRANSFER AIR GRILLE
T
A
SIDE WALL SUPPLY DIFFUSER
SIDE WALL RETURN GRILLE
DIFFUSER MARK/CFM CALLOUT
"X"
"X" CFM
FIRE DAMPER
EMERGENCY SHUTOFF SWITCH
MMOTOR OPERATED DAMPER
THERMOSTAT
T-XX
ES
FD
SSMOKE DAMPER
RH RH-XXRELATIVE HUMIDITY SENSOR
FLEXIBLE DUCT
SECTION MARKER
X-XXX
X
COMBINATION THERMOSTAT & RH SENSOR
TH-XX
PS PS-XXDIFFERENTIAL PRESSURE SENSOR
TH
MAXIMUM VENTILATION OVERRIDE BUTTON
(1-HOUR TIMER) MO
FURNACEF
REFRIGERANT LIQUID LINE (SUPPLY)
ABBREVIATION PLAN SYMBOLDESCRIPTION
RLL
REFRIGERANT SUCTION LINE
(RETURN)
RSL
1/2" RLL
3/4" RSL
HYDRONIC HOT WATER SUPPLY HWS
HYDRONIC HOT WATER RETURN HWR
2" HWS
2" HWR
DESCRIPTION PLAN SYMBOLS ABBREVIATION DESCRIPTION
DUCT MOUNTED SMOKE DETECTORDSD
DUCTLESS SPLIT SYSTEMDSS
EXHAUST AIREA
(POL) FLUID DISTRIBUTION PUMPFDP
COMBUSTION AIR (EXHAUST)FLUE
DUCTLESS SPLIT CONDENSING UNITDCU
CONDENSING UNITCU
OUTDOOR AIR OA
TRANSFER AIRTA
DIAMETERDIA
TYPICALTYP
MOTORIZED DAMPERMD
COMBUSTION AIR (SUPPLY)C/A
PETROLEUM, OIL, AND LUBRICANTSPOL
BALL VALVEBV
PENTHOUSE LOUVERPL
PRESSURE SENSOR (DUCT / BUILDING)PS - (D / B)
UNIT HEATERUH
VOLUME DAMPERVD
BOTTOM OF DUCTBOD
AIR FLOW MEASUREMENT APPARATUS / STATIONAFMA
CONCENTRIC COMBUSTION AIR / EXHAUST VENT
THROUGH ROOF (OR WALL)
C-VTR
HOT WATERHW
DUCTED RESISTANCE HEATERDEH
DIFFERENTIAL PRESSURE TRANSDUCERDPT
MANUAL OVERRIDE (SET VENTILATION RATE TO MAX FOR 1 HOUR)MO
CONDENSATE PIPING (MIN. 1/8" / 12" HORIZ. SLOPE)CD
US Army Corps of Engineers ®
SHEET ID
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
T
E D
B Y
S
IZ
E
C H
E C
K E
D B
Y
A N
S I D
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
N
3 5 7 9 11 13 15 17 19
L
J
G
E
C
A
D A
T E
M A
R K
D E
S C
R
IP
T
IO
N
F ile
P a th
P lo t D a te
2 4 6 8 10 12 14 16 18 20
P
M
K
H
F
D
B
C E
R T
IF
IE
D F
IN
U
IS
V
IL
L E
D
IS
T R
IC
T
D
R M
A R
T
IN
L U
T H
E R
K
IN
G J
R P
L A
C E
L O
U
IS
V
IL
L E
K
Y
W R
IG
H
T P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E O
H
A R
E A
M A
IN
T
E N
A N
C E
S U
P P
O R
T A
C T
IV
IT
Y A
R M
Y R
E S
E R
V E
C E
N T
E R
F Y
P
N P
A M
S A
P
N
P
A R
C
O C
T O
B E
R
J M
A C
M
IL
L A
N
C
U s e rs
\H E
D D
M F
C \D o c u m e n ts
\4 R e v it M
A
M S
A H
E
D D
M F
C .r v t
/2 /2
:5
:4
P
M
M-001
H V
A C
L E
G E
N D
M C
A L L A
N
M C
A L L A
N
C G
R E
E N
W E
L L
AMSA
MECHANICAL SYMBOL LEGEND MECHANICAL ABBREVIATIONS
1. GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH
MECHANICAL DRAWING OF THIS SET. NOTES SPECIFIC TO INDIVIDUAL
MECHANICAL DRAWINGS WILL BE SHOWN ON THE RESPECTIVE
MECHANICAL DRAWING.
2. SECTION DRAWINGS ARE ON M-300 SERIES SHEETS. ENLARGED
DRAWINGS ARE ON M-400 SERIES SHEETS. ISOMETRIC DRAWINGS ARE ON
M-900 SERIES SHEETS.
3. DETAILS ARE SHOWN ON M-500 SERIES SHEETS.
4. ALL WORK SHALL BE INSTALLED PER THE DETAILS PROVIDED
REGARDLESS OF WHETHER OR NOT THE DETAILS ARE CALLED OUT ON
THE PLANS.
5. EQUIPMENT SCHEDULES ARE SHOWN ON M-600 SERIES SHEETS.
6. CONTROL DRAWINGS ARE ON M-700 SERIES SHEETS. REQUIREMENTS
SHOWN IN THE CONTROLS DRAWINGS APPLY TO FIELD INSTALLED
CONTROLS, PACKAGED CONTROLS, AND INTERLOCKS.
7. THE MECHANICAL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
MANUFACTURER RECOMMENDATIONS , THE INTERNATIONAL MECHANICAL
CODE, AND NFPA STANDARDS AND SPECIFICATIONS.
8. THE CONTRACTOR SHALL MAKE TESTS FOR ACCEPTANCE AND APPROVAL
AS REQUIRED BY CODE AND THE REQUIREMENTS OF APPLICABLE
REGULATORY AGENCIES. REQUIRED TESTS SHALL BE PERFORMED IN THE
PRESENCE OF THE GOVERNMENT UNLESS OTHERWISE WAIVED IN
WRITING.
9. THE CONTRACTOR SHALL OBTAIN AND PAY FOR ALL PERMITS, LICENSES,
DOCUMENTS, AND SERVICES RELATED TO INSTALLATION OF THE WORK.
10. FURNISH ALL LABOR, INSTALL ALL MATERIALS AND EQUIPMENT, AND
INCLUDE ALL SERVICES AND INCIDENTALS PROPER TO THE
INSTALLATIONS OF WORK INVOLVED FOR A COMPLETE AND OPERATING
FACILITY.
11. WHERE TWO OR MORE PRODUCTS OF THE SAME TYPE OF EQUIPMENT
ARE REQUIRED, THE PRODUCTS OF A SINGLE MANUFACTURER SHALL BE
USED.
12. ROOF PENETRATIONS SHALL NOT VOID OR DIMINISH THE ROOF AND
ASSOCIATED MATERIAL WARRANTIES.
13. LAYOUT OF PIPING AND DUCTWORK IS DIAGRAMMATIC. DO NOT SCALE
DRAWINGS. RUN ALL EXPOSED PIPING AND DUCTWORK AS HIGH AS
POSSIBLE UNLESS OTHERWISE NOTED. PROVIDE ANY ADDITIONAL
DROPS, RISES, OR OFFSETS REQUIRED FOR A COMPLETE INSTALLATION.
14. SEAL ALL PIPE, DUCT, VENT, AND CONDUIT PENETRATIONS THROUGH THE
AIR BARRIER.
15. COORDINATE ALL WORK WITH THE OTHER TRADES AND OBSTRUCTIONS
IN ORDER TO RESOLVE ANY CONFLICT THAT MIGHT ARISE DUE TO THE
LOCATION OF EQUIPMENT OR THE USE OF SPACE.
16. PIPE AND DUCT SIZES SHALL BE CONTINUED IN THE DIRECTION OF FLOW
UNTIL ANOTHER SIZE IS SHOWN.
17. ARROWS ON DUCTS AND PIPES INDICATE DIRECTIONS OF FLOW.
18. RUN ALL HORIZONTAL PIPING AND DUCTWORK ABOVE CEILING UNLESS
OTHERWISE NOTED.
19. DUCTWORK SIZES ARE INSIDE CLEAR DIMENSIONS.
20. CUT OPENINGS, AS REQUIRED, IN THE CONSTRUCTION FOR THE
INSTALLATION OF PIPING, DUCTWORK, AND EQUIPMENT. PATCH AND
REPAIR TO MATCH THE EXISTING ADJACENT CONSTRUCTION AND TO
MAINTAIN THE RATING OF CONSTRUCTION. THE ANNULAR SPACE OF ALL
PENETRATIONS SHALL BE FILLED WITH AN APPROVED MATERIAL IN
COMPLIANCE WITH UL ASSEMBLY REQUIREMENTS OR SOUND
TRANSMISSION CLASS REQUIREMENTS.
21. MAKE DUCT PENETRATIONS OF ALL WALLS WITH SHEET METAL DUCTS.
FLEXIBLE DUCT PENETRATIONS OF WALLS ARE NOT ACCEPTABLE.
22. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT
LOCATION OF DIFFUSERS, REGISTERS, AND GRILLES.
23. ALL ELBOWS IN DUCTWORK SHALL BE RADIUS ELBOWS UNLESS
OTHERWISE NOTED. WHERE SQUARE ELBOWS ARE SHOWN, INSTALL
TURNING VANES.
24. DO NOT INSTALL EQUIPMENT, PIPING OR DUCTWORK OVER ANY
ELECTRICAL EQUIPMENT OR ELECTRICAL SERVICE SPACE.
25. LOCATE THERMOSTATS 54" ABOVE FINISHED FLOOR OR AS NOTED ON
THE PLANS.
26. DUCTS TO DIFFUSERS, REGISTERS, AND GRILLES SHALL BE SAME SIZE AS
DIFFUSER NECK UNLESS OTHERWISE NOTED.
27. FLEX DUCT SHALL NOT BE MORE THAN 5-FT IN LENGTH AND SHALL BE
INSTALLED FREE OF KINKS AND ABRUPT TURNS. MAXIMUM UNSUPPORTED
LENGTH SHALL BE 3-FT. FLEXIBLE DUCT SHALL NOT BE USED IN RETURN
AND EXHAUST SYSTEMS.
GENERAL NOTES
28. PROVIDE VOLUME DAMPER WITH LOCKING QUADRANT AT ALL DUCT
RUNOUT TO DIFFUSERS OR GRILLES AND AT ANY OTHER LOCATION
NECESSARY TO BALANCE THE AIRSIDE SYSTEM TO THE AIR FLOW RATES
SHOWN. PROVIDE STAND-OFF LOCKING QUADRANT STEM WHERE
INSULATION IS TO BE INSTALLED ON THE DUCTWORK.
29. PROVIDE DYNAMIC FIRE DAMPERS IN ACCORDANCE WITH THEIR U.L.
LISTING AND THE REQUIREMENTS OF NFPA-90A.
30. COORDINATE AND PROVIDE ALL DUCT AND PIPING TRANSITIONS
REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED
EQUIPMENT..
31. LOCATE AND SIZE 6" THICK CONCRETE HOUSEKEEPING PADS AND CURBS
TO COORDINATE WITH ACTUAL EQUIPMENT PURCHASED. EXTEND PAD
BEYOND EQUIPMENT 6" IN ALL DIRECTIONS.
32. BOTTOM OF OUTDOOR AIR INTAKE LOUVERS SHALL BE LOCATED A
MINIMUM 10'-0" ABOVE FINISHED FLOOR.
33. PROVIDE LOW-LEAKAGE DAMPERS AT ALL OUTSIDE AIR, RELIEF AIR, AND
EXHAUST AIR CONNECTIONS TO THE EXTERIOR. LOW-LEAKAGE DAMPERS
SHALL HAVE A MAXIMUM LEAKAGE OF 3 CFM/SF WITH A DIFFERENTIAL
PRESSURE OF 1 INCH OF WATER GAUGE ACROSS THE DAMPER.
34. ALL EQUIPMENT 31 LBS OR MORE INSTALLED OVERHEAD SHALL BE
BRACED TO WITHSTAND FORCES OF 0.5 TIMES THE EQUIPMENT RATE IN
THE HORIZONTAL DIRECTION AND 1.5 TIMES THE EQUIPMENT RATE IN THE
VERTICAL DIRECTION.
35. PROVIDE CLEARANCES AROUND EQUIPMENT AS RECOMMENDED BY
MANUFACTURER. EQUIPMENT SHALL BE INSTALLED TO ALLOW FILTERS,
COILS, AND TUBES FULL CLEARANCE SPACE TO BE REMOVED WITHOUT
CUTTING OR REMOVAL OF EXISTING ADJACENT EQUIPMENT, WALLS,
ROOF, OR STRUCTURE. INSTALL MECHANICAL EQUIPMENT TO FACILITATE
SERVICING, MAINTENANCE, AND REPAIR OR REPLACEMENT OF
EQUIPMENT COMPONENTS. AS MUCH AS PRACTICAL, CONNECT
EQUIPMENT FOR EASE OF DISCONNECTING, WITH A MINIMUM OF
INTERFERENCE WITH OTHER INSTALLATIONS.
36. PROVIDE ACCESS PANELS FOR INSTALLATION IN DUCTWORK, WALLS, AND
CEILINGS, WHERE REQUIRED, TO SERVICE CONTROLS DEVICES,
DAMPERS, VALVES, DUCTWORK, SMOKE DETECTORS, AND OTHER
CONCEALED MECHANICAL EQUIPMENT. ACCESS PANEL INSTALLATION
SHALL BE COORDINATED WITH ARCHITECTURAL WORK TO MATCH
MATERIALS AND FINISHES.
37. MAINTAIN A MINIMUM OF 6’-8” CLEARANCE TO UNDERSIDE OF PIPES,
DUCTS, CONDUITS, SUSPENDED EQUIPMENT, ETC. IN MECHANICAL
ROOMS.
38. INSTALL PIPING SO THAT ALL VALVES, STRAINERS, UNIONS, TRAPS,
FLANGES, AND OTHER APPURTENANCES REQUIRING ACCESS ARE EASILY
ACCESSIBLE. ALL VALVES SHALL BE INSTALLED SO THAT THE VALVE
REMAINS IN SERVICE WHEN EQUIPMENT OR PIPING ON EQUIPMENT SIDE
OF VALVE IS REMOVED. ALL BALANCING VALVES AND BUTTERFLY VALVES
SHALL BE PROVIDED WITH POSITION INDICATORS AND MAXIMUM
ADJUSTABLE STOPS (AKA MEMORY STOPS). ALL VALVES (EXCEPT
CONTROL VALVES) AND STRAINERS SHALL BE FULL SIZE OF PIPE BEFORE
REDUCING SIZE TO MAKE CONNECTIONS TO EQUIPMENT AND CONTROLS.
39. ALL CONTROL WIRING EXCEPT IN EQUIPMENT ROOMS SHALL BE RUN
CONCEALED. WIRING IN WALLS SHALL BE IN CONDUIT. CONTROL WIRING
IN EXPOSED AREAS SHALL BE BUNDLED AND SECURED OR RUN IN
CONDUIT. CONTROL WIRING IN MECHANICAL ROOMS SHALL BE RUN IN
CONDUIT. NO WIRING SHALL BE SURFACE MOUNTED IN FINISHED SPACES.
ALL ELECTRICAL WORK SHALL BE IN ACCORDANCE WITH NATIONAL
ELECTRICAL CODE. ALL WIRING SHALL BE PLENUM RATED.
40. COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS WITH ELECTRICAL
DRAWINGS.
41. EXTEND CONDENSATE DRAIN LINES TO NEAREST FLOOR DRAIN OR AS
INDICATED. ALL CONDENSATE DRAIN PIPING SHALL BE TRAPPED AND
PITCHED DOWN IN DIRECTION OF FLOW A MINIMUM OF 1" PER 8 FEET. DO
NOT BEND OR TWIST WHEN INSTALLING.
42. COMBUSTION AIR, FLUE AIR, VENT PIPE, AND DUCT WITH EXTERIOR
LOCATED INLETS AND OUTLETS WITH OPENINGS GREATER THAN 1" SHALL
BE INSTALLED WITH A BIRD SCREEN.
43. DUCTWORK TO BE INSTALLED AND TESTED IN ACCORDANCE TO SMACNA
STANDARDS SHOWN ON SHEET M-603 "DUCTWORK CONSTRUCTION AND
LEAKAGE TESTING TABLE".
44. EMERGENCY SHUTOFF SHALL BE WIRED TO SHUT DOWN AIR
DISTRIBUTION AND EXHAUST SYSTEMS THROUGH OUT THE BUILDING AND
CLOSE ALL DAMPERS LEADING TO OUTSIDE. THE SWITCH SHALL BE
CAPABLE OF SHUTTING DOWN ALL REQUIRED SYSTEMS AND
CLOSING ALL REQUIRED DAMPERS, EVEN IF THE LOCAL
HAND/OFF/AUTO SWITCH IS IN THE HAND POSITION, WITHIN 30 SECONDS
OF SWITCH ACTIVATION.
45. ALL EXPOSED DUCTWORK SHALL HAVE AN INNER AND OUTER METAL
WALL WITH INSULATION SANDWITCHED IN BETWEEN. THE OUTER METAL
SURFACE SHALL BE PAINTED. SEE INTERIORS DRAWINGS SET FOR
ADDITIONAL INFORMATION.
46. TWO SEPARATE EMERGENCY SHUTOFF BUTTONS, ONE FOR THE ADMIN /
SUPPORT AREA (ES-1) ONE FOR THE REPAIR BAYS (ES-2), SHALL BE WIRED
TO SHUT DOWN AIR DISTRIBUTION AND EXHAUST SYSTEMS FOR THEIR
RESPECTIVE PORTIONS OF THE BUILDING. EACH SHUTOFF SHALL CLOSE
ALL DAMPERS LEADING TO OUTSIDE, FOR THE RESPECTIVE AREA
SERVED. THE SWITCH SHALL BE CAPABLE OF SHUTTING DOWN ALL
REQUIRED SYSTEMS AND CLOSING ALL REQUIRED DAMPERS, EVEN IF THE
LOCAL HAND/OFF/AUTO SWITCH IS IN THE HAND POSITION, WITHIN 30
SECONDS OF SWITCH ACTIVATION. FOR SYSTEM ASSIGNMENTS SEE
EQUIPMENT SEQUENCES OF OPERATION IN M-700 CONTROLS SHEETS.
47. LABEL AND TAG ALL MECHANICAL EQUIPMENT. ALSO LABEL CEILING GRID
WHERE MECHANICAL EQUIPMENT IS LOCATED ABOVE…
This is the start of the file's text. The full file is on GovTribe.