W912QR21R0065_Plans_Vol1-0000.pdf
PDF 39 MB Posted
- Solicitation number
- W912QR21R0065
About this file
This solicitation is for a firm-fixed-price construction contract to replace the existing high-temperature hot water and steam heating system serving 22 buildings at Wright-Patterson Air Force Base with new natural gas boilers and associated piping and controls infrastructure. The U.S. Army Corps of Engineers Louisville District will issue the request for proposal. Work includes demolishing and capping existing steam and hot water piping, installing new natural gas supply piping and separate boilers for each building, and tying into existing facility heating distribution systems. The contract duration is 730 calendar days with a target ceiling of approximately $8 million. The North American Industry Classification System code is 238220. Proposals will be evaluated using best value tradeoff considering past performance, technical, small business participation, and price factors. Award may be made without discussions but the agency reserves the right to conduct discussions.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT TEAM
4454 Idea Center Blvd
Dayton, OH 45430
Fax: 937.461.0743 www.woolpert.com
WOOLPERT
Tel: 937.461.5660
10411 Meeting Street
Prospect, Kentucky 40059
Fax: 502.326.2691 www.cmta.com
CMTA
Tel: 502.326.3085
1441 King Avenue
Columbus, Ohio 43212
Fax: 614.481.8610 www.lawhon-assoc.com
LAWHON & ASSOCIATES, Inc.
Tel: 614.481.8600
ARCHITECTURE ENGINEERING GEOSPATIAL
VICINITY MAP
LOCATION MAP
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of
Engineers ®
A N
S I
'D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
US Army Corps of Engineers ®
SOLICITATION NO.:
CONTRACT NO.:
ISSUE DATE:
VOLUME:
B
IM
/W
P A
F B
H
T H
W L in e D
/0 G e n e ra l_ S h e e ts
P h a se
I A
R C
H R
.r vt
/1
/2
:1
:2
A
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
P N
Z H
T V
F
Y P
JU
N
E
LOUISVILLE DISTRICT
J.
E
L D
E R
G
R O
D D
Y
J.
E
L D
E R
G-001
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J.
S
T E
W A
R T
P H
A S
E I C
O V
E R
CERTIFIED FINAL - JUNE 2021
LOUISVILLE DISTRICT
JUNE 2021
WRIGHT-PATTERSON AIR FORCE BASE (WPAFB), OHIO
REPAIR STEAM & HTHW LINE D (PHASE I)
PROJECT NUMBER: ZHTV 120044
P2 NUMBER: 485741
KEY PLAN - AREA A
30055 30069
30109 30110
30140 30142
30151 30152
30219
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
ARCHITECTURAL
JILL M. ELDER ARC.1917677
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
LIFE SAFETY/FIRE PROTECTION
JAMES D. MUSGROVE PE-2005001024
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
STRUCTURAL
(NAME AND LICENSE)
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
CIVIL
JAY BOLTZ PE.79552
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
PLUMBING
DENNIS PATRICK FINN JR 31581
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
ELECTRICAL
PETER G. DIETERLEN 70741
THIS WORK WAS PREPARED BY
ME OR UNDER MY SUPERVISION
MECHANICAL
DENNIS PATRICK FINN JR 31581
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
JAMES I. GUFFEY PE.83917
12 July 2021
W912QR21R0065
W
2Q R
R
-0
ARIMS: 200A Disposition: Maintain for 15yrs after construction
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of
Engineers ®
A N
S I
'D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
/W
P A
F B
H
T H
W L in e D
/0 G e n e ra l_ S h e e ts
P h a se
I A
R C
H R
.r vt
/1
/2
:3
:1
A
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
P N
Z H
T V
F
Y P
JU
N
E
LOUISVILLE DISTRICT
J.
E
L D
E R
G
R O
D D
Y
J.
E
L D
E R
G-002
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J.
S
T E
W A
R T
P H
A S
E I S
H E
E T
I N
D E
X A
N D
F A
C
IL
IT
Y
A R
E A
S
CERTIFIED FINAL - JUNE 2021
DRAWING INDEX SHEET - PHASE I
SHEET NUMBER SHEET TITLE
PLUMBING
P-001 PLUMBING LEGENDS
P-101J FACILITY 30055 - OVERALL PLUMBING PLAN
P-101K FACILITY 30069 - OVERALL PLUMBING PLAN
P-101L FACILITY 30109 - OVERALL PLUMBING PLAN
P-101M FACILITY 30110 - OVERALL PLUMBING PLAN
P-101O FACILITY 30140 - OVERALL PLUMBING PLAN
P-101P FACILITY 30142 - OVERALL PLUMBING PLAN
P-101R FACILITY 30151 - OVERALL PLUMBING PLAN
P-101S FACILITY 30152 - OVERALL PLUMBING PLAN
P-101T FACILITY 30219 - OVERALL PLUMBING PLAN
P-501 PLUMBING DETAILS
P-502 PLUMBING DETAILS
MECHANICAL
M-001 MECHANICAL LEGENDS
M-002 MECHANICAL NOTES
MECHANICAL
MD101K FACILITY 30069 MECHANICAL DEMOLITION PLANS
MD101R FACILITY 30151 MECHANICAL DEMOLITION PLAN
MD101S FACILITY 30152 MECHANICAL DEMOLITION PLAN
MECHANICAL
M-101J FACILITY 30055 MECHANICAL DEMOLITION AND NEW
WORK PLANS
M-101K FACILITY 30069 MECHANICAL NEW WORK PLANS
M-101L FACILITY 30109 MECHANICAL DEMOLITION AND NEW
WORK PLANS
M-101M FACILITY 30110 MECHANICAL PLAN
M-401M FACILITY 30110 MECHANICAL ENLARGED PLAN
M-101O FACILITY 30140 MECHANICAL PLAN
M-401O FACILITY 30140 MECHANICAL ENLARGED PLAN
M-101P FACILITY 30142 MECHANICAL PLAN
M-401P FACILITY 30142 MECHANICAL ENLARGED PLAN
M-101R FACILITY 30151 MECHANICAL PLAN
M-101S FACILITY 30152 MECHANICAL PLAN
M-401S FACILITY 30152 MECHANICAL ENLARGED PLAN
M-101T FACILITY 30219 MECHANICAL DEMOLITION AND NEW
WORK PLANS
M-501 MECHANICAL DETAILS
M-502 MECHANICAL DETAILS
M-503 MECHANICAL DETAILS
M-504 MECHANICAL DETAILS
M-601 MECHANICAL SCHEDULES
M-602 MECHANICAL SCHEDULES
M-603 MECHANICAL SCHEDULES
M-701 FACILITY 30110 PIPING SCHEMATIC
M-702 FACILITY 30140 PIPING SCHEMATIC
M-703 FACILITY 30142 PIPING SCHEMATIC
M-704 FACILITY 30151 PIPING SCHEMATIC
M-705 FACILITY 30152 PIPING SCHEMATIC
M-706 FACILITY 30219 PIPING SCHEMATIC
M-801 MECHANICAL CONTROL DIAGRAMS
M-802 MECHANICAL CONTROL DIAGRAMS
ELECTRICAL
E-001 ELECTRICAL LEGENDS
E-101J FACILITY 30055 POWER PLAN
E-101K FACILITY 30069 POWER PLAN
E-101L FACILITY 30109 POWER PLAN
E-101M FACILITY 30110 POWER PLAN
E-101O FACILITY 30140 POWER PLAN
E-101P FACILITY 30142 POWER PLAN
E-101R FACILITY 30151 POWER PLAN
E-101S FACILITY 30152 POWER PLAN
E-101T FACILITY 30219 POWER PLAN
ELECTRICAL
E-601K FACILITY 30069 ELECTRICAL SCHEDULES
E-601M FACILITY 30110 ELECTRICAL SCHEDULES
E-601O FACILITY 30140 ELECTRICAL SCHEDULES
E-601P FACILITY 30142 ELECTRICAL SCHEDULES
E-601R FACILITY 30151 ELECTRICAL SCHEDULES
E-601S FACILITY 30152 ELECTRICAL SCHEDULES
E-601T FACILITY 30219 ELECTRICAL SCHEDULES
DRAWING INDEX SHEET - PHASE I
SHEET NUMBER SHEET TITLE
GENERAL
G-001 PHASE I COVER
G-002 PHASE I SHEET INDEX AND FACILITY AREAS
G-003 GENERAL NOTES
G-004 ABBREVIATIONS AND SYMBOLS
LIFE SAFETY
GI101J FACILITY 30055 LIFE SAFETY PLAN
GI101K FACILITY 30069 LIFE SAFETY PLAN
GI101L FACILITY 30109 LIFE SAFETY PLAN
GI101M FACILITY 30110 LIFE SAFETY PLAN
GI101O FACILITY 30140 LIFE SAFETY PLAN
GI101P FACILITY 30142 LIFE SAFETY PLAN
GI101R FACILITY 30151 LIFE SAFTEY PLAN
GI101S FACILITY 30152 LIFE SAFETY PLAN
GI101T FACILITY 30219 LIFE SAFETY PLAN
HAZARDOUS
H-101R FACILITY 30151 FLOOR PLANS
H-101S FACILITY 30152 FLOOR PLANS
CIVIL
C-001 VICINITY MAP AND PROPOSED PHASING
C-002 PROP. HAUL ROUTE AND LAYDOWN AREA
C-101 NATURAL GASLINE PLAN VIEW
C-102 NATURAL GASLINE PLAN VIEW
C-103 NATURAL GASLINE PLAN VIEW
C-104 NATURAL GASLINE PLAN VIEW
C-105 WATERLINE AND FOUNDATION PLAN VIEW
C-201 GENERAL DETAILS
C-202 GENERAL DETAILS
C-203 WATER DETAILS
C-204 WATER DETAILS
C-205 WATER DETAILS
C-206 LANE CLOSURE DETAILS
C-207 ROAD CLOSURE TYPE 3 BARRICADE
STRUCTURAL
S-001 GENERAL NOTES
S-010 SPECIAL INSPECTIONS
S-101 FACILITY F30151 FOUNDATION PLAN
S-201 FOUNDATION AND ROOF FRAMING DETAILS
ARCHITECTURE
A-101J FACILITY 30055 FLOOR PLAN & ROOF PLAN
A-101K FACILITY 30069 FLOOR PLANS
A-121K FACILITY 30069 ROOF PLAN
A-101L FACILITY 30109 FLOOR PLANS
A-121L FACILITY 30109 ROOF PLAN
A-101M FACILITY 30110 FLOOR PLANS
A-121M FACILITY 30110 ROOF PLAN
A-101O FACILITY 30140 FLOOR PLANS
A-101P FACILITY 30142 FLOOR PLANS
A-121P FACILITY 30142 ROOF PLAN
A-101R FACILITY 30151 FLOOR PLANS
A-101S FACILITY 30152 FLOOR PLANS
A-121S FACILITY 30152 ROOF PLAN
A-101T FACILITY 30219 FLOOR PLANS
A-201T FACILITY 30219 EXTERIOR ELEVATIONS
A-501 ROOF DETAILS & MISC. DETAILS
A-601 PHASE I DOOR SCHEDULE & DETAILS & FINISH
SCHEDULE
FIRE PROTECTION
FA101J FACILITY 30055 FIRE ALARM PLAN
FA101K FACILITY 30069 FIRE ALARM PLAN
FA101L FACILITY 30109 FIRE ALARM PLAN
FA101M FACILITY 30110 FIRE ALARM PLAN
FA101O FACILITY 30140 FIRE ALARM PLAN
FA101P FACILITY 30142 FIRE ALARM PLAN
FA101R FACILITY 30151 FIRE ALARM PLAN
FA101S FACILITY 30152 FIRE ALARM PLAN
FA101T FACILITY 30219 FIRE ALARM PLAN
FIRE PROTECTION
FX101K FACILITY 30069 FIRE SUPPRESSION PLAN
FX101L FACILITY 30109 FIRE SUPPRESSION PLAN
FX101M FACILITY 30110 FIRE SUPPRESSION PLAN
FX101O FACILITY 30140 FIRE SUPPRESSION PLAN
FX101P FACILITY 30142 FIRE SUPPRESSION PLAN
FX101S FACILITY 30152 FIRE SUPPRESSION PLAN
FX101T FACILITY 30219 FIRE SUPPRESSION PLAN
Facility Number Floor Area Number of Floors Mezzanine Overall Facility Area
30055 2049 SF 1 No 2049 SF
30069 43008 SF 1 No 43008 SF
30109 20200 SF 1 No 20200 SF
30110 31014 SF 1 No 31014 SF
30140 4823 SF 1 No 4823 SF
30142 31636 SF 1 No 31636 SF
30151 3807 SF 1 No 3807 SF
30152 35455 SF 1 Yes 40261 SF
30219 8916 SF 4 No 35352 SF
FACILITY AREAS - PHASE I
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
GENERAL NOTES
A. FIELD VERIFY INFORMATION, DIMENSIONS, ETC. PRIOR TO ORDERING OR
FABRICATING MATERIALS OR BEGINNING CONSTRUCTION.
B. THE CONTRACTOR SHALL ARRANGE FOR THE PREMISES TO BE MAINTAINED IN AN
ORDERLY MANNER, FREE OF DUST AND DEBRIS, THROUGHOUT THE COURSE OF THE
WORK. PROVIDE AND MAINTAIN TEMPORARY BARRICADES AS REQUIRED TO PROTECT
THE PUBLIC AND CONTRACTING OFFICERS PERSONNEL DURING CONSTRUCTION. THE
CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE EXISTING STRUCTURE
OR EQUIPMENT. ANY SUCH DAMAGE SHALL BE REPAIRED AT THE CONTRACTOR'S
EXPENSE.
C. CONTRACTOR SHALL PROVIDE DAILY OR MORE FREQUENT GENERAL CLEAN UP IN
COMPLIANCE WITH EM385-1-1 REQUIREMENTS OF AREAS WITHIN THE LIMITS OF
CONSTRUCTION, AND FINAL CLEAN UP AT CONCLUSION OF WORK.
D. CONTRACTOR TO REVIEW OTHER DRAWINGS ISSUED FOR THIS PROJECT FOR
ADDITIONAL INFORMATION TO COORDINATE THE REQUIRED SCOPE OF WORK.
E. DO NOT SCALE FROM THE DRAWINGS. WRITTEN DIMENSIONS SHALL TAKE
PRECEDENCE. THE CONTRACTING OFFICER MUST BE NOTIFIED OF ANY CONFLICTS IN
DIMENSIONING.
F. ALL MATERIALS, FIXTURES AND EQUIPMENT INDICATED IN THE CONSTRUCTION
DOCUMENTS SHALL BE NEW AND AS SPECIFIED, UNLESS IDENTIFIED OTHERWISE.
G. ALL NEW FINISHED AND PATCHED SURFACES SHALL BE SMOOTH, CONTINUOUSLY
FREE OF IMPERFECTIONS AND IN PROPER CONDITION TO RECEIVE THE SPECIFIED
FINISH. PATCHED AREAS SHALL MATCH THE ADJACENT MATERIALS CONSTRUCTION AND
FINISH.
H. ALL FLOORS ON EITHER SIDE OF A DOORWAY OR OPENING SHALL BE LEVEL AND
HAVE A MAXIMUM ELEVATION DIFFERENCE OR THRESHOLD HEIGHT OF 1/2".
I. DOOR OPENINGS NOT LOCATED BY DIMENSION SHALL BE 4" FROM THE FACE OF
FINISHED WALL TO OUTSIDE EDGE OF DOOR FRAME JAMB UNLESS NOTED OTHERWISE
J. THE CONTRACTOR SHALL EXAMINE THE SITE AND PORTIONS THEREOF WHICH AFFECT
THE WORK AND SHALL VERIFY ALL DIMENSIONS AND CONDITIONS, INCLUDING, BUT NOT
LIMITED TO: WALLS, FLOORS, MECHANICAL, PLUMBING, AND ELECTRICAL
CONSTRUCTION.
K. ANY NEW PENETRATIONS TO BE SEALED, INCLUDING ALL UNUSED WALL
PENETRATIONS. INSTALL FIRE CAULK AT ANY RATED WALL PENETRATIONS.
L. EACH TRADE CONTRACTOR SHALL BE RESPONSIBLE FOR FIRESTOPPING OPENINGS
THROUGH FIRE RATED WALLS NECESSARY OR CREATED FOR THE INSTALLATION OF
THEIR WORK. ANY EXISTING PENETRATIONS OR OPENINGS SHOULD ALSO BE
FIRESTOPPED TO MAINTAIN RATING OF WALL.
M. DOOR AND WINDOW SIZES, STYLES, AND SPECIFICATIONS, ROUGH OPENING SIZES
AND EXACT LOCATIONS TO BE CHECKED AND VERIFIED BY THE CONTRACTOR BEFORE
ORDERING AND BEFORE CONSTRUCTION BEGINS.
N. CONTRACTOR TO MAINTAIN A TARPED CONSTRUCTION WASTE DUMPSTER IN
LOCATION SPECIFIED BY CONTRACTING OFFICER. ALSO PATH FROM WORKSPACE TO
SAID DUMPSTER MUST BE MAINTAINED AND CLEANED PER CONTRACTING OFFICER'S
SATISFACTION. AT NO TIME SHALL ANY CONSTRUCTION DEBRIS BE LEFT UNATTENDED
WHILE IN ROUTE FROM WORKSPACE TO DUMPSTER.
O. AT NO TIME SHALL CONSTRUCTION MATERIAL BE LEFT UNATTENDED WHILE IN ROUTE
TO WORKSPACE.
P. THE CONTRACTING OFFICER AND CONSTRUCTION MANAGER HAVE THE RIGHT TO
CONTROL THE LOCATION OF ALL CONTRACTOR'S SUPPLIES AND STORAGE
Q. SPECIAL CARE SHOULD BE TAKEN WHEN WORKING NEAR ELECTRIC, WATER, STEAM,
AND GAS SUPPLY LINES.
R. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROTECT THE HEALTH AND
SAFETY OF THEIR EMPLOYEES.
S. THE CONTRACTOR SHALL COMPLY WITH THE REQUIREMENTS REGARDING CONFINED
SPACE, SCAFFOLDING AND LIFTS INCLUDING ASSOCIATED PROGRAMS, PERMITS,
TRAINING AND TESTING PER OSHA AND EM-385-1-1, WHICHEVER IS MORE RESTRICTIVE.
T. THE CONTRACTOR IS RESPONSIBLE FOR FOLLOWING AND ADHERING TO ALL
APPLICABLE FEDERAL, STATE, AND LOCAL REGULATIONS INCLUDING, BUT NOT LIMITED
TO, THOSE SET FORTH BY THE USEPA, OSHA, EM-385-1-1 AND ODH, WHICHEVER IS MORE
RESTRICTIVE.
U. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH WPAFB SPECIFICATION
SECTION 01 35 43 GENERAL ENVIRONMENTAL REQUIREMENTS (WPAFB).
V. NO ASBESTOS-CONTAINING MATERIAL SHALL BE INSTALLED DURING THIS PROJECT.
W. SOIL DISTURBANCE DURING THIS PROJECT, INCLUDING EQUIPMENT STAGING AREAS,
WILL REQUIRE EROSION CONTROL MEASURES. FOR PROJECTS THAT DISTURB LESS
THAN AN ACRE OF SOIL, AN EROSION CONTROL PLAN IS REQUIRED PRIOR TO SOIL
DISTURBANCE. FOR PROJECTS THAT DISTURB MORE THAN AN ACRE, A NOTICE OF
INTENT (NOI) MUST BE APPROVED BY THE OHIO EPA PRIOR TO ANY SOIL BEING
DISTURBED AS WELL AS A STORM WATER POLLUTION PREVENTION PLAN (SWPPP)
APPROVED BY 88 CEG/CEIEA. PLEASE CONTACT THE 88 CEG/CEIEA WATER PM MIKE
VAUGHN, (937-257-8028 OR MICHAEL.VAUGHN.3@US.AF.MIL) FOR ADDITIONAL
INFORMATION.
X. THE GENERATION OF FUGITIVE EMISSIONS MUST BE KEPT TO A MINIMUM USING
APPROVED DUST SUPPRESSING METHODS SUCH AS WATER SPRAYS ON AREA OF HIGH
DUST GENERATION. FOR ADDITIONAL INFORMATION PLEASE CONTACT THE 88 CEG/CEIEA
AIR PM CHRIS TUMBUSCH AT 937-257-2455 OR BY EMAIL AT
CHRISTOPHER.TUMBUSCH@US.AF.MIL
Y. REMOVE AND DISPOSE OF ANY ASBESTOS CONTAINING MATERIAL IN ACCORDANCE
WITH WPAFB SPECIFICATION SECTION 01 35 43.
Z. ALL WINDOW AND DOOR FRAME CAULKING AND GLAZING WILL BE TREATED AS
CONTAINING ASBESTOS UNLESS TESTING PROVES IT TO BE ASBESTOS FREE.
AA. DEMOLITION OF LOAD-BEARING WALLS OR STRUCTURAL COMPONENTS REQUIRE
NOTIFICATION OF DEMOLITION AND RENOVATION TO THE REGIONAL AIR POLLUTION AND
CONTROL AGENCY (RAPCA) A MINIMUM OF 10 WORK DAYS PRIOR TO BEGINNING
CONSTRUCTION.
BB. ALL HAZARDOUS MATERIALS MUST BE PROPERLY MANAGED, LABELED AND STORED.
ANY HAZARDOUS WASTE GENERATED FROM THIS CONSTRUCTION ACTIVITY MUST BE
PROPERLY CHARACTERIZED, LABELED AND MANAGED BY TRAINED EMPLOYEE OF THE
CONTRACTOR WITH KNOWLEDGE OF THE ACTIVITY / PROCESS WHERE THE WASTE WAS
GENERATED. ALL HAZARDOUS WASTE WILL BE TURNED OVER TO THE GOV’T FOR
DISPOSAL. IN ADDITION PROPER COORDINATION IS NEEDED WITH 88 CEG/CEIEC.
QUESTIONS CONCERNING THE REQUIREMENTS FOR STORAGE AND DISPOSAL OF ANY
HAZARDOUS MATERIALS CAN BE ADDRESSED BY THE 88 CEG/CEIEC HAZARDOUS
MATERIALS PM, KAREN.BEASON@US.AF.MIL OR BY PHONE AT 937-257-5899 OR 88
CEG/CEIEC HAZARDOUS WASTE FIELD LIAISON, JASON BALDWIN, JASON.BALDWIN.17
@US.AF.MIL or 937-257-5531.
CC. LEAD BASED PAINT WASTE GENERATED FROM ABATEMENT ACTIVITIES SHALL BE
MANAGED AND DISPOSED AS HAZARDOUS WASTE IN ACCORDANCE WITH WPAFB
SPECIFICATION SECTION 01 35 43.
A. THE CONTRACTOR SHALL CAREFULLY STUDY AND COMPARE THE CONTRACT DOCUMENTS WITH
EACH OTHER AND SHALL AT ONCE REPORT TO THE CONTRACTING OFFICER ANY ERRORS,
INCONSISTENCIES OR OMISSIONS DISCOVERED. IF THE CONTRACTOR PERFORMS ANY
CONSTRUCTION ACTIVITY KNOWING IT INVOLVES A RECOGNIZED ERROR, INCONSISTENCY OR
OMISSION IN THE CONTRACT DOCUMENTS WITHOUT SUCH NOTICE TO USACE, THE CONTRACTOR
SHALL ASSUME APPROPRIATE RESPONSIBILITY FOR SUCH PERFORMANCE AND SHALL BEAR AN
APPROPRIATE AMOUNT OF THE ATTRIBUTABLE COSTS FOR CORRECTION. THE CONTRACTOR SHALL TAKE FIELD MEASUREMENTS AND VERIFY FIELD CONDITIONS AND SHALL CAREFULLY COMPARE SUCH
FIELD MEASUREMENTS AND CONDITIONS AND OTHER INFORMATION KNOWN TO THE CONTRACTOR
WITH THE CONTRACT DOCUMENTS BEFORE COMMENCING ACTIVITIES. ERRORS, INCONSISTENCIES
OR OMISSIONS DISCOVERED SHALL BE REPORTED TO USACE AT ONCE.
B. THE CONTRACTOR SHALL BE RESPONSIBLE FOR CUTTING, GRINDING, SANDING, FILLING, FITTING
OR PATCHING REQUIRED TO COMPLETE THE WORK OR TO MAKE ITS PARTS FIT TOGETHER
PROPERLY.
C. THE CONTRACTOR SHALL NOT DAMAGE OR ENDANGER A PORTION OF THE WORK OR FULLY OR
PARTIALLY COMPLETED CONSTRUCTION BY CUTTING, PATCHING, EXCAVATING OR OTHERWISE
ALTERING SUCH CONSTRUCTION. THE CONTRACTOR SHALL NOT CUT OR OTHERWISE ALTER SUCH
CONSTRUCTION BY OTHER CONTRACTORS OR BY THE CONTRACTING OFFICER'S OWN FORCES
EXCEPT WITH WRITTEN CONSENT OF USACE. CONTRACTING OFFICER, AND SUCH OTHER
CONTRACTORS; SUCH CONSENT SHALL NOT BE UNREASONABLY WITHHELD. THE CONTRACTOR
SHALL NOT UNREASONABLY WITHHOLD FROM THE OTHER CONTRACTORS OR USACE THE
CONTRACTOR'S CONSENT TO CUTTING OR OTHERWISE ALTERING THE WORK.
D. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL DAMAGE THAT OCCURS, TO ANY EXISTING
MATERIALS, FINISHES, EQUIPMENT, ETC. TO REMAIN AS A RESULT OF THE CONTRACTOR'S WORK. IF
DAMAGE DOES OCCUR AS A RESULT OF THE CONTRACTOR'S WORK, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR PATCHING AND REPAIRING AS REQUIRED OR COMPLETE REPLACEMENT AS PER
THE DIRECTION OF THE CONTRACTING OFFICER.
E. CONTRACTOR SHALL PROVIDE ALL TEMPORARY SHORING AND BRACING AS REQUIRED FOR ALL DEMOLITION AND NEW WORK AS REQUIRED. IF ANY DAMAGE OCCURS TO THE EXISTING BUILDING OR
NEW CONSTRUCTION AS A RESULT OF IMPROPER OR INADEQUATE SHORING OR BRACING, THE
CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR REPAIR AND/ OR REPLACEMENT OF
DAMAGED AREAS. DAMAGED AREAS SHALL INCLUDE BUT NOT BE LIMITED TO STRUCTURE, WINDOWS, FINISHES, EQUIPMENT, FURNISHINGS, MOVEMENT OF ADJACENT PAVEMENT/ WALKS/ CURBS/
STRUCTURES.
F. CONTRACTOR SHALL REMOVE AND DISPOSE OF EXISTING STRUCTURES, ELECTRICAL
COMPONENTS, CASEWORK, FURNISHINGS, FINISHES, ETC., THAT IS SHOWN ON THE DEMOLITION
DRAWINGS.
G. AT STRUCTURES TO BE REMOVED; INCLUDING CONCRETE MASONRY UNIT PARTITIONS AND
WALLS, METAL STUD PARTITIONS AND WALLS, GYPSUM BOARD AND/ OR PLASTER CEILINGS, ETC..
PARTITIONS AND WALLS SHALL BE SAW CUT WITH SMOOTH AND STRAIGHT EDGES AS REQUIRED FOR
NEW ADJACENT CONSTRUCTION.
H. AT ALL ELECTRICAL UTILITIES FOR PROPOSED DEMOLISHED; INCLUDING POWER LINES, LIGHTING AND COMMUNICATION LINES. REFER TO ELECTRICAL DEMOLITION DRAWINGS, SUCH AS TO PULL
EXISTING CIRCUIT BACK TO NEAREST HOT BOX OR TO THE MAIN PANEL BOARD.
J. EACH CONTRACTOR IS RESPONSIBLE FOR COORDINATING THEIR WORK WITH ALL SURROUNDING
CONSTRUCTION ELEMENTS AND TRADES AFFECTED.
K. EACH CONTRACTOR IS RESPONSIBLE FOR CREATING ALL OPENINGS, PENETRATIONS, LINTELS, ETC. AS REQUIRED TO PERFORM THEIR PORTION OF WORK.
L. ALL DEMOLISHED ITEMS, UNLESS OTHERWISE NOTED, SHALL BE DISPOSED OF (REMOVED FROM)
OFF SITE IN A LEGAL MANNER AND PER THE REQUIRED CONTRACTOR'S CONSTRUCTION AND
DEMOLITION WASTE PLAN.
M. COORDINATE DEMOLITION WORK SCOPE WITH ASSOCIATED DOCUMENTS FOR RENOVATION
WORK BY OTHER TRADES TO DETERMINE SIZES AND LOCATIONS OF OPENINGS IN EXISTING WALLS, FLOORS, CEILINGS, AND PARTITIONS.
N. CONTRACTOR WILL TEST MATERIALS FOR HAZARDOUS MATERIALS AND PROVIDE ANY ABATEMENT PRIOR TO STARTING WORK. IF CONTRACTOR FINDS ANY ADDITIONAL MATERIALS THEY SUSPECT TO
CONTAIN HAZARDOUS MATERIALS, THEY ARE TO CEASE WORK AND NOTIFY THE CONTRACTING
OFFICER.
O. CONTRACTOR SHALL BUILD TEMPORARY BARRICADE BEFORE ANY DEMOLITION. THE ERECTION
AND REMOVAL OF BARRICADES SHALL OCCUR AT NIGHT.
P. CONTRACTOR SHALL PATCH AND REPAIR ALL EXISTING WALLS AND FLOORS WHERE ELECTRICAL ITEMS HAVE BEEN REMOVED, UNLESS OTHERWISE NOTED. PATCH AND REPAIR LOCATIONS SHALL
BE TO THE SAME LEVEL AND FINISH OF ADJACENT EXISTING MATERIALS
Q. GENERAL CONTRACTOR TO BE RESPONSIBLE FOR REMOVAL OF ALL EXISTING UNUSED OR
VACANT ELECTRICAL CONDUIT, GAS PIPING, LIMITED AREA SPRINKLER PIPING, WATER PIPING, AND
DUCTWORK.
R. FIELD VERIFY ALL DIMENSIONS.
S. PROVIDE LABOR AND MATERIAL TO CONTROL AND CONTAIN CONSTRUCTION DEBRIS.
T. PROVIDE LABOR AND MATERIAL TO REMOVE ALL CONSTRUCTION DEBRIS FROM SITE.
U. REMOVE AND RELOCATE ALL EXISTING EQUIPMENT TO CONTRACTING OFFICER SPECIFIED
LOCATIONS PRIOR TO ANY DEMOLITION.
V. DEMO AND REMOVE EXISTING WALLS FROM FLOOR TO DECK IN SPECIFIED LOCATIONS, TO
INCLUDE DOORS AND FRAMES WHERE APPLICABLE.
W. DEMO AND REMOVE EXISTING FLOORING AND WALL BASE IN ALL RENOVATED SPACES IN
INDICATED AREAS.
X. THE GOVERNMENT/OWNER SHALL BE PROVIDED THE OPPORTUNITY TO SALVAGE ANY BUILDING
SYSTEMS OR EQUIPMENT FROM THE PROJECT AREAS PRIOR TO DEMOLITION.
Y. IF ASBESTOS IS SUSPECTED IN ANY EXISTING MATERIALS, IT MUST BE TESTED AND REMOVED IN
ACCORDANCE WITH WPAFB SPECIFICATIONS AND BY A LICENSED ASBESTOS
INSPECTOR/CONTRACTOR.
Z. ANY PENETRATIONS CREATED THROUGHOUT THIS PROJECT SHALL BE SEALED. SEAL ALL UNUSED
PENETRATIONS. SEAL ALL PENETRATIONS OF EXTERIOR WALLS..
AA. EXISTING CLEAN OUTS, FLOOR DRAINS, TRENCH DRAINS, AND THRU WALL LOUVERS TO REMAIN
UNLESS OTHERWISE NOTED.
BB. PATCH ALL AREAS WHERE EQUIPMENT OR CONCRETE CURB HAS BEEN REMOVED AND
CONCRETE IS DAMAGED.
CC. CONTRACTOR TO NOTIFY CONTRACTING OFFICER TWO WEEKS IN ADVANCE OF CONTROLS TO BE
DEMOLISHED FOR SALVAGE OR REUSE BY GOVERNMENT.
DD. CONTRACTOR IS RESPONSIBLE TO THOROUGHLY REVIEW THE HAZMAT REPORT AND H SERIES
DRAWINGS AND CROSS REFERENCE WITH THE ARCHITECTURAL DRAWINGS FOR LOCATIONS OF
HAZARDOUS MATERIALS FOR NEW PENETRATIONS, DEMOLITION, AND PATCHING WHERE HAZARDOUS
MATERIALS OCCUR OR ARE ASSUMED TO BE PRESENT.
GENERAL DEMOLITION NOTES
DD. ALL METAL AND WIRING SHALL BE RECYCLED AT THE WPAFB BASE RECYCLING
CENTER. THE WPAFB RECYCLING CENTER IS AVAILABLE FOR CONTRACTOR USE TO
REDUCE WASTE DISPOSAL. ALL RECYCLABLE METAL IS TO BE RECYCLED THROUGH THE
BASE RECYCLING CENTER. ALL RECYCLING MUST BE ACCOMPLISHED IN ACCORDANCE
WITH WPAFB SPECIFICATION SECTION 01 35 43. CONTACT WPAFB RECYCLING PROGRAM
MANAGER AT 937-257-5060 TO CONFIRM WHAT MATERIALS ARE RECYCLABLE AND TO
COORDINATE TURN-IN. THE CONTRACTOR SHALL SUBMIT A QUARTERLY SUMMARY
REPORT TO THE GOVERNMENT CONTRACT REPRESENTATIVE IAW WPAFB
SPECIFICATION SECTION 01 35 43 STATING (1) THE COST TO RECYCLE AND THE TONNAGE
OF CONSTRUCTION AND DEMOLITION MATERIALS RECYCLED, (2) THE COST TO
DIVERT/REUSE THE TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS
DIVERTED/REUSE, (3) THE COST TO MULCH AND THE TONNAGE AND COST OF
CONSTRUCTION AND DEMOLITION MATERIALS MULCHED, (4) THE COST FOR WASTE-TO-
ENERGY AND THE TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS
CONVERTED FROM WASTE-TO-ENERGY, (5) THE COST TO LANDFILL AND THE TONNAGE
OF CONSTRUCTION AND DEMOLITION MATERIALS LAND-FILLED, (6) THE COST TO
INCINERATE AND THE TONNAGE OF CONSTRUCTION AND DEMOLITION MATERIALS
INCINERATED, AND (7) EXPLANATION OF THE DIVERSION RATE IF LESS THAN 60%. THE
QUARTERLY SUMMARY REPORTS SHALL BE RECEIVED ON APRIL 7, JULY 7, OCTOBER 7,
AND JANUARY 7 COVERING THE THREE MONTHS PRIOR. THE QUARTERLY SUMMARY
REPORTS SHALL BE ON THE WPAFB DIVERSION FORM. FOR ADDITIONAL INFORMATION
CONTACT THE RECYCLING PM, DAVE DALTON, AT 937-257-5060 OR DAVID.DALTON.2
@US.AF.MIL.
EE. TURN-IN ALL MERCURY CONTAINING DEVICES, SWITCHES AND THERMOSTATS TO 88
CEG/CEIE IN ACCORDANCE WITH WPAFB SPECIFICATION SECTION 01 35 43 FOR
RECYCLING.
FF. TURN-IN ALL MERCURY CONTAINING LAMPS TO 88 CEG/CEIE IN ACCORDANCE WITH
WPAFB SPECIFICATION SECTION 01 35 43.
GG. TURN-IN ALL PCB CONTAINING LIGHT BALLAST TO 88 CEG/CEIE IN ACCORDANCE
WITH WPAFB SPECIFICATION SECTION 01 35 43.
HH. 30 DAYS PRIOR TO START OF WORK, THE CONTRACTOR SHALL TAKE A
REPRESENTATIVE SAMPLE OF THE HVAC SYSTEM WATER TO DETERMINE WHETHER IT
CAN BE DRAINED DIRECTLY INTO THE SANITARY SEWER. ANALYZE THE WATER TO
DETERMINE THE TOTAL LEVEL OF EACH OF THE FOLLOWING: ARSENIC, CADMIUM,
CHROMIUM, COPPER, CYANIDE, LEAD, MERCURY, MOLYBDENUM, NICKEL, SELENIUM,
SILVER, ZINC, SULFIDE, OIL AND GREASE, PHOSPHORUS, COD, BOD. THE LAB
PERFORMING THE ANALYSES MUST BE CERTIFIED BY OHIO EPA TO ANALYZE FOR THESE
PARAMETERS. PROVIDE A COPY OF THE LAB’S REPORT TO THE CONTRACTING OFFICER,
WHO WILL IN TURN FORWARD IT TO 88 CEG/CEIEA FOR A DETERMINATION ON THE
WASTEWATER DISPOSAL METHOD.
II. COORDINATE DISPOSITION OF EXCESS RADIOACTIVE COMMODITIES, E.G. IONIZATION
TYPE SMOKE DETECTORS, RADIOLUMINESCENT EMERGENCY EXIT SIGNS, OR ANY OTHER
RADIOACTIVE COMMODITY AND/OR RADIOACTIVE CONTAMINANT THROUGH THE
INSTALLATION RADIATION SAFETY OFFICER, 88 OMRS/SGXB.
JJ. PROJECT IS WITHIN THE HUFFMAN RETARDING BASIN (HRB). PRIOR TO PLACING ANY
FILL MATERIAL (TOPSOIL, CONCRETE, PAVEMENT, GRAVEL OR OTHER MATERIAL), WITHIN
THE PROJECT SITE THE MIAMI CONSERVANCY DISTRICT SHALL BE CONSULTED TO
DETERMINE IF A STORAGE COMPENSATION AGREEMENT (SCA) IS REQUIRED. THE
CONTRACTOR SHALL MAINTAIN DOCUMENTATION FOR THE VOLUME AND TYPE FILL
MATERIAL IMPORTED TO THE PROJECT SITE AND THE VOLUME AND TYPE OF FILL
MATERIAL REMOVED FROM THE PROJECT SITE TO COMPLETE SCA RECORD KEEPING
REQUIREMENTS. ALL FILL MATERIAL REMOVED FROM THE SITE MUST BE REMOVED FROM
THE HRB UNLESS WRITTEN APPROVAL IS RECEIVED FROM THE WPAFB NATURAL
RESOURCE PM. CONTACT DARRYN WARNER, NATURAL RESOURCE PM AT
DARRYN.WARNER@US.AF.MIL or 937-257-4857.
KK. FOR ANY UNTESTED BUILDING COMPONENTS SUSPECTED TO CONTAIN ASBESTOS
AND LOCATED IN AREAS IMPACTED BY THE WORK, NOTIFY THE CONTRACTING OFFICER
(CO) WHO WILL HAVE THE OPTION OF ORDERING BULK SAMPLES TO BE OBTAINED AT
THE CONTRACTOR'S EXPENSE AND DELIVERED TO A LABORATORY ACCREDITED UNDER
THE NATIONAL INSTITUTE OF STANDARDS AND TECHNOLOGY (NIST) "NATIONAL
VOLUNTARY LABORATORY ACCREDITATION PROGRAM (NVLAP)" AND ANALYZED BY PLM.
IF THE ASBESTOS CONTENT IS LESS THAN 10 PERCENT, AS DETERMINED BY A METHOD
OTHER THAN POINT COUNTING, THE ASBESTOS CONTENT SHALL BE VERIFIED BY POINT
COUNTING. ANY ADDITIONAL COMPONENTS IDENTIFIED AS ACM THAT HAVE BEEN
APPROVED BY THE CO FOR REMOVAL SHALL BE REMOVED AND WILL BE PAID FOR BY AN
EQUITABLE ADJUSTMENT TO THE CONTRACT PRICE UNDER THE CONTRACT CLAUSE
TITLE "CHANGES". SAMPLING SHALL BE CONDUCTED BY PERSONNEL WHO HAVE
SUCCESSFULLY COMPLETED THE EPA MODEL ACCREDITATION PLAN (MAP) "BUILDING
INSPECTOR" TRAINING COURSE AND IS EPA / STATE CERTIFIED / LICENSED AS A
"BUILDING INSPECTOR".
LL. CONTRACTORS ARE FREE TO USE ANY PRODUCT WHICH MEETS THE GOVERNMENT'S
MINIMUM REQUIREMENTS AND NOT IN CONFLICT WITH OTHER CONTRACT PROVISIONS.
UNLESS INDICATED OTHERWISE ON THE PLANS OR SPECIFICATIONS (E.G. SOLE-
SOURCE), ALL LISTED MANUFACTURERS ARE THE BASIS OF DESIGN. FOR THESE BASIS
OF DESIGN PRODUCTS, OTHER MANUFACTURERS MAY BE SUBSTITUTED AS LONG AS
THE STANDARD OF QUALITY AND CHARACTERISTICS OF THE SUBSTITUTED
MANUFACTURER MEET OR EXCEED THE STANDARD OF QUALITY AND CHARACTERISTICS
OF THE BASIS OF DESIGN.
MM. CONTRACTOR IS RESPONSIBLE TO THOROUGHLY REVIEW THE HAZMAT REPORT
AND H SERIES DRAWINGS AND CROSS REFERENCE WITH THE ARCHITECTURAL
DRAWINGS FOR LOCATIONS OF HAZARDOUS MATERIALS FOR NEW PENETRATIONS,
DEMOLITION, AND PATCHING WHERE HAZARDOUS MATERIALS OCCUR OR ARE ASSUMED
TO BE PRESENT.
NN. WHERE CAULK IS REMOVED (AS REQUIRED BY NEW, DEMOLITION, OR PATCH WORK)
THAT HAS ASBESTOS CONTAINING MATERIALS, REPLACE WITH NEW CAULK.
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of
Engineers ®
A N
S I
'D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
/W
P A
F B
H
T H
W L in e D
/0 G e n e ra l_ S h e e ts
P h a se
I A
R C
H R
.r vt
/1
/2
:3 :0
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
P N
Z H
T V
F
Y P
JU
N
E
LOUISVILLE DISTRICT
J.
E
L D
E R
G
R O
D D
Y
J.
E
L D
E R
G-003
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J.
S
T E
W A
R T
G E
N E
R A
L N
O T
E S
CERTIFIED FINAL - JUNE 2021
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
DRAWING ABBREVIATIONS
LEGEND
CONCRETE/ PRECAST
CONCRETE
SOIL
SAND, EIFS FINISH COAT,
OR CEMENT PLASTER
BRICK
CMU
STONE
FIBERGLASS SEMI RIGID
INSULATION
FIBERGLASS BATT
INSULATION
MINERAL WOOL SEMI
RIGID INSULATION
EXPANDED
POLYSTYRENE RIGID
INSULATION
EXTRUDED
POLYSTYRENE RIGID
INSULATION
POLYISOCYANURATE
RIGID INSULATION
GYPSUM BOARD
EXTERIOR GYPSUM
SHEATHING
EXTERIOR CEMENT
BOARD
COATED GLASS MAT
WATER RESISTANT
GYP BD
PLYWOOD
COVER BOARD
MATERIALS
ANNOTATION CALLOUTS/DRAWING SYMBOLS
CEILING SYMBOLS
A ---------------------
A LABEL CLASS A DOOR
A/C AIR CONDITION
A/C UNIT AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AB ANCHOR BOLT
ACC ACCESSIBLE
ACS AUTOMATIC CONTROL SYSTEM
ACS DR ACCESS DOOR
ACS PNL ACCESS PANEL
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADMIN ADMINISTRATION
AFC ABOVE FINISHED COUNTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFS ABOVE FINISHED SLAB
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AIB AIR INFILTRATION BARRIER
ALT ALTERNATE
ALUM ALUMINUM
ANOD ANODIZE
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR AS REQUIRED
ARCH ARCHITECT
ASC ABOVE SUSPENDED CEILING
ASSY ASSEMBLY
ATC ACOUSTICAL TILE CEILING
AVG AVERAGE
AW ARCHITECTURAL WOODWORK
AWT ACOUSTICAL WALL TREATMENT
B ---------------------
B LABEL CLASS B DOOR
BALC BALCONY
BB BASEBOARD
BC BOOKCASE
BD BOARD
BDRY BOUNDARY
BFF BELOW FINISH FLOOR
BHMA BUILDER'S HARDWARE MANUFACTURER'S ASSOCIATION
BLDG BUILDING
BLKG BLOCKING
BLT IN BUILT-IN
BN BULLNOSE
BOS BOTTOM OF STEEL
BOT BOTTOM
BP BUILDING PAPER
BRKT BRACKET
BSMT BASEMENT
BTWN BETWEEN
BUR BUILT-UP ROOFING
C ---------------------
C CONC CAST CONCRETE
C LABEL CLASS C DOOR
CAB CABINET
CATW CATWALK
CAV CAVITY
CBB CEMENTITIOUS (BACKER) BOARD
CD CONSTRUCTION DOCUMENTS
CDW CHILLED DRINKING WATER
CEM PLAS CEMENT PLASTER
CER CERAMIC
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/CONTRACTOR INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CFLG COUNTERFLASHING
CFM CUBIC FEET PER MINUTE
CFMF COLD-FORMED METAL FRAMING
CFS CUBIC FEET PER SECOND
CG CORNER GUARD
CI CAST IRON
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLG DIFF CEILING DIFFUSER
CLG HT CEILING HEIGHT
CLL COLUMN LINE
CLO CLOSET
CLR COLOR
CLRM CLASSROOM
CMU CONCRETE MASONRY UNIT
CNDS CONDENSATE
CDR CARD READER
CO CLEANOUT
COL COLUMN
COMM COMMUNICATION
CONC CONCRETE
CONC FLR CONCRETE FLOOR
CONF CONFERENCE
CONT CONTINUE
COORD COORDINATE
CORR CORRIDOR
CP CONCRETE PIPE
CPT CARPET
CR CONTROL ROOM
CS CAST STONE
CSWK CASEWORK
CT CERAMIC TILE
CTB CERAMIC TILE BASE
CTF CERAMIC TILE FLOOR
CTR CENTER
CU FT CUBIC FEET
CW CASEMENT WINDOW
D ---------------------
D DEPTH
D LABEL CLASS D DOOR
DBL DOUBLE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIR DIRECTION
DIST DISTANCE
DOC DOCUMENT
DR DOOR
DS DOWNSPOUT
E ---------------------
E LABEL CLASS E DOOR
EA EACH
EF EACH FACE
EIFS EXTERIOR INSULATION AND FINISH SYSTEM
EJ EXPANSION JOINT
ES EACH SIDE
EL ELEVATION
ELEV ELEVATOR
ENTR ENTRANCE
EPS EXPANDED POLYSTYRENE BOARD (INSULATION)
EQ EQUAL
EWC ELECTRIC WATER COOLER
EXP EXPOSED
EXT EXTERIOR
EXT EXTINGUISHER
EXT GR EXTERIOR GRADE
F ---------------------
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FAS BD FASCIA BOARD
FC BRK FACE BRICK
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
1i
GRID / COLUMN
LINE
DESIGNATOR
EQUIPMENT NUMBER
DOOR NUMBER
1i
WALL TYPE
WINDOW TYPE
Room name
101 ROOM NAME/NUMBER
REVISION TAG
PLAN NORTH
NORTH ARROW w/
TRUE NORTH
INDICATION
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FED FEDERAL
FF FINISH FACE
FF EL FINISH FLOOR ELEVATION
FF INSUL FOIL BACKED INSULATION
FGL FIBERGLASS
FH FIRE HOSE
FHP FULL HEIGHT PARTITION
FIN FINISH
FIN BS FINISH BOTH SIDES
FIN FLR FINISH FLOOR
FIN GR FINISH GRADE
FIXT FIXTURE
FLDG FOLDING
FLEX FLEXIBLE
FLG FLOORING
FLMT FLUSH MOUNT
FLR FLOOR
FM FACTORY MUTUAL
FOC FACE OF CONCRETE
FOM FACE OF MASONRY
FR FIRE RESISTANT
FRG FIBER REINFORCED GYPSUM
FRMG FRAMING
FRP FIBERGLASS REINFORCED PLASTIC
FRTW FIRE RETARDANT TREATED WOOD
FS FEDERAL SPECIFICATION
FSTNR FASTENER
FT FEET
FTG FOOTING
FV FIELD VERIFY
FWC FABRIC WALLCOVERING
G ---------------------
G NATURAL GAS
GALV GALVANIZED
GB GRAB BAR
GFCI GOVERNMENT FURNISHED CONTRACTOR
INSTALLED
GFGI GOVERNMENT FURNISHED GOVERNMENT
INSTALLED
GFRG GLASS-FIBER-REINFORCED GYPSUM
GLZ GLAZING
GR FL GROUND FLOOR
GUT GUTTER
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
H ---------------------
HB HOSE BIBB
HDPE HIGH DENSITY POLYETHYLENE
HDW HARDWARE
HDWD HARDWOOD
HEPA HIGH EFFICIENCY PARTICULATE AIR
(FILTER)
HM HOLLOW METAL
HMD HOLLOW METAL DOOR
HORIZ HORIZONTAL
HT HEIGHT
HYDR HYDRAULIC
I ---------------------
IBC INTERNATIONAL BUILDING CODE
INSUL INSULATION
INT INTERIOR
ILO IN LIEU OF
J ---------------------
JAN JANITOR
K ---------------------
KPD KEYPAD
KIT KITCHEN
KPL KICKPLATE
L ---------------------
LAM LAMINATE
LAV LAVATORY
LBR LUMBER
LBS POUND
LDG LANDING
LF LINEAR FEET (FOOT)
LIB LIBRARY
LIN LINEAR
LKR LOCKER
LOC LOCATION
LT LIGHT
LVDR LOUVER DOOR
LVR LOUVER
M ---------------------
MACH RM MACHINE ROOM
MATL MATERIAL
MAX MAXIMUM
MC MOISTURE CONTENT
MD METAL DECK
MECH MECHANICAL
MECH RM MECHANICAL ROOM
MEMB MEMBRANE
MF MILL FINISH
MFR MANUFACTURER
MID MIDDLE
MIL STD MILITARY STANDARD
MIN MINIMUM, MINUTE
MIRR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING (MOULDING)
MO MASONRY OPENING
MOD MODIFY
MB MOISTURE BARRIER
MTG MOUNTING
MTL METAL
MVBL MOVABLE
MWP MEMBRANE WATERPROOFING
N ---------------------
N NORTH
NA NOT APPLICABLE
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NO PAINT
NRC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
O -------------------
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OFD OVERFLOW DRAIN
OFF OFFICE
OGL OBSCURE GLASS
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
OPQ OPAQUE
OWSJ OPEN WEB STEEL JOIST
OPR OPERABLE
ORD OVERFLOW ROOF DRAIN
ORIG ORIGINAL
P --------------------
PA PUBLIC ADDRESS
PAR PARAPET
PAT PATTERN
PB PULL BOX
PBD PARTICLEBOARD
PCC PRECAST CONCRETE
PCF POUNDS PER CUBIC FOOT
PCT PERCENT
PERF PERFORATED
PERIM PERIMETER
PH PHASE
PIL PILASTER
PL PROPERTY LINE
PL GL PLATE GLASS
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLG PILING
PLYWD PLYWOOD
PNL PANEL
PP PL PUSH/PULL PLATE
PR PAIR
PRCST PRECAST
PRKG PARKING
PS CONC PRESTRESSED CONCRETE
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
PT PRESSURE TREATED
PTD PAPER TOWEL DISPENSER
PTDR PAPER TOWEL DISPENSER AND
RECEPTACLE
PTN PARTITION
PWR POWER
Q --------------------
QT QUARRY TILE
QTY QUANTITY
R --------------------
RB RESILIENT BASE
RBM REINFORCED BRICK MASONRY
RBR RUBBER
RC REINFORCED CONCRETE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
RDG INS RIGID INSULATION, SOLID
REC RECESSED
REC ROOMRECREATION ROOM
REF REFERENCE
REM REMOVABLE
REP REPAIR
REPL REPLACE
REQ REQUIRE
REQD REQUIRED
RESIL RESILIENT
REST RESTROOM
RF RESILIENT FLOORING
RFG ROOFING
RH ROOF HATCH
RHR RIGHT HAND REVERSE
RL ROOF LEADER
RLG RAILING
RM ROOM
RO ROUGH OPENING
RSD ROLLING STEEL DOOR
RV ROOF VENT
RVL REVEAL
S --------------------
SB SPLASH BLOCK
SC SEALED CONCRETE
SCHED SCHEDULE
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SFTWD SOFTWOOD
SGL SINGLE
SHT MTL FLASH SHEET METAL (FLASHING)
SHTHG SHEATHING
SHV SHELVING
SIM SIMILAR
SJ SCORED JOINT
SKLT SKYLIGHT
SLNT SEALANT
SMK SMOKE
SMLS SEAMLESS
SP EL SPOT ELEVATION
SPEC SPECIFICATION
SQ SQUARE
SQ IN SQUARE INCH
SQ YD SQUARE YARD
SST STAINLESS STEEL
ST STAIRS
STD STANDARD
STL JST STEEL JOIST
STL RF DK STEEL ROOF DECK
STOR STORAGE
STR STRINGERS
STRB/HRN STROBE/HORN
SUB FL SUBFLOOR
SV SHEET VINYL
SW SIDEWALK
T --------------------
T TREAD
T/S TUB/SHOWER
TC TERRA COTTA
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
TER TERRAZZO
TFF TOP OF FINISH FLOOR
THK THICKNESS
TK BD TACKBOARD
TMPD GL TEMPERED GLASS
TN TRUE NORTH
TOF TOP OF FOOTING
TOM TOP OF MASONRY
TOP TOP OF PARAPET
TOPO TOPOGRAPHY
TOS TOP OF SLAB
TRANS TRANSOM
TRTD TREATED
TV TELEVISION
TYP TYPICAL
2' x 2' ACT CEILING
4' x 4' ACT CEILING
GYP. BD. CEILING
1' x 1' ACT CEILING
ELEVATION NUMBER
SECTION
EXTERIOR ELEVATION
ENLARGEMENT,
DETAIL
SPOT ELEVATION
Name
Elevation
FLOOR LEVEL & NAME
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
# SHEET KEYNOTE
INTERIOR ELEVATION
A-101
PLATE NUMBER WHERE
SECTION/DETAIL IS
DRAWN
A101
A101
SIM
A101
1 Ref
R e f
1Ref
R e f
DOOR CONVENTION
EXISTING
NEW
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of
Engineers ®
A N
S I
'D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
/W
P A
F B
H
T H
W L in e D
/0 G e n e ra l_ S h e e ts
P h a se
I A
R C
H R
.r vt
/1
/2
:3 :0
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
P N
Z H
T V
F
Y P
JU
N
E
LOUISVILLE DISTRICT
J.
E
L D
E R
G
R O
D D
Y
J.
E
L D
E R
G-004
L O
U
IS
V
IL
L E
D
IS
T R
IC
T
L O
U
IS
V
IL
L E
K
E N
T U
C K
Y
J.
S
T E
W A
R T
A B
B R
E V
IA
T
IO
N
S A
N D
S Y
M B
O L S
CERTIFIED FINAL - JUNE 2021
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
CAR WASH
61'
TD
57'
TD
EXIT
EXIT
APPLICABLE CODES AND STANDARDS
• UFC 1-200-01, DoD BUILDING CODE (08 OCTOBER 2019)
• UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS
(CHANGE 1, 20 MARCH 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
(CHANGE 5, 24 SEPTEMBER 2020)
• NFPA 1, FIRE CODE, AS ADOPTED BY UFC (2021)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS (2019)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES (2019)
• NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEM (2021)
• NFPA 101, LIFE SAFETY CODE (2018)
• NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER
OPENING PROTECTIVES (2019)
• INTERNATIONAL BUILDING CODE (IBC), AS ADOPTED BY UFC
PROJECT CLASSIFICATION PER UFC 3-600-01
CATEGORY OF WORK: RENOVATION
PROJECT TYPE: MAJOR PROJECT
LIFE SAFETY SHEET NOTES
1. NO FIRE RESISITANCE RATING OR SMOKE RATING
REQUIREMENTS BETWEEN THE GAS FIRED UNIT HEATERS AND
PROJECT AREA.
LIFE SAFETY SUMMARY
EXISTING BUILDING OCCUPANCY: INDUSTRIAL
PROJECT AREA OCCUPANCY: INDUSTRIAL
SPRINKLER PROTECTED: NO
FIRE ALARM SYSTEM: NO
MASS NOTIFICATION SYSTEM: NO
TRAVEL DISTANCE: REQUIRED 200 FT (MAX); PROVIDED
61 FT.
COMMON PATH OF TRAVEL: N/A
DEAD END CORRIDOR: N/A
MINIMUM EGRESS WIDTH: 32 INCHES
PROVIDED EGRESS: 34 INCHES
DOOR CAPACITY FACTOR: 0.2 INCHES/PERSON
INTERIOR WALL FINISH: A, B, OR C
INTERIOR FLOOR FINISH: I OR II
LIFE SAFETY LEGEND
TRAVEL DISTANCE (TD)
XXX EXIT IDENTIFIER
EXIT
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of Engineers ®
A N
S I '
D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
W
P A
F B
H
T H
W L in e
D /0
B
LD
G
_3
_M
E P
F _R
.r v t
6/
/2
5:
:2
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
(B U
IL
D
IN
G
P N
Z H
T V
F
Y P
JU
N
E
W
2Q R
-X X
-X -X
X X
X
W
2Q R
-X X
-X -X
X X
X
LOUISVILLE DISTRICT
J.
M
U S
G R
O V
E
P . B
U T
T
J.
M
U S
G R
O V
E
GI101J
LO
U
IS
V
IL
LE
D
IS
T R
IC
T
LO
U
IS
V
IL
LE
, K E
N T
U C
K Y
J.
Z
IM
M
E R
M A
N
F A
C
IL
IT
Y
L
IF
E
S A
F E
T Y
P L A
N
CERTIFIED FINAL - JUNE 2021
30055
SCALE : 1/4" = 1'-0"A1 FACILITY 30055 - LIFE SAFETY PLAN
OCCUPANT LOAD - FIRST FLOOR
ROOM NO. ROOM NAME OCCUPANCY USE
AREA
(APPROX.)
OCCUPANT
LOAD
FACTOR
OCCUPANT
LOAD
101 CAR WASH STORAGE AND UTILITY SPACES 1997 SF 500 4
TOTAL 4
PLAN NORTH
4'0 8' 16'
KEY PLAN - AREA A
30055
EXIT SUMMARY - FIRST FLOOR
EXIT
IDENTIFIER
DOOR
CLEAR
WIDTH
(IN)
DOOR
CAPACITY
FACTOR
(IN/PERSON)
DOOR
CAPACITY
(PERSONS)
STAIR
WIDTH
(IN)
STAIR
CAPACITY
FACTOR
(IN/PERSONS)
STAIR
CAPACITY
(PERSONS)
LIMITING
CAPACITY
(PERSONS)
ACTUAL USE
(PERSONS)
101 34 0.2 170 N/A N/A N/A 170 2
102 34 0.2 170 N/A N/A N/A 170 2
TOTAL 4
THIS DRAWING IS FOR REFERENCE ONLY. IT IS NOT PART OF THE
CONSTRUCTION CONTRACT AND ALL INFORMATION HERE IS LOCATED
ON CONSTRUCTION DOCUMENTS
EGRESS ARRANGEMENT FIRST FLOOR
MARK DISTANCE FROM ROOM TO EXIT
TD 57' CAR WASH 101 EXIT 101
TD 61' CAR WASH 101 EXIT 102
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
ARIMS: 200A Disposition: Maintain for 15yrs after construction schwarz Snapshot
X X
X X
X X
X X
X X
X X
X X
X X
X
X XX X
X X
X X
X X
X X
X
X XX X X X X X X
X X
X X X XX X
X XX X X
X XX X X X X X
X X
X X
X X
X X
X X
X X
X
APPLICABLE CODES AND STANDARDS
• UFC 1-200-01, DoD BUILDING CODE (08 OCTOBER 2019)
• UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS
(CHANGE 1, 20 MARCH 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
(CHANGE 5, 24 SEPTEMBER 2020)
• NFPA 1, FIRE CODE, AS ADOPTED BY UFC (2021)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS (2019)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES (2019)
• NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS (2021)
• NFPA 101, LIFE SAFETY CODE (2018)
• NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER
OPENING PROTECTIVES (2019)
• INTERNATIONAL BUILDING CODE (IBC), AS ADOPTED BY UFC
PROJECT CLASSIFICATION PER UFC 3-600-01
CATEGORY OF WORK: RENOVATION
PROJECT TYPE: MAJOR PROJECT
LIFE SAFETY SHEET NOTES
1. NO FIRE RESISITANCE RATING OR SMOKE RATING
REQUIREMENTS BETWEEN THE GAS FIRED UNIT HEATERS AND
PROJECT AREA.
LIFE SAFETY SUMMARY
EXISTING BUILDING OCCUPANCY:
STORAGE WITH ORDINARY HAZARD STORAGE
CONTENTS (PREDOMINANT OCCUPANCY)
EXISTING BUSINESS (INCIDENTAL OCCUPANCY)
PROJECT AREA OCCUPANCY: STORAGE WITH
ORDINARY HAZARD STORAGE CONTENTS
SPRINKLER PROTECTED: YES
FIRE ALARM SYSTEM: NO
MASS NOTIFICATION SYSTEM: NO
TRAVEL DISTANCE: REQUIRED 400 FT (MAX); PROVIDED
259 FT.
COMMON PATH OF TRAVEL: REQUIRED 100 FT (MAX);
PROVIDED 160 FT.
DEAD END CORRIDOR: N/A
MINIMUM EGRESS WIDTH: 32 INCHES
PROVIDED EGRESS: 34 INCHES
DOOR CAPACITY FACTOR: 0.2 INCHES/PERSON
INTERIOR WALL FINISH: A, B, OR C
INTERIOR FLOOR FINISH: I OR II
LIFE SAFETY LEGEND
XXX EXIT IDENTIFIER
TRAVEL DISTANCE (TD)
COMMON PATH OF TRAVEL (CPT)
EXIT
SMOKE PARTITION
• DOORS TO RESIST THE PASSAGE OF
SMOKE; SMOKE SEALS NOT REQUIRED
• DOORS REQURIED TO BE SELF-CLOSING
AND POSITIVE LATCHING
• SMOKE DAMPERS NOT REQUIRED
• FIRE DAMPERS NOT REQUIRED
PROJECT AREA
(NO HATCHING)
OUTSIDE OF
PROJECT AREA
WAREHOUSE
EXIT
102E
EXIT
102B
EXIT
102C
EXIT
102D
160'
CPT
60'
TD
156'
TD
259'
TD
134'
TD
127'
TD
EXIT
102A
MECH RM
MECH RM
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
SHEET KEYNOTES:
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of Engineers ®
A N
S I '
D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
W
P A
F B
H
T H
W L in e
D /0
B
LD
G
_3
_M
E P
F _R
.r v t
6/
/2
5:
:1
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
(B U
IL
D
IN
G
P N
Z H
T V
F
Y P
JU
N
E
W
2Q R
-X X
-X -X
X X
X
W
2Q R
-X X
-X -X
X X
X
LOUISVILLE DISTRICT
J.
M
U S
G R
O V
E
P . B
U T
T
J.
M
U S
G R
O V
E
GI101K
LO
U
IS
V
IL
LE
D
IS
T R
IC
T
LO
U
IS
V
IL
LE
, K E
N T
U C
K Y
J.
Z
IM
M
E R
M A
N
F A
C
IL
IT
Y
L
IF
E
S A
F E
T Y
P L A
N
CERTIFIED FINAL - JUNE 2021
30069
EGRESS ARRANGEMENT FIRST FLOOR
MARK DISTANCE FROM ROOM TO EXIT
CPT 160' WAREHOUSE 103 WAREHOUSE 102
TD 60' WAREHOUSE 103 EXIT 102D
TD 127' WAREHOUSE 103 EXIT 102A
TD 134' WAREHOUSE 103 EXIT 102B
TD 156' WAREHOUSE 103 EXIT 102C
TD 259' WAREHOUSE 103 EXIT 102C
EXIT SUMMARY - FIRST FLOOR
EXIT
IDENTIFIER
DOOR
CLEAR
WIDTH
(IN)
DOOR
CAPACITY
FACTOR
(IN/PERSON)
DOOR
CAPACITY
(PERSONS)
STAIR
WIDTH
(IN)
STAIR
CAPACITY
FACTOR
(IN/PERSONS)
STAIR
CAPACITY
(PERSONS)
LIMITING
CAPACITY
(PERSONS)
ACTUAL
USE
(PERSONS)
120A 34 0.2 170 N/A N/A N/A 170 15
102B 34 0.2 170 N/A N/A N/A 170 16
102C 34 0.2 170 N/A N/A N/A 170 16
102D 34 0.2 170 N/A N/A N/A 170 16
102E 34 0.2 170 N/A N/A N/A 170 16
TOTAL 79
OCCUPANT LOAD - FIRST FLOOR
ROOM NO. ROOM NAME OCCUPANCY USE
AREA
(APPROX.)
OCCUPANT
LOAD
FACTOR
OCCUPANT
LOAD
102 MECH RM STORAGE AND UTILITY SPACES 38 SF 500 1
103 WAREHOUSE STORAGE AND UTILITY SPACES 38839 SF 500 78
TOTAL 79
PLAN NORTH
0 8' 16' 32'SCALE : 1/16" = 1'-0"A1 FACILITY 30069 LIFE SAFETY PLAN
KEY PLAN - AREA A
30069
901 EXISTING EGRESS ARRANGEMENT TO REMAIN. WORK PERFORMED
IN THE PROJECT AREA DOES NOT MAKE THE BUILDING LESS CODE
CONFORMING THAN IT WAS BEFORE THE WORK IN THIS PROJECT
SCOPE IS PERFORMED.
906 PROVIDE COMBINATION EXIT SIGN/EMERGENCY LIGHT. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
909 PROVIDE EMERGENCY LIGHTING. REFER TO ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
912 THIS AREA IS CONSIDERED PART OF THE PROJECT AREA ONLY AS
SUPPORT FOR THE WORK OCCURING WHERE MECHANICAL
EQUIPMENT IS BEING PROVIDED AT OTHER LOCATIONS IN THE
BUILDING. EVALUATIONS OF LIFE SAFETY, FIRE ALARM AND OR
FIRE SUPPRESSION SYSTEMS ARE NOT BEING PROVIDED UNDER
THIS SCOPE OF WORK.
THIS DRAWING IS FOR REFERENCE ONLY. IT IS NOT PART OF THE
CONSTRUCTION CONTRACT AND ALL INFORMATION HERE IS LOCATED
ON CONSTRUCTION DOCUMENTS
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
ARIMS: 200A Disposition: Maintain for 15yrs after construction
APPLICABLE CODES AND STANDARDS
• UFC 1-200-01, DoD BUILDING CODE (08 OCTOBER 2019)
• UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS
(CHANGE 1, 20 MARCH 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
(CHANGE 5, 24 SEPTEMBER 2020)
• NFPA 1, FIRE CODE, AS ADOPTED BY UFC (2021)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS (2019)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES (2019)
• NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS (2021)
• NFPA 101, LIFE SAFETY CODE (2018)
• NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER
OPENING PROTECTIVES (2019)
• INTERNATIONAL BUILDING CODE (IBC), AS ADOPTED BY UFC
PROJECT CLASSIFICATION PER UFC 3-600-01
CATEGORY OF WORK: RENOVATION
PROJECT TYPE: MAJOR PROJECT
LIFE SAFETY SHEET NOTES
1. NO FIRE RESISITANCE RATING OR SMOKE RATING
REQUIREMENTS BETWEEN THE GAS FIRED UNIT HEATERS AND
PROJECT AREAS.
LIFE SAFETY SUMMARY
EXISTING BUILDING OCCUPANCY:
STORAGE WITH ORDINARY HAZARD STORAGE
CONTENTS (PREDOMINANT OCCUPNACY)
EXISTING BUSINESS (INCIDENTAL OCCUPANCY)
PROJECT AREA OCCUPANCY: STORAGE WITH
ORDINARY HAZARD STORAGE CONTENTS
SPRINKLER PROTECTED: YES
FIRE ALARM SYSTEM: NO
MASS NOTIFICATION SYSTEM: NO
TRAVEL DISTANCE: REQUIRED 400 FT (MAX); PROVIDED
127 FT.
COMMON PATH OF TRAVEL: REQUIRED 100 FT (MAX);
PROVIDED 31 FT.
DEAD END CORRIDOR: N/A
MINIMUM EGRESS WIDTH: 32 INCHES
PROVIDED EGRESS: 34 INCHES
DOOR CAPACITY FACTOR: 0.2 INCHES/PERSON
INTERIOR WALL FINISH: A, B, OR C
INTERIOR FLOOR FINISH: I OR II
LIFE SAFETY LEGEND
XXX EXIT IDENTIFIER
TRAVEL DISTANCE (TD)
EXIT
PROJECT AREA
(NO HATCHING)
OUTSIDE OF
PROJECT AREA
96'
TD
127'
TD
115'
TD
BAY 2
BAY 1
EXIT
VV
EXIT
WW
EXIT
XX
31'
CPT
YY
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
SHEET KEYNOTES:
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
L
IC
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of Engineers ®
A N
S I '
D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
W
P A
F B
H
T H
W L in e
D /0
B
LD
G
_3
_M
E P
F _R
.r v t
6/
/2
5:
:3
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
(B U
IL
D
IN
G
P N
Z H
T V
F
Y P
JU
N
E
W
2Q R
-X X
-X -X
X X
X
W
2Q R
-X X
-X -X
X X
X
LOUISVILLE DISTRICT
J.
M
U S
G R
O V
E
P . B
U T
T
J.
M
U S
G R
O V
E
GI101L
LO
U
IS
V
IL
LE
D
IS
T R
IC
T
LO
U
IS
V
IL
LE
, K E
N T
U C
K Y
J.
Z
IM
M
E R
M A
N
F A
C
IL
IT
Y
L
IF
E
S A
F E
T Y
P L A
N
CERTIFIED FINAL - JUNE 2021
30109
EGRESS ARRANGEMENT FIRST FLOOR
MARK DISTANCE FROM ROOM TO EXIT
CPT 31' BAY 2 102 BAY 1 101
TD 96' BAY 2 102 EXIT VV
TD 115' BAY 1 101 EXIT VV
TD 127' BAY 2 102 EXIT WW
EXIT SUMMARY - FIRST FLOOR
EXIT
IDENTIFIER
DOOR
CLEAR
WIDTH
(IN)
DOOR
CAPACITY
FACTOR
(IN/PERSON)
DOOR
CAPACITY
(PERSONS)
STAIR
WIDTH
(IN)
STAIR
CAPACITY
FACTOR
(IN/PERSONS)
STAIR
CAPACITY
(PERSONS)
LIMITING
CAPACITY
(PERSONS)
ACTUAL
USE
(PERSONS)
VV 34 0.2 170 N/A N/A N/A 170 6
WW 34 0.2 170 N/A N/A N/A 170 6
XX 34 0.2 170 N/A N/A N/A 170 4
YY 34 0.2 170 N/A N/A N/A 170 9
TOTAL 27
OCCUPANT LOAD - FIRST FLOOR
ROOM NO. ROOM NAME OCCUPANCY USE
AREA
(APPROX.)
OCCUPANT
LOAD
FACTOR
OCCUPANT
LOAD
101 BAY 1 STORAGE AND UTILITY SPACES 7909 SF 500 16
102 BAY 2 STORAGE AND UTILITY SPACES 4366 SF 500 9
TOTAL 25
PLAN NORTH
0 8' 16' 32'
SCALE : 3/32" = 1'-0"A1 FACILITY 30109 - LIFE SAFETY PLAN
KEY PLAN - AREA A
30109
THIS DRAWING IS FOR REFERENCE ONLY. IT IS NOT
PART OF THE CONSTRUCTION CONTRACT AND ALL
INFORMATION HERE IS LOCATED ON CONSTRUCTION
DOCUMENTS
906 PROVIDE COMBINATION EXIT SIGN/EMERGENCY LIGHT. REFER TO
ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
909 PROVIDE EMERGENCY LIGHTING. REFER TO ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION.
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
ARIMS: 200A Disposition: Maintain for 15yrs after construction
COF
COF
UP
UP
REF
REF
EXIT
WW
32'
TD MECH RM
106A
APPLICABLE CODES AND STANDARDS
• UFC 1-200-01, DoD BUILDING CODE (08 OCTOBER 2019)
• UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS
(CHANGE 1, 20 MARCH 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
(CHANGE 5, 24 SEPTEMBER 2020)
• NFPA 1, FIRE CODE, AS ADOPTED BY UFC (2021)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS (2019)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES (2019)
• NFPA 90A, STANDARD FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS (2021)
• NFPA 101, LIFE SAFETY CODE (2018)
• NFPA 105, STANDARD FOR SMOKE DOOR ASSEMBLIES AND OTHER
OPENING PROTECTIVES (2019)
• INTERNATIONAL BUILDING CODE (IBC), AS ADOPTED BY UFC
PROJECT CLASSIFICATION PER UFC 3-600-01
CATEGORY OF WORK: RENOVATION
PROJECT TYPE: NOT A MAJOR PROJECT
LIFE SAFETY SHEET NOTES
1. NON-RATED SMOKE PARTITION PERMITTED TO SEPARATE THE
PROJECT AREA SINCE BUILDING IS PROVIDED WITH SPRINKLER
PROTECTION.
LIFE SAFETY SUMMARY
EXISTING BUILDING OCCUPANCY:
EXISTING BUSINESS (PREDOMINANT OCCUPANCY),
EXISTING ASSEMBLY (INCIDENTAL OCCUPANCY),
STORAGE (INCIDENTAL OCCUPANCY)
PROJECT AREA OCCUPANCY: STORAGE
SPRINKLER PROTECTED: YES
FIRE ALARM SYSTEM: YES
MASS NOTIFICATION SYSTEM: YES
TRAVEL DISTANCE: REQUIRED 250FT (MAX); PROVIDED
32 FT.
COMMON PATH OF TRAVEL: N/A
DEAD END CORRIDOR: N/A
MINIMUM EGRESS WIDTH: 32 INCHES
PROVIDED EGRESS: 34 INCHES
DOOR CAPACITY FACTOR: 0.2 INCHES/PERSON
INTERIOR WALL FINISH: A, B, OR C
INTERIOR FLOOR FINISH: I OR II
LIFE SAFETY LEGEND
SMOKE PARTITION
• DOORS TO RESIST THE PASSAGE OF
SMOKE; SMOKE SEALS NOT REQUIRED
• DOORS REQURIED TO BE SELF-CLOSING
AND POSITIVE LATCHING
• SMOKE DAMPERS NOT REQUIRED
• FIRE DAMPERS NOT REQUIRED
XXX EXIT IDENTIFIER
TRAVEL DISTANCE (TD)
EXIT
PROJECT AREA
(NO HATCHING)
OUTSIDE OF
PROJECT AREA
A R
C H
IT
E
C T
U R
E E
N G
IN
E
E R
IN
G
G E
O S
P A
T
IA
L
1 2 3 4 5
D R
A W
N B
Y
D E
S
IG
N E
D B
Y
S U
B M
IT
B
Y
S
IZ
E
F
IL
E N
A M
E
IS
S
U E
D A
T E
C O
N T
R A
C T
N O
S O
LI
C
IT
A
T
IO
N N
O
U S
A R
M Y
C O
R P
S O
F E
N G
IN
E
E R
S
C K
E C
K E
D B
Y
US Army Corps of Engineers ®
A N
S I '
D
D
C
B
A
F
IL
E N
U M
B E
R
SHEET ID
B
IM
W
P A
F B
H
T H
W L in e
D /0
B
LD
G
_3
_M
E P
F _R
.r v t
6/
/2
5:
:5
P
M W R
IG
H
T -P
A T
T E
R S
O N
A
IR
F O
R C
E B
A S
E
W P
A F
B
O H
IO
R
E P
A
IR
S T
E A
M
H T
H W
L
IN
E D
P
H A
S E
I
(B U
IL
D
IN
G
P N
Z H
T V
F
Y P
JU
N
E
W
2Q R
-X X
-X -X
X X
X
W
2Q R
-X X
-X -X
X X
X
LOUSIVILLE DISTRICT
J.
M
U S
G R
O V
E
P . B
U T
T
J.
M
U S
G R
O V
E
GI101M
LO
U
S
IV
IL
LE
D
IS
T R
IC
T
LO
U
IS
V
IL
LE
, K E
N T
U C
K Y
J.
Z
IM
M
E R
M A
N
F A
C
IL
IT
Y
L
IF
E
S A
F E
T Y
P L A
N
CERTIFIED FINAL - JUNE 2021
30110
SCALE : 1/16" = 1'-0"A1 FACILITY 30110 - LIFE SAFETY PLAN
EGRESS ARRANGEMENT FIRST FLOOR
MARK DISTANCE FROM ROOM TO EXIT
TD 32' MECH RM 106A EXIT WW
EXIT SUMMARY - FIRST FLOOR
EXIT
IDENTIFIER
DOOR
CLEAR
WIDTH
(IN)
DOOR
CAPACITY
FACTOR
(IN/PERSON)
DOOR
CAPACITY
(PERSONS)
STAIR
WIDTH
(IN)
STAIR
CAPACITY
FACTOR
(IN/PERSONS)
STAIR
CAPACITY
(PERSONS)
LIMITING
CAPACITY
(PERSONS)
ACTUAL
USE
(PERSONS)
WW 68 0.2 340 N/A N/A N/A 340 2
TOTAL 2
OCCUPANT LOAD - FIRST FLOOR
ROOM NO. ROOM NAME OCCUPANCY USE
AREA
(APPROX.)
OCCUPANT
LOAD
FACTOR
OCCUPANT
LOAD
106A MECH RM STORAGE AND UTILITY SPACES 541 SF 500 2
TOTAL 2
PLAN NORTH
0 8' 16' 32'
KEY PLAN - AREA A
30110
THIS DRAWING IS FOR REFERENCE ONLY. IT IS NOT PART OF THE
CONSTRUCTION CONTRACT AND ALL INFORMATION HERE IS LOCATED
ON CONSTRUCTION DOCUMENTS
M A
R K
D E
S C
R
IP
T
IO
N D
A T
E A
P P
R
W
2Q R
R
-0
ARIMS: 200A Disposition: Maintain for 15yrs after construction
14'
TD
EXIT
YY
MECH RM
SECURE STORAGE
Space
Space
APPLICABLE CODES AND STANDARDS
• UFC 1-200-01, DoD BUILDING CODE (08 OCTOBER 2019)
• UFC 3-520-01, INTERIOR ELECTRICAL SYSTEMS
(CHANGE 1, 20 MARCH 2019)
• UFC 3-600-01, FIRE PROTECTION ENGINEERING FOR FACILITIES
(CHANGE 5, 24 SEPTEMBER 2020)
• NFPA 1, FIRE CODE, AS ADOPTED BY UFC (2021)
• NFPA 13, STANDARD FOR THE INSTALLATION OF SPRINKLER
SYSTEMS (2019)
• NFPA 70, NATIONAL ELECTRIC CODE (2020)
• NFPA 72, NATIONAL FIRE ALARM AND SIGNALING CODE (2019)
• NFPA 80, STANDARD FOR FIRE DOORS AND OTHER OPENING
PROTECTIVES (2019)
• NFPA 90A, STANDARD FOR…
This is the start of the file's text. The full file is on GovTribe.