W912QR21R0015Plans_Vol2-0000.pdf

PDF 35 MB Posted

Attached to
Ft. Campbell Vehicle Maintenance Shop
Solicitation number
W912QR21R0015
Issued by

About this file

This document provides details on a federal contract solicitation for construction services. The U.S. Army Corps of Engineers Engineering District Louisville is soliciting proposals to construct a new Vehicle Maintenance Shop at Fort Campbell, Kentucky with an estimated construction cost between $25-100 million. The NAICS code for this opportunity is 236220 with a size standard of $39.5 million. This is a full and open procurement that requires a 10% price evaluation for HUBZone businesses. The response deadline will be provided on the formal solicitation release scheduled for April 16, 2021, at which time additional pre-proposal and question submission details will be available. Interested offerors must comply with System for Award Management registration requirements.

View the file

Other files

Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

STEIN.JEFFREY.1232249877 Digitally signed by STEIN.JEFFREY.1232249877 Date: 2020.12.15 11:54:53 -05'00'

FUNK.TROY.ALAN.1039429256 Digitally signed by FUNK.TROY.ALAN.1039429256 Date: 2020.12.15 12:20:54 -05'00'

HENDREN.TRACY.LEE.1229932868

2020.12.15 12:55:31 -05'00'

W

2Q R

R

-0

ARIMS: 200A Disposition: Maintain for 15yrs after construction

16 March 2021

W912QR21R0015

A N

S I

D

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

S A

V A

N N

A H D

IS

T R

IC

T

W

O G

L E

T H

O R

P E A

V E

S A

V A

N N

A H

G A

C H

E C

K E

D B

Y

D R

A W

N B

Y

IS

S

U E D

A T

E

J

H A

IR

E

J

H A

IR

E

J

M C

T

IE

R N

A N

J S

T E

IN

D E

C E

M B

E R

W

Q R -2

-R -0

F O

R T C

A M

P B

E L L

K E

N T

U C

K Y

V E

H

IC

L E M

A

IN

T E

N A

N C

E S

H O

P

P N

P

:3

V O

L U

M E B

U

IL

D

IN

G

SHEET ID

READY TO ADVERTISE (RTA)

F

IL

E N

A M

E

B

C

D

E

F

G

2 3 4 5 6 7 8 9 10

S O

L

IC

IT

A T

IO

N N

O

D E

S

IG

N E

D B

Y

A

M A

R K

S

IZ

E

S U

B M

IT

T E

D B

Y

D A

T E

C O

N T

R A

C T N

O

®of Engineers

US Army Corps k6enxjlh

15-DEC-2020 11:24

C:\Users\k6enxjlh\Desktop\Projects\ProjectWise_Projects\Cam0009\05_W912HN-##-#-####\PDF\Volume 2\GI001V2.dgn

C A

T E

G O

R Y C

O D

E

-1

-0

GI001

IN

D

E X O

F D

R A

W

IN

G S

G I0

V .d g n

SHEET ID.

INDEX OF DRAWINGS

D E

S C

R

IP

T

IO

N

D

R

M A

R T

IN

L

U T

H E

R K

IN

G J

R P

L

U .S

A R

M Y C

O R

P S O

F E

N G

IN

E E

R S

L O

U

IS

V

IL

L E D

IS

T R

IC

T

L O

U

IS

V

IL

L E

K Y

SHEET ID.

TITLESHEET ID.

TITLETITLE

G-001 COVER SHEET

GI001 INDEX OF DRAWINGS

GI002 GENERAL NOTES, ABBREVIATIONS

S-001 GENERAL STRUCTURAL NOTES

S-002 GENERAL STRUCTURAL NOTES

SB101 COMPOSITE PLANS

SB102 FOUNDATION PLAN - AREA A

SB103 FOUNDATION PLAN - AREA B

SB104 SLAB PLAN - AREA A

SB105 SLAB PLAN - AREA B

SB501 FOUNDATION DETAILS

SB502 FOUNDATION DETAILS

SB503 FOUNDATION DETAILS

SB504 FOUNDATION DETAILS

SB505 MASONRY DETAILS

SB506 MASONRY DETAILS

SB601 FOUNDATION SCHEDULES

SF100 MASONRY FRAMING

SF101 SECOND FLOOR FRAMING PLAN

SF102 COMPOSITE ROOF FRAMING PLAN

SF103 HIGH ROOF FRAMING PLAN - AREA A

SF104 LOW ROOF FRAMING PLAN - AREA B

SF201 MASONRY DETAILS

SF301 FRAMING ELEVATIONS

SF302 FRAMING ELEVATIONS

SF303 FRAMING ELEVATIONS

SF304 FRAMING ELEVATIONS

SF401 ENLARGED MAINTENACE PIT PLAN AND DETAILS

SF402 ENLARGED MAINTENANCE PIT PLAN AND DETAILS

SF403 CONCRETE VAULT SECTION AND DETAILS

SF404 FRAMING SECTIONS AND DETAILS

SF501 FRAMING DETAILS

SF502 FRAMING DETAILS

SF503 FRAMING DETAILS

SF504 FRAMING DETAILS

SF505 LADDER AND CATWALK DETAILS

A-001 GENERAL NOTES AND SYMBOLS

A-100 COMPOSITE FLOOR PLANS

A-101 FIRST FLOOR PLAN - AREA A

A-102 FIRST FLOOR PLAN - AREA B

A-103 SECOND FLOOR PLAN

A-104 CLERESTORY PLAN

A-105 COMPOSITE ROOF PLAN

A-106 ROOF PLAN - AREA A

A-107 ROOF PLAN - AREA B

A-110 COMPOSITE REFLECTED CEILING PLANS

A-111 REFLECTED CEILING PLANS - FIRST FLOOR

A-112 REFLECTED CEILING PLANS - FIRST FLOOR

A-113 REFLECTED CEILING PLANS - SECOND FLOOR

A-201 EXTERIOR ELEVATIONS

A-202 EXTERIOR ELEVATIONS

A-203 EXTERIOR ELEVATIONS

A-204 EXTERIOR ELEVATIONS

A-301 BUILDING SECTIONS

A-302 BUILDING SECTIONS

A-303 BUILDING SECTIONS

A-310 WALL SECTIONS

A-311 WALL SECTIONS

A-312 WALL SECTIONS

A-313 WALL SECTIONS AND DETAILS

A-314 WALL SECTIONS AND DETAILS

A-401 ENLARGED STAIR AND ELEVATOR PLANS

A-402 ENLARGED STAIR SECTIONS

A-403 ENLARGED STAIR SECTIONS

A-404 ENLARGED ELEVATOR SECTIONS

A-405 STAIR DETAILS

A-406 ENLARGED RESTROOM PLANS AND ELEVATIONS

A-407 ENLARGED RESTROOM PLANS AND ELEVATIONS

A-408 ENLARGED TRAINING ROOM AND CASEWORK ELEVATIONS AND SECTIONS

A-409 ENLARGED MAINTENANCE PIT DETAILS

A-501 ROOF DETAILS

A-502 ROOF DETAILS

A-503 ROOF DETAILS

A-504 ROOF DETAILS

A-505 PARTITION TYPES

A-506 PARTITIONS TYPES AND DETAILS

A-507 EXTERIOR DETAILS

A-508 EXTERIOR DETAILS

A-509 INTERIOR DETAILS

A-510 INTERIOR DETAILS

A-601 ROOM FINISH SCHEDULE

A-602 DOOR SCHEDULE AND DETAILS

A-603 DOOR DETAILS

A-604 DOOR DETAILS

A-605 WINDOW TYPES AND DETAILS

A-606 WINDOW DETAILS

A-607 LOUVER SCHEDULE AND DETAILS

A-701 LIFE SAFETY DATA

A-702 LIFE SAFETY PLANS

A-801 AIR BARRIER TESTING BOUNDARIES

A-802 AIR BARRIER SECTIONS AND DETAILS

I-100 FIRST FLOOR FURNITURE PLAN PART A

I-101 FIRST FLOOR FURNITURE PLAN PART B

I-102 SECOND FLOOR FURNITURE PLAN

I-500 SIGNAGE TYPICALS

I-501 FINISH LEGENDS & DETAILS

I-502 FINISH DETAILS

I-600 ROOM FINISH SCHEDULE

I-601 SIGNAGE SCHEDULE & DETAILS

FA001 FIRE ALARM LEGEND AND OPERATIONS MATRIX

FA101 FIRE ALARM AND MNS FLOOR PLAN - 1ST FLOOR, AREA A

FA102 FIRE ALARM AND MNS FLOOR PLAN - 1ST FLOOR, AREA B

FA103 FIRE ALARM AND MNS FLOOR PLAN - 2ND FLOOR

FA501 FIRE ALARM AND MNS DETAILS

FA601 FIRE ALARM, MNS DIAGRAM AND NOTES

FX001 FIRE PROTECTION LEGEND AND GENERAL NOTES

FX101 FIRE PROTECTION FLOOR PLAN - FIRST FLOOR, AREA A

FX102 FIRE PROTECTION PLAN - FIRST FLOOR, AREA B

FX103 FIRE PROTECTION FLOOR PLAN - 2ND FLOOR

FX501 FIRE PROTECTION DETAILS I

FX502 FIRE PROTECTION DETAILS II

FX503 FIRE PROTECTION DETAILS III

FX901 FIRE PUMP ISOMETRIC

PL001 PLUMBING LEGEND AND GENERAL NOTES

PL101 DOMESTIC WATER FIRST FLOOR PLAN AREA A

PL102 DOMESTIC WATER FIRST FLOOR PLAN AREA B

PL103 DOMESTIC WATER SECOND FLOOR PLAN

PL104 SANITARY FIRST FLOOR PLAN AREA A

PL105 SANITARY FIRST FLOOR PLAN AREA B

PL106 SANITARY SECOND FLOOR PLAN

PL107 COMPRESSED AIR FIRST FLOOR PLAN AREA A

PL108 COMPRESSED AIR FIRST FLOOR PLAN AREA B

PL109 POL FIRST FLOOR PLAN AREA A

PL110 POL FIRST FLOOR PLAN AREA B

PL401 PLUMBING ENLARGED PLANS

PL402 PLUMBING ENLARGED PLANS

PL501 PLUMBING DETAILS I

PL502 PLUMBING DETAILS II

PL503 PLUMBING DETAILS III

PL504 PLUMBING DETAILS IV

PL505 PLUMBING DETAILS V

PL506 PLUMBING DETAILS VI

PL507 PLUMBING DETAILS VII

PL601 PLUMBING SCHEDULES

PL703 POL SUPPLY RISER DIAGRAM

PL704 COMPRESSED AIR RISER DIAGRAM

PL701 DOMESTIC WATER RISER DIAGRAMS

PL702 SANITARY RISER DIAGRAMS

M-001 HVAC LEGEND

M-501 MECHANICAL DETAILS

M-502 MECHANICAL DETAILS

M-503 MECHANICAL DETAILS

M-504 MECHANICAL DETAILS

M-505 MECHANICAL DETAILS

M-506 MECHANICAL DETAILS

M-507 MECHANICAL DETAILS

M-508 HVAC DETAILS

M-509 HVAC DETAILS

MH101 HVAC FIRST & SECOND FLOOR PLANS - OVERALL

MH102 HVAC FIRST FLOOR PLAN (AREA A)

MH103 HVAC FIRST FLOOR PLAN (AREA B)

MH104 HVAC SECOND FLOOR PLAN

MH105 1ST & 2ND HVAC - THERMOSTAT & SENSOR LOCATION PLANS

MH301 HVAC SECTIONS

MH401 HVAC ENLARGED PLANS

MH601 HVAC SCHEDULES (TEMF)

MH602 HVAC SCHEDULES (TEMF)

MH603 HVAC SCHEDULES (TEMF)

MI001 CONTROLS LEGEND

MI002 HVAC CONTROLS GENERAL NOTES

MI003 HVAC SCHEDULING INSTRUCTIONS

MI801 AHU-1&2 CONTROLS SCHEMATIC

MI802 AHU-1&2 SEQUENCE

MI803 DOAS-1 CONTROLS SCHEMATIC

MI804 DOAS-1 SEQUENCE OF OPERATION

MI805 HVU CONTROL SCHEMATIC

MI806 HVU SEQUENCE OF CONTROL

MI807 B-1&2 BOILER CONTROLS SCHEMATIC AND SEQUENCE

MI808 MISC CONTROL SCHEMATICS

MI809 MISC CONTROL SEQUENCES

MI810 AHU-1 & 2 POINTS SCHEDULE

MI811 DOAS-1 POINTS SCHEDULE

MI812 HVU POINTS SCHEDULE

MI813 B-1&2 POINTS SCHEDULE

MI814 MISC POINTS SCHEDULES

MI815 MISC POINTS SCHEDULE

MI816 MISC POINTS SCHEDULES

MI817 DWH-1 CONTROL SCHEMATIC, POINTS & SEQUENCE

MI818 CONTROL SENSOR, VALVE, AND DAMPER SCHEDULES

MP101 HVAC HYDRONIC OVERHEAD PIPING PLAN - OVERALL

MP102 HVAC HYDRONIC OVERHEAD PIPING PLAN - 1ST FLOOR (AREA A)

MP103 HVAC HYDRONIC OVERHEAD PIPING PLAN - 1ST FLOOR (AREA B)

MP104 HVAC HYDRONIC OVERHEAD PIPING PLAN - 2ND FLOOR

MP105 HVAC HYDRONIC IN-FLOOR PIPING PLAN - OVERALL

MP106 HVAC HYDRONIC IN-FLOOR PIPING PLAN (AREA A)

MP107 HVAC HYDRONIC IN-FLOOR PIPING PLAN (AREA B)

E-001 LEGEND AND NOTES

E-101 ELECTRICAL HAZARD CLASSIFICATION PLAN

EL101 REPAIR BAY LIGHTING PLAN

EL102 LIGHTING FLOOR PLAN - 1ST FLOOR AREA B

EL103 LIGHTING FLOOR PLAN - 2ND FLOOR

EL401 ENLARGED LIGHTING PLANS

EL501 LIGHT FIXTURE SCHEDULE AND DETAILS

EL502 LIGHT FIXTURE DETAILS

EL601 LIGHTING CONTROL SCHEDULES AND DIAGRAMS

EL602 LIGHTING CONTROL DIAGRAMS & STRATEGIES

EL603 LIGHTING CONTROL PANEL DIAGRAMS

EP101 POWER FLOOR PLAN - 1ST FLOOR, AREA A

EP102 POWER FLOOR PLAN - 1ST FLOOR, AREA B

EP103 POWER FLOOR PLAN - 2ND FLOOR

EP104 POWER EQUIPMENT PLAN - 1ST FLOOR, AREA A

EP105 POWER EQUIPMENT PLAN - 1ST FLOOR, AREA B

EP106 POWER EQUIPMENT PLAN - 2ND FLOOR

EP401 ENLARGED POWER PLANS

EP501 POWER DETAILS

EP502 POWER DETAILS

EP601 POWER RISER DIAGRAM & ONE-LINE DIAGRAM

EP602 PANEL SCHEDULES

EP701 PANEL SCHEDULES

EP702 PANEL SCHEDULES

EP703 PANEL SCHEDULES

EP704 PANEL SCHEDULES

EP705 PANEL SCHEDULES

EP706 PANEL SCHEDULES

EG101 LIGHTNING PROTECTION PLAN AREA A

EG102 LIGHTNING PROTECTION PLAN AREA B

EG501 GROUNDING DETAILS

EG502 GROUNDING DETAILS

T-001 COMMUNICATIONS LEGEND AND GENERAL NOTES

TN101 COMMUNICATIONS FLOOR PLAN - 1ST FLOOR, AREA A

TN102 COMMUNICATIONS FLOOR PLAN - 1ST FLOOR, AREA B

TN103 COMMUNICATIONS FLOOR PLAN - 2ND FLOOR

TN401 ENLARGED TELECOMMUNICATIONS ROOMS

TN501 COMMUNICATIONS DETAILS

TN601 COMMUNICATIONS DIAGRAMS

TN601X COMMUNICATIONS DIAGRAMS

TN602 COMMUNICATIONS DIAGRAM

S-101X ORGANIZATIONAL STORAGE BUILDING - PLAN AND DETAILS

A-101X ORGANIZATIONAL STORAGE BUILDING - OVERALL PLANS AND ELEVATIONS

A-102X ORGANIZATIONAL STORAGE BUILDING - PLAN, ELEVATIONS, AND SECTIONS

A-201X ORGANIZATIONAL STORAGE BUILDING - DOOR SCHEDULE & DETAILS, AND LOUVER SCHEDULE

FA001X FIRE ALARM LEGEND AND OPERATIONS MATRIX

FA101X ORGANIZATIONAL STORAGE BUILDING - FIRE ALARM AND MNS FLOOR PLAN

FA601X ORGANIZATIONAL STORAGE BUILDING - FIRE ALARM AND MNS DIAGRAM

FX101X ORGANIZATIONAL STORAGE BUILDING - FIRE PROTECTION FLOOR PLAN

FX501X ORGANIZATIONAL STORAGE BUILDING - FIRE SPRINKLER RISER DETAIL

PL101X PLUMBING FLOOR PLAN - NATURAL GAS

MH101X ORGANIZATIONAL STORAGE BUILDING - HVAC FLOOR PLAN

MH301X ORGANIZATIONAL STORAGE BUILDING - HVAC SECTIONS

MH601X ORGANIZATIONAL STORAGE BUILDING - HVAC SCHEDULES (OSB)

E-001X LEGEND AND NOTES

EL101X LIGHTING PLAN

EL501X LIGHT FIXTURE SCHEDULE AND DETAILS

EP101X POWER PLAN

EP601X PANEL SCHEDULES

EG101X LIGHTNING PROTECTION PLAN

EG501X MISC GROUNDING DETAILS

T-001X ORGANIZATIONAL STORAGE BUILDING - COMMUNICATIONS LEGEND & GENERAL NOTES

TN101X ORGANIZATIONAL STORAGE BUILDING - COMMUNICATIONS PLAN

TN501X COMMUNICATIONS DETAILS

S-101Y POL/HW STORAGE BUILDING - PLAN

A-101Y POL / HW STORAGE BUILDINGS - PLAN

W

2Q R

R

-0

ARIMS: 200A Disposition: Maintain for 15yrs after construction

SHEET LOGICMATERIALS

EARTH

DRAWING ABBREVIATIONS GENERAL NOTES

C (cont) ---------------------

CONC CONCRETE

CONC FLR CONCRETE FLOOR

CONF CONFERENCE

CONT CONTINUE, CONTINUOUS

COORD COORDINATE

CORR CORRIDOR

CP CONCRETE PIPE

CPT CARPET

CR CONTROL ROOM

CS CAST STONE

CSWK CASEWORK

CT CERAMIC TILE

CTB CERAMIC TILE BASE

CTF CERAMIC TILE FLOOR

CTR CENTER

CU FT CUBIC FEET

D ---------------------

D DEPTH

D LABEL CLASS D DOOR

DBL DOUBLE

DEMO DEMOLITION

DEPT DEPARTMENT

DET DETAIL

DF DRINKING FOUNTAIN

DIA DIAMETER

DIR DIRECTION

DIST DISTANCE

DN DOWN

DOC DOCUMENT

DR DOOR

DS DOWNSPOUT

DWGS DRAWING/DRAWINGS

E ---------------------

E LABEL CLASS E DOOR

EA EACH

EF EACH FACE

EIFS EXTERIOR INSULATION

AND FINISH SYSTEM

EJ EXPANSION JOINT

ES EACH SIDE

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

ENTR ENTRANCE

EPS EXPANDED POLYSTYRENE

EQ EQUAL

EQUIP EQUIPMENT

EWC ELECTRIC WATER COOLER

EXP EXPOSED, EXPANSION

EXT EXTERIOR, EXTINGUISHER

EXT GR EXTERIOR GRADE

F ---------------------

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR

PANEL

FAS BD FASCIA BOARD

FCO FLOOR CLEANOUT

FD FLOOR DRAIN

FDTN FOUNDATION

FE FIRE EXTINGUISHER

FEB FIRE EXTINGUISHER BRACKET

FEC FIRE EXTINGUISHER CABINET

FED FEDERAL

FF FINISH FLOOR

FFE FINISH FLOOR ELEVATION

FF INSUL FOIL BACKED INSULATION

FGL FIBERGLASS

FH FIRE HOSE

FHP FULL HEIGHT PARTITION

FIN FINISH

FIN BS FINISH BOTH SIDES

FIN FLR FINISH FLOOR

FIN GR FINISH GRADE

FIXT FIXTURE

FLDG FOLDING

FLEX FLEXIBLE

FLG FLOORING

FLMT FLUSH MOUNT

FLR FLOOR

FM FACTORY MUTUAL

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FR FIRE RESISTANT

FRG FIBER REINFORCED GYPSUM

FRMG FRAMING

FRP FIBERGLASS REINFORCED

PLASTIC

FRT FIRE RETARDANT TREATED

FS FEDERAL SPECIFICATION

FSTNR FASTENER

FT FEET / FOOT

FTG FOOTING

FV FIELD VERIFY

FWC FABRIC WALLCOVERING

G ---------------------

G NATURAL GAS

GA GAUGE

GALV GALVANIZED

GB GRAB BAR / GYPSUM BOARD

GEJ GUTTER EXPANSION JOINT

GFCI GOVERNMENT FURNISHED /

CONTRACTOR INSTALLED

GFGI GOVERNMENT FURNISHED /

GOVERNMENT INSTALLED

GFRG GLASS-FIBER-REINFORCED

GYPSUM

GL GLASS / GLAZING

GR GRADE

GR FL GROUND FLOOR

GUT GUTTER

GWB GYPSUM WALL BOARD

GYP BD GYPSUM BOARD

H -------------

H HIGH

HB HOSE BIBB

HC HANDICAPPED

HDPE HIGH DENSITY POLYETHYLENE

HDW HARDWARE

HDWD HARDWOOD

HEPA HIGH EFFICIENCY

PARTICULATE AIR (FILTER)

HM HOLLOW METAL

HMD HOLLOW METAL DOOR

HORIZ HORIZONTAL

HR HOUR

HT HEIGHT

HYDR HYDRAULIC

I ---------------------

IBC INTERNATIONAL BUILDING

CODE

ID INSIDE DIAMETER

INSUL INSULATION

INT INTERIOR

ILO IN LIEU OF

J ---------------------

JAN JANITOR

JT JOINT

K ---------------------

KPD KEYPAD

KIT KITCHEN

KPL KICKPLATE

L ---------------------

LAM LAMINATE

LAV LAVATORY

LBR LUMBER

LBS POUND

LDG LANDING

LF LINEAR FEET (FOOT)

LG LIGHT GAUGE

LIB LIBRARY

LIN LINEAR

LKR LOCKER

LOC LOCATION

LT LIGHT

LVDR LOUVER DOOR

LVR LOUVER

M ---------------------

MACH RM MACHINE ROOM

MATL MATERIAL

MAX MAXIMUM

MBM METAL BUILDING

MANUFACTURER

MC MOISTURE CONTENT

MD METAL DECK

MECH MECHANICAL

MECH RM MECHANICAL ROOM

MEMB MEMBRANE

MF MILL FINISH

MFR MANUFACTURER

MID MIDDLE

MIN MINIMUM, MINUTE

MIRR MIRROR

MISC MISCELLANEOUS

MLDG MOLDING (MOULDING)

MO MASONRY OPENING

MOD MODIFY

MB MOISTURE BARRIER

MTD MOUNTED

MTG MOUNTING

MTL METAL

MVBL MOVABLE

MWP MEMBRANE WATERPROOFING

N ---------------------

N NORTH

NA NOT APPLICABLE

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NP NO PAINT

NRC NOISE REDUCTION

COEFFICIENT

NTS NOT TO SCALE

O -------------------

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OFF OFFICE

OH OVERHEAD

OPH OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPQ OPAQUE

OWSJ OPEN WEB STEEL JOIST

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

ORIG ORIGINAL

OSF OUTSIDE FACE

P --------------------

PA PUBLIC ADDRESS

PAT PATTERN

PB PULL BOX

PBD PARTICLEBOARD

PCC PRECAST CONCRETE

PCF POUNDS PER CUBIC FOOT

PCT PERCENT

PEMB PRE-ENGINEERED METAL

BUILDING

PERF PERFORATED

PERIM PERIMETER

PH PHASE

PIL PILASTER

PL PROPERTY LINE

PL GL PLATE GLASS

PLAM PLASTIC LAMINATE

PLBG PLUMBING

PLG PILING

PLYWD PLYWOOD

PNL PANEL

PP PL PUSH/PULL PLATE

PR PAIR

PRCST PRECAST

PREFIN PREFINISHED

PRKG PARKING

PS CONC PRESTRESSED CONCRETE

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PRESSURE TREATED

PTD PAPER TOWEL DISPENSER

PTDR PAPER TOWEL DISPENSER

AND RECEPTACLE

PTN PARTITION

PWR POWER

Q --------------------

QT QUARRY TILE

QTY QUANTITY

R --------------------

R RISER

RAD RADIUS

RB RESILIENT BASE

RBM REINFORCED BRICK

MASONRY

RBR RUBBER

RC REINFORCED CONCRETE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

RDG INS RIGID INSULATION, SOLID

REC RECESSED

REF REFERENCE

REM REMOVABLE

REP REPAIR

REPL REPLACE

REQ REQUIRE

REQD REQUIRED

RESIL RESILIENT

REST RESTROOM

RF RESILIENT FLOORING

RFG ROOFING

RH ROOF HATCH

RHR RIGHT HAND REVERSE

RL ROOF LEADER

RLG RAILING

RM ROOM

R (cont) --------------------

RO ROUGH OPENING

RSD ROLLING STEEL DOOR

RV ROOF VENT

RVL REVEAL

S --------------------

SAB SOUND ATTENUATION BLANKET

SB SPLASH BLOCK

SCHED SCHEDULE

SD SMOKE DETECTOR

SECT SECTION

SF SQUARE FOOT (FEET)

SGL SINGLE

SHT MTL SHEET METAL FLASHING

SHTHG SHEATHING

SHV SHELVING

SIM SIMILAR

SJ SCORED JOINT

SKLT SKYLIGHT

SLNT SEALANT

SMK SMOKE

SMLS SEAMLESS

SOG SLAB ON GRADE

SP EL SPOT ELEVATION

SPEC SPECIFICATION

SQ SQUARE

SQ IN SQUARE INCH

SQ YD SQUARE YARD

SS STAINLESS STEEL

SSMR STANDING SEAM METAL ROOF

ST STAIRS

STC SOUND TRANSMISSION CLASS

STD STANDARD

STL STEEL

STL JST STEEL JOIST

STL RF DK STEEL ROOF DECK

STOR STORAGE

STR STRINGERS

STRB/HRN STROBE/HORN

STRUC STRUCTURAL

SUB FL SUBFLOOR

SUSP SUSPENDED

SW SIDEWALK

T --------------------

T TREAD

T/S TUB/SHOWER

TB TACKBOARD

TD TRENCH DRAIN

TEL TELEPHONE

TEMP TEMPORARY

TER TERRAZZO

TFF TOP OF FINISH FLOOR

THK THICK / THICKNESS

TMPD GL TEMPERED GLASS

TN TRUE NORTH

TOF TOP OF FOOTING

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOPO TOPOGRAPHY

TOS TOP OF SLAB

TRANS TRANSOM

TRTD TREATED

TV TELEVISION

TYP TYPICAL

U --------------------

UG UNDERGROUND

UH UNIT HEATER

UL UNDERWRITER LABORATORIES

UNO UNLESS NOTED OTHERWISE

UPS UNINTERRUPTIBLE POWER

SYSTEM

V --------------------

VAV VARIABLE AIR VOLUME/UNIT

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VTR VENT THRU ROOF

W --------------------

W WIDTH

W/ WITH

WC WATER CLOSET

WD WOOD

WDW WINDOW

W/O WITHOUT

WWF WELDED WIRE FABRIC

X --------------------

XFMR TRANSFORMER

A ---------------------

A LABEL CLASS A DOOR

A/C AIR CONDITION

A/C UNIT AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AB ANCHOR BOLT

ABV ABOVE

ACC ACCESSIBLE

ACS AUTOMATIC CONTROL

SYSTEM

ACS DR ACCESS DOOR

ACS PNL ACCESS PANEL

ACT ACOUSTICAL CEILING TILE

ADA AMERICANS WITH

DISABILITIES ACT

ADJ ADJACENT

ADMIN ADMINISTRATION

AFC ABOVE FINISHED COUNTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AFS ABOVE FINISHED SLAB

AGGR AGGREGATE

AHU AIR HANDLING UNIT

AIB AIR INFILTRATION BARRIER

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZED

APPROX APPROXIMATE

AR AS REQUIRED

ARCH ARCHITECTURAL

ASC ABOVE SUSPENDED

CEILING

ASSY ASSEMBLY

ATC ACOUSTICAL TILE CEILING

AVG AVERAGE

AWT ACOUSTICAL WALL

TREATMENT

B ---------------------

B LABEL CLASS B DOOR

BALC BALCONY

BD BOARD

BDRY BOUNDARY

BEJ BRICK EXPANSION JOINT

BFF BELOW FINISH FLOOR

BHMA BUILDER'S HARDWARE

MANUFACTURER'S

ASSOCIATION

BLDG BUILDING

BLKG BLOCKING

BLT IN BUILT-IN

BM BEAM

BN BULLNOSE

BO BOTTOM OF

BOS BOTTOM OF STEEL

BOT BOTTOM

BRG BEARING

BRKT BRACKET

BSMT BASEMENT

BTWN BETWEEN

BUR BUILT-UP ROOFING

C ---------------------

C LABEL CLASS C DOOR

CAB CABINET

CATW CATWALK

CAV CAVITY

CBB CEMENTITIOUS (BACKER)

BOARD

CD CONSTRUCTION DOCUMENTS

CDW CHILLED DRINKING WATER

CER CERAMIC

CF CONTRACTOR FURNISHED

CFCI CONTRACTOR FURNISHED /

CONTRACTOR INSTALLED

CFE CONTRACTOR FURNISHED

EQUIPMENT

CFM CUBIC FEET PER MINUTE

CFMF COLD-FORMED METAL

FRAMING

CFS CUBIC FEET PER SECOND

CG CORNER GUARD

CI CAST IRON

CIP CAST-IN-PLACE

CJ CONTROL JOINT

CL CENTER LINE

CLG CEILING

CLG DIFF CEILING DIFFUSER

CLG HT CEILING HEIGHT

CLL COLUMN LINE

CLO CLOSET

CLR COLOR

CMU CONCRETE MASONRY UNIT

CNDS CONDENSATE

CDR CARD READER

CO CLEANOUT

COL COLUMN

COMM COMMUNICATION

0 GRID/COLUM

N LINE

DESIGNATOR

INTERIOR ELEVATION

SECTION

ROOM

NAME/NUMBE

R

REVISION

TAG

PLAN, BLOW-UP

DETAIL

PLAN NORTH

NORTH ARROW

w/ TRUE NORTH

INDICATION

SPOT ELEVATION

Name Elevation REFERENCE LEVEL

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

A-101

SIM

EXTERIOR ELEVATION

PLATE NUMBER WHERE

SECTION/DETAIL IS

DRAWN

A-101

SYMBOLS

INTERIOR ELEVATION

SYMBOL

EXTERIOR ELEVATION

SYMBOL

SECTION SYMBOL

CALLOUT SYMBOL

ELEVATION SYMBOL

LEVEL SYMBOL

GENERAL SYMBOLS

Room name

Room name

150 SF

ROOM

NAME/NUMBER

W/ AREA

CENTERLINE

INDICATOR

1/2 1 21

SCALE: 1"=1'-0"

SCALE BAR

1 View Name 1/8" = 1'-0"R101

MATCHLINE INDICATOR

VIEW TITLE BAR

1 / A-101

1 / A-102

REFERENCE

SHEETS

SAND

CONCRETE/ PRECAST

CONCRETE

STONE

BRICK

CMU

PLYWOOD

RIGID INSULATION

BATT INSULATION

GYPSUM BOARD,

PLASTER

EIFS

1. THESE LEGENDS ARE COMPOSED OF STANDARD SYMBOLS AND ARE PERTINENT TO THE CONDITIONS

ON THIS SET OF DRAWINGS TO THE EXTENT APPLICABLE.

2. ADDITIONAL LEGENDS AND/OR ABBREVIATIONS MAY APPEAR IN THIS SET OF DRAWINGS TO INDICATE

SPECIFIC CONDITIONS IN LIEU OF SYMBOLS SHOWN ON THIS SHEET.

AE201

DISCIPLINE*:

G - GENERAL

C - CIVIL

L - LANDSCAPE

S - STRUCTURAL

A - ARCHITECTURE

DISCIPLINE DESIGNATOR

SHEET TYPE

DESIGNATOR

SHEET SEQUENCE

NUMBER

F- FIRE PROTECTION

P - PLUMBING

M - MECHANICAL

E - ELECTRICAL

T-

TELECOMMUNICATIONS

*ADDITIONAL DISCIPLINES MAY BE USED

IN THIS DRAWING SET.

DRAWING NAMING CONVENTION

SHEET ID

SHEET ID

D R

AW

N

B Y:

D

ES

IG

N

B Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

D

C

B

A

C

AT

EG

O

R Y

C O

D E:

AN

SI

D

E

F

G

2 3 4 5 6 7 8 9 10

C:\Users\k6enxjlh\Desktop\Projects\ProjectWise_Projects\Cam0009\05_W912HN-##-#-####\Revit\FY19PN64296-PROJ_R18_TW Current.rvt15-Dec-20 10:36:29 AM

D

EC

EM

BE

R

W

2Q R

-2 1-

R -0

J.

H

AI

R

E

J.

S

TE

IN

4-

-0

GI002

G

EN

ER

AL

N O

TE

S, A

BB

R

EV

IA

TI

O N

S

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R . M

AR

TI

N L

U

TH

ER

K

IN

G

J R

P L.

LO

U

IS

VI

LL

E, K Y

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SA

VA

N N

AH

D

IS

TR

IC

T

W . O

G

LE

TH

O

R

PE

A

VE

SA

VA

N

N

AH

, G A

FO

R

T C

AM

PB

EL

L, K

EN

TU

C

KY

VE

H

IC

LE

M

AI

N

TE

N

AN

C

E

SH

O P

PN

P2

:3

VO

LU

M E

-B

U

IL

D

IN

G

J.

M

C

TI

ER

N

AN

READY TO ADVERTISE (RTA)

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

W

2Q R

R

-0

GENERAL NOTES:

1. USE STRUCTURAL DRAWINGS IN CONJUNCTION WITH ALL OTHER DRAWINGS. COORDINATE THE WORK OF OTHER TRADES INCLUDING, BUT NOT LIMITED TO, THE REQUIREMENTS FOR SLEEVES, INSERTS, HOLES, HANGERS, AND ANCHORS. STRUCTURE SHALL BE DESIGNED TO BE SELF SUPPORTING.

2. REPORT DISCREPANCIES IN DIMENSIONS BETWEEN DIFFERENT DRAWINGS TO OWNER'S

REPRESENTATIVE PRIOR TO BEGINNING WORK IN AREAS THAT WILL BE AFFECTED. CONTRACT

DOCUMENTS DO NOT INDICATE MEANS AND METHODS.

3. DETAILS TITLED OR NOTED AS "TYPICAL" APPLY NOT ONLY WHERE SPECIFICALLY INDICATED OR

REFERENCED, BUT ALSO IN ALL OTHER CASES WHERE THE NATURE OF THE CONSTRUCTION

REQUIRES THEIR USE. DETERMINE APPLICABILITY OF TYPICAL DETAILS FROM DESCRIPTIVE TITLES OR FROM THE SIMILARITY OF A CONSTRUCTION CONDITION TO ANOTHER CONDITION WHERE THE DETAIL

IS SPECIFICALLY INDICATED OR REFERENCED.

4. PROVIDE TEMPORARY BRACING AND SHORING OF THE STRUCTURE AND COMPONENTS UNTIL ALL COMPONENTS ARE ERECTED AND ALL CONNECTIONS ARE FULLY MADE, AS NECESSARY, TO ENSURE

STABILITY DURING CONSTRUCTION. BRACE ALL WALLS DURING CONSTRUCTION AGAINST WIND

AND/OR CONSTRUCTION LOADS.

5. ELEVATIONS ON THE STRUCTURAL DRAWINGS ARE DENOTED AS [±X'-X"] REFERENCED TO THE FINISHED FIRST FLOOR ELEVATION DATUM [0'-0"]. SEE CIVIL DRAWINGS FOR ACTUAL DATUM

ELEVATION.

6. REPRODUCTION OF CONTRACT DRAWINGS SHALL NOT BE USED AS SHOP DRAWINGS UNDER ANY

CIRCUMSTANCE.

7. NON-STRUCTURAL ELEMENTS OF THE BUILDING (ARCHITECTURAL FINISHES, MASONRY, VENEER AND ASSOCIATED TIES, INSULATION, SHEATHING, DUCTWORK, PIPING, ETC.) ARE TYPICALLY NOT SHOWN ON THE STRUCTURAL DRAWINGS, THEY ARE SHOWN FOR REFERENCE AND DESIGN INTENT ONLY. NON-

STRUCTURAL ELEMENTS SHALL BE CONSTRUCTED AS SHOWN ON THE OTHER DISCIPLINE DRAWINGS.

DESIGN CODE NOTES:

1. STRUCTURAL DESIGN IS IN ACCORDANCE WITH THE FOLLOWING CODES AND SPECIFICATIONS:

A. IBC 2015, INTERNATIONAL BUILDING CODE

B. ASCE 7-16, MINIMUM DESIGN LOADS FOR BUILDINGS AND STRUCTURES

C. ACI 318-14, BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE

D. ACI 360R-10, DESIGN OF SLABS ON GRADE

E. ACI 530-13, BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES

F. AISC 360-10, SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS

G. AISI S100-07/S2-10, NORTH AMERICAN SPECIFICATION FOR THE DESIGN OF COLD-FORMED

STEEL STRUCTURAL MEMBERS, WITH SUPPLEMENT 2, DATED 2010.

H. SDI, STEEL DECK INSTITUTE: DESIGN MANUAL FOR COMPOSITE DECK, FORM DECK, & ROOF

DECK

I. UFC 1-200-01, GENERAL BUILDING REQUIREMENTS

J. UFC 3-301-01, STRUCTURAL ENGINEERING

K. UFC 3-310-04, SEISMIC DESIGN OF BUILDINGS

L. UFC 3-320-06A, CONCRETE FLOOR SLABS SUBJECTED TO HEAVY LOADS

M. UFC 4-010-01, DOD MINIMUM ANTITERRORISM STANDARDS FOR BUILDINGS

N. UFC 4-214-02, TACTICAL EQUIPMENT MAINTENANCE FACILITIES (TEMF)

STANDARD DESIGN

O. METAL BUILDING SYSTEM MANUAL (MBMA) 2012,

DESIGN LOAD CRITERIA:

2. FIRST FLOOR LIVE LOADS:

OFFICES 50 PSF

FIRST FLOOR SLAB ON GRADE UNO 100 PSF

FIRST FLOOR SLAB ON GRADE UNO (OSB/POL) 125 PSF

MECHANICAL/ELECTRICAL ROOMS 125 PSF

STORAGE ROOMS 125 PSF

HAZMAT/OIL STORAGE FLOOR 250 PSF

REPAIR BAY/MAINTENANCE AREA 1000 PSF

VAULT ROOMS 150 PSF

3. SECOND FLOOR LIVE LOADS:

PARTITION WALLS 20 PSF

OFFICES 50 PSF

CORRIDORS 80 PSF

TRAINING ROOMS 100 PSF

BREAK/TRAINING CONFERENCE ROOMS 100 PSF

STAIRS 100 PSF

CATWALKS FOR MAINTENANCE ACCESS 40 PSF

LATRINE 75 PSF

COLLATERAL LOADS 20 PSF

4. ROOF LIVE LOAD: 20 PSF

5. SNOW LOADS:

RISK CATEGORY II

SNOW IMPORTANCE FACTOR, Is 1.0 MINIMUM GROUND SNOW LOAD, Pg 15 PSF SNOW EXPOSURE FACTOR, Ce 0.9 SNOW THERMAL FACTOR, Ct 1.0 ROOF SLOPE FACTOR, Cs 1.0

FROST PENETRATION DEPTH 22 IN

BALANCED SNOW LOADING:

MINIMUM LOW SLOPE ROOF SNOW LOAD, Pm 15 PSF

UNBALANCED SNOW LOADING: SEE S-002

SNOW DRIFT LOADING: SEE S-002

6. WIND LOADS:

RISK CATEGORY II

WIND IMPORTANCE FACTOR, Iw 1.0

BASIC WIND SPEED, V 115 MPH (ULTIMATE)

WIND EXPOSURE CATEGORY C

GUST EFFECT FACTOR, G 0.85

INTERNAL PRESSURE COEFFICIENTS, GCpi +/- 0.18

7. SEISMIC LOADS:

RISK CATEGORY II

SEISMIC IMPORTANCE FACTOR, Ie 1.0 MAPPED SPECTRAL RESPONSE ACCELERATION, Ss 0.50

MAPPED SPECTRAL RESPONSE ACCELERATION, S1 0.20

SITE CLASS D

DESIGN SPECTRAL RESPONSE ACCELERATION, Sds 0.47 DESIGN SPECTRAL RESPONSE ACCELERATION, Sd1 0.27

SEISMIC DESIGN CATEGORY D

SEISMIC ANALYSIS PROCEDURE BY MBM

SEISMIC-FORCE RESISTING SYSTEM (TEMF) BY MBM

RESPONSE MODIFICATION FACTOR, R (TEMF) BY MBM

SEISMIC RESPONSE COEFFICIENT, Cs (TEMF) BY MBM

SEISMIC-FORCE RESISTING SYSTEM (OSB) BY MBM

RESPONSE MODIFICATION FACTOR, R (OSB) BY MBM

SEISMIC RESPONSE COEFFICIENT, Cs (OSB) BY MBM

8. ANTI-TERRORISM/FORCE PROTECTION CRITERIA:

NEW BUILDING LOCATION GREATER THAN 20 FT FROM INSTALLATION

PERIMENTER

BUILDING CATEGORY INHABITED BUILDING

DESIGN LEVEL OF PROTECTION (LOP) VERY LOW (VLOP)

CONVENTIONAL CONSTR STANDOFF DISTANCE 56 FT

APPLICABLE EXPLOSIVE WEIGHT CLASS II

PROGRESSIVE COLLAPSE CRITERIA APPLIES NO (<3 STORIES)

FOUNDATION AND SLAB NOTES:

1. FOUNDATIONS FOR THIS PROJECT ARE DESIGNED IN ACCORDANCE WITH THE RECOMMENDATIONS OF THE GEOTECHNICAL REPORT EVALUATION PROVIDED BY THE LOUISVILLE DISTRICT, DATED JULY 2020.

PRIOR TO CONSTRUCTION, A FINALIZED REPORT STATING THE FINAL FOUNDATION AND SOIL

RECOMMENDATIONS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER OF RECORD FOR REVIEW.

SEE NOTE MB-7 ON THIS SHEET FOR PEMB FOUNDATION REQUIREMENTS.

2. BASED ON THE FOUNDATION REPORT, THE FOUNDATIONS SHALL BE DESIGNED TO BEAR ON SOIL CAPABLE OF SUPPORTING A MAXIMUM NET ALLOWABLE BEARING PRESSURE OF 3,000 POUNDS PER SQUARE (PSF) FOOT FOR COLUMN FOOTINGS AND 1,500 PSF IN FILL AREAS TO CONTROL SETTLEMENT.

CONTINUOUS WALL FOOTINGS SHALL BE SIZED FOR A MAXIMUM NET ALLOWABLE BEARING PRESSURE OF 2,500 PSF. WHERE A TOP OF FOOTING ELEVATION IS NOT SHOWN ON PLANS, ALL FOUNDATION WORK SHALL BE CONSTRUCTED TO BEAR AT OR BELOW THE FROST DEPTH OF 22" AS INDICATED IN

UFC 3-301-01.

3. THE CONTRACTOR SHALL HIRE AN INDEPENDENT TESTING LABORATORY AND GEOTECHNICAL

ENGINEER, REGISTERED AND LICENSED IN THE STATE WHERE THE WORK WILL BE ACCOMPLISHED, TO

VERIFY THAT ALL PLANS AND SPECIFICATIONS HAVE BEEN FOLLOWED AND ACCOMPLISHED.

4. ALL EXCAVATION SHALL BE PERFORMED SO THAT THE SITE AND AREA IMMEDIATELY SURROUNDING THE SITE WHICH AFFECTS CONSTRUCTION OPERATIONS WILL BE CONTINUALLY AND EFFECTIVELY DRAINED. THE CONTRACTOR SHALL PROVIDE DRAINAGE AND DEWATERING AS REQUIRED TO ENSURE THAT ALL FOOTING EXCAVATIONS ARE ACCOMPLISHED WITH SUBGRADE SOILS REMAINING DRY AND

FIRM UNTIL AFTER FOOTINGS ARE PLACED AND BACKFILLED. REMOVAL OF SURFACE WATER,

GROUNDWATER, AND ANY PERCHED WATER CONDITIONS THAT MIGHT BE ENCOUNTERED DURING

EXCAVATIONS SHALL BE ACCOMPLISHED BY APPROVED MEANS. REFER TO SPECIFICATION 31 00 00, EARTHWORK, FOR ADDITIONAL REQUIREMENTS.

5. DO NOT PLACE FOUNDATION CONCRETE ON FROZEN OR SATURATED SUBGRADES.

6. ENSURE THAT EARTH-FORMED FOOTINGS CONFORM TO THE SHAPE, LINES, AND THICKNESS

INDICATED ON THE FOUNDATION PLAN, SECTIONS, AND FOOTING SCHEDULES. EXCAVATION WIDTHS

SHALL BE A MINIMUM OF 4" GREATER THAN DIMENSIONS INDICATED.

7. DO NOT INSTALL FOUNDATIONS UNTIL FOUNDATION WORK HAS BEEN COORDINATED WITH ADJACENT

UNDERGROUND UTILITIES.

8. FOOTINGS SHALL BE LOWERED AS REQUIRED TO PASS UNDER UTILITY LINES. IN LIEU OF STEPPED FOOTINGS, PIPE SLEEVES THROUGH FOOTINGS MAY BE PROVIDED AS NECESSARY ACCORDING TO ACI 318-14.

9. PLACE 10 MIL VAPOR RETARDER AND 6" CAPILLARY WATER BARRIER UNDER ALL SLABS-ON-GRADE.

10. ALL 8" SLAB-ON-GRADE CONSTRUCTION JOINTS SHALL BE DOWELED CONSTRUCTION JOINTS.

SEE DOWELED CONSTRUCTION JOINT DETAILS.

11. WHERE SLABS OF VARYING THICKNESS ABUT AND SLAB SAW JOINTS ARE WITHIN 24" OF DETAIL

CENTERLINE, LOCATE SLAB SAW JOINT IN SLAB OF LESSER THICKNESS.

12. DURING CONSTRUCTION, ALL FOUNDATION EXCAVATIONS SHALL BE INSPECTED AND APPROVED BY THE CONTRACTOR'S PROFESSIONAL GEOTECHNICAL ENGINEER PRIOR TO PLACING CONCRETE, CONCRETE CONSTRUCTION NOTES:

1. ALL CONCRETE CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE PROVISIONS OF THE "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318-14) AND THE SPECIFICATIONS FOR

STRUCTURAL CONCRETE (ACI 301-16) OF THE AMERICAN CONCRETE INSTITUTE (ACI).

2. ALL CAST-IN-PLACE CONCRETE SHALL ATTAIN MINIMUM 28-DAY COMPRESSIVE STRENGTH (f'c) OF 4000

PSI.

3. CONCRETE SHALL BE NORMAL WEIGHT WITH A DENSITY OF 140 PCF TO 150 PCF UNLESS NOTED

OTHERWISE ON PLANS.

4. CONCRETE REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M.

SHOP FABRICATE REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.

5. WELDED WIRE REINFORCEMENT SHALL CONFORM TO ASTM A1064/A1064M. PROVIDE SHEET-TYPE WELDED WIRE REINFORCEMENT. SHEET LAPS SHALL BE TIED AND LAPPED ONE FULL MESH SPACING

PLUS 2".

6. CONCRETE REINFORCING STEEL SHALL BE CONTINUOUS UNLESS OTHERWISE INDICATED.

CONTINUOUS REINFORCING STEEL SHALL BE SPLICED AS INDICATED ON DRAWINGS. REINFORCING STEEL SHALL BE PLACED SO THAT SPACING IS NOT GREATER THAN OR EQUAL TO 2h or 18".

7. MINIMUM CONCRETE COVER FOR REINFORCING STEEL SHALL BE AS INDICATED. IN NO CASE SHALL

REINFORCEMENT COVER BE LESS THAN THE REQUIREMENTS OF ACI 301.

A. CONCRETE DEPOSITED AGAINST THE GROUND 3"

B. CONCRETE EXPOSED TO EARTH OR WEATHER 2"

C. SLABS AND WALLS (NOT EXPOSED TO EARTH OR WEATHER) 1"

8. CONCRETE REINFORCING STEEL MARKED STANDARD HOOK SHALL HAVE A 90° HOOK A MINIMUM OF 12 BAR DIAMETERS IN LENGTH, UNLESS OTHERWISE NOTED. STIRRUPS, TIES, AND 180° HOOKS SHALL

CONFORM TO THE REQUIREMENTS OF ACI 318.

9. PROVIDE 1/2" THICK PRE-MOLDED JOINT FILLER MATERIAL WHERE SLABS ON GRADE ABUT VERTICAL

SURFACES.

10. ALL EMBEDDED ITEMS SHALL BE PROPERLY PLACED, ACCURATELY POSITIONED AND MAINTAINED

SECURELY IN PLACE PRIOR TO AND DURING CONCRETE PLACEMENT.

11. REINFORCING STEEL SHALL BE SPREAD AT SLEEVES, ANCHORS, RECESSES AND OTHER EMBEDDED

ITEMS UNLESS OTHERWISE INDICATED. REINFORCEMENT SHALL NOT BE CUT TO FACILITATE

PLACEMENT OF EMBEDDED ITEMS, UNLESS INDICATED.

12. NO CONCRETE SHALL BE PLACED UNTIL THE OWNER OR THE OWNER'S DESIGNATED

REPRESENTATIVE HAS INSPECTED ALL EMBEDDED WORK, INCLUDING REINFORCEMENT.

13. ALL EXPOSED CONCRETE EDGES SHALL BE CHAMFERED 3/4" OR AS INDICATED.

14. ALUMINUM SHALL NOT BE PLACED IN DIRECT CONTACT WITH CONCRETE UNLESS EFFECTIVELY

COATED OR COVERED TO PREVENT ALUMINUM-CONCRETE REACTION AND ELECTROLYTIC ACTION

BETWEEN ALUMINUM AND STEEL.

15. CONCRETE SLAB ON GRADE JOINTS INDICATED ARE DIAGRAMMATIC AND DO NOT REPRESENT ALL OF

THE JOINTS REQUIRED FOR SLAB-ON-GRADE CONSTRUCTION.

16. CONTRACTOR SHALL PROVIDE JOINTS AT ALL RE-ENTRANT CORNERS INCLUDING, BUT NOT LIMITED TO, PIERS (AS SHOWN IN TYPICAL COLUMN ISOLATION JOINT), SLAB RECESSES, AROUND ALL TRENCH DRAIN RE-ENTRANT CORNERS (INCLUDING BETWEEN MAINTENANCE PIT AND TRENCH DRAIN, ENDS OF

TRENCH DRAINS TO PERIMETER PIERS, AND END OF TRENCH DRAIN TO INTERIOR PIPES.)

17. IN ADDITION, CONTRACTOR SHALL COORDINATE SLAB ON GRADE JOINT REQUIREMENTS WITH SLAB-

ON-GRADE CONSTRUCTION SEQUENCING. CONTRACTOR SHALL SHOW JOINT LAYOUT ON

REINFORCING SHOP DRAWING SUBMITTAL FOR APPROVAL.

MASONRY CONSTRUCTION NOTES:

1. ALL MASONRY CONSTRUCTION SHALL BE IN ACCORDANCE WITH "BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES" (ACI 530-13/ASCE 5-11/TMS 402-13) AND "SPECIFICATION FOR MASONRY

STRUCTURES" (ACI 530.1-13/ASCE 6-13/TMS 602-13).

2. DESIGN MASONRY ASSEMBLAGE STRENGTH, f'm = 2,500 PSI. NET AREA COMPRESSIVE STRENGTH OF

CONCRETE MASONRY UNITS SHALL BE A MINIMUM OF 2650 PSI. UTILIZE TYPE, S MORTAR.

3. CONCRETE MASONRY UNITS SHALL CONFORM TO ASTM C90 AND BE MANUFACTURED WITH NORMAL

WEIGHT AGGREGATE.

4. GROUT SHALL CONFORM TO ASTM C476 AND SHALL NOT CONTAIN ADMIXTURES. S-TYPE GROUT SHALL

ATTAIN A MINIMUM 28-DAY COMPRESSIVE STRENGTH OF 2500 PSI.

5. REINFORCEMENT SHALL BE DEFORMED BARS CONFORMING TO ASTM A615/A615M, GRADE 60 AND

SHALL HAVE FABRICATION TOLERANCES IN ACCORDANCE WITH ACI 315. SHOP FABRICATE

REINFORCING BARS WHICH ARE INDICATED TO BE BENT OR HOOKED.

6. LOCATE JOINT REINFORCEMENT 16 INCHES ON CENTER VERTICALLY AND ADDITIONALLY AT THE TOP OF ALL FOUNDATIONS AND IN THE TWO JOINTS IMMEDIATELY ABOVE AND BELOW ALL OPENINGS, EXTENDING A MINIMUM OF 24 INCHES BEYOND THE JAMB ON EACH SIDE.

7. PLACE PIPES AND CONDUITS PASSING HORIZONTALLY THROUGH MASONRY IN STEEL OR PVC SLEEVES

OR CORED HOLES UNLESS OTHERWISE INDICATED ON THE DRAWINGS.

8. ALUMINUM CONDUITS, PIPES, AND ACCESSORIES SHALL NOT BE EMBEDDED IN MASONRY GROUT, OR

MORTAR, UNLESS EFFECTIVELY COATED OR COVERED TO PREVENT ALUMINUM-CEMENT CHEMICAL

REACTION OR ELECTROLYTIC REACTION BETWEEN ALUMINUM AND STEEL.

9. UNLESS OTHERWISE NOTED OR DETAILED, CENTER WALL REINFORCEMENT IN BLOCK CELLS. USE

NONMETALLIC BAR POSITIONERS,

10. PROVIDE DOWEL REINFORCEMENT FROM WALLS INTO FOUNDATION OF SAME SIZE AND SPACING AS

VERTICAL WALL REINFORCEMENT. WHERE VERTICAL REINFORCEMENT IS NON-CONTINUOUS,

PROVIDE SPLICE LENGTH AS SHOWN IN SCHEDULE ON SB601.

CRANE DESIGN NOTES:

1. DOUBLE GIRDER OVERHEAD BRIDGE CRANE SHALL BE TOP RUNNING WITH CAPACITY OF 10 TONS

(IMPERIAL).

2. CRANE SHALL HAVE HOOK CLEARANCE HEIGHT OF 20’-0” ABOVE FINISHED FLOOR.

3. CRANE SHALL BE DESIGNED FOR A CRANE SERVICE DUTY CLASSIFICATION OF CLASS C (MODERATE

SERVICE) AS DEFINED BY THE CRANE MANUFACTURER’S ASSOCIATION OF AMERICA (CMAA).

4. STRUCTURE SUPPORTING THE BRIDGE CRANE SHALL BE DESIGNED FOR THE TOTAL VERTICAL LOAD FROM THE WEIGHT OF THE BRIDGE, TROLLEY HOIST, AND RATED CAPACITY OF THE CRANE. TOTAL VERTICAL LOAD SHALL BE ADJUSTED FOR THE FOLLOWING IMPACT LOAD FACTOR EXPRESSED AS A PERCENTAGE OF THE TOTAL VERTICAL LOAD. CRANE RUNWAY BEAMS AND RAILS SHALL ALSO BE DESIGNED FOR A LATERAL AND LONGITUDINAL FORCE EQUIVALENT TO A PERCENTAGE OF THE TOTAL

VERTICAL LOAD AS SHOWN BELOW. SEE ASCE 7-10, SECTION 4.9 FOR DETAILS.

VERTICAL IMPACT FORCE 10%

LATERAL FORCE 20%

LONGITUDINAL FORCE 10%

5. PROVIDE END STOPS AT EACH END OF CRANE RAIL. END STOPS SHALL BE DESIGNED FOR LOADS

REQUIRED FOR THE CRANE PROVIDED.

METAL BUILDING:

1. THE METAL BUILDING SYSTEM HAS BEEN PLANNED TO CONSIST OF A RIGID CLEAR SPAN STRUCTURE IN THE PLAN NORTH-SOUTH DIRECTION AND PORTAL FRAMES IN THE PLAN EAST-WEST DIRECTION.

THE LATERAL FORCE RESISTING SYSTEM AND ALL LATERAL BRACING SHALL BE DESIGNED BY THE METAL BUILDING MANUFACTURER (MBM). DESIGN BUILDING SYSTEM(S) IN ACCORDANCE WITH THE LATEST EDITIONS OF IBC, ASCE, AISC, UFC, AND THE MBMA METAL BUILDING SYSTEMS MANUAL.

2. *THE CONTRACTOR WILL BE RESPONSIBLE FOR THE FULL DESIGN OF THE METAL BUILDING

AND INTERIOR 2ND FLOOR SYSTEM AND IT VERTICAL AND LATERAL SUPPORTS. CMU STAIRWELLS AND ELEVATOR WALLS BETWEEN METAL BUILDING COLUMNS WILL BE DESIGNED AS SELF SUPPORTING.

3. DESIGN BUILDING SYSTEM FOR LIVE LOADS INDICATED AND A COLLATERAL DEAD LOAD OF 20 PSF IN

ADDITION TO BUILDING DEAD LOADS, WIND LOADS AND SEISMIC LOADS. PARAMETERS FOR

DEVELOPMENT OF WIND AND SEISMIC LOADS ARE LISTED IN THE GENERAL NOTES. INCLUDE THE

EFFECTS OF WINDWARD AND LEEWARD WIND PRESSURE AND SUCTION LOADS. USE SPREADER

BEAMS WHERE CONCENTRATED LOADS EXCEED PURLIN CAPACITY.

4. LOAD COMBINATIONS SHALL BE IN ACCORDANCE WITH LATEST EDITION OF IBC UNLESS THE MBMA METAL BUILDING SYSTEMS MANUAL (LATEST EDITION) LOAD COMBINATIONS ARE MORE STRINGENT.

5. LIMIT THE STORY DRIFT OF THE STRUCTURE IN BOTH DIRECTIONS TO H/400 FOR THE TEMF FOR

SERVICE WIND LOADS OF A 50-YEAR MEAN RECURRENCE INTERVAL AND H/240 FOR ALL OTHER

BUILDINGS FOR SERVICE WIND LOADS OF A 10-YEAR MEAN RECURRENCE INTERVAL.

6. THE STANDING SEAM ROOFING SHALL NOT BE PERMITTED TO ACT AS A DIAPHRAGM TO TRANSFER THE LATERAL LOADS. INSULATED WALLS AND ROOF PANELS BE FOR ATFP DESIGN LOADS (UFC 4-0140-01).

7. REDUNDANCY SHALL BE PROVIDED TO THE VERTICAL AND HORIZONTAL BRACING SYSTEMS BY USING

MULTIPLE BAYS OF LATERAL MEMBERS.

8. FOUNDATIONS AND PIERS SHOWN ARE PRICING ESTIMATES FOR THE BUILDING AND ARE TO BE USED AS A GUIDE FOR THE BUILDING. THE CONTRACTOR SHALL HIRE A PROFESSIONAL ENGINEER TO REDESIGN THE METAL BUILDING FOUNDATIONS AND PIERS FOR ACTUAL BUILDING LOADS PROVIDED

BY METAL BUILDING MANUFACTURER. THE DESIGN SHALL BE BASED ON THE SOIL PARAMETERS

SPECIFIED IN NOTE F-1 ON THIS SHEET AND THE FINAL COLUMN REACTIONS REPORTED BY THE MBM.

THE FOUNDATION DESIGN SHALL BE SIGNED AND SEALED BY THE PROFESSIONAL ENGINEER AND SHALL BE SUBMITTED TO THE CONTRACTING OFFICER FOR APPROVAL. FOUNDATIONS FOR ELEMENTS

OTHER THAN MBM COLUMN FOUNDATIONS WILL BE CONSTRUCTED AS SHOWN. SEE PLAN FOR

LOCATIONS.

9. THE CONTRACTOR SHALL COORDINATE THE COLUMN ANCHOR BOLT LAYOUT WITH THE MBM. AT LEAST FOUR (4) ANCHOR BOLTS ARE REQUIRED FOR COLUMN BASE PLATES UNO. ANCHOR BOLTS SHALL NOT BE LESS THAN 3/4" NOMINAL SIZE. ANCHOR BOLTS SHALL BE DESIGNED BY THE MBM.

COLUMN ANCHOR BOLTS SHALL BE POSITIVELY LOCATED USING 1/8" SHEET METAL TEMPLATES FOR ALL COLUMN BASE PLATES. BASE PLATE TEMPLATE ANCHOR BOLT HOLES SHALL NOT EXCEED BOLT DIA. +/- 1/6”. PROVISION SHALL BE MADE FOR ALL ANCHOR BOLTS TO BE RIGIDLY HELD IN POSITION TO

PREVENT MOVEMENT DURING CONCRETE PLACEMENT. ANCHOR BOLTS SHALL NOT BE TIGHTENED

PRIOR TO 14 DAYS FOLLOWING CONCRETE PLACEMENT.

10. THE CONTRACTOR SHALL DESIGN, PROVIDE, AND COORDINATE STRUCTURAL FRAMING MEMBERS FOR THE SUPPORT OF ALL FALL PROTECTION, CATWALKS, OPERABLE PARTITIONS, HVAC UNITS, DUCTS, FANS, PIPING, ELECTRICAL COMPONENTS, ETC.

11. THE MBM IS RESPONSIBLE FOR PROVIDING ADDITIONAL STRUCTURAL MEMBERS AND CONNECTIONS TO BUILDING SUB-FRAMING AS NECESSARY AROUND WINDOW AND SKYLIGHT OPENINGS SUCH THAT

FRAME ATTACHMENTS MEET ANTITERRORISM/FORCE PROTECTION CRITERIA PER UFC 4-010-01.

DOOR/WINDOW/SKYLIGHT CONNECTIONS TO SUPPORT STRUCTURE, AND SUPPORTING FRAMING

MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH ATFP CRITERIA FOR A 3 SECOND EQUIVALENT LOAD OF 55 PSF APPLIED UNIFORMLY TO DOOR, WINDOW, AND SKYLIGHT AREAS. WALL PANELS AS

INDICATED ON THE ARCHITECTURAL DRAWINGS SHALL BE EVALUATED TO MEET ATFP LOAD

REQUIREMENTS.

12. THE METAL BUILDING SHALL BE DELEGATED THE DESIGNED FOR A 10 TON CAPACITY BRIDGE CRANE.

SUPPORT STRUCTURE (CRANE RUNWAY BEAMS AND RAILS) SHALL BE DESIGNED AND PROVIDED BY

THE MBM AND SHALL INCLUDE ACCOMMODATIONS FOR THE WEIGHT OF THE CRANE AND SUPPORT

RAILS. SEE DRAWINGS FOR CRANE EXTENTS.

SPECIAL INSPECTION NOTES:

1. INSPECTION OF FABRICATORS SHALL BE CONDUCTED IN ACCORDANCE WITH IBC 2015,

SECTION 1704.2.5

2. INSPECTION OF STEEL CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE WITH IBC

2015, SECTION 1705.2

3. INSPECTION OF CONCRETE CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE WITH

IBC 2015, SECTION 1705.3 AND TABLE 1705.3.

4. INSPECTION OF MASONRY CONSTRUCTION SHALL BE CONDUCTED IN ACCORDANCE WITH

IBC 2015, SECTION 1705.4.

5. INSPECTIONS FOR SEISMIC RESISTANCE SHALL BE AS PER IBC 2015, SECTION 1704.3.2

6. INCLUDE SPECIAL INSPECTIONS REQUIREMENTS IN CONTRACTOR'S QUALITY CONTROL

(CQC) PLAN.

7. THE CONTRACTOR SHALL RETAIN THIRD PARTY QUALITY ASSURANCE AGENCIES TO

CONDUCT SPECIAL INSPECTIONS REQUIRED BY IBC. INSPECTING AGENCY SHALL PROVIDE

REPORTS OF SPECIAL INSPECTIONS DIRECTLY TO THE GOVERNMENT.

STEEL CONSTRUCTION NOTES:

1. FABRICATION AND ERECTION OF STRUCTURAL STEEL AND DESIGN OF CONNECTIONS SHALL BE IN ACCORDANCE WITH AISC 360-10, "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS" DATED JUNE 22, 2010 AND AISC 303-10, "CODE OF STANDARD PRACTICE FOR BUILDING AND BRIDGES" DATED APRIL 14, 2010.

2. UNLESS OTHERWISE NOTED, STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE ABOVE-LISTED

AISC SPECIFICATION AND THE FOLLOWING:

A. WIDE FLANGE SHAPES (50 KSI) ASTM A992

B. HSS HOLLOW SHAPES (46 KSI) ASTM A500, GRADE B

C. PLATES AND ANGLES ASTM A36

D. HIGH STRENGTH BOLTS ASTM A325

E. ANCHOR RODS W/ NUT AND WASHER ASTM F1554, GRADE 36

3. ALL SHOP AND FIELD WELDING SHALL BE BY CERTIFIED WELDERS AND SHALL CONFORM TO AWS

STANDARDS. USE E70XX ELECTRODES UNLESS OTHERWISE NOTED. MINIMUM WELD SIZE FOR

STRUCTURAL STEEL IS 3/16" FILLET, UNLESS OTHERWISE NOTED ON PLANS. CURRENT AWS

CERTIFICATIONS SHALL BE AVAILABLE AT THE JOB SITE FOR REVIEW BY THE OWNERS'

REPRESENTATIVE.

4. ALL BOLTED CONNECTIONS, UNLESS OTHERWISE NOTED, SHALL USE 3/4" DIAMETER HIGH STRENGTH BOLTS WITH HARDENED CARBON STEEL WASHERS AS REQUIRED FOR THE CONNECTION LOADS. IF LOADS ARE NOT INDICATED ON THE DRAWINGS, STEEL FABRICATOR SHALL SIZE CONNECTIONS FOR A MINIMUM OF 3/4 OF THE UNIFORM LOAD CAPACITY OF THE BEAM AS INDICATED IN THE AISC MANUAL.

5. FIELD CUTTING OF STRUCTURAL STEEL MEMBERS BY ANY TRADE SHALL NOT BE PERMITTED. BOLT

HOLES SHALL NOT BE CUT OR ENLARGED BY FLAME CUTTING IN THE FIELD.

6. ALL FIELD-BOLTED SHEAR CONNECTIONS SHALL BE SNUG TIGHT BEARING-TYPE CONNECTIONS, THREADS INCLUDED IN THE SHEAR PLANE. BOLTED CONNECTIONS FOR METAL BUILDING PER METAL

BUILDING MANUFACTURER AND SPEC 13 34 19.

7. THE CONTRACTOR SHALL SUBMIT FOR APPROVAL DRAWINGS AND DESIGN CALCULATIONS FOR ANY ALTERNATE DETAILS AND MEMBER SPLICES. DRAWINGS AND CALCULATIONS SHALL BE SEALED BY AN

ENGINEER LICENSED IN THE STATE OF THE PROJECT.

8. SHOP OR FIELD SPLICES OF STRUCTURAL STEEL MEMBERS ARE PROHIBITED EXCEPT AS DETAILED ON THE DRAWINGS, PERMITTED IN THE SPECIFICATIONS, AS INDICATED ON APPROVED SUBMITTALS, AND AS SPECIFICALLY APPROVED ON SHOP DRAWINGS PRIOR TO FABRICATION.

9. PAINT ALL STEEL BELOW GRADE WITH BITUMINOUS COATING.

STRUCTURAL ABBREVIATIONS

SYMBOL DESCRIPTION

AFF ABOVE FINISHED FLOOR

APPROX APPROXIMATELY

ARCH ARCHITECTURAL

BOC BOTTOM OF CONCRETE

BOF BOTTOM OF FOOTING

BOM BOTTOM OF MASONRY

BOS BOTTOM OF STEEL

BOT BOTTOM

BRG BEARING

CJ CONSTRUCTION JOINT

CL CENTER LINE

CLR CLEAR

CMU CONCRETE MASONRY UNIT

COL COLUMN

CONN CONNECTION

CONC CONCRETE

CONT CONTINUOUS

CONSTR CONSTRUCTION

DCJ DOWELED CONSTRUCTION JOINT

DEG DEGREE

DIA DIAMETER

DN DOWN

DWG(S) DRAWING(S)

EA EACH

EF EACH FACE

EJ EXPANSION JOINT

EL ELEVATION

EOF EDGE OF FOUNDATION

EST ESTIMATED

EQ EQUAL

EW EACH WAY

FF FINISHED FLOOR

FDN FOUNDATION

FTG FOOTING

GA GAUGE

GALV GALVANIZED

GOVT GOVERNMENT

HORIZ HORIZONTAL

KIP (k) 1000 POUNDS

SYMBOL DESCRIPTION

LG LONG

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

MAX MAXIMUM

MBM METAL BUILDING MANUFACTURER

MECH MECHANICAL

MEP MECHANICAL, ELECTRICAL, PLUMBING

MFR MANUFACTURER

MIN MINIMUM

NTS NOT TO SCALE

OC ON CENTER

OPP OPPOSITE

PJF PREMOLDED JOINT FILLER

PL PLATE

PLF POUNDS PER LINEAR FOOT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

REINF REINFORCEMENT

REQD REQUIRED

SCHED SCHEDULE

SE SLAB EDGE

SJ SAWED CONTRACTION JOINT

SJI STEEL JOIST INSTITUTE

SIM SIMILAR

SL SLOPE(D)

SOG SLAB ON GRADE

SPCG SPACING

STD STANDARD

T&B TOP AND BOTTOM

TO TOP OF

TOC TOP OF CONCRETE

TOF TOP OF FOOTING

TOM TOP OF MASONRY

TOS TOP OF SLAB

TS THICKENED SLAB

TYP TYPICAL

UNO UNLESS NOTED OTHERWISE

VERT VERTICAL

WP WORKING POINT

WWF WELDED WIRE FABRIC

STRUCTURAL LEGEND

SLOPE DIRECTION

INDICATES ELEVATION

REFERENCED

TO FINISHED FLOOR

KEYED PLAN NOTE

COLUMN REFERENCE LINE

(CENTER LINE OF COLUMN)

SPOT ELEVATION

DN

X

[+/- X’-X”]

X

[+/- X’-X”]

SLAB DEPRESSION

BRICK WALL

CONCRETE ELEMENT

COMPACTED EARTH FILL

GROUT

CONCRETE MASONRY UNIT

(CMU)

POROUS FILL

WELDED WIRE FABRIC (WWF)

METAL BUILDING:

13. APPROXIMATE WEIGHT AND LOCATIONS OF ERV AND VEF EQUIPMENT ARE SHOWN ON ROOF PLANS.

VERIFY UNIT SIZE AND WEIGHT WITH EQUIPMENT MANUFACTURER. SEE MECHANICAL DRAWINGS FOR EQUIPMENT LOCATIONS. MBM SHALL DESIGN THE ROOF STRUCTURE TO ACCOMMODATE THE WEIGHT

OF MECHANICAL EQUIPMENT AND CATWALK TO BE SUSPENDED FROM ROOF MEMBERS. CATWALK

SYSTEM AND BRACING SHALL ALSO BE DESIGNED AND PROVIDED BY THE MBM AT APPROXIMATE

LOCATIONS SHOWN ON PLANS.

SHEET ID

D R

AW

N

B Y:

D

ES

IG

N

B Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

D

C

B

A

C

AT

EG

O

R Y

C O

D E:

AN

SI

D

E

F

G

2 3 4 5 6 7 8 9 10

C:\Users\K6ENDCNB\Documents\Craig's Stuff\2020 Projects and Reviews\Latest Fort CAMPBELL TEMF\FY19PN64296-STRUC_R18_TW Current.rvt1/19/2021 10:57:16 AM

D

EC

EM

BE

R

W

2Q R

-2 1-

R -0

C . B

O

LE

S

C . B

O

LE

S

J.

S

TE

IN

C am

B or de r S he et

.d gn

4-

-0

S-001

G

EN

ER

AL

S

TR

U C

TU

R

AL

N

O

TE

S

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R . M

AR

TI

N L

U

TH

ER

K

IN

G

J R

. P L

LO

U

IS

VI

LL

E, K Y

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SA

VA

N N

AH

D

IS

TR

IC

T

W . O

G

LE

TH

O

R

PE

A

VE

SA

VA

N

N

AH

, G A

FO

R

T C

AM

PB

EL

L, K

EN

TU

C

KY

VE

H

IC

LE

M

AI

N

TE

N

AN

C

E

SH

O P

PN

P2

:3

VO

LU

M E

-B

U

IL

D

IN

G

J.

W

H

IT

TA

KE

R

READY TO ADVERTISE (RTA)

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

W

2Q R

R

-0 a a a a a a a a

SLOPE:1/2:12

ROOF ZONE 1

WALL ZONE 4

ROOF ZONE 2e,2n,2r

WALL ZONE 5

ROOF ZONE 3e,3r

POL HAZARDOUS MATERIAL BUILDING

ORGANIZED STORAGE BUILDING

TEMF BUILDING

(NOT TO SCALE)

(NOT TO SCALE)

(NOT TO SCALE)

a a a a a a

+21 /-65

ROOF ZONES

TEMF HIGH ROOF

C AND C WIND PRESSURES (PSF)

ULTIMATE

10 SF

EFFECTIVE

WIND

AREA 1&2e

WALLOVERHANG ZONES

1. GROSS WIND PRESSURES SHOWN ABOVE CORRESPOND TO WIND

PRESSURE DIAGRAMS.

2. EDGE ZONES 'a' = 10'-0"

3. WIND PRESSURES SHOWN SHALL BE USED IN CONJUNCTION WITH LOAD

COMBINATIONS SPECIFIED IN SECTIONS 2.3 AND 2.4 OF ASCE 7-10.

4. NEGATIVE WIND PRESSURES REPRESENT WIND PRESSURES ACTING AWAY

FROM THE COMPONENT AND CLADDING SURFACES.

20 SF

50 SF

100 SF

+21 / -94 +21 /-112 +35 / -38

+33 / -34

+31 / -33

+35 / -47

+33 / -44

+31 / -39

+30 / -36

- 145

2n,2r,3e 3r ZONE 4 ZONE 5

2 SF +26 / - 65 +26 / - 94 +26 / - 112

1 &2e 2n,2r 3e 3r

- 79 - 109 - 127

- 79 - 99 - 110 - 123+19 /-79 +19 /-81 +19 /-96

+16 /-39 +16 /-65 +16 /-75

+16 /-20 +16 /-52 +16 /-59

- 63 - 87 - 88 - 95

- 50 - 77 - 72 - 73 +30 / -33

+19 /-58

ROOF ZONES

TEMF LOW ROOF

C AND C WIND PRESSURES (PSF)

ULTIMATE

10 SF

EFFECTIVE

WIND

AREA 1&2e

WALLOVERHANG ZONES

20 SF

50 SF

100 SF

+19 / -84 +19 /-100 +31 / -34

+30 / -29

+28 / -29

+31 / -42

+30 / - 39

+28 / -35

+27 / -33

- 130

2n,2r,3e 3r ZONE 4 ZONE 5

2 SF +23 / - 58 +23 / - 84 +23 / - 100

1 &2e 2n,2r 3e 3r

- 71 - 98 - 114

- 71 - 89 - 99 - 110+17 /-58 +17 /- 63 +17 /-86

+16 /-35 +16 /- 35 +16 /-67

+16 /-18 +16 /- 31 +16 /-53

- 56 - 78 - 79 - 85

- 45 - 69 - 64 - 66 +27 / - 29

+25 / -23

1 &2e

ROOF ZONES

OPEN CANOPIES

C AND C WIND PRESSURES (PSF)

ULTIMATE

9 SF

EFFECTIV

E WIND

AREA

1. GROSS WIND PRESSURES SHOWN ABOVE CORRESPOND

TO WIND PRESSURE DIAGRAMS SHOWN BELOW.

2. EDGE ZONES 'a' = 3'-0"

3. WIND PRESSURES SHOWN SHALL BE USED IN

CONJUNCTION WITH LOAD COMBINATIONS SPECIFIED IN

SECTIONS 2.3 AND 2.4 OF ASCE 7-10.

4. NEGATIVE WIND PRESSURES REPRESENT GOVERNING

WIND PRESSURES ACTING AWAY FROM THE COMPONENT

AND CLADDING SURFACES.

36 SF

>36 SF

+25 / -23

+25 / -23

+38 / -36

+38 / -36

+25 / -23

+51 / -69

+38 / -36

+25 / -23

2n,2r,3e 3r

+18 / -55

1 &2e

ROOF ZONES

ORG STORAGE BUILDING

C AND C WIND PRESSURES (PSF)

ULTIMATE

10 SF

EFFECTIVE

WIND

AREA

WALLOVERHANG

1. GROSS WIND PRESSURES SHOWN ABOVE CORRESPOND TO WIND

PRESSURE DIAGRAMS.

2. EDGE ZONES 'a' = 3'-0"

3. WIND PRESSURES SHOWN SHALL BE USED IN CONJUNCTION WITH LOAD

COMBINATIONS SPECIFIED IN SECTIONS 2.3 AND 2.4 OF ASCE 7-10.

4. NEGATIVE WIND PRESSURES REPRESENT WIND PRESSURES ACTING AWAY

FROM THE COMPONENT AND CLADDING SURFACES.

20 SF

50 SF

100 SF

+16 / -68

+16 / -33

+16 / -17

+30 / -32

+28 / -29

+27 / -28

+22 / -25

+30 / -40

+28 / -37

+27 / -34

+25 / -31

- 68 - 93

- 85

- 74

- 66

2n, 2r,2e 3r ZONE 4 ZONE 51 & 2e 2n,2r

- 68

- 53

- 42

3e 3r

+18 / -80

+16 / -69

+16 / - 55

+16 / -30

+18 / -95

+16 / -95

+16 / - 64

+16 / -50

- 108

- 94

- 75

- 61

-123

-105

-81

-63

+18 / -55

1 &2e

ROOF ZONES

HAZ/POL

C AND C WIND PRESSURES (PSF)

ULTIMATE

10 SF

EFFECTIVE

WIND

AREA

WALLOVERHANG

20 SF

50 SF

100 SF

+16 / -68

+16 / -33

+16 / -17

+30 / -32

+28 / -29

+27 / -28

+22 / -25

+30 / -40

+28 / -37

+27 / -34

+25 / -31

- 68 - 93

- 85

- 74

- 66

2n, 2r,2e 3r ZONE 4 ZONE 51 & 2e 2n,2r

- 68

- 53

- 42

3e 3r

+18 / -80

+16 / -69

+16 / - 55

+16 / -30

+18 / -95

+16 / -95

+16 / - 64

+16 / -50

- 108

- 94

- 75

- 61

-123

-105

-81

-63

15 PSF

31.11 PSF

4.5 PSF

FROM RIDGE

10' - 10"

UNBALANCED SNOW LOAD

(NOT TO SCALE)

18' - 0"

15 PSF

15 PSF

69 PSF MAX INTENSITY OF SURCHARGE LOAD

SNOW DRIFT LOADING

(HIGH ROOF / LOW ROOF)

NOTE: THIS LOAD CASE SHALL BE MIRRORED ABOUT RIDGE.

(NOT TO SCALE)

SHEET ID

D R

AW

N

B Y:

D

ES

IG

N

B Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

D

C

B

A

C

AT

EG

O

R Y

C O

D E:

AN

SI

D

E

F

G

2 3 4 5 6 7 8 9 10

C:\Users\K6ENDCNB\Desktop\Latest Fort CAMPBELL TEMF\FY19PN64296-STRUC_R18_TW Current.rvt

12/10/2020 07:56:35 AM

D

EC

EM

BE

R

W

2Q R

-2 1-

R -0

C . B

O

LE

S

C . B

O

LE

S

J.

S

TE

IN

C am

B or de r S he et

.d gn

4-

-0

S-002

G

EN

ER

AL

S

TR

U C

TU

R

AL

N

O

TE

S

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R . M

AR

TI

N L

U

TH

ER

K

IN

G

J R

. P L

LO

U

IS

VI

LL

E, K Y

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SA

VA

N N

AH

D

IS

TR

IC

T

W . O

G

LE

TH

O

R

PE

A

VE

SA

VA

N

N

AH

, G A

FO

R

T C

AM

PB

EL

L, K

EN

TU

C

KY

VE

H

IC

LE

M

AI

N

TE

N

AN

C

E

SH

O P

PN

P2

:3

VO

LU

M E

-B

U

IL

D

IN

G

J.

W

H

IT

TA

KE

R

READY TO ADVERTISE (RTA)

COMPONENT AND CLADDING WIND PRESSURES2UNBALANCED SNOW LOADING DIAGRAMS1

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

W

2Q R

R

-0

F

2 3 4 5 7 111098

33' - 0" 33' - 0" 32' - 4" 23' - 5" 34' - 6"

G

23' - 3"

B

C

D

E

B.2

D.1

* 9 5'

35' - 11" 7' - 7" 24' - 10"

P1

P1

P1

P1

P2 P4 P4 P4

P4 P4 P4 P3 P3 P3 P4 P4 P2

P1

P1

P1

P1

P2 P4P4P3

P2

2'

8"

270' - 11"

7.5

12' - 2" 11' - 0"

SF403

A

F

2 3 4 5 7

* 9 5'

111098

G

B

C

D

E

B.2

D.1

23' - 3" 34' - 6"35' - 11" 33' - 0" 33' - 0" 32' - 4" 7' - 7" 24' - 10" 23' - 5"

2'

8"

270' - 11"

7.5

12' - 2" 11' - 0"

SF403

1. FOR GENERAL STRUCTURAL NOTES AND ABBREVIATIONS,

SEE S-001.

2. SEE SF301 AND FOLLOWING FOR FRAME SECTIONS.

3. SEE SB501 AND FOLLOWING FOR SLAB AND FOUNDATION

SECTIONS AND DETAILS.

4. P-X INDICATES CONCRETE PIER. SEE PIER SCHEDULE ON

SB503 FOR SIZE AND REINFORCEMENT.

5. CF-X.Y INDICATES COLUMN FOOTING FOUNDED IN SOIL

WITH AN ALLOWABLE BEARING CAPACITY OF 3000 PSF AS

DEFINED IN THE FOUNDATION NOTES ON S-001. SEE

FOOTING SCHEDULE ON SB601 FOR SIZE AND

REINFORCEMENT.

6. TOP OF INT FTG = (-) 2'-0" UNO

TOP OF EXT FTG = (-) 4'-0" UNO

7. * INDICATES DIMENSION SHALL BE COORDINATED WITH

METAL BUILDING MANUFACTURER.

8. PIERS AND FOUNDATIONS SUPPORTING MB COLUMNS ARE

PRELIMINARY FOR ESTIMATING PURPOSES ONLY AND ARE

NOT FINAL. THE CONTRACTOR SHALL BE RESPONSIBLE

FOR FINAL DESIGN OF MB PIERS AND FOUNDATIONS

BASED ON FINAL MB REACTIONS. SEE GENERAL NOTES

FOR ADDITIONAL INFORMATION.

9. INDICATES FOOTING STEP. SEE DETAIL 3/SB504

10. WF INDICATES WALL FOOTING. SEE SCHEDULE ON SB601

AND SECTIONS AND DETAILS.

11. COORDINATE UNDERGROUND UTILITY LINES WITH CIVIL,

ELECTRICAL PLUMBING, AND FIRE PROTECTION

DRAWINGS PRIOR TO CONSTRUCTION OF FOOTINGS AND

SLABS-ON-GRADE. .

12. DRAINAGE AND DEWATERING: ALL EXCAVATION SHALL BE

PREFORMED SO THAT THE SITE AND THE AREA

IMMEDIATELY SURROUNDING THE SITE WHICH AFFECTS

CONSTRUCTION OPERATIONS WILL BE CONTINUALLY AND

EFFECTIVELY DRAINED. THE CONTRACTOR SHALL

PROVIDE DRAINAGE AND DEWATERING AS REQUIRED TO

ENSURE THAT ALL FOOTING EXCAVATIONS ARE

ACCOMPLISHED WITH THE SUBGRADE SOILS REMAINING

DRY AND FIRM UNTIL AFTER FOOTINGS ARE PLACED AND

BACKFILLED. REMOVAL OF SURFACE WATER,

GROUNDWATER, AND ANY PERCHED-WATER CONDITIONS,

WHICH MIGHT BE ENCOUNTERED DURING EXCAVATIONS

SHALL BE ACCOMPLISHED BY APPROVED MEANS. REFER

TO SPECIFICATION 31 00 00 EARTHWORK FOR ADDITIONAL

REQUIREMENTS.

S

SHEET ID

D R

AW

N

B Y:

D

ES

IG

N

B Y:

SU

BM

IT

TE

D B

Y:

SI

ZE

FI

LE

N

AM

E:

IS

SU

E D

AT

E:

C O

N

TR

AC

T

N O

SO

LI

C

IT

AT

IO

N N

O

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

C H

EC

KE

D B

Y:

US Army Corps of Engineers ®

D

C

B

A

C

AT

EG

O

R Y

C O

D E:

AN

SI

D

E

F

G

2 3 4 5 6 7 8 9 10

C:\Users\K6ENDCNB\Desktop\Latest Fort CAMPBELL TEMF\FY19PN64296-STRUC_R18_TW Current.rvt

12/10/2020 07:56:51 AM

D

EC

EM

BE

R

W

2Q R

-2 1-

R -0

C . B

O

LE

S

C . B

O

LE

S

J.

S

TE

IN

C am

B or de r S he et

.d gn

4-

-0

SB101

C O

M

PO

SI

TE

P

LA

N S

LO

U

IS

VI

LL

E

D

IS

TR

IC

T

D

R . M

AR

TI

N L

U

TH

ER

K

IN

G

J R

. P L

LO

U

IS

VI

LL

E, K Y

U .S

. A R

M Y

C O

R

PS

O F

EN

G

IN

EE

R S

SA

VA

N N

AH

D

IS

TR

IC

T

W . O

G

LE

TH

O

R

PE

A

VE

SA

VA

N

N

AH

, G A

FO

R

T C

AM

PB

EL

L, K

EN

TU

C

KY

VE

H

IC

LE

M

AI

N

TE

N

AN

C

E

SH

O P

PN

P2

:3

VO

LU

M E

-B

U

IL

D

IN

G

J.

W

H

IT

TA

KE

R

READY TO ADVERTISE (RTA)

OVERALL FOUNDATION PLAN1

GENERAL NOTES

GRAPHIC LEGEND

PLAN NORTH

8 16 3241216

SCALE: 1/16"=1'-0"

OVERALL FIRST FLOOR PLAN2

BA

1ST FLR 2ND FLR

KEY PLAN

M

AR

K D

ES

C

R

IP

TI

O

N D

AT

E

W

2Q R

R

-0

2 3 4 5 32' - 4"

FR

AM

E O

U T-

T O -O

U T , A

SS

U M

ED

2" G

IR

TS

* 9 5'

B

C

D

E

* 1 0'

1/ 2"

* 1 0'

1/ 2"

33' - 0" 33' - 0"

BR

AC

ED

B

AY

C O

O R

W / A

R C

H

BR

AC

ED

B

A…