Questions and Answers Attachement 1.pdf

PDF 2 MB Posted

Attached to
NYARNG FMS Building 5 Improvements
Solicitation number
W912PQ23Q0036
Issued by

About this file

This document contains installation instructions and specifications for an electric strike and rim exit device. Key details include specifications for the 0563/0563LM series surface mounted rim strike, which operates in fail secure or fail safe mode at 12.7-24VDC. It provides average current draw figures and instructions for proper installation, including frame preparation, testing latch engagement, setting the operational mode, making electrical connections, mounting and adjusting the strike horizontally, and securing it in place. Dimensional details and warnings regarding proper latch clearance are also included.

The related federal contract opportunity is a solicitation from the Department of the Army New York Army National Guard seeking improvements to Building 5 at the NYARNG FMS facility. No further details are provided on the products, services, or work required.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DC = Direct Current *Peak Current: 153mA @12.7VDC 298mA @24VDC

I N S T A L L A T I O N 0563 / 0563LM

0 SerieS SUrFACe MOUNTeD riM STriKe

IS0563 PCN18003

R03-18GR-1

important:

• Ensure the listed exit device functions as intended for life safety concerns by verifying electric strike and exit device compatibility.

• Maximum latch projection is essential to obtain full holding force. Use 1/8" spacers to maximize latch contact.

• The strike and all devices connected to it, shall be installed with wires less than 30m in length.

• When installed in a Fail Secure manner, the local Authority Having Jurisdiction shall be consulted with regards to the use of selected panic hardware to ensure emergency exit from the secured area.

Catalog Specifications Model Mode Voltage duty aVerage Current

0563 / 0563LM Fail Secure / Fail Safe 12.7-24VDC Auto-Sensing Continuous 19mA @12.7VDC * 26mA @24VDC * instructions

1. Carefully prepare the frame per template T0563.

2. Test fit electric strike to ensure full latch engagement.

Add provided spacers, if required.

3. Set Fail Secure or Fail Safe mode using the dip switch identified on the strike. Factory set to Fail Secure.

NOTE: Strike must be cycled once for change to take effect.

4a. Make wire connections from the power source to the wire harness supplied.

4b. Make wire connection for monitoring latch (0563lM only).

Black: Common Blue: Normally Closed (NC)* Orange: Normally Open (NO)*

*with door open

SPDT Switch: 1A resistive 24VDC

Installations of this RIM strike, qualify as “Indoor Use Only”, when not continuously exposed to an outdoor environment.

© 2018 dormakaba Canada Inc.

www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.com

Typical Fail Secure Application

12/24VDC

POWER

SUPPLY

BLACK (-)

(+) RED

KEYPAD / READER0563 (LM) STRIKE

CNO

WIRE HARNESS

MUST NOT BE CUT *

ORANGE (NO)

BLACK (C)

BLUE (NC)

LATCH MONITOR WIRES

IN DOOR OPEN STATE

NC

BLACK (-)

RED (+)

* Please contact RCI for proper wiring support if these wires are cut

LOCKDOWN SCREW

(2 PLACES)

ø3/4" (19mm)

WIRE ACCESS

HOLE(S)

1/4-20 UNC

(2 PLACES)

DOOR FRAMEDOOR FRAME STOP

MOUNTING SCREW

(2 PLACES)

MOUNTING SCREW

(2 PLACES)

1/4-20 UNC

(2 PLACES)

3/4" (19mm)

WIRE ACCESS HOLE(S)

DOOR FRAME STOP

*Second wire access hole required for 0563LM model only.

note: Not to scale. Specifications are subject to change without notice.

5. Mount the electric strike with 1/4-20 UNC screws provided in the horizontal adjustment mounting holes (the outer slots). Adjust electric strike horizontally until exit device latch fully engages with the door closed.

note: Ensure a 1/16" (1.5mm) clearance between exit device latch and the electric strike keeper is maintained. Failing to do so will preload the strike and in turn, will not allow the strike to release the door when energized.

WarnIng: For proper operation a minimum gap of 1/8" (3.2mm) is required between latch and back of strike. If gap is less than 1/8” (3.2mm), the latch will jam and the keeper won’t rotate.

1/2" (13mm)1-3/4" (45mm)

Horizontal Adjustment Mounting Holes

Lock Down Holes

8- 1/

4" (2 m m

5- 9/

1m m

1- 5/

8" (4

2m m

9" (2 m m

6. Tighten the two mounting screws and check operation.

Adjust the horizontal position of electric strike as required.

7. Use the electric strike as a template to mark the two lock down holes. Remove strike. Drill & tap for 1/4-20 UNC locking screws. Using the 1/4-20 UNC screws provided, secure the electric strike through the lock down holes.

Dimensional Details

STRIKE KEEPER

EXIT DEVICE LATCH

FRAMEBACK OF

STRIKE

1/16" (1.5mm)

1/8" (3.2mm)

MINIMUM

© 2018 dormakaba Canada Inc.

www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.com