Questions and Answers Attachement 1.pdf
PDF 2 MB Posted
- Attached to
- NYARNG FMS Building 5 Improvements
- Solicitation number
- W912PQ23Q0036
About this file
This document contains installation instructions and specifications for an electric strike and rim exit device. Key details include specifications for the 0563/0563LM series surface mounted rim strike, which operates in fail secure or fail safe mode at 12.7-24VDC. It provides average current draw figures and instructions for proper installation, including frame preparation, testing latch engagement, setting the operational mode, making electrical connections, mounting and adjusting the strike horizontally, and securing it in place. Dimensional details and warnings regarding proper latch clearance are also included.
The related federal contract opportunity is a solicitation from the Department of the Army New York Army National Guard seeking improvements to Building 5 at the NYARNG FMS facility. No further details are provided on the products, services, or work required.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DC = Direct Current *Peak Current: 153mA @12.7VDC 298mA @24VDC
I N S T A L L A T I O N 0563 / 0563LM
0 SerieS SUrFACe MOUNTeD riM STriKe
IS0563 PCN18003
R03-18GR-1
important:
• Ensure the listed exit device functions as intended for life safety concerns by verifying electric strike and exit device compatibility.
• Maximum latch projection is essential to obtain full holding force. Use 1/8" spacers to maximize latch contact.
• The strike and all devices connected to it, shall be installed with wires less than 30m in length.
• When installed in a Fail Secure manner, the local Authority Having Jurisdiction shall be consulted with regards to the use of selected panic hardware to ensure emergency exit from the secured area.
Catalog Specifications Model Mode Voltage duty aVerage Current
0563 / 0563LM Fail Secure / Fail Safe 12.7-24VDC Auto-Sensing Continuous 19mA @12.7VDC * 26mA @24VDC * instructions
1. Carefully prepare the frame per template T0563.
2. Test fit electric strike to ensure full latch engagement.
Add provided spacers, if required.
3. Set Fail Secure or Fail Safe mode using the dip switch identified on the strike. Factory set to Fail Secure.
NOTE: Strike must be cycled once for change to take effect.
4a. Make wire connections from the power source to the wire harness supplied.
4b. Make wire connection for monitoring latch (0563lM only).
Black: Common Blue: Normally Closed (NC)* Orange: Normally Open (NO)*
*with door open
SPDT Switch: 1A resistive 24VDC
Installations of this RIM strike, qualify as “Indoor Use Only”, when not continuously exposed to an outdoor environment.
© 2018 dormakaba Canada Inc.
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.com
Typical Fail Secure Application
12/24VDC
POWER
SUPPLY
BLACK (-)
(+) RED
KEYPAD / READER0563 (LM) STRIKE
CNO
WIRE HARNESS
MUST NOT BE CUT *
ORANGE (NO)
BLACK (C)
BLUE (NC)
LATCH MONITOR WIRES
IN DOOR OPEN STATE
NC
BLACK (-)
RED (+)
* Please contact RCI for proper wiring support if these wires are cut
LOCKDOWN SCREW
(2 PLACES)
ø3/4" (19mm)
WIRE ACCESS
HOLE(S)
1/4-20 UNC
(2 PLACES)
DOOR FRAMEDOOR FRAME STOP
MOUNTING SCREW
(2 PLACES)
MOUNTING SCREW
(2 PLACES)
1/4-20 UNC
(2 PLACES)
3/4" (19mm)
WIRE ACCESS HOLE(S)
DOOR FRAME STOP
*Second wire access hole required for 0563LM model only.
note: Not to scale. Specifications are subject to change without notice.
5. Mount the electric strike with 1/4-20 UNC screws provided in the horizontal adjustment mounting holes (the outer slots). Adjust electric strike horizontally until exit device latch fully engages with the door closed.
note: Ensure a 1/16" (1.5mm) clearance between exit device latch and the electric strike keeper is maintained. Failing to do so will preload the strike and in turn, will not allow the strike to release the door when energized.
WarnIng: For proper operation a minimum gap of 1/8" (3.2mm) is required between latch and back of strike. If gap is less than 1/8” (3.2mm), the latch will jam and the keeper won’t rotate.
1/2" (13mm)1-3/4" (45mm)
Horizontal Adjustment Mounting Holes
Lock Down Holes
8- 1/
4" (2 m m
5- 9/
1m m
1- 5/
8" (4
2m m
9" (2 m m
6. Tighten the two mounting screws and check operation.
Adjust the horizontal position of electric strike as required.
7. Use the electric strike as a template to mark the two lock down holes. Remove strike. Drill & tap for 1/4-20 UNC locking screws. Using the 1/4-20 UNC screws provided, secure the electric strike through the lock down holes.
Dimensional Details
STRIKE KEEPER
EXIT DEVICE LATCH
FRAMEBACK OF
STRIKE
1/16" (1.5mm)
1/8" (3.2mm)
MINIMUM
© 2018 dormakaba Canada Inc.
www.rutherfordcontrols.com • Phone: 1.800.265.6630 • Fax: 1.800.482.9795 • E-mail: sales_RCI@dormakaba.com