This document provides details for improvements required at Field Maintenance Shop 5 located in Syracuse, New York. The scope of work includes replacing the vehicle exhaust system with five spring-operated exhaust hose reels and blowers, extending power to new blower motors, and providing ductwork and controls. Additional requirements consist of replacing exterior doors and frames with new steel doors and frames compatible with electronic locks. The related federal contract opportunity is solicitation number W912PQ23Q0036 from the Department of the Army New York Army National Guard to provide the specified improvements at the Syracuse facility. The response deadline and award date are not stated.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Syracuse, Field Maintenance Shop #5, Replace vehicle exhaust system

Remove existing vehicle exhaust system, ductwork and controls.

Syracuse, Field Maintenance Shop #5, Replace Vehicle Exhaust System

Statement of Work:

Construction: provide five 8” X 36’ hose reels with blowers (design basis Exhaust Hose Reels | Spring Operated | HRS-2MIL-0836-L | Fume-A-Vent (fumeavent.com). Extend existing power to new blower motors. Provide on/off NEMA-3 push button pendant with rubber cord (SO/SJ w/strain reliefs) for local motor control. Provide duct manifold at clerestory as shown. Provide 5- 10” spiral duct, one from each hose reel thru the manifold and terminate with the vent hood as shown below.

3’6”

2’-0”

New Wall Opening Duct Manifold

EF-4

EF-4B

EF-4C

EF-4E

EF-4D

Existing thru wall duct (to be removed)

Field verify measurements.

Angling of hose reels and/or duct work towards the exterior exhaust point is suggested to reduce the amount of angle points which will help to maintain rate of air flow.

Hose reels and duct work does not have to be reinstalled in the current locations if there is a better position and location.

https://www.fumeavent.com/exhaust-hose-reels/spring-operated/HRS-2MIL-0836-L.html

WEST BAYS

EAST BAYS

trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight

SAME EXHAUST VIA WINDOW OPENING EAST

EXHAUST VIA WINDOW OPENING WEST

trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight

EAST BAYS

Highlight trenton.k.roeske Highlight

Syracuse, Field Maintenance Shop #5, Replace Exterior Doors and Frames

Single steel door and frame with overhead transom window.

Single steel door and frame with transom window, new door and frame to be electronic lock compatible.

This location has an overhead and east side transom windows.

Double steel doors and frame.

Single steel door and frame without transom window.

trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight trenton.k.roeske Highlight

Existing Single Doors in Clockwise Direction from main entrance.

Main Entrance Warm Up Bay Storage Room Lube Bay Waste Handling

Existing Single Doors in Clockwise Direction from main entrance.

Work Bay Northwest

Work Bay Northeast

Existing Double Doors in Clockwise Direction from main entrance.

Boiler Room Hazard Storage POL Storage Supply Room Supply Room

Photo shows pavement and concrete pitching towards the supply room door.