Question number 17: Are you call for a true Class A fire alarm system with circuits leaving and returning to the FACP in separate conduits with a least 24” of separation per NEC code?

Answer: Yes.

Question number 16: Is all the conduit in the hangars to be rigid galvanized conduit?

Answer: Use EMT with compression type fittings. Use rigid galvanized metal conduit in classified areas using explosion proof fittings (i.e. EY/EYS seals, etc.)