RFP No. W912PM-16-R-0005
SOF Special Tactics Facility, Phase 2
PN: 76513
Fort Bragg, North Carolina
Specifications – Volume 3 of 3
May 2016
*IMPORTANT: THIS CONTRACT MUST COMPLY
WITH THE 2014 EDITION OF THE EM 385-1-1
*** ***FOR OFFICIAL USE ONLY
Specifications - Volume 3
READY TO ADVERTISE
May 9, 2016
Wilmington District prepared for
Solicitation #: W912PM-16-R-0005
PN #: 76513
M&H Project #: 0142.01
Fort Bragg, NC
SOF Special Tactics Facility, Phase 2
SOF SPECIAL TACTICS FACILITY, PHASE 2 PN 76513
FT. BRAGG W912PM-16-R-0005
PROJECT TABLE OF CONTENTS
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
STANDARD FORM 1442
00 10 00 SOLICITATION, CONTRACT LINE ITEM NUMBER (CLIN) SCHEDULE
00 21 16 INSTRUCTIONS TO PROPOSERS
00 45 00 REPRESENTATIONS AND CERTIFICATIONS
00 70 00 CONDITIONS OF THE CONTRACT
00 73 00 SUPPLEMENTARY CONDITIONS
DIVISION 01 - GENERAL REQUIREMENTS
01 00 60 JSOC SECURITY
01 10 00.10 38 SUPPLEMENTARY SPECIAL CONTRACT REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 14 00 WORK RESTRICTIONS
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 33 00 SUBMITTAL PROCEDURES
01 33 29.00 37 SUSTAINABILITY
01 35 26 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.10 10 QUALITY CONTROL SYSTEM (QCS)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 16 TEMPORARY PEST CONTROL
01 57 19.37 INDOOR AIR QUALITY (IAQ) MANAGEMENT
01 57 20.00 06 ENVIRONMENTAL PROTECTION AND PERMITS
01 57 23 TEMPORARY STORM WATER POLLUTION CONTROL
01 62 35 RECYCLED/RECOVERED/BIOBASED MATERIALS
01 74 19.37 CONSTRUCTION AND DEMOLITION WASTE MANAGEMENT
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 91 00.00 37 COMMISSIONING
DIVISION 03 - CONCRETE
03 11 13.00 10 CONCRETE FORMING
03 15 00.00 10 CONCRETE ACCESSORIES
03 20 00.00 10 CONCRETE REINFORCING
03 30 00.00 10 CAST-IN-PLACE CONCRETE
03 35 00.00 10 CONCRETE FINISHING
03 39 00.00 10 CONCRETE CURING
03 40 00.00 10 PLANT-PRECAST CONCRETE PRODUCTS FOR BELOW GRADE
CONSTRUCTION
DIVISION 04 - MASONRY
04 20 00 MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 16 LONGSPAN STEEL JOIST FRAMING
05 21 19 OPEN WEB STEEL JOIST FRAMING
05 21 23 STEEL JOIST GIRDER FRAMING
PROJECT TABLE OF CONTENTS Page 1
05 30 00 STEEL DECKS
05 40 00 COLD-FORMED METAL FRAMING
05 50 13 MISCELLANEOUS METAL FABRICATIONS
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
06 20 00 FINISH CARPENTRY
06 41 16.00 10 LAMINATE CLAD ARCHITECTURAL CASEWORK
06 61 16 SOLID POLYMER (SOLID SURFACING) FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 05 23 PRESSURE TESTING AN AIR BARRIER SYSTEM FOR AIR TIGHTNESS
07 13 53 ELASTOMERIC SHEET WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 21 16 MINERAL FIBER BLANKET INSULATION
07 21 29 SPRAYED INSULATION
07 22 00 ROOF AND DECK INSULATION
07 26 10 SELF-ADHERING AIR AND VAPOR BARRIER
07 27 10.00 10 BUILDING AIR BARRIER SYSTEM
07 42 63 FABRICATED WALL PANEL ASSEMBLIES
07 52 00 MODIFIED BITUMINOUS MEMBRANE ROOFING
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 84 00 FIRESTOPPING
07 92 00 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 14 00 WOOD DOORS
08 33 23 OVERHEAD COILING DOORS
08 34 59 ARMORY DOORS
08 34 73 SOUND CONTROL DOOR ASSEMBLIES
08 35 13.26 HORIZONTAL SLIDING, ACCORDION-TYPE FIRE OR SMOKE DOORS
08 41 13 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
08 45 00 INSULATED TRANSLUCENT WALL AND ROOF PANEL SYSTEMS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 06 90 COLOR SCHEDULE
09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 GYPSUM BOARD
09 30 13 CERAMIC TILING
09 51 00 ACOUSTICAL CEILINGS
09 62 38 STATIC-CONTROL FLOORING
09 65 00 RESILIENT FLOORING
09 65 66 RESILIENT ATHLETIC FLOORING
09 67 23.13 01 STANDARD RESINOUS FLOORING
09 67 66 FLUID APPLIED ATHLETIC FLOORING
09 68 00 CARPETING
09 69 13 RIGID GRID ACCESS FLOORING
PROJECT TABLE OF CONTENTS Page 2
09 77 20 FIBERGLASS REINFORCED WALL PANELS
09 83 13 ACOUSTICAL WALL TREATMENT
09 90 00 PAINTS AND COATINGS
09 96 00 HIGH-PERFORMANCE COATINGS
DIVISION 10 - SPECIALTIES
10 10 00 VISUAL COMMUNICATIONS SPECIALTIES
10 14 00.20 INTERIOR SIGNAGE
10 14 01 EXTERIOR SIGNAGE
10 21 13 TOILET COMPARTMENTS
10 22 13.00 48 WIRE MESH PARTITIONS
10 22 39 FOLDING PANEL PARTITIONS
10 26 13 WALL AND CORNER GUARDS
10 28 13 TOILET ACCESSORIES
10 44 16 FIRE EXTINGUISHERS
10 51 13 METAL LOCKERS
10 51 26 PLASTIC LOCKERS AND BENCHES
DIVISION 11 - EQUIPMENT
11 13 10 DOCK LEVELERS
DIVISION 13 - SPECIAL CONSTRUCTION
13 15 00 SWIMMING POOL SYSTEMS
13 17 20 TREADMILL THERAPEUTIC TREATMENT POOL
13 17 30 POLAR PLUNGE THERAPEUTIC TREATMENT POOLS
13 17 40 THERMAL THERAPEUTIC TREATMENT POOLS
DIVISION 14 - CONVEYING EQUIPMENT
14 24 00 HYDRAULIC ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
21 13 13.00 10 WET PIPE SPRINKLER SYSTEM, FIRE PROTECTION
21 22 00.00 10 CLEAN AGENT FIRE EXTINGUISHING SYSTEMS
DIVISION 22 - PLUMBING
22 00 00 PLUMBING, GENERAL PURPOSE
22 15 13.16 40 HIGH-PRESSURE COMPRESSED-AIR PIPING, PIPING COMPONENTS,
AND VALVES, STAINLESS
22 15 14.00 40 GENERAL SERVICE COMPRESSED-AIR SYSTEMS, LOW PRESSURE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 00 00 AIR SUPPLY, DISTRIBUTION, VENTILATION, AND EXHAUST SYSTEMS
23 05 15 COMMON PIPING FOR HVAC
23 05 48.00 40 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 09 23 LONWORKS DIRECT DIGITAL CONTROL FOR HVAC AND OTHER
BUILDING CONTROL SYSTEMS
23 64 26 CHILLED, CHILLED-HOT, AND CONDENSER WATER PIPING SYSTEMS
23 73 13.00 40 MODULAR INDOOR CENTRAL-STATION AIR-HANDLING UNITS
23 81 47 WATER-LOOP AND GROUND-LOOP HEAT PUMP SYSTEMS
PROJECT TABLE OF CONTENTS Page 3
23 82 00.00 20 TERMINAL HEATING AND COOLING UNITS
23 82 02.00 48 UNITARY HEATING AND COOLING EQUIPMENT
DIVISION 25 - INTEGRATED AUTOMATION
25 10 10 UTILITY MONITORING AND CONTROL SYSTEM (UMCS) FRONT END
AND INTEGRATION
DIVISION 26 - ELECTRICAL
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00 SWITCHBOARDS AND SWITCHGEAR
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
26 32 14.00 10 DIESEL-GENERATOR SET, STATIONARY 15-300 KW, STANDBY
APPLICATIONS
26 32 15.00 10 DIESEL-GENERATOR SET STATIONARY 100-2500 KW, WITH
AUXILIARIES
26 36 00.00 10 AUTOMATIC TRANSFER SWITCH AND BY-PASS/ISOLATION SWITCH
26 41 00 LIGHTNING PROTECTION SYSTEM
26 51 00 INTERIOR LIGHTING WITH LED
DIVISION 27 - COMMUNICATIONS
27 05 14.00 10 CABLE TELEVISION PREMISES DISTRIBUTION SYSTEM
27 10 00 BUILDING TELECOMMUNICATIONS CABLING SYSTEM
27 51 16 POOL AREA PUBLIC ADDRESS SYSTEMS
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 23 23.00 10 CLOSED CIRCUIT TELEVISION SYSTEMS
28 31 76 INTERIOR FIRE ALARM AND MASS NOTIFICATION SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 22.00 06 GEOTEXTILES USED AS FILTERS
31 11 00 CLEARING AND GRUBBING
31 31 16 SOIL TREATMENT FOR SUBTERRANEAN TERMITE CONTROL
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 01 19 FIELD MOLDED SEALANTS FOR SEALING JOINTS IN RIGID
PAVEMENTS
32 05 33 LANDSCAPE ESTABLISHMENT
32 11 23 AGGREGATE AND/OR GRADED-CRUSHED AGGREGATE BASE COURSE
32 12 10 BITUMINOUS TACK AND PRIME COATS
32 12 11 BITUMINOUS SURFACE TREATMENT
32 12 16 HOT-MIX ASPHALT (HMA) FOR ROADS
32 13 13.06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SITE
FACILITIES
32 16 13 CONCRETE SIDEWALKS AND CURBS AND GUTTERS
32 17 24.00 10 PAVEMENT MARKINGS
32 92 19 SEEDING
32 92 23 SODDING
32 93 00 EXTERIOR PLANTS
DIVISION 33 - UTILITIES
33 11 00 WATER DISTRIBUTION
PROJECT TABLE OF CONTENTS Page 4
33 30 00 SANITARY SEWERS
33 40 00 STORM DRAINAGE UTILITIES
33 46 13 FOUNDATION DRAINAGE SYSTEM
33 46 16 SUBDRAINAGE SYSTEM
33 61 00 PREFABRICATED UNDERGROUND HEATING/COOLING DISTRIBUTION
SYSTEM
33 70 02.00 10 ELECTRICAL DISTRIBUTION SYSTEM, UNDERGROUND
33 82 00 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 23.19 PARALOFT HOISTS
41 22 23.20 DIVING TOWER HOISTS
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 5
SOF SPECIAL TACTICS FACILITY, PHASE 2 014201
SECTION 26 20 00
INTERIOR DISTRIBUTION SYSTEM
02/14
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by the basic designation only.
ASTM INTERNATIONAL (ASTM)
ASTM B1 (2013) Standard Specification for Hard-Drawn Copper Wire
ASTM B8 (2011) Standard Specification for Concentric-Lay-Stranded Copper Conductors, Hard, Medium-Hard, or Soft
ASTM D709 (2013) Laminated Thermosetting Materials
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)
IEEE 100 (2000; Archived) The Authoritative Dictionary of IEEE Standards Terms
IEEE 81 (2012) Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System
IEEE C2 (2012; Errata 2012; INT 1-4 2012; INT 5-7 2013; INT 8 2014) National Electrical Safety Code
INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)
NETA ATS (2013) Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)
ANSI C12.1 (2008) Electric Meters Code for Electricity Metering
ANSI C80.1 (2005) American National Standard for Electrical Rigid Steel Conduit (ERSC)
ANSI C80.3 (2005) American National Standard for Electrical Metallic Tubing (EMT)
ANSI C80.5 (2005) American National Standard for Electrical Rigid Aluminum Conduit
NEMA 250 (2008) Enclosures for Electrical Equipment
SECTION 26 20 00 Page 1
(1000 Volts Maximum)
NEMA FU 1 (2012) Low Voltage Cartridge Fuses
NEMA ICS 1 (2000; R 2008; E 2010) Standard for Industrial Control and Systems: General Requirements
NEMA ICS 2 (2000; R 2005; Errata 2008) Standard for Controllers, Contactors, and Overload Relays Rated 600 V
NEMA ICS 4 (2010) Terminal Blocks
NEMA ICS 6 (1993; R 2011) Enclosures
NEMA KS 1 (2013) Enclosed and Miscellaneous Distribution Equipment Switches (600 V Maximum)
NEMA MG 1 (2011; Errata 2012) Motors and Generators
NEMA MG 10 (2013) Energy Management Guide for Selection and Use of Fixed Frequency Medium AC Squirrel-Cage Polyphase Induction Motors
NEMA MG 11 (1977; R 2012) Energy Management Guide for Selection and Use of Single Phase Motors
NEMA RN 1 (2005; R 2013) Polyvinyl-Chloride (PVC) Externally Coated Galvanized Rigid Steel Conduit and Intermediate Metal Conduit
NEMA ST 20 (1992; R 1997) Standard for Dry-Type Transformers for General Applications
NEMA TC 3 (2013) Standard for Polyvinyl Chloride (PVC) Fittings for Use With Rigid PVC Conduit and Tubing
NEMA TP 1 (2002) Guide for Determining Energy Efficiency for Distribution Transformers
NEMA VE 1 (2009) Standard for Metal Cable Tray Systems
NEMA WD 1 (1999; R 2005; R 2010) Standard for General Color Requirements for Wiring Devices
NEMA WD 6 (2012) Wiring Devices Dimensions Specifications
NEMA Z535.4 (2011) American National Standard for Product Safety Signs and Labels
SECTION 26 20 00 Page 2
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 70 (2014; AMD 1 2013; Errata 1 2013; AMD 2 2013; Errata 2 2013; AMD 3 2014; Errata 3-4 2014; AMD 4-6 2014) National Electrical Code
NFPA 70E (2015) Standard for Electrical Safety in the Workplace
NFPA 780 (2014) Standard for the Installation of Lightning Protection Systems
TELECOMMUNICATIONS INDUSTRY ASSOCIATION (TIA)
TIA-568-C.1 (2009; Add 2 2011; Add 1 2012) Commercial Building Telecommunications Cabling Standard
TIA-569 (2012c; Addendum 1 2013; Errata 2013) Commercial Building Standard for Telecommunications Pathways and Spaces
TIA-607 (2011b) Generic Telecommunications Bonding and Grounding (Earthing) for Customer Premises
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.147 Control of Hazardous Energy (Lock Out/Tag Out)
UNDERWRITERS LABORATORIES (UL)
UL 1 (2005; Reprint Jul 2012) Standard for Flexible Metal Conduit
UL 5 (2011) Surface Metal Raceways and Fittings
UL 1063 (2006; Reprint Jul 2012) Machine-Tool Wires and Cables
UL 1242 (2006; Reprint Mar 2014) Standard for Electrical Intermediate Metal Conduit -- Steel
UL 1283 (2005; Reprint Feb 2013) Electromagnetic Interference Filters
UL 1449 (2014) Surge Protective Devices
UL 1660 (2014) Liquid-Tight Flexible Nonmetallic Conduit
UL 198M (2003; Reprint Feb 2013) Standard for Mine-Duty Fuses
UL 20 (2010; Reprint Feb 2012) General-Use Snap Switches
SECTION 26 20 00 Page 3
UL 360 (2013; Reprint Aug 2014) Liquid-Tight Flexible Steel Conduit
UL 4248-1 (2007; Reprint Oct 2013) UL Standard for Safety Fuseholders - Part 1: General Requirements
UL 4248-12 (2007; Reprint Dec 2012) UL Standard for Safety Fuseholders - Part 12: Class R
UL 44 (2014; Reprint Jun 2014) Thermoset-Insulated Wires and Cables
UL 467 (2007) Grounding and Bonding Equipment
UL 486A-486B (2013; Reprint Feb 2014) Wire Connectors
UL 486C (2013; Reprint Feb 2014) Splicing Wire Connectors
UL 489 (2013; Reprint Mar 2014) Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
UL 498 (2012; Reprint Oct 2014) Attachment Plugs and Receptacles
UL 5 (2011) Surface Metal Raceways and Fittings
UL 50 (2007; Reprint Apr 2012) Enclosures for Electrical Equipment, Non-environmental Considerations
UL 508 (1999; Reprint Oct 2013) Industrial Control Equipment
UL 510 (2005; Reprint Jul 2013) Polyvinyl Chloride, Polyethylene and Rubber Insulating Tape
UL 514A (2013) Metallic Outlet Boxes
UL 514B (2012; Reprint Nov 2014) Conduit, Tubing and Cable Fittings
UL 514C (2014) Nonmetallic Outlet Boxes, Flush-Device Boxes, and Covers
UL 6 (2007; Reprint Nov 2014) Electrical Rigid Metal Conduit-Steel
UL 67 (2009; Reprint Nov 2014) Standard for Panelboards
UL 6A (2008; Reprint Nov 2014) Electrical Rigid Metal Conduit - Aluminum, Red Brass, and Stainless Steel
SECTION 26 20 00 Page 4
UL 797 (2007; Reprint Dec 2012) Electrical Metallic Tubing -- Steel
UL 817 (2001; Reprint Jul 2014) Standard for Cord Sets and Power-Supply Cords
UL 83 (2014) Thermoplastic-Insulated Wires and Cables
UL 869A (2006) Reference Standard for Service Equipment
UL 870 (2008; Reprint Feb 2013) Standard for Wireways, Auxiliary Gutters, and Associated Fittings
UL 943 (2006; Reprint Jun 2012) Ground-Fault Circuit-Interrupters
UL 984 (1996; Reprint Sep 2005) Hermetic Refrigerant Motor-Compressors
1.2 DEFINITIONS
Unless otherwise specified or indicated, electrical and electronics terms used in these specifications, and on the drawings, are as defined in
IEEE 100 .
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submittals with an "S" are for inclusion in the Sustainability Notebook, in conformance with Section 01 33 29.00 37 SUSTAINABILITY. Submit the following in accordance with Section 01 33 00.
SD-02 Shop Drawings
Panelboards; G
Transformers; G
Cable trays; G
Wireways; G
SD-03 Product Data
Receptacles; G
Circuit breakers; G
Switches; G
Transformers; G
Enclosed circuit breakers; G
SECTION 26 20 00 Page 5
Motor controllers; G
Manual motor starters; G
CATV outlets; G
Telecommunications Grounding Busbar; G
Surge protective devices; G
Include performance and characteristic curves.
SD-06 Test Reports
600-volt wiring test; G
Grounding system test; G
Transformer tests; G
Ground-fault receptacle test; G
SD-07 Certificates
Fuses; G
SD-09 Manufacturer's Field Reports
Transformer factory tests
SD-10 Operation and Maintenance Data
Electrical Systems, Data Package 5; G
Submit operation and maintenance data in accordance with Section 01 78 23, OPERATION AND MAINTENANCE DATA and as specified herein.
1.4 QUALITY ASSURANCE
1.4.1 Fuses
Submit coordination data as specified in paragraph, FUSES of this section.
1.4.2 Regulatory Requirements
In each of the publications referred to herein, consider the advisory provisions to be mandatory, as though the word, "shall" or "must" had been substituted for "should" wherever it appears. Interpret references in these publications to the "authority having jurisdiction," or words of similar meaning, to mean the Contracting Officer. Provide equipment, materials, installation, and workmanship in accordance with the mandatory and advisory provisions of NFPA 70 unless more stringent requirements are specified or indicated.
1.4.3 Standard Products
Provide materials and equipment that are products of manufacturers regularly engaged in the production of such products which are of equal
SECTION 26 20 00 Page 6 material, design and workmanship and:
a. Have been in satisfactory commercial or industrial use for 2 years prior to bid opening including applications of equipment and materials under similar circumstances and of similar size.
b. Have been on sale on the commercial market through advertisements, manufacturers' catalogs, or brochures during the 2-year period.
c. Where two or more items of the same class of equipment are required, provide products of a single manufacturer; however, the component parts of the item need not be the products of the same manufacturer unless stated in this section.
1.4.3.1 Alternative Qualifications
Products having less than a 2-year field service record will be acceptable if a certified record of satisfactory field operation for not less than 6000 hours, exclusive of the manufacturers' factory or laboratory tests, is furnished.
1.4.3.2 Material and Equipment Manufacturing Date
Products manufactured more than 3 years prior to date of delivery to site are not acceptable.
1.5 MAINTENANCE
1.5.1 Electrical Systems
Submit operation and maintenance manuals for electrical systems that provide basic data relating to the design, operation, and maintenance of the electrical distribution system for the building. Include the following:
a. Single line diagram of the "as-built" building electrical system.
b. Schematic diagram of electrical control system (other than HVAC, covered elsewhere).
c. Manufacturers' operating and maintenance manuals on active electrical equipment.
1.6 WARRANTY
Provide equipment items supported by service organizations that are reasonably convenient to the equipment installation in order to render satisfactory service to the equipment on a regular and emergency basis during the warranty period of the contract.
PART 2 PRODUCTS
2.1 MATERIALS AND EQUIPMENT
As a minimum, meet requirements of UL, where UL standards are established for those items, and requirements of NFPA 70 for all materials, equipment, and devices.
SECTION 26 20 00 Page 7
2.2 CONDUIT AND FITTINGS
Conform to the following:
2.2.1 Rigid Metallic Conduit
2.2.1.1 Rigid, Threaded Zinc-Coated Steel Conduit
ANSI C80.1 , UL 6 .
2.2.1.2 Rigid Aluminum Conduit
ANSI C80.5 , UL 6A .
2.2.2 Intermediate Metal Conduit (IMC)
UL 1242 , zinc-coated steel only.
2.2.3 Electrical, Zinc-Coated Steel Metallic Tubing (EMT)
UL 797 , ANSI C80.3 .
2.2.4 Plastic-Coated Rigid Steel and IMC Conduit
NEMA RN 1, Type 40( 40 mils thick).
2.2.5 Flexible Metal Conduit
UL 1 .
2.2.5.1 Liquid-Tight Flexible Metal Conduit, Steel
UL 360 .
2.2.6 Fittings for Metal Conduit, EMT, and Flexible Metal Conduit
UL 514B . Ferrous fittings: cadmium- or zinc-coated in accordance with
UL 514B .
2.2.6.1 Fittings for Rigid Metal Conduit and IMC
Threaded-type. Split couplings unacceptable.
2.2.6.2 Fittings for EMT
Steel compression type.
2.2.7 Fittings for Rigid Nonmetallic Conduit
NEMA TC 3 for PVC, and UL 514B .
2.2.8 Liquid-Tight Flexible Nonmetallic Conduit
UL 1660 .
SECTION 26 20 00 Page 8
2.3 SURFACE RACEWAY
2.3.1 Surface Metal Raceway
UL 5 , two-piece painted steel, totally enclosed, snap-cover type.
2.4 CABLE TRAYS
NEMA VE 1. Provide the following:
a. Cable trays: form a wireway system, with a nominal depth as indicated.
b. Cable trays: constructed of aluminum or steel that has been zinc-coated after fabrication.
c. Cable trays: include splice and end plates, dropouts, and miscellaneous hardware.
d. Edges, fittings, and hardware: finished free from burrs and sharp edges.
e. Fittings: ensure not less than load-carrying ability of straight tray sections and have manufacturer's minimum standard radius.
f. Radius of bends: as indicated.
2.4.1 Basket-Type Cable Trays
Provide size as indicated with maximum wire mesh spacing of 2 by 4 inch.
2.4.2 Ladder-Type Cable Trays
Provide size as indicated.
2.5 OUTLET BOXES AND COVERS
UL 514A , cadmium- or zinc-coated, if ferrous metal. UL 514C , if nonmetallic.
2.5.1 Floor Outlet Boxes
Provide the following:
a. Boxes: adjustable and concrete tight.
b. Each outlet: consisting of cast-metal body with threaded openings, for conduits, adjustable, brass flange ring, and cover plate with 1 1/4 inch threaded plug.
c. Telecommunications outlets: consisting of flush, aluminum or stainless steel housing with a receptacle as specified and 1 inch bushed side opening 3/4 inch top opening.
d. Receptacle outlets: consisting of flush aluminum or stainless steel housing with duplex-type receptacle as specified herein.
e. Provide gaskets where necessary to ensure watertight installation.
f. Provide plugs with installation instructions to the Contracting
SECTION 26 20 00 Page 9
Officer for 5 percent of outlet boxes for the capping of outlets upon removal of service fittings.
2.5.2 Outlet Boxes for Telecommunications System
Provide the following:
a. Standard type 4 11/16 inches square by 2 1/8 inches deep.
b. Outlet boxes for wall-mounted telecommunications outlets: 4 by 2 1/8 by 2 1/8 inches deep.
c. Depth of boxes: large enough to allow manufacturers' recommended conductor bend radii.
d. Outlet boxes for fiber optic telecommunication outlets: include a minimum 3/8 inch deep single or two gang plaster ring as shown and installed using a minimum 1 inch conduit system.
2.6 CABINETS, JUNCTION BOXES, AND PULL BOXES
Volume greater than 100 cubic inches, UL 50 , hot-dip, zinc-coated, if sheet steel.
2.7 WIRES AND CABLES
Provide wires and cables in accordance applicable requirements of NFPA 70 and UL for type of insulation, jacket, and conductor specified or indicated. Do not use wires and cables manufactured more than 12 months prior to date of delivery to site.
2.7.1 Conductors
Provide the following:
a. Conductor sizes and capacities shown are based on copper, unless indicated otherwise.
b. Conductors No. 8 AWG and larger diameter: stranded.
c. Conductors No. 10 AWG and smaller diameter: solid.
d. Conductors for remote control, alarm, and signal circuits, classes 1, 2, and 3: stranded unless specifically indicated otherwise.
e. All conductors: copper.
2.7.1.1 Minimum Conductor Sizes
Provide minimum conductor size in accordance with the following:
a. Branch circuits: No. 12 AWG.
b. Class 1 remote-control and signal circuits: No. 14 AWG.
c. Class 2 low-energy, remote-control and signal circuits: No. 16 AWG.
d. Class 3 low-energy, remote-control, alarm and signal circuits: No. 22
AWG.
SECTION 26 20 00 Page 10
2.7.2 Color Coding
Provide color coding for service, feeder, branch, control, and signaling circuit conductors.
2.7.2.1 Ground and Neutral Conductors
Provide color coding of ground and neutral conductors as follows:
a. Grounding conductors: Green.
b. Neutral conductors: White.
c. Exception, where neutrals of more than one system are installed in same raceway or box, other neutrals color coding: white with a different colored (not green) stripe for each.
2.7.2.2 Ungrounded Conductors
Provide color coding of ungrounded conductors in different voltage systems as follows:
a. 208/120 volt, three-phase
(1) Phase A - black
(2) Phase B - red
(3) Phase C - blue
b. 480/277 volt, three-phase
(1) Phase A - brown
(2) Phase B - orange
(3) Phase C - yellow
2.7.3 Insulation
Unless specified or indicated otherwise or required by NFPA 70 , provide power and lighting wires rated for 600-volts, Type THWN/THHN conforming to UL 83 , except that grounding wire may be type TW conforming to UL 83 ;
remote-control and signal circuits: Type TW or TF, conforming to UL 83 .
Where lighting fixtures require 90-degree Centigrade (C) conductors, provide only conductors with 90-degree C insulation or better.
2.7.4 Bonding Conductors
ASTM B1, solid bare copper wire for sizes No. 8 AWG and smaller diameter;
ASTM B8, Class B, stranded bare copper wire for sizes No. 6 AWG and larger diameter.
2.7.4.1 Telecommunications Bonding Backbone (TBB)
Provide a copper conductor TBB in accordance with TIA-607 with No. 6 AWG minimum size, and sized at 2 kcmil per linear foot of conductor length up to a maximum size of 3/0 AWG. Provide insulated TBB with insulation as
SECTION 26 20 00 Page 11 specified in the paragraph INSULATION and meeting the fire ratings of its pathway.
2.7.4.2 Bonding Conductor for Telecommunications
Provide a copper conductor Bonding Conductor for Telecommunications between the telecommunications main grounding busbar (TMGB) and the electrical service ground in accordance with TIA-607 . Size the bonding conductor for telecommunications the same as the TBB.
2.7.5 Cord Sets and Power-Supply Cords
UL 817 .
2.8 SPLICES AND TERMINATION COMPONENTS
UL 486A-486B for wire connectors and UL 510 for insulating tapes.
Connectors for No. 10 AWG and smaller diameter wires: insulated, pressure-type in accordance with UL 486A-486B or UL 486C (twist-on splicing connector). Provide solderless terminal lugs on stranded conductors.
2.9 DEVICE PLATES
Provide the following:
a. UL listed, one-piece device plates for outlets to suit the devices installed.
b. For metal outlet boxes, plates on unfinished walls: zinc-coated sheet steel or cast metal having round or beveled edges.
c. For nonmetallic boxes and fittings, other suitable plates may be provided.
d. Plates on finished walls: nylon or lexan, minimum 0.03 inch wall thickness and same color as receptacle or toggle switch with which they are mounted.
e. Screws: machine-type with countersunk heads in color to match finish of plate.
f. Sectional type device plates are not be permitted.
g. Plates installed in wet locations: gasketed and UL listed for "wet locations."
2.10 SWITCHES
2.10.1 Toggle Switches
NEMA WD 1, UL 20 , single pole, three-way, and four-way, totally enclosed with bodies of thermoplastic or thermoset plastic and mounting strap with grounding screw. Include the following:
a. Handles: ivory thermoplastic.
b. Wiring terminals: screw-type, side-wired.
SECTION 26 20 00 Page 12
c. Contacts: silver-cadmium and contact arm - one-piece copper alloy.
d. Switches: rated quiet-type ac only, 120/277 volts, with current rating and number of poles indicated.
2.10.2 Switch with Red Pilot Handle
NEMA WD 1. Provide the following:
a. Pilot lights that are integrally constructed as a part of the switch's handle.
b. Pilot light color: red and illuminate whenever the switch is closed or "on".
c. Pilot lighted switch: rated 20 amps and 120 volts or 277 volts as indicated.
d. The circuit's neutral conductor to each switch with a pilot light.
2.10.3 Disconnect Switches
NEMA KS 1. Provide heavy duty-type switches. Utilize Class R fuseholders and fuses for fused switches, unless indicated otherwise. Provide horsepower rated for switches serving as the motor-disconnect means.
Provide switches in NEMA, enclosure as indicated per NEMA ICS 6 .
2.11 FUSES
NEMA FU 1. Provide complete set of fuses for each fusible switch.
Coordinate time-current characteristics curves of fuses serving motors or connected in series with circuit breakers or other circuit protective devices for proper operation. Submit coordination data for approval.
Provide fuses with a voltage rating not less than circuit voltage.
2.11.1 Fuseholders
Provide in accordance with UL 4248-1 .
2.11.2 Cartridge Fuses, Current Limiting Type (Class R)
UL 198M , Class RK-1 time-delay type. Provide only Class R associated fuseholders in accordance with UL 4248-12 .
2.11.3 Cartridge Fuses, High-Interrupting Capacity, Current Limiting Type (Classes J, L, and CC)
UL 198M , Class J for zero to 600 amperes, Class L for 601 to 6,000 amperes, and Class CC for zero to 30 amperes.
2.11.4 Cartridge Fuses, Current Limiting Type (Class T)
UL 198M , Class T for zero to 1,200 amperes, 300 volts; and zero to 800 amperes, 600 volts.
2.12 RECEPTACLES
Provide the following:
SECTION 26 20 00 Page 13
a. UL 498 , hard use (also designated heavy-duty), grounding-type.
b. Ratings and configurations: as indicated.
c. Bodies: ivory as per NEMA WD 1.
d. Face and body: thermoplastic supported on a metal mounting strap.
e. Dimensional requirements: per NEMA WD 6.
f. Screw-type, side-wired wiring terminals.
g. Grounding pole connected to mounting strap.
h. The receptacle: containing triple-wipe power contacts and double or triple-wipe ground contacts.
2.12.1 Weatherproof Receptacles
Provide receptacles, UL listed for use in "wet locations". Include cast metal box with gasketed, hinged, lockable and weatherproof while-in-use, die-cast metal/aluminum cover plate.
2.12.2 Ground-Fault Circuit Interrupter Receptacles
UL 943 , duplex type for mounting in standard outlet box. Provide device capable of detecting current leak of 6 milliamperes or greater and tripping per requirements of UL 943 for Class A ground-fault circuit interrupter devices. Provide screw-type, side-wired wiring terminals or pre-wired (pigtail) leads.
2.13 PANELBOARDS
Provide panelboards in accordance with the following:
a. UL 67 and UL 50 having a short-circuit current rating as indicated.
b. Panelboards for use as service disconnecting means: additionally conform to UL 869A .
c. Panelboards: circuit breaker-equipped.
d. Designed such that individual breakers can be removed without disturbing adjacent units or without loosening or removing supplemental insulation supplied as means of obtaining clearances as required by UL.
e. "Specific breaker placement" is required in panelboards to match the breaker placement indicated in the panelboard schedule on the drawings.
f. Use of "Subfeed Breakers" is not acceptable unless specifically indicated otherwise.
g. Main breaker: "separately" mounted "above" or "below" branch breakers.
h. Where "space only" is indicated, make provisions for future installation of breakers.
SECTION 26 20 00 Page 14
i. Directories: indicate load served by each circuit in panelboard.
j. Directories: indicate source of service to panelboard (e.g., Panel PA served from Panel MDP).
k. Type directories and mount in holder behind transparent protective covering.
l. Panelboards: listed and labeled for their intended use.
m. Panelboard nameplates: provided in accordance with paragraph FIELD
FABRICATED NAMEPLATES.
2.13.1 Enclosure
Provide panelboard enclosure in accordance with the following:
a. UL 50 .
b. Cabinets mounted outdoors or flush-mounted: hot-dipped galvanized after fabrication.
c. Cabinets: painted in accordance with paragraph PAINTING.
d. Outdoor cabinets: NEMA 3R raintight with conduit hubs welded to the cabinet.
e. Front edges of cabinets: form-flanged or fitted with structural shapes welded or riveted to the sheet steel, for supporting the panelboard front.
f. All cabinets: fabricated such that no part of any surface on the finished cabinet deviates from a true plane by more than 1/8 inch.
g. Holes: provided in the back of indoor surface-mounted cabinets, with outside spacers and inside stiffeners, for mounting the cabinets with a 1/2 inch clear space between the back of the cabinet and the wall surface.
h. Flush doors: mounted on hinges that expose only the hinge roll to view when the door is closed.
i. Each door: fitted with a combined catch and lock, except that doors over 24 inches long provided with a three-point latch having a knob with a T-handle, and a cylinder lock.
j. Keys: two provided with each lock, with all locks keyed alike.
k. Finished-head cap screws: provided for mounting the panelboard fronts on the cabinets.
2.13.2 Panelboard Buses
Support bus bars on bases independent of circuit breakers. Design main buses and back pans so that breakers may be changed without machining, drilling, or tapping. Provide isolated neutral bus in each panel for connection of circuit neutral conductors. Provide separate ground bus identified as equipment grounding bus per UL 67 for connecting grounding conductors; bond to steel cabinet.
SECTION 26 20 00 Page 15
2.13.3 Circuit Breakers
UL 489 , thermal magnetic-type having a minimum short-circuit current rating equal to the short-circuit current rating of the panelboard in which the circuit breaker will be mounted. Breaker terminals: UL listed as suitable for type of conductor provided. Where indicated on the drawings, provide circuit breakers with shunt trip devices. Series rated circuit breakers and plug-in circuit breakers are unacceptable.
2.13.3.1 Multipole Breakers
Provide common trip-type with single operating handle. Design breaker such that overload in one pole automatically causes all poles to open.
Maintain phase sequence throughout each panel so that any three adjacent breaker poles are connected to Phases A, B, and C, respectively.
2.13.3.2 Circuit Breaker With Ground-Fault Circuit Interrupter
UL 943 and NFPA 70 . Provide with "push-to-test" button, visible indication of tripped condition, and ability to detect and trip on current imbalance of 6 milliamperes or greater per requirements of UL 943 for Class A ground-fault circuit interrupter.
2.13.3.3 Circuit Breakers for HVAC Equipment
Provide circuit breakers for HVAC equipment having motors (group or individual) marked for use with HACR type and UL listed as HACR type.
2.14 CIRCUIT BREAKERS
UL 489 , thermal magnetic-type with interrupting capacity as indicated.
Breaker terminals: UL listed as suitable for the type of conductor provided.
2.14.1 Multipole Breakers
Provide common trip-type with single operating handle. Provide a breaker design such that overload in one pole automatically causes all poles to open. Maintain phase sequence throughout each panel so that any two adjacent breaker poles are connected to alternate phases in sequence.
2.15 ENCLOSED CIRCUIT BREAKERS
UL 489 . Individual molded case circuit breakers with voltage and continuous current ratings, number of poles, overload trip setting, and short circuit current interrupting rating as indicated. Enclosure type as indicated. Provide solid neutral.
2.16 TRANSFORMERS
Provide transformers in accordance with the following:
a. NEMA ST 20 , general purpose, dry-type, self-cooled, ventilated.
b. Provide transformers in NEMA 1 enclosure.
c. Transformer insulation system:
SECTION 26 20 00 Page 16
(1) 220 degrees C insulation system for transformers 15 kVA and greater, with temperature rise not exceeding 80 degrees C under full-rated load in maximum ambient of 40 degrees C.
d. Transformer of 80 degrees C temperature rise: capable of carrying continuously 130 percent of nameplate kVA without exceeding insulation rating.
e. Transformers: quiet type with maximum sound level at least 3 decibels less than NEMA standard level for transformer ratings indicated.
2.16.1 Specified Transformer Efficiency
Transformers, indicated and specified with: 480V primary, 80 degrees C or 115 degrees C temperature rise, kVA ratings of 37.5 to 100 for single phase or 30 to 500 for three phase, energy efficient type. Minimum efficiency, based on factory test results: not be less than NEMA Class 1 efficiency as defined by NEMA TP 1 .
2.17 MOTORS
Provide motors in accordance with the following:
a. NEMA MG 1.
b. Hermetic-type sealed motor compressors: Also comply with UL 984 .
c. Provide the size in terms of HP, or kVA, or full-load current, or a combination of these characteristics, and other characteristics, of each motor as indicated or specified.
d. Determine specific motor characteristics to ensure provision of correctly sized starters and overload heaters.
e. Rate motors for operation on 208-volt, 3-phase circuits with a terminal voltage rating of 200 volts, and those for operation on 480-volt, 3-phase circuits with a terminal voltage rating of 460 volts.
f. Use motors designed to operate at full capacity with voltage variation of plus or minus 10 percent of motor voltage rating.
g. Unless otherwise indicated, use continuous duty type motors if rated 1 HP and above.
h. Where fuse protection is specifically recommended by the equipment manufacturer, provide fused switches in lieu of non-fused switches indicated.
2.17.1 High Efficiency Single-Phase Motors
Single-phase fractional-horsepower alternating-current motors: high efficiency types corresponding to the applications listed in NEMA MG 11.
In exception, for motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
SECTION 26 20 00 Page 17
2.17.2 Premium Efficiency Polyphase Motors
Select polyphase motors based on high efficiency characteristics relative to typical characteristics and applications as listed in NEMA MG 10. In addition, continuous rated, polyphase squirrel-cage medium induction motors must meet the requirements for premium efficiency electric motors in accordance with NEMA MG 1, including the NEMA full load efficiency ratings. In exception, for motor-driven equipment with a minimum seasonal or overall efficiency rating, such as a SEER rating, provide equipment with motor to meet the overall system rating indicated.
2.17.3 Motor Sizes
Provide size for duty to be performed, not exceeding the full-load nameplate current rating when driven equipment is operated at specified capacity under most severe conditions likely to be encountered. When motor size provided differs from size indicated or specified, make adjustments to wiring, disconnect devices, and branch circuit protection to accommodate equipment actually provided. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage. Provide protection for motors from immediate restart by a time adjustable restart relay.
2.17.4 Wiring and Conduit
Provide internal wiring for components of packaged equipment as an integral part of the equipment. Provide power wiring and conduit for field-installed equipment as specified herein. Power wiring and conduit:
conform to the requirements specified herein. Control wiring: provided under, and conform to, the requirements of the section specifying the associated equipment.
2.18 MOTOR CONTROLLERS
Provide motor controllers in accordance with the following:
a. UL 508 , NEMA ICS 1 , and NEMA ICS 2 .
b. Provide controllers with thermal overload protection in each phase, and one spare normally open auxiliary contact, and one spare normally closed auxiliary contact.
c. Provide controllers for motors rated 1-hp and above with electronic phase-voltage monitors designed to protect motors from phase-loss, undervoltage, and overvoltage.
d. Provide protection for motors from immediate restart by a time adjustable restart relay.
e. When used with pressure, float, or similar automatic-type or maintained-contact switch, provide a hand/off/automatic selector switch with the controller.
f. Connections to selector switch: wired such that only normal automatic regulatory control devices are bypassed when switch is in "hand" position.
g. Safety control devices, such as low and high pressure cutouts, high
SECTION 26 20 00 Page 18 temperature cutouts, and motor overload protective devices: connected in motor control circuit in "hand" and "automatic" positions.
h. Control circuit connections to hand/off/automatic selector switch or to more than one automatic regulatory control device: made in accordance with indicated or manufacturer's approved wiring diagram.
i. Provide selector switch with the means for locking in any position.
j. Provide a disconnecting means, capable of being locked in the open position, for the motor that is located in sight from the motor location and the driven machinery location. As an alternative, provide a motor controller disconnect, capable of being locked in the open position, to serve as the disconnecting means for the motor if it is in sight from the motor location and the driven machinery location.
l. Overload protective devices: provide adequate protection to motor windings; be thermal inverse-time-limit type; and include manual reset-type pushbutton on outside of motor controller case.
m. Cover of combination motor controller and manual switch or circuit breaker: interlocked with operating handle of switch or circuit breaker so that cover cannot be opened unless handle of switch or circuit breaker is in "off" position.
n. Minimum short circuit withstand rating of combination motor controller: 10,000 rms symmetrical amperes.
2.18.1 Control Wiring
Provide control wiring in accordance with the following:
a. All control wire: stranded tinned copper switchboard wire with 600-volt flame-retardant insulation Type SIS meeting UL 44 , or Type MTW meeting UL 1063 , and passing the VW-1 flame tests included in those standards.
b. Hinge wire: Class K stranding.
c. Current transformer secondary leads: not smaller than No. 10 AWG.
d. Control wire minimum size: No. 14 AWG.
e. Power wiring for 480-volt circuits and below: the same type as control wiring with No. 12 AWG minimum size.
f. Provide wiring and terminal arrangement on the terminal blocks to permit the individual conductors of each external cable to be terminated on adjacent terminal points.
2.18.2 Control Circuit Terminal Blocks
Provide control circuit terminal blocks in accordance with the following:
a. NEMA ICS 4 .
b. Control circuit terminal blocks for control wiring: molded or fabricated type with barriers, rated not less than 600 volts.
SECTION 26 20 00 Page 19
c. Provide terminals with removable binding, fillister or washer head screw type, or of the stud type with contact and locking nuts.
d. Terminals: not less than No. 10 in size with sufficient length and space for connecting at least two indented terminals for 10 AWG conductors to each terminal.
e. Terminal arrangement: subject to the approval of the Contracting Officer with not less than four (4) spare terminals or 10 percent, whichever is greater, provided on each block or group of blocks.
f. Modular, pull apart, terminal blocks are acceptable provided they are of the channel or rail-mounted type.
g. Submit data showing that any proposed alternate will accommodate the specified number of wires, are of adequate current-carrying capacity, and are constructed to assure positive contact between current-carrying parts.
2.18.2.1 Types of Terminal Blocks
a. Short-Circuiting Type: Short-circuiting type terminal blocks:
furnished for all current transformer secondary leads with provision for shorting together all leads from each current transformer without first opening any circuit. Terminal blocks: comply with the requirements of paragraph CONTROL CIRCUIT TERMINAL BLOCKS above.
b. Load Type: Load terminal blocks rated not less than 600 volts and of adequate capacity: provided for the conductors for NEMA Size 3 and smaller motor controllers and for other power circuits, except those for feeder tap units. Provide terminals of either the stud type with contact nuts and locking nuts or of the removable screw type, having length and space for at least two indented terminals of the size required on the conductors to be terminated. For conductors rated more than 50 amperes, provide screws with hexagonal heads. Conducting parts between connected terminals must have adequate contact surface and cross-section to operate without overheating. Provide eEach connected terminal with the circuit designation or wire number placed on or near the terminal in permanent contrasting color.
2.18.3 Control Circuits
Control circuits: maximum voltage of 120 volts derived from a separate control source. Provide terminals and terminal boards. Provide separate control disconnect switch within controller. Provide one fused secondary lead with the other lead grounded.
2.18.4 Enclosures for Motor Controllers
NEMA ICS 6 .
2.18.5 Multiple-Speed Motor Controllers and Reversible Motor Controllers
Across-the-line-type, electrically and mechanically interlocked.
Multiple-speed controllers: include compelling relays and multiple-button, station-type with pilot lights for each speed.
SECTION 26 20 00 Page 20
2.18.6 Pushbutton Stations
Provide with "start/stop" momentary contacts having one normally open and one normally closed set of contacts, and red lights to indicate when motor is running. Stations: heavy duty, oil-tight design.
2.18.7 Pilot and Indicating Lights
Provide LED cluster lamps.
2.18.8 Reduced-Voltage Controllers
Provide for polyphase motors 25 horsepower and larger. Reduced-voltage starters: single-step, closed transition solid state-type, or as indicated, with an adjustable time interval between application of reduced and full voltages to motors.
2.19 MANUAL MOTOR STARTERS (MOTOR RATED SWITCHES)
Single pole designed for flush or surface mounting with overload protection.
2.20 LOCKOUT REQUIREMENTS
Provide disconnecting means capable of being locked out for machines and other equipment to prevent unexpected startup or release of stored energy in accordance with 29 CFR 1910.147 . Comply with requirements of Division 23, "Mechanical" for mechanical isolation of machines and other equipment.
2.21 TELECOMMUNICATIONS SYSTEM
Provide system of telecommunications wire-supporting structures (pathway), including: outlet boxes, conduits with pull wires wireways, cable trays, and other accessories for telecommunications outlets and pathway in accordance with TIA-569 and as specified herein. Additional telecommunications requirements are specified in Section 27 10 00, BUILDING TELECOMMUNICATIONS CABLING SYSTEM.
2.22 COMMUNITY ANTENNA TELEVISION (CATV) SYSTEM
2.22.1 CATV Outlets
Provide flush mounted, RJ-45 outlet as described on the plans in standard electrical outlet boxes with mounting frame.
2.22.2 CATV Faceplates
Provide modular faceplates for mounting of CATV Outlets. Faceplate:
include designation labels and label covers for circuit identification.
Faceplate color: match outlet and switch coverplates.
2.23 GROUNDING AND BONDING EQUIPMENT
2.23.1 Ground Rods
UL 467 . Ground rods: copper-clad steel, with minimum diameter of 3/4 inch and minimum length 10 feet. Sectional ground rods are permitted.
SECTION 26 20 00 Page 21
2.23.2 Ground Bus
Copper ground bus: provided in the electrical equipment rooms as indicated.
2.23.3 Telecommunications and CATVGrounding Busbar
Provide corrosion-resistant grounding busbar suitable for indoor installation in accordance with TIA-607 . Busbars: plated for reduced contact resistance. If not plated, clean the busbar prior to fastening the conductors to the busbar and apply an anti-oxidant to the contact area to control corrosion and reduce contact resistance. Provide a telecommunications main grounding busbar (TMGB) in the telecommunications room and a (TGB) in all other telecommunications rooms and equipment rooms.
The telecommunications main grounding busbar (TMGB) and the telecommunications grounding busbar (TGB): sized in accordance with the immediate application requirements and with consideration of future growth. Provide telecommunications grounding busbars with the following:
a. Predrilled copper busbar provided with holes for use with standard sized lugs,
b. Minimum dimensions of 0.25 in thick by 4 in wide for the TMGB and 2 in wide for TGBs with length as indicated;
c. Listed by a nationally recognized testing laboratory.
2.24 MANUFACTURER'S NAMEPLATE
Provide on each item of equipment a nameplate bearing the manufacturer's name, address, model number, and serial number securely affixed in a conspicuous place; the nameplate of the distributing agent will not be acceptable.
2.25 FIELD FABRICATED NAMEPLATES
Provide field fabricated nameplates in accordance with the following:
a. ASTM D709.
b. Provide laminated plastic nameplates for each equipment enclosure, relay, switch, and device; as specified or as indicated on the drawings.
c. Each nameplate inscription: identify the function and, when applicable, the position.
d. Nameplates: melamine plastic, 0.125 inch thick, white with black center core.
e. Surface: matte finish. Corners: square. Accurately align lettering and engrave into the core.
f. Minimum size of nameplates: one by 2.5 inches.
g. Lettering size and style: a minimum of 0.25 inch high normal block style.
SECTION 26 20 00 Page 22
2.26 WARNING SIGNS
Provide warning signs for flash protection in accordance with NFPA 70E and NEMA Z535.4 for switchboards, panelboards, industrial control panels, and motor control centers that are in other than dwelling occupancies and are likely to require examination, adjustment, servicing, or maintenance while energized. Provide field installed signs to warn qualified persons of potential electric arc flash hazards when warning signs are not provided by the manufacturer. Provide marking that is clearly visible to qualified persons before examination, adjustment, servicing, or maintenance of the equipment.
2.27 FIRESTOPPING MATERIALS
Provide firestopping around electrical penetrations in accordance with Section 07 84 00, FIRESTOPPING .
2.28 WIREWAYS
UL 870 . As indicated on the drawings.
2.29 SURGE PROTECTIVE DEVICES
Provide parallel type surge protective devices (SPD) which comply with UL 1449 at the service entranceand panelboards. Provide surge protectors in a NEMA 1 enclosure per NEMA ICS 6 . Use Type 1 or Type 2 SPD and connect on the load side of a dedicated circuit breaker.
Provide the following modes of protection:
FOR SINGLE PHASE AND THREE PHASE WYE CONNECTED SYSTEMS-
Phase to phase ( L-L ) Each phase to neutral ( L-N ) Neutral to ground ( N-G ) Phase to ground ( L-G )
SPDs at the service entrance: provide with a minimum surge current rating of 80,000 amperes for L-L mode minimum and 40,000 amperes for other modes (L-N, L-G, and N-G).
Provide SPDs per NFPA 780 for the lightning protection system.
Maximum L-N, L-G, and N-G Voltage Protection Rating:
600V for 120V, single phase system 600V for 208Y/120V, three phase system 1,200V for 480Y/277V, three phase system
Maximum L-L Voltage Protection Rating:
1,200V for 120V, single phase system 1,200V for 208Y/120V, three phase system 1,200V for 480Y/277V, three phase system
The minimum MCOV (Maximum Continuous Operating Voltage) rating for L-N and L-G modes of operation: 120% of nominal…