A02._L25_Formal_Circuit_Schedule,_F-O_Reterm.pdf
PDF 98 KB Posted
- Attached to
- Fiber Optic Cable Retermination
- Solicitation number
- W912P919T0042
About this file
Lock and Dam 25 Circuit Schedule
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Lock & Dam No. 25 Formal Circuit Listing
Circuit Dwg. Nos. Conductor Volt Type Function Origin Destination Routing Notes
C251 E90, E91 1 - 12-FIBER CABLE N/A H IPC NETWORK TO LOWER LAND WALL
CONTROL BOOTH
LAN (CENTRAL
CONTROL
CONSOLE)
IPC3 (CB-1) R93, R99, R110 OR R117,
R147
REPLACES ORIGINAL 6-
FIBER CABLE
C252 E90, E91 1 - 12-FIBER CABLE N/A H IPC NETWORK TO UPPER LAND WALL
CONTROL BOOTH
LAN (CENTRAL
CONTROL
CONSOLE)
IPC4 (CB-2) R93, R99, R209, R217, R247 REPLACES ORIGINAL 6-
FIBER CABLE
C260 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK TO LOWER LAND WALL
REMOTE RACK
MCC3-PLC RR-MG1 R117, R147, R182 REPLACES ORIGINAL 6-
FIBER CABLE
C261 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK FROM LOWER LAND WALL
REMOTE TO UPPER LAND WALL REMOTE
RR-MG1 RR-MG2 R117, R147, R182, R217,
R244
REPLACES ORIGINAL 6-
FIBER CABLE
C262 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK FROM UPPER LAND WALL
REMOTE TO LOWER RIVER WALL REMOTE
RR-MG2 RR-MG3 R217, R307, R6??, R244,
R375
C263 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK FROM LOWER RIVER WALL
REMOTE TO UPPER RIVER WALL REMOTE
RR-MG3 RR-MG4 R421, R307, R375, R507 REPLACES ORIGINAL 6-
FIBER CABLE
C265 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO LOWER LAND WALL
REMOTE RACK
MCC3-PLC RR-MG1 R117, R147, R182, R158 REPLACED BY 12-FIBER C260
C266 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO UPPER LAND WALL REMOTE
RACK
RR-MG1 RR-MG2 R117, R147, R182, R158,
R217, R244, R272, R269
REPLACED BY 12-FIBER C261
C267 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO LOWER I- WALL REMOTE
RACK
RR-MG2 RR-MG3 R217, R244, R629, R307,
R375, R381
C268 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO UPPER I- WALL REMOTE
RACK
RR-MG3 RR-MG4 R421, R507, R433, R307,
R375
REPLACED BY 12-FIBER C263
C1190 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-
TG1 THRU RR-TG8
MCC1&2-PLC RR-TG1 R629, R828, R467, R713,
R1919, R1021
C1191 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG2 RR-TG1 RR-TG2 R1061 C1192 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG3 RR-TG2 RR-TG3 R1101 C1193 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG4 RR-TG3 RR-TG4 R1141 C1194 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG5 RR-TG4 RR-TG5 R1181 C1195 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG6 RR-TG5 RR-TG6 R1221 C1196 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG7 RR-TG6 RR-TG7 R1261 C1197 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG8 RR-TG7 RR-TG8 R1301 C1200 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR- RR-TG8 RR-TG9 R1341 C1201 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG12 RR-TG13 R1932, R1381, R1421, R1501 C1202 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG13 RR-TG14 R1541 C1203 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG14 RR-TG15 R1581 C1204 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG15 RR-TG16 R1621 C1205 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG16 RR-TG17 R1661
C1210 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-
RG10
RR-RG9 RR-RG10 R629, R828, R467, R713,
R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341, R1932
C1211 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG10 RR-RG11 R1381 C1212 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG11 RR-RG12 R1421
C1230 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-
TG1 THRU RR-TG8
MCC1&2-PLC RR-TG1 R629, R828, R467, R713,
R1919, R1021
C1231 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG2 RR-TG1 RR-TG2 R1061
C1232 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG3 RR-TG2 RR-TG3 R1101
C1233 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG4 RR-TG3 RR-TG4 R1141
Lock & Dam No. 25
Circuit Dwg. Nos. Conductor Volt Type Function Origin Destination Routing Notes C1234 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG5 RR-TG4 RR-TG5 R1181
C1235 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG6 RR-TG5 RR-TG6 R1221
C1236 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG7 RR-TG6 RR-TG7 R1261
C1237 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG8 RR-TG7 RR-TG8 R1301
C1240 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-
TG9
RR-TG8 RR-TG9 R629, R828, R467, R713,
R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341
C1241 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
TG13
RR-RG12 RR-TG13 R1932, R1381, R1421, R1501
C1242 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
TG14
RR-TG13 RR-TG14 R1541
C1243 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
TG15
RR-TG14 RR-TG15 R1581
C1244 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
TG16
RR-TG15 RR-TG16 R1621
C1245 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
TG17
RR-TG16 RR-TG17 R1661
C1250 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-
RG10
RR-RG9 RR-RG10 R629, R828, R467, R713,
R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341, R1932
C1251 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
RG11
RR-RG10 RR-RG11 R1381
C1252 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-
RG12
RR-RG11 RR-RG12 R1421
Lock Dam No. 25
TYPE DESCRIPTION
A Control Cable, Multi-Conductor, Type TC, 600V, with moisture barrier. ICEA Method 1, Option A Color Code (no W or G wires).
B Control Cable, Multi-Conductor, Type TC, 600V, with moisture barrier. ICEA Method 1, Option B Color Code (has W wire)
C Power Cable, Multi-Conductor, Type TC, 600V, with moisture barrier, #12 thru #4/0
AWG
D Power Cable, Single Conductor, Type TC, 600V, with moisture barrier
E Control Cable, Multi-Conductor, Type TC, 600V. ICEA Method 1, Option A Color Code (no W or G wires). THHN/THWN with PVC jacket
F Control Cable, Multi-Conductor, 600V. ICEA Method 1, Option B Color Code (has W wire)
G Power Cable, Single Conductor, THHN/THWN 600V H Fiber Optic Cable, 62.5/125, Multimode, Glass, Heavy-duty jacket type J Twisted Pair Shielded Instrumentation Cable K Lighting Panel Circuit
L Control Cable, Multi-Conductor, THHW/THWN, 600V, with extra-flexible stranding.
ICEA Method 1, Option B Color Code (has W wire)
M Ethernet Cable N Communication cable as required by interconnecting equipment manufacturers P Power Cable, Multi-Conductor, 600V, Flexible Hard Service Cord, #18 thru #2 AWG
| L25CISCH1 |
| Cable Schedule |
File details come from the government source that posted it.