Lock & Dam No. 25 Formal Circuit Listing

Circuit Dwg. Nos. Conductor Volt Type Function Origin Destination Routing Notes

C251 E90, E91 1 - 12-FIBER CABLE N/A H IPC NETWORK TO LOWER LAND WALL

CONTROL BOOTH

LAN (CENTRAL

CONTROL

CONSOLE)

IPC3 (CB-1) R93, R99, R110 OR R117,

R147

REPLACES ORIGINAL 6-

FIBER CABLE

C252 E90, E91 1 - 12-FIBER CABLE N/A H IPC NETWORK TO UPPER LAND WALL

CONTROL BOOTH

LAN (CENTRAL

CONTROL

CONSOLE)

IPC4 (CB-2) R93, R99, R209, R217, R247 REPLACES ORIGINAL 6-

FIBER CABLE

C260 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK TO LOWER LAND WALL

REMOTE RACK

MCC3-PLC RR-MG1 R117, R147, R182 REPLACES ORIGINAL 6-

FIBER CABLE

C261 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK FROM LOWER LAND WALL

REMOTE TO UPPER LAND WALL REMOTE

RR-MG1 RR-MG2 R117, R147, R182, R217,

R244

REPLACES ORIGINAL 6-

FIBER CABLE

C262 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK FROM UPPER LAND WALL

REMOTE TO LOWER RIVER WALL REMOTE

RR-MG2 RR-MG3 R217, R307, R6??, R244,

R375

C263 E91 1 - 12-FIBER CABLE N/A H PLC NETWORK FROM LOWER RIVER WALL

REMOTE TO UPPER RIVER WALL REMOTE

RR-MG3 RR-MG4 R421, R307, R375, R507 REPLACES ORIGINAL 6-

FIBER CABLE

C265 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO LOWER LAND WALL

REMOTE RACK

MCC3-PLC RR-MG1 R117, R147, R182, R158 REPLACED BY 12-FIBER C260

C266 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO UPPER LAND WALL REMOTE

RACK

RR-MG1 RR-MG2 R117, R147, R182, R158,

R217, R244, R272, R269

REPLACED BY 12-FIBER C261

C267 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO LOWER I- WALL REMOTE

RACK

RR-MG2 RR-MG3 R217, R244, R629, R307,

R375, R381

C268 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO UPPER I- WALL REMOTE

RACK

RR-MG3 RR-MG4 R421, R507, R433, R307,

R375

REPLACED BY 12-FIBER C263

C1190 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-

TG1 THRU RR-TG8

MCC1&2-PLC RR-TG1 R629, R828, R467, R713,

R1919, R1021

C1191 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG2 RR-TG1 RR-TG2 R1061 C1192 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG3 RR-TG2 RR-TG3 R1101 C1193 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG4 RR-TG3 RR-TG4 R1141 C1194 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG5 RR-TG4 RR-TG5 R1181 C1195 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG6 RR-TG5 RR-TG6 R1221 C1196 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG7 RR-TG6 RR-TG7 R1261 C1197 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG8 RR-TG7 RR-TG8 R1301 C1200 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR- RR-TG8 RR-TG9 R1341 C1201 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG12 RR-TG13 R1932, R1381, R1421, R1501 C1202 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG13 RR-TG14 R1541 C1203 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG14 RR-TG15 R1581 C1204 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG15 RR-TG16 R1621 C1205 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-TG16 RR-TG17 R1661

C1210 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-

RG10

RR-RG9 RR-RG10 R629, R828, R467, R713,

R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341, R1932

C1211 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG10 RR-RG11 R1381 C1212 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR- RR-RG11 RR-RG12 R1421

C1230 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-

TG1 THRU RR-TG8

MCC1&2-PLC RR-TG1 R629, R828, R467, R713,

R1919, R1021

C1231 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG2 RR-TG1 RR-TG2 R1061

C1232 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG3 RR-TG2 RR-TG3 R1101

C1233 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG4 RR-TG3 RR-TG4 R1141

Lock & Dam No. 25

Circuit Dwg. Nos. Conductor Volt Type Function Origin Destination Routing Notes C1234 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG5 RR-TG4 RR-TG5 R1181

C1235 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG6 RR-TG5 RR-TG6 R1221

C1236 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG7 RR-TG6 RR-TG7 R1261

C1237 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-TG8 RR-TG7 RR-TG8 R1301

C1240 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-

TG9

RR-TG8 RR-TG9 R629, R828, R467, R713,

R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341

C1241 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

TG13

RR-RG12 RR-TG13 R1932, R1381, R1421, R1501

C1242 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

TG14

RR-TG13 RR-TG14 R1541

C1243 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

TG15

RR-TG14 RR-TG15 R1581

C1244 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

TG16

RR-TG15 RR-TG16 R1621

C1245 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

TG17

RR-TG16 RR-TG17 R1661

C1250 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACKS RR-

RG10

RR-RG9 RR-RG10 R629, R828, R467, R713,

R1919, R1021, R1061, R1101, R1141, R1181, R1221, R1261, R1301, R1341, R1932

C1251 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

RG11

RR-RG10 RR-RG11 R1381

C1252 E91 1 - 6-FIBER CABLE N/A H PLC NETWORK TO DAM REMOTE RACK RR-

RG12

RR-RG11 RR-RG12 R1421

Lock Dam No. 25

TYPE DESCRIPTION

A Control Cable, Multi-Conductor, Type TC, 600V, with moisture barrier. ICEA Method 1, Option A Color Code (no W or G wires).

B Control Cable, Multi-Conductor, Type TC, 600V, with moisture barrier. ICEA Method 1, Option B Color Code (has W wire)

C Power Cable, Multi-Conductor, Type TC, 600V, with moisture barrier, #12 thru #4/0

AWG

D Power Cable, Single Conductor, Type TC, 600V, with moisture barrier

E Control Cable, Multi-Conductor, Type TC, 600V. ICEA Method 1, Option A Color Code (no W or G wires). THHN/THWN with PVC jacket

F Control Cable, Multi-Conductor, 600V. ICEA Method 1, Option B Color Code (has W wire)

G Power Cable, Single Conductor, THHN/THWN 600V H Fiber Optic Cable, 62.5/125, Multimode, Glass, Heavy-duty jacket type J Twisted Pair Shielded Instrumentation Cable K Lighting Panel Circuit

L Control Cable, Multi-Conductor, THHW/THWN, 600V, with extra-flexible stranding.

ICEA Method 1, Option B Color Code (has W wire)

M Ethernet Cable N Communication cable as required by interconnecting equipment manufacturers P Power Cable, Multi-Conductor, 600V, Flexible Hard Service Cord, #18 thru #2 AWG