Building 16

- Positive VAT/mastic materials are present almost over the entire building area (see Appendix B) and are in good condition with low potential for damage. The VAT/mastic is covered with either VFT, or carpet. Approximately 13,500 sq.ft of VAT and asbestos containing mastic is present. Priority 5 was assigned

- VAT and mastic are assumed to be present under the ceramic tiles located in bathrooms 1 to 8, kitchen and lobby 2 (2,100 sq.ft). Priority 5 was assigned.

Building 16

Building 16 is a Reserve Forces Opl & Training facility. The building was constructed in 1965 with a total floor space of20,896 sq.ft.

Homogeneous Areas (see Table 1)

The visual survey resulted in the identification of seven potential ACM homogeneous areas as described below.

mastic. Priority 5 was assigned.

Therefore immediate action is not required. Visual re-evaluations are required every six months and control activities will be needed if deterioration will take place.

Control activities are to be performed in accordance with EQB requirements under regulation 422.