Addendum_AT_FP_Drawing.pdf
PDF 454 KB Posted
- Attached to
- Construct Billeting Office Federal contract opportunity
- Solicitation number
- W912L7-18-B-7001
About this file
AT FP Drawing
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Abstract_of_offers_18B7001_signed.pdf | ||
| W912L718B7001_Amendment_4.pdf | ||
| W912L718B7001_Amendment_3.pdf | ||
| W912L718B7001_Amendment_2.pdf | ||
| W912L718B7001_Amendment_1.pdf | ||
| Specifications_Amendment_1.zip | ZIP file | |
| Preproposal_minutes_W912L718B7001.pdf | ||
| Site_Visit_Slides_20_Apr_2018.pdf | ||
| Sign_in_Sheet.pdf | ||
| W912L718B7001_8_Apr_2018.pdf | ||
| JA-Brand_Name_Simplex.pdf | ||
| Specifications.zip | ZIP file | |
| 21-17007_134th_Billeting_Office_-_Alcoa,_TN.pdf | ||
| Drawings.zip | ZIP file |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C
C
C
W
F
M
W
W
N
E
Z
N
E
Z
N
E
Z
M
A
G
N
A
I
L
M
A
G
N
A
I
L
M
A
G
N
A
I
L
C
C
C
C
G
G
G
G
G
G
G
G
G
G
G
W
W
W
W
W
W
W
W
W
W
AT/FP
A T/
FP
H
U S
PF
O
B
A S
E D
E S
IG
N
S
TA
N D
A R
D
A
TF
P S
TA
N
D O
FF
S
B A
S E
W
ID
E
D R
A W
IN
G
S
RJB
CJS
SCALE: 1 INCH = 20 FEET
0 20 40 60
100%
SUBMITTAL
ANTI-TERRORISM/FORCE PROTECTION CHECKLIST
PER REQUIREMENTS OF UFC 4-010-01 DATED 1 OCTOBER 2013
FACILITY CATEGORY INFORMATION
NEW CONSTRUCTION: REINFORCED MASONRY; LOAD BEARING EXTERIOR WALLS
PERIMETER: CONTROLLED
BUILDING POPULATION: 11
BUILDING CATEGORY: INHABITED (ROUTINELY OCCUPIED BY 11 OR MORE)
STANDARD 1. STANDOFF DISTANCES
TABLE B-1, B-2
PARKING & ROADWAYS WITHIN CONTROLLED PERIMETER CONVENTIONAL
CONSTRUCTION STANDOFF DISTANCE (CCSD) - MINIMUM OF 30' FROM LOAD
BEARING WALLS.
TRASH CONTAINERS - MINIMUM OF 30' FROM LOAD BEARING WALLS FOR NEW
CONSTRUCTION.
DESIGN: DESIGN COMPLIES WITH STANDOFF TO PARKING & ROADWAYS.
EXISTING PARKING AND DRIVE AISLES WILL BE DEMOLISHED FOR THE BUILDING
AND ALL OTHER DRIVE AISLES FOR EXISTING ROADWAYS SHALL REMAIN.
TRASH CONTAINERS SHALL BE LOCATED OUTSIDE OF CCSD AS DENOTED ON
THIS PLAN. DESIGN COMPLIES WITH STANDOFF TO TRASH CONTAINERS.
STANDARD 2. UNOBSTRUCTED SPACE
B-1.2 ENSURE THAT OBSTRUCTIONS WITHIN CCSD OF INHABITED BUILDINGS OR
PORTIONS THEREOF DO NOT ALLOW FOR CONCEALMENT FROM OBSERVATION
OF EXPLOSIVE DEVICES 6 INCHES OR GREATER IN HEIGHT.
DESIGN: NO OBSTRUCTIONS WITHIN CCSD OF THE BUILDING.
STANDARD 3. DRIVE-UP/DROP-OFF AREAS
B-1.3 PERMITTED WITHIN STAND-OFF AREAS, MEETING THESE CRITERIA: NO
UNATTENDED VEHICLES ARE PERMITTED IN THESE AREAS. CANNOT BE
LOCATED UNDER ANY INHABITED PORTION OF A BUILDING.
DESIGN: NO DRIVE-UP/DROP-OFF AREAS PROVIDED
STANDARD 4. ACCESS ROADS
B-1.4 ACCESS CONTROL MEASURES REQUIRED TO PROHIBIT UNAUTHORIZED
VEHICLES FROM USING ACCESS ROADS WITHIN THE APPLICABLE STANDOFF
DISTANCES IN TABLES B-1 AND B-2.
DESIGN: NO ADDITIONAL ACCESS CONTROL PROVIDED ADJACENT TO BUILDING.
THE BASE CURRENTLY HAS RESTRICTED ACCESS.
STANDARD 5. PARKING BENEATH BUILDINGS OR ON ROOFTOPS
B-1.5 ELIMINATE PARKING BENEATH INHABITED BUILDINGS OR ON ROOFTOPS OF
INHABITED BUILDINGS
DESIGN: NO PARKING BENEATH BUILDINGS OR ON ROOFTOPS
STANDARD 6. PROGRESSIVE COLLAPSE AVOIDANCE
B-2.1 APPLIES TO BUILDING OF THREE OR MORE STORIES ONLY
DESIGN: APPLIES TO BUILDING OF THREE OR MORE STORIES ONLY
STANDARD 7. STRUCTURAL ISOLATION
B-2.2.1 APPLIES TO ADDITIONS TO EXISTING BUILDINGS
DESIGN: THIS IS NEW CONSTRUCTION AND IS A SEPARATE FACILITY.
STANDARD 8. BUILDING OVERHANGS AND BREEZEWAYS
B-2.2.3 AVOID BUILDING OVERHANGS WITH INHABITED SPACES ABOVE THEM
DESIGN: NO OVERHANGS WITH INHABITED SPACES ABOVE.
STANDARD 9. EXTERIOR MASONRY WALLS
B-2.3.2 REQUIRED TO MEET CCSD STANDOFF DISTANCE OR PROVIDE
MITIGATING MEASURES TO PROVIDE THE APPLICABLE LEVEL OF PROTECTION
AS IDENTIFIED IN TABLE 2-1
DESIGN: EXTERIOR WALLS OF NEW BUILDING WILL BE REINFORCED MASONRY.
STANDARD 10. WINDOWS AND SKYLIGHTS
TABLE B-2 APPLICABLE LEVEL OF PROTECTION: VERY LOW, EXPLOSIVE WEIGHTS I & II
DESIGN: WINDOWS WILL BE ATFP WINDOWS.
STANDARD 11. BUILDING ENTRANCE LAYOUT
B-3.2.2 ENSURE THAT THE MAIN ENTRANCE TO THE BUILDING DOES NOT FACE
AN INSTALLATION PERIMETER OR OTHER UNCONTROLLED VANTAGE POINT WITH
DIRECT LINES OF SIGHT TO THE ENTRANCE, OR PROVIDE MEANS TO BLOCK THE
LINES OF SIGHT.
DESIGN: THE MAIN ENTRANCE OF THE BUILDING DOES NOT FACE THE
CONTROLLED PERIMETER DIRECTLY AND CONTAINS A VESTIBULE.
STANDARD 12. EXTERIOR DOORS
B-3.3 EXTERIOR DOORS INTO INHABITED AREAS MUST OPEN OUTWARDS
DESIGN: ALL EXTERIOR DOORS OPEN OUTWARDS
STANDARD 13. MAIL ROOMS
B-3.4 APPLIES TO FACILITIES WITH MAIL ROOMS
DESIGN: NO MAIL ROOMS IN THE BUILDING
STANDARD 14. ROOF ACCESS
B-3.5.2 FOR EXISTING BUILDINGS, ELIMINATE EXTERNAL ROOF ACCESS WHERE
POSSIBLE OR SECURE EXTERNAL LADDERS OR STAIRWAYS WITH LOCKED
CAGES OR SIMILAR MECHANISMS
DESIGN: NO ROOF ACCESS
STANDARD 15. OVERHEAD MOUNTED ARCHITECTURAL FEATURES
B-3.6 OVERHEAD FEATURES WEIGHING 31 LBS. OR MORE - MOUNTED SO THAT THEY
RESIST 0.5 TIMES THE COMPONENT WEIGHT IN ANY HORIZONTAL DIRECTION
AND 1.5 TIMES THE COMPONENT WEIGHT IN THE DOWNWARD DIRECTION
DESIGN: DESIGN WILL COMPLY WITH THESE REQUIREMENTS.
STANDARD 16. AIR INTAKES
B-4.1.2 AT LEAST 3 METERS (10') ABOVE THE GROUND
DESIGN: DESIGN WILL COMPLY WITH THIS REQUIREMENT
STANDARD 17. MAIL ROOM AND LOADING DOCK VENTILATION
B-4.2 APPLIES ONLY TO MAIL ROOMS AND DOCKS
DESIGN: NOT APPLICABLE, NO MAIL ROOM OR LOADING DOCKS IN THIS PROJECT
STANDARD 18. EMERGENCY AIR DISTRIBUTION SHUTOFF
B-4.3 PROVIDE EMERGENCY SHUTOFF SWITCH IN HVAC CONTROL SYSTEM
DESIGN: DESIGN WILL COMPLY WITH THIS REQUIREMENT
STANDARD 19. EQUIPMENT BRACING
B-4.4 OVERHEAD UTILITIES AND FIXTURES WEIGHING 31 LBS. OR MORE - MOUNTED SO
THAT THEY RESIST 0.5 TIMES THE COMPONENT WEIGHT IN ANY HORIZONTAL
DIRECTION AND 1.5 TIMES THE COMPONENT WEIGHT IN THE DOWNWARD
DIRECTION
DESIGN: DESIGN WILL SHOW BRACES AND ATTACHMENT DETAILS OF OVERHEAD
UTILITIES AND FIXTURES WEIGHING 31 LBS. OR MORE.
STANDARD 20. UNDER BUILDING ACCESS
B-4.5 APPLIES TO BUILDINGS WITH CRAWL SPACES, UTILITY TUNNELS, OR OTHER
MEANS OF UNDER BUILDING ACCESS
DESIGN: NO UNDER BUILDING ACCESS PROVIDED
STANDARD 21. MASS NOTIFICATION
B-4.6.2 PROVIDE CAPABILITY FOR REAL-TIME INFORMATION TO OCCUPANTS OR
PERSONNEL IN THE IMMEDIATE VICINITY DURING EMERGENCY SITUATIONS.
DESIGN: PUBLIC ADDRESS SYSTEM WILL BE PROVIDED IN THE FACILITY AND
CONNECT TO THE BASE WIDE GIANT VOICE SYSTEM
on st ru ct B ill et in g
O ffi ce
4t h A ir R ef u el in g W in g
PSXE132005
11.03.17