RFQ W912L7-15-Q-1112 (Question and Answer 1)
Q. Who is the current controls company for the chiller being replace?
A. Automated Logic.
Q. It was noted at the site visit that appox. 350-400 gallons of fuel was contaminated in the generator at building 757. Would filtering the fuel or draining the tank be priced as an option to the repair bid?
A. Not an option. The contractor will remove and dispose of the contaminated fuel. The contactor will clean the fuel tank. The government will replace the fuel.