SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01686-000
Selfridge Air
National Guard
Base
SANG 117 & 126 Mechanical
Renovation
Harrison Township, MI 48045
SANG Project No.: VGLZ 162045
M8-02
Control Diagrams
I
T
HOOD
SP 65° F
GMAU-1 MAKE-UP AIR UNIT & INTERLOCKED EXHAUST FANS CONTROL DIAGRAM
SEQUENCE OF OPERATION
DURING OPERATION THE GAS FIRED MAKE-UP AIR UNITS GAS HEATING SECTION SHALL MODULATE AS NECESSARY TO
MAINTAIN THE SPACE
TEMPERATURE SET POINT. WELDING HOOD AND DUST COLLECTOR EXHAUST FANS SHALL BE INTERLOCKED
TO START WHEN THE MAKE UP AIR UNIT IS STARTED. MAKE UP AIR UNIT AND EXHAUST FANS OPERATIONAL STATUS
SHALL BE IDENTIFIED AT THE DDC CONTROLLER. IF EITHER EXHAUST FAN FAILS TO INDICATE OPERATION THROUGH ITS
ASSOCIATED CURRENT TRANSFORMER (IY) WITHIN 30 SECS ( ADJ.) AFTER START INITIATION A FAILURE ALARM SHALL
BE INITIATED. THE MAKE UP AIR UNIT OPERATIONAL STATUS AND COMMON ALARM SHALL BE IDENTIFIED TO THE DDC
SYSTEM.
OA
MS
M
MS
M
AUTOMATED LOGIC (DDC)PANEL
IY IY
SA
T E
M P
E R
A T
U R
E
S
E T
P
O I N
T
M U
A
O
N O
F F
S
T A
T U
S
M U
A
C
O M
M O
N
A
L A
R M
EXHAUST FANS START/STOP INTERLOCK
DUST COLLECTOR EXHAUST FAN STATUS
WELDING HOOD EXHAUST FAN STATUS
GMAU-1 DUST COLLECTOR
EXHAUST FAN
WELDING HOOD
EXHAUST FAN
BMS
SA
WARM AIR FURNACE WAF-126-1, 4, 5, AND 6 CONTROL DIAGRAM (FIXED OUTDOOR AIR)
T
AUTOMATED LOGIC (DDC)PANEL
11/15/16 CD (65%) Submittal
RA
DP
M
NC
OUTDOOR AIR
MOTORIZED TWO-POSITION
OUTDOOR AIR DAMPER
CONTROL
SECTION
CONTROL
SECTION
M
WAF-126-1
WAF-126-4
WAF-126-5
WAF-126-6
ACU-126-1
ACU-126-4
ACU-126-5
ACU-126-6
FILTER MEDIA
BOX
AIR COOLED
CONDENSING UNIT
SPACE
TEMPERATURE
SENSOR
SEQUENCE OF OPERATION:
OCCUPIED/UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE AUTOMATED LOGIC DDC CONTROL SYSTEM.
OCCUPIED:
WARM AIR FURNACE BLOWER OPERATES CONTINUOUSLY OUTDOOR AIR DAMPER OPENS TO FIXED OUTDOOR AIR POSITION
SPACE TEMPERATURE SENSOR CYCLES GAS FIRED FURNACE HEATING SECTION OR DX COOLING SECTION TO MAINTAIN
DESIRED SPACE TEMPERATURE
UNOCCUPIED:
OUTDOOR AIR DAMPER CLOSES, WARM AIR FURNACE BLOWER AND GAS FIRED HEATING SECTION CYCLE TO MAINTAIN SPACE
SET-BACK TEMPERATURE. DX COOLING SYSTEM IS LOCKED OUT.
ALARMS:
CLOGGED AIR FILTER (DP)
WARM AIR FURNACE GENERAL ALARM.
HIGH SPACE TEMPERATURE (T)
LOW SPACE TEMPERATURE (T)
BAS SYSTEM
SA
TWINNED WARM AIR FURNACE WAF-126-2A/2B AND 3A/3B CONTROL DIAGRAM (MODULATING ECONOMIZER)
T
AUTOMATED LOGIC (DDC)PANEL
RA
DP
M
NC
OUTDOOR AIR
MOTORIZED MODULATING
OUTDOOR AIR DAMPER
CONTROL
SECTION
CONTROL
SECTION
M
WAF-126-2A
WAF-126-2B
WAF-126-3A
WAF-126-3B
ACU-126-2A
ACU-126-2B
ACU-126-3A
ACU-126-3B
FILTER MEDIA
BOX
AIR COOLED
CONDENSING UNIT
SPACE
TEMPERATURE
SENSOR
SEQUENCE OF OPERATION:
OCCUPIED/UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE AUTOMATED LOGIC DDC CONTROL SYSTEM.
OCCUPIED:
FURNACE "A" AND "B" ARE INTERLOCKED (TWINNED) FOR SIMULTANEOUS OPERATION AS A SINGLE UNIT.
WARM AIR FURNACE BLOWER OPERATES CONTINUOUSLY.
IN HEATING MODE OUTDOOR AIR DAMPER OPENS TO MINIMUM POSITION SPACE TEMPERATURE SENSOR MODULATES GAS
FIRED HEATING SECTION TO MAINTAIN DESIRED SPACE TEMPERATURE.
IN COOLING MODE ECONOMIZER IS FIRST STAGE OF COOLING PROVIDED THAT THE OUTDOOR AIR ENTHALPY IS EQUAL TO OR
LESS THAN RETURN AIR ENTHALPY OUTDOOR AIR AND RELIEF AIR DAMPERS ARE MODULATED BY THE BAS TO MAINTAIN
DESIRED SPACE TEMPERATURE. IF OUTDOOR AIR ENTHALPY IS GREATER THAN RETURN AIR ENTHALPY THE OUTDOOR AIR
DAMPERS RETURN TO MINIMUM POSITION AND THE MECHANICAL DX COOLING SYSTEM IS CYCLED TO MAINTAIN DESIRED SPACE
TEMPERATURE.
UNOCCUPIED:
OUTDOOR AIR DAMPER CLOSES, WARM AIR FURNACE BLOWER AND GAS FIRED HEATING SECTION CYCLE TO MAINTAIN SPACE
SET-BACK TEMPERATURE. DX COOLING SYSTEM IS LOCKED OUT.
ALARMS:
CLOGGED AIR FILTER (DP) EACH FILTER.
WARM AIR FURNACE GENERAL ALARM, EACH FURNACE.
HIGH SPACE TEMPERATURE (T)
LOW SPACE TEMPERATURE (T)
BAS SYSTEM
M
NO
MOTORIZED MODULATING
RELIEF AIR DAMPER OPEN TO
ATTIC SPACE
GAS FIRED RADIANT TUBE HEATER SEQUENCE OF OPERATION
GAS FIRED RADIANT TUBE HEATERS ARE CONTROLLED BY THE BAS DDC CONTROL
SYSTEM. OCCUPIED/UNOCCUPIED MODES OF OPERATION ARE DETERMINED BY THE
DDC SYSTEM.
OCCUPIED:
SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES RADIANT TUBE HEATERS
TO MAINTAIN DESIRED OCCUPIED SPACE TEMPERATURE.
UNOCCUPIED:
SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES RADIANT TUBE HEATERS
TO MAINTAIN DESIRED SET-BACK TEMPERATURE.
GAS FIRED UNIT HEATER SEQUENCE OF OPERATION
GAS FIRED UNIT HEATERS ARE CONTROLLED BY THE BAS DDC CONTROL SYSTEM.
OCCUPIED/UNOCCUPIED MODES OF OPERATION ARE DETERMINED BY THE DDC
SYSTEM.
OCCUPIED:
SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES UNIT HEATER FAN AND
GAS FIRED HEATING SECTION TO MAINTAIN DESIRED OCCUPIED SPACE TEMPERATURE.
UNOCCUPIED:
SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES UNIT HEATER FAN AND
GAS FIRED HEATING SECTION TO MAINTAIN DESIRED SET-BACK TEMPERATURE.
ELECTRIC UNIT HEATER SEQUENCE OF OPERATION
ELECTRIC UNIT HEATER IS CONTROLLED BY WALL MOUNTED ELECTRIC WALL
THERMOSTAT.
WALL MOUNTED THERMOSTAT CYCLES UNIT HEATER FAN AND ELECTRIC HEATING
ELEMENT TO MAINTAIN DESIRED SPACE TEMPERATURE..
01/13/17 Pre-Final (95%) Submittal
02/08/17 Final (100%) Submittal