SANG 117 & 126 Mechanical

Renovation

Harrison Township, MI 48045

SANG Project No.: VGLZ 162045

M8-02

Control Diagrams

I

T

HOOD

SP 65° F

GMAU-1 MAKE-UP AIR UNIT & INTERLOCKED EXHAUST FANS CONTROL DIAGRAM

SEQUENCE OF OPERATION

DURING OPERATION THE GAS FIRED MAKE-UP AIR UNITS GAS HEATING SECTION SHALL MODULATE AS NECESSARY TO

MAINTAIN THE SPACE

TEMPERATURE SET POINT. WELDING HOOD AND DUST COLLECTOR EXHAUST FANS SHALL BE INTERLOCKED

TO START WHEN THE MAKE UP AIR UNIT IS STARTED. MAKE UP AIR UNIT AND EXHAUST FANS OPERATIONAL STATUS

SHALL BE IDENTIFIED AT THE DDC CONTROLLER. IF EITHER EXHAUST FAN FAILS TO INDICATE OPERATION THROUGH ITS

ASSOCIATED CURRENT TRANSFORMER (IY) WITHIN 30 SECS ( ADJ.) AFTER START INITIATION A FAILURE ALARM SHALL

BE INITIATED. THE MAKE UP AIR UNIT OPERATIONAL STATUS AND COMMON ALARM SHALL BE IDENTIFIED TO THE DDC

SYSTEM.

OA

MS

M

MS

M

AUTOMATED LOGIC (DDC)PANEL

IY IY

SA

T E

M P

E R

A T

U R

E

S

E T

P

O I N

T

M U

A

O

N O

F F

S

T A

T U

S

M U

A

C

O M

M O

N

A

L A

R M

EXHAUST FANS START/STOP INTERLOCK

DUST COLLECTOR EXHAUST FAN STATUS

WELDING HOOD EXHAUST FAN STATUS

GMAU-1 DUST COLLECTOR

EXHAUST FAN

WELDING HOOD

EXHAUST FAN

BMS

SA

WARM AIR FURNACE WAF-126-1, 4, 5, AND 6 CONTROL DIAGRAM (FIXED OUTDOOR AIR)

T

AUTOMATED LOGIC (DDC)PANEL

11/15/16 CD (65%) Submittal

RA

DP

M

NC

OUTDOOR AIR

MOTORIZED TWO-POSITION

OUTDOOR AIR DAMPER

CONTROL

SECTION

CONTROL

SECTION

M

WAF-126-1

WAF-126-4

WAF-126-5

WAF-126-6

ACU-126-1

ACU-126-4

ACU-126-5

ACU-126-6

FILTER MEDIA

BOX

AIR COOLED

CONDENSING UNIT

SPACE

TEMPERATURE

SENSOR

SEQUENCE OF OPERATION:

OCCUPIED/UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE AUTOMATED LOGIC DDC CONTROL SYSTEM.

OCCUPIED:

WARM AIR FURNACE BLOWER OPERATES CONTINUOUSLY OUTDOOR AIR DAMPER OPENS TO FIXED OUTDOOR AIR POSITION

SPACE TEMPERATURE SENSOR CYCLES GAS FIRED FURNACE HEATING SECTION OR DX COOLING SECTION TO MAINTAIN

DESIRED SPACE TEMPERATURE

UNOCCUPIED:

OUTDOOR AIR DAMPER CLOSES, WARM AIR FURNACE BLOWER AND GAS FIRED HEATING SECTION CYCLE TO MAINTAIN SPACE

SET-BACK TEMPERATURE. DX COOLING SYSTEM IS LOCKED OUT.

ALARMS:

CLOGGED AIR FILTER (DP)

WARM AIR FURNACE GENERAL ALARM.

HIGH SPACE TEMPERATURE (T)

LOW SPACE TEMPERATURE (T)

BAS SYSTEM

SA

TWINNED WARM AIR FURNACE WAF-126-2A/2B AND 3A/3B CONTROL DIAGRAM (MODULATING ECONOMIZER)

T

AUTOMATED LOGIC (DDC)PANEL

RA

DP

M

NC

OUTDOOR AIR

MOTORIZED MODULATING

OUTDOOR AIR DAMPER

CONTROL

SECTION

CONTROL

SECTION

M

WAF-126-2A

WAF-126-2B

WAF-126-3A

WAF-126-3B

ACU-126-2A

ACU-126-2B

ACU-126-3A

ACU-126-3B

FILTER MEDIA

BOX

AIR COOLED

CONDENSING UNIT

SPACE

TEMPERATURE

SENSOR

SEQUENCE OF OPERATION:

OCCUPIED/UNOCCUPIED MODE OF OPERATION IS DETERMINED BY THE AUTOMATED LOGIC DDC CONTROL SYSTEM.

OCCUPIED:

FURNACE "A" AND "B" ARE INTERLOCKED (TWINNED) FOR SIMULTANEOUS OPERATION AS A SINGLE UNIT.

WARM AIR FURNACE BLOWER OPERATES CONTINUOUSLY.

IN HEATING MODE OUTDOOR AIR DAMPER OPENS TO MINIMUM POSITION SPACE TEMPERATURE SENSOR MODULATES GAS

FIRED HEATING SECTION TO MAINTAIN DESIRED SPACE TEMPERATURE.

IN COOLING MODE ECONOMIZER IS FIRST STAGE OF COOLING PROVIDED THAT THE OUTDOOR AIR ENTHALPY IS EQUAL TO OR

LESS THAN RETURN AIR ENTHALPY OUTDOOR AIR AND RELIEF AIR DAMPERS ARE MODULATED BY THE BAS TO MAINTAIN

DESIRED SPACE TEMPERATURE. IF OUTDOOR AIR ENTHALPY IS GREATER THAN RETURN AIR ENTHALPY THE OUTDOOR AIR

DAMPERS RETURN TO MINIMUM POSITION AND THE MECHANICAL DX COOLING SYSTEM IS CYCLED TO MAINTAIN DESIRED SPACE

TEMPERATURE.

UNOCCUPIED:

OUTDOOR AIR DAMPER CLOSES, WARM AIR FURNACE BLOWER AND GAS FIRED HEATING SECTION CYCLE TO MAINTAIN SPACE

SET-BACK TEMPERATURE. DX COOLING SYSTEM IS LOCKED OUT.

ALARMS:

CLOGGED AIR FILTER (DP) EACH FILTER.

WARM AIR FURNACE GENERAL ALARM, EACH FURNACE.

HIGH SPACE TEMPERATURE (T)

LOW SPACE TEMPERATURE (T)

BAS SYSTEM

M

NO

MOTORIZED MODULATING

RELIEF AIR DAMPER OPEN TO

ATTIC SPACE

GAS FIRED RADIANT TUBE HEATER SEQUENCE OF OPERATION

GAS FIRED RADIANT TUBE HEATERS ARE CONTROLLED BY THE BAS DDC CONTROL

SYSTEM. OCCUPIED/UNOCCUPIED MODES OF OPERATION ARE DETERMINED BY THE

DDC SYSTEM.

OCCUPIED:

SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES RADIANT TUBE HEATERS

TO MAINTAIN DESIRED OCCUPIED SPACE TEMPERATURE.

UNOCCUPIED:

SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES RADIANT TUBE HEATERS

TO MAINTAIN DESIRED SET-BACK TEMPERATURE.

GAS FIRED UNIT HEATER SEQUENCE OF OPERATION

GAS FIRED UNIT HEATERS ARE CONTROLLED BY THE BAS DDC CONTROL SYSTEM.

OCCUPIED/UNOCCUPIED MODES OF OPERATION ARE DETERMINED BY THE DDC

SYSTEM.

OCCUPIED:

SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES UNIT HEATER FAN AND

GAS FIRED HEATING SECTION TO MAINTAIN DESIRED OCCUPIED SPACE TEMPERATURE.

UNOCCUPIED:

SPACE TEMPERATURE SENSOR THROUGH THE DDC CYCLES UNIT HEATER FAN AND

GAS FIRED HEATING SECTION TO MAINTAIN DESIRED SET-BACK TEMPERATURE.

ELECTRIC UNIT HEATER SEQUENCE OF OPERATION

ELECTRIC UNIT HEATER IS CONTROLLED BY WALL MOUNTED ELECTRIC WALL

THERMOSTAT.

WALL MOUNTED THERMOSTAT CYCLES UNIT HEATER FAN AND ELECTRIC HEATING

ELEMENT TO MAINTAIN DESIRED SPACE TEMPERATURE..

01/13/17 Pre-Final (95%) Submittal

02/08/17 Final (100%) Submittal