SHEET NO:

SHEET TITLE:

PROJECT NUMBER:

COPYRIGHT © 2016

DATE ISSUE

26913 NORTHWESTERN HWY

SUITE 200

SOUTHFIELD, MICHIGAN

48033 | USA

(T) 248 262 1500

WWW.HED.DESIGN

2016-01686-000

Selfridge Air

National Guard

Base

SANG 117 & 126 Mechanical

Renovation

Harrison Township, MI 48045

SANG Project No.: VGLZ 162045

M-G1

Mechanical Symbols and

Legends Buildings 117&126

RISE

DROP

CEILING DIFFUSER (SQUARE OR RECTANGULAR)

LINEAR SLOT DIFFUSER

SUPPLY REGISTER

SENSING DEVICE WITH

AVERAGING TYPE ELEMENT

SENSING DEVICE WITH

RIGID TYPE ELEMENT

SENSING DEVICE WITH

RIGID TYPE ELEMENT

MOUNTED IN WELL

POSITION SWITCH

(LIMIT SWITCH)

LEVEL ELEMENT

(PROBE TYPE)

PRESSURE SENSING ELEMENT

(L=LOW, H=HIGH)

M

ZS

SD

H

L

AS

I

T

NEW PIPE

EXIST. PIPE

NEW CONNECTION TO EXISTING

REFRIGERANT DISCHARGERD

RS REFRIGERANT SUCTION

REFRIGERANT LIQUIDRL

NON-POTABLE HOT WATER

NPCW NON-POTABLE COLD WATER

FUEL OIL RETURNFOR

FOS FUEL OIL SUPPLY

ENERGY RECOVERY RETURNERR

ERS ENERGY RECOVERY SUPPLY

GLYCOL WATER RETURNGWR

GWS GLYCOL WATER SUPPLY

CONDENSER WATER RETURNCWR

CWS CONDENSER WATER SUPPLY

CHILLED WATER RETURNCHWR

CHWS CHILLED WATER SUPPLY

HEATING HOT WATER RETURN

HHWR

HHWS HEATING HOT WATER SUPPLY

EXISTING PIPE TO BE REMOVED

PIPING DESIGNATIONS

MISCELLANEOUS SYMBOLS

STEAM TRAP

UNION

STRAINER

FLOOR DRAIN (F.D.)FD-X

PIPE ANCHOR

EXPANSION JOINT

THERMOMETER

WATER HAMMER ARRESTER

REDUCER OR INCREASER

FLANGES

DRIP POCKET

PITCH DOWN IN DIRECTION OF FLOW

FIRE HYDRANT (F.H.)

BRANCH CONNECTION OUT OF SIDE

CAPPED TEE

AUTOMATIC FIRE SPRINKLER RISER (ASR)

FIRE DEPARTMENT CONNECTION (SIAMESE) (FDC)

FIRE PROTECTION SPRINKLER HEAD (UPRIGHT)

FIRE PROTECTION SPRINKLER HEAD (PENDENT)

SIDEWALL FIRE PROTECTION SPRINKLER HEADS

FIRE PUMP TEST HEADER

FIN TUBE RADIATION

GENERAL DUCTWORK SYMBOLS

6"

FLEXIBLE DUCT

SUPPLY AIR/OSA DUCT UP

DOUBLE LINE DUCTWORK SYMBOLS

EXISTING DUCT TO BE REMOVED

CEILING DIFFUSER (ROUND)

FLEXIBLE DUCT CONNECTION

DUCT TRANSITION

INCLINED DROP WITH RESPECT TO AIR FLOW

INCLINED RISE WITH RESPECT TO AIR FLOW

D

R

AD

20X20

12X12

ACOUSTICALLY LINED DUCT

DUCT SIZE (A=SIDE SHOWN, B=SIDE NOT SHOWN)

AXB

SINGLE LINE DUCTWORK SYMBOLS

EXISTING DUCT TO REMAIN

EXISTING DUCT TO BE REMOVED

DUCT ELBOW DOWN

DUCT ELBOW UP

FLEXIBLE CONNECTION

DUCT TRANSITION

INCLINED DROP WITH RESPECT TO AIR FLOW

INCLINED RISE WITH RESPECT TO AIR FLOW

AD

ACOUSTICALLY LINED DUCT

AXB

CONTROL SYMBOLS

FLOW SWITCH

SMOKE DETECTOR

POWER WIRING

ELECTRICAL/ELECTRONIC

PNEUMATIC SIGNAL

INSTRUMENT AIR SUPPLY

CONTROL SIGNAL WIRING

INTERLOCK

(NOTE: ARROWS ON LINES

INDICATE CONTROL LOGIC FLOW)

MOTOR

VIA HARDWIRE CONNECTION

FLEXIBLE CONNECTOR PIPE

NPHW

DEIONIZED WATERDI

A COMPRESSED AIR

MEDICAL COMPRESSED AIRMA

VAC VACUUM

NITROUS OXIDE

N2

NITROGEN

OXYGENO2

STEAM (INDICATE PSI __ )

HPWR

HPWS HEAT PUMP WATER SUPPLY

HEAT PUMP WATER RETURN

PRESSURE GAUGE AND COCK

PUR PURIFIED WATER

HORIZONTAL FIRE DAMPER

HORIZONTAL SMOKE DAMPER

HORIZONTAL FIRE/SMOKE DAMPER

SOUND ATTENUATOR

SA

ACCESS DOOR

MANUAL VOLUME DAMPER

ACCESS DOOR

MANUAL VOLUME DAMPER

HVC

HVC

HVC

HOSE VALVE CABINET

(SURFACE MOUNTED)

HOSE VALVE CABINET

(SURFACE MOUNTED - STAIRWELL)

HOSE VALVE CABINET

(RECESSED)

MOTORIZED DAMPER

AUTOMATIC AIR VENT

MANUAL AIR VENT

FLOW SWITCH

MV

FS

AV

STRAINER WITH BLOW DOWN VALVE

DIGITAL INPUT

DIGITAL OUTPUT

ANALOG OUTPUT

ANALOG INPUT

LIGHT TROFFER DIFFUSER

LINEAR SLOT DIFFUSER

SUPPLY REGISTER

NO

STM __

COND __ CONDENSATE (INDICATE PSI __ )

PLUMBING DESIGNATIONS

HORIZONTAL OR WALL CLEAN OUT

FLOOR CLEANOUT OR CLEANOUT AT GRADE

PIPE CAP

PIPE DROP

PIPE RISE

45 OR 90 DEGREES OFF TOP

45 OR 90 DEGREES OFF BOTTOM

DUCT SIZE (A=SIZE IN VIEW, B=SIZE IN DEPTH)

VERTICAL FIRE/SMOKE DAMPER WITH ACCESS DOOR

VERTICAL SMOKE DAMPER WITH ACCESS DOOR

VERTICAL FIRE DAMPER WITH ACCESS DOOR

MITERED ELBOW WITHOUT TURNING VANES

MITERED ELBOW WITH TURNING VANES

VERTICAL FIRE/SMOKE DAMPER WITH ACCESS DOOR

VERTICAL SMOKE DAMPER ACCESS DOOR

VERTICAL FIRE DAMPER ACCESS DOOR

PRESSURE TEMPERATURE TAP

THERMOSTAT

FLANGED CONNECTION

AUTOMATIC CONTROL DAMPER

M

STRUCTURAL STEEL OPENING (SEE STRUCT. DWGS.)

SHUT-OFF VALVE IN YARD BOX

DROP OR RISE

VALVE IN VERTICAL

VVB

XXX

VVB

XXX

SUPPLY AIR/OSA DUCT DN

EXHAUST AIR UP

EXHAUST AIR DN

CVB

XXX

RB/EB

XXX

DETAIL DESIGNATION

SHEET NO.

DETAIL NO.

Ø DIAMETER

SQUARE FOOT

LOUVER (DOOR OR WALL)

AND FREE AREA

FA

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

LAB WASTE VENTLV

PLUMBING VENT PIPING

DRAIN TILE CONNECTION

ST

LAB WASTELW

SAN

SHW

SCW

D DRAIN

SOFT COLD WATER

SOFT HOT WATER

GW GREASE WASTE

TP TRAP PRIMER LINE

TEMPERED WATER

TEMPERED WATER RETURN

OVERFLOW STORM DRAIN

TWR

OSD

TW

V ATMOSPHERIC VENT

G NATURAL GAS

SPRINKLER PIPESP

F FIRE LINE

PC

T

D&T

STEAM DRIP AND TRAP ASSEMBLY

SAN WASTE BELOW GRADE

WASTE ABOVE GRADE

ST STORM BELOW GRADE

STORM ABOVE GRADE

PIPE SLEEVE OR GUIDE

TEMPERATURE AND PRESSURE TEST PLUG

AUTOMATIC FLOW CONTROL VALVE

INDICATES DIRECTION OF FLOW

FLOW MEASURING STATION

VALVE SYMBOLS

RELIEF OR SAFETY VALVE

THREE-WAY ELECTRONIC CONTROL VALVE

TWO-WAY ELECTRONIC CONTROL VALVE

GLOBE VALVE

GATE VALVE

BALL VALVE

PRESSURE REDUCING VALVE

ANGLE VALVE

BUTTERFLY VALVE

PLUG VALVE

NON-FREEZE WALL HYDRANT

WH

WALL

S

OUTSIDE STEM & YOKE GATE VALVE

BALANCING VALVE (SEE SPECS)

BFP BACKFLOW PREVENTER

CHECK VALVE

(ARROW INDICATES FLOW DIRECTION)

SOLENOID VALVE

DRAIN VALVE

HOSE VALVE

PRESSURE RELIEF VALVE

P&T

PRESS.AND TEMP. RELIEF VALVE

VARIABLE VOLUME BOX W/REHEAT COIL

(XXX=DESIGNATION)

CONSTANT VOLUME BOX W/REHEAT COIL

(XXX=DESIGNATION)

VARIABLE VOLUME BOX

(XXX=DESIGNATION)

RETURN/EXHAUST AIR BOX

(XXX=DESIGNATION)

CEILING SUPPLY AIR DIFFUSER (ROUND)

CEILING SUPPLY AIR DIFFUSER (SQUARE OR RECTANGULAR)

CEILING RETURN AIR GRILLE (SQUARE OR RECTANGULAR)

CEILING EXHAUST AIR GRILLE (SQUARE OR RECTANGULAR)

AUTOMATIC CONTROL DAMPER

BDD

ACD

AUTOMATIC CONTROL DAMPER

BACKDRAFT DAMPER

BACKDRAFT DAMPER

BDD

ACD

DUCT CAP

RETURN AIR DUCT UP

RETURN AIR DUCT DN

EXISTING PIPE TO REMAIN

THREE-WAY PNEUMATIC CONTROL VALVE

TWO-WAY PNEUMATIC CONTROL VALVE

HW

CW

HWR

MISCELLANEOUS SYMBOLS (CONTINUED)

SINGLE LINE DUCTWORK SYMBOLS

STRAINER

TRIPLE DUTY VALVE

NOTE:

NOT ALL SYMBOLS INDICATED MAY

APPLY ON THIS PROJECT.

LIGHT TROFFER DIFFUSER

EXISTING DUCT TO REMAIN

PUMPED CONDENSATE

10/11/16 Preliminary (35%) Submittal

11/15/16 CD (65%) Submittal

01/13/17 Pre-Final (95%) Submittal

02/08/17 Final (100%) Submittal