SHEET NO:

SHEET TITLE:

PROJECT NUMBER:

COPYRIGHT © 2016

DATE ISSUE

26913 NORTHWESTERN HWY

SUITE 200

SOUTHFIELD, MICHIGAN

48033 | USA

(T) 248 262 1500

WWW.HED.DESIGN

2016-01686-000

Selfridge Air

National Guard

Base

SANG 117 & 126 Mechanical

Renovation

Harrison Township, MI 48045

SANG Project No.: VGLZ 162045

M5-01

Mechanical Details

SCALE : NO SCALE

"X"

VOLUME DAMPER

AIR FLOW

"W"

"L"

"X"

"X"

"X"

AIR FLOW

AIR FLOW

AIR FLOW

VOLUME DAMPER

VOLUME DAMPER

L =1/2 W OR 4" MIN.

SHEETMETAL

REDUCER FTG.

DOUBLE WIDTH AIR

TURNING VANES

SHEETMETAL

REDUCER FTG.

SHEETMETAL

REDUCER FTG.

DOUBLE WIDTH AIR

FOIL TURNING VANES

NOTE: BRANCH TAKE-OFFS TO BE LOCATED IN CENTER OF REDUCER FITTINGS.

SUPPLY AIR DUCT CONNECTION DETAILS

SCALE : NO SCALE

RETURN AIR BRANCH

DUCT CONNECTION DETAIL

MAIN DUCT (SEE FLOOR PLAN FOR SIZE)

MANUAL VOLUME DAMPER

AIR

FLOW

A I R

F L O

W

1 1/2 OF "D"

15 DEG. F

15 DEG. F TRANSITION TO

OCCUR PRIOR TO EXHAUST OR

RETURN DUCT CONNECTION

"D" (SIZE AS INDICATED

ON FLOOR PLAN)

SPLAY IN DIRECTION

OF AIR FLOW. OF

AIR FLOW. MAINTAIN

DEPTH OF BRANCH

DUCT

BRANCH EXHAUST OR

RETURN DUCT

6" MIN.

45 DEG. F

MIN.

SCALE : NO SCALE

HOT WATER HEATING COIL PIPING DIAGRAM

(WITH CIRC. PUMP AND 3-WAY CONTROL VALVE)

R

E

T

U

R

N

L

I

N

E

S

U

P

P

Y

I

N

E

CALIBRATED BALANCE

VALVE (TYP)

3-WAY CONTROL VALVE

NC

NO

C

BALL VALVE

(TYP)

STRAINER

REDUCER (TYP)

CIRCULATING PUMP (HHWP-1, HHWP-2)

CHECK VALVE (TYP)

MANUAL AIR

VENT (TYP)

PIPING TO OTHER

COIL(S) IN SAME

COIL BANK

HEATING

COIL

AIR

FLOW

PRESSURE GAUGE

(TYP)

THERMOMETER (TYP)

FLEX CONNECTION

(TYP) NOTES 2 & 3

3.

1. PROVIDE VALVES AND FITTINGS, AS INDICATED, FOR EACH

COIL (WHERE MULTIPLE COIL BANKS ARE INSTALLED)

NOTES:

FLEXIBLE HOSE ASSEMBLY MAY BE USED IN

USED IN LIEU OF FLEXIBLE CONNECTORS

AT COIL CONNECTIONS.

2. PROVIDE FLEXIBLE CONNECTORS AT

LOCATIONS SHOWN IF ASSOCIATED AHU FAN

IS NOT INTERNALLY ISOLATED.

11/15/16 CD (65%) Submittal

01/13/17 Pre-Final (95%) Submittal

MINIMUM 6" LONG

FULL SIZE

DIRT POCKET

UNION

GAS SERVICE

VALVE

DOUBLE DEFLECTION

SUPPLY GRILLE

PROVIDE CROSS

BRACING TWO

DIRECTIONS

ALL THREAD

SUSPENSION

ROD (TYP.)

G

SCALE : NO SCALE

TYPICAL GAS UNIT HEATER DETAIL

SUPPLY AIR

FLEX

CONNECTOR

(TYP.) SUPPLY

DUCT

WAF-126-2A

MECHANICAL

ROOM

FLOOR

SUPPORT RETURN

DUCT FROM FLOOR

(TYP.)

RETURN AIR

PROVIDE FURNACE

SUPPORT FRAME

SUFFICIENT HEIGHT TO ALLOW

INSTALLATION OF RETURN

DUCT AND FILTER MEDIA BOX

UNDER FURNACE

ALL WELDED

GALVANIZED

STEEL ANGLE

FURNACE SUPPORT

FRAME

FILTER MEDIA BOX

AT BOTTOM. FURNACE

RETURN AIR INLET

ACCESSIBLE FROM FRONT

OF FURNACE

SCALE : NO SCALE

FRONT VIEW TWINNED FURNACES DETAIL

WAF-126-2A/WAF-126-2B AND WAF-126-3A/WAF-126-3B

SUPPLY

DUCT

WAF-126-3A

WAF-126-2B

WAF-126-3B

FLEX

CONNECTOR

(TYP.)

SUPPLY AIR

SUPPLY

DUCT

WAF-126-2A

MECHANICAL

ROOM

FLOOR

SCALE : NO SCALE

SIDE VIEW TWINNED FURNACES DETAIL

WAF-126-2A/WAF-126-2B AND WAF-126-3A/WAF-126-3B

WAF-126-3A

FLEX

CONNECTION

DX-126-2A

DX-126-3A

DX-126-2B

DX-126-3B

DX-126-2A

DX-126-3A

RETURN AIR

FILTER MEDIA CABINET

ACCESS FROM

FRONT OF FURNACE

FLEX

CONNECTION

EXPANSION BOLT

FURNACE SUPPORTS

FRAM TO FLOOR

PROVIDE DIAGONAL

BRACE BOTH ENDS

SUPPORT RETURN AIR

DUCT FROM FLOOR

(TYP.)

ALL WELDED

GALVANIZED

FURNACE

SUPPORT

FRAME

02/08/17 Final (100%) Submittal

2/7/2017 10:50:55 AM

M-401
M5-01