SHEET NO:
SHEET TITLE:
PROJECT NUMBER:
COPYRIGHT © 2016
DATE ISSUE
26913 NORTHWESTERN HWY
SUITE 200
SOUTHFIELD, MICHIGAN
48033 | USA
(T) 248 262 1500
WWW.HED.DESIGN
2016-01686-000
Selfridge Air
National Guard
Base
SANG 117 & 126 Mechanical
Renovation
Harrison Township, MI 48045
SANG Project No.: VGLZ 162045
M-G2
Hanger and Supports
Buildings 117&126
STEEL BEAM
BEAM CLAMP
SCALE : NO SCALE
TYPICAL CONCENTRIC
HANGER TO STEEL BEAM
NOTE:
ALL HEIGHTS,WIDTHS AND LENGTHS OF CONCRETE PADS
ARE TO BE COORDINATED W/ MECH.,ELECT. AND ARCH.
CONCENTRIC BEAM
CLAMP
USE FOR SINGLE PIPE/CONDUIT
GREATER THAN 3" HANG FROM
BEAM CENTER LINE.
SCALE : NO SCALE
USE ONLY FOR SINGLE
3" OR LESS PIPE/CONDUIT
4"
MAX.
PROVIDE SUPPLEMENTAL
FRAMING BETWEEN BEAMS
FOR PIPE/CONDUIT GREATER
THAN 3" OR DISTANCE
GREATER THAN 4" FROM BEAM
CENTERLINE.
TYPICAL HANGER SUPPORT
SCALE : NO SCALE
SUPPLEMENTAL FRAMING
4"
MAX.
PROVIDE SUPPLEMENTAL
FRAMING BETWEEN BEAMS
FOR PIPE/CONDUIT GREATER
THAN 3" OR DISTANCE
GREATER THAN 4" FROM BEAM
CENTERLINE.
TYPICAL HANGER SUPPORT
SCALE : NO SCALE
ROOF OR FLOOR DECK
BEAM
HANGER
1000# MAX.
FORCE
PC WT (SKEWED AS REQ'D)
L 3x3 (MIN.) TYP.
L 3x3 (MIN.) TYP.
HANGER
A
A
PIPE (W/ OR W/O
INSULATION, SEE MECH,)
SCALE : NO SCALE
TYPICAL PIPE ANCHORAGE W/ BEAMS
PARALLEL TO PIPE RUN
3/8" PL (MIN.)
WELDED TO PIPE
SECTION A - A
ROOF OR FLOOR DECK
BEAM
PC WT (SKEWED AS REQ'D)
1000# MAX.
FORCE
HANGER
L 3x3 (MIN.) TYP.
DESIGN AS
COMPRESSION STRUT
SCALE : NO SCALE
TYP. PIPE ANCHORAGE W/ BEAMS
PERPENDICULAR TO PIPE RUN
PIPE
M
I N
A B
O V
E
P
I P
E
O R
I N
S U
3/8" PL (MIN.)
WELDED TO PIPE
NOTES:
HANGERS TO STEEL BEAMS AND JOISTS:
A. LOADS INDICATED REFER TO THE SUMMATION OF ALL TRADES
(CONDUITS, PIPING, DUCTS ETC.)
B. LOADS INDICATED ARE THE TOTAL FOR ALL TRADES PER JOISTS PANEL.
C. ECCENTRIC HANGERS TO BE USED ONLY AS INDICATED.
D. JOISTS FOR EXISTING STRUCTURES:
1) DO NOT HANG AT LOCATIONS OTHER THAN PANEL POINTS.
A) EXCEPTION WHERE A REINFORCING STRAP IS PROVIDED, LOADS
MAY BE SUPPORTED BETWEEN PANEL POINTS.
E. JOISTS FOR NEW CONSTRUCTION:
1) DO NOT HANG LOADS GREATER THAN 250# AT LOCATIONS OTHER THAN
PANEL POINTS.
A) EXCEPTION: WHERE A REINFORCING STRAP IS PROVIDED, LOADS
IN EXCESS OF 250# MAY BE SUPPORTED BETWEEN PANEL POINTS
F. DO NOT USE "C" CLAMPS AT JOISTS OR BEAMS.
ROOF OR FLOOR DECK
OPEN WEB STEEL JOIST
HANGER
L 3x3 (MIN.) TYP.
1000# MAX.
FORCE
PIPE
DESIGN AS
COMPRESSION STRUT
M
I N
A B
O V
E
P
I P
E
S U
3/8" PL WELDED
TO PIPE
SCALE : NO SCALE
TYP. HANGER ANCHORAGE W/STEEL
JOISTS PERPENDICULAR TO PIPE RUN
HANGER
PIPE
A
1000# MAX.
FORCE
A
PC WT (SKEWED AD REQ'D)
L 2x2 (MIN.)
3/8" PL (MIN.) WELDED TO PIPE
(APPROX.)
PC WT (SKEWED AS REQD)
CONNECT @ JOIST PANEL
POINTS ONLY
L 3x3 (MIN.) TYP.
(4 REQ'D)
OPEN WEB
STEEL JOIST
SCALE : NO SCALE
TYP. HANGER ANCHORAGE W/JOISTS
PARALLEL TO PIPE RUN
3/8" PL (MIN.)
WELDED TO PIPE
SECTION A - A
ROOF OR
FLOOR DECK
OPEN WEB
STEEL JOIST
HANGER
SUPPORT,
CONNECT
@ PANEL POINT
PANEL POINTS
(TYP)
SCALE : NO SCALE
TYPICAL HANGER SUPPORT
EXISTING STEEL JOIST CONSTRUCTION
P
R
O
H
I
B
I
T
E
D
SUPPLEMENTAL FRAMING
DO NOT ECCENTRICALLY
HANG LOAD FROM JOISTS.
TYPICAL HANGER SUPPORT
@ STEEL JOIST TOP CHORD
SCALE : NO SCALE
TYPICAL HANGER SUPPORT
@ STEEL JOIST BOTTOM CHORD
SCALE : NO SCALE
DO NOT
ECCENTRICALLY
HANG LOAD
FROM JOISTS.
HANG FROM CENTER
LINE OF JOISTS.
NOTES:
SEE DETAILS ELSEWHERE
ON THIS DRAWING FOR
LOAD LIMITATIONS IF NOT
HUNG AT PANEL POINTS.
TYPICAL HANGER TO STEEL JOIST
SCALE : NO SCALE
DO NOT
ECCENTRICALLY
HANG LOAD
FROM JOISTS.
SCALE : NO SCALE
TYPICAL CONCRETE EQUIPMENT PAD
V A
R I E
S
#4@12" O.C.
EACH WAY
SOAK SCARIFIED SLAB FOR
MIN 24 HRS.PRIOR TO PLACING
CONC APPLY LATEX
BONDING AGENT
SCARIFY 1/4" CONCRETE SLAB
PIPE AND INSULATION
INSULATION PROTECTION
SHIELD
HIGH COMPRESSIVE STRENGTH
INSULATION INSERT UNDER SHIELD
WELD PIPE SADDLE SUPPORT
TO PIPE. PROVIDE WATER
TIGHT CONNECTION
SEALANT
8 in
4 in
12 in MIN.
CLAMPING RING
PRE-MOULDING FLEXIBLE PIPE
COUNTER FLASHING
METAL BASE FLASH
WELD PLATE TO PIPE
VARIES
ROOF SURFACE
8 x 8 x 1/3 STEEL PLATE
ROOF SYSTEM INSULATION
AND MEMBRANE
CONCRETE ROOF SLAB
OR STEEL ROOF DECK
SECURE TO ROOF SLAB WITH
(4) DIA. EXPANSION BOLTS
OR WELD TO STEEL DECK
SCALE : NO SCALE
TYPICAL PIPE SUPPORT ON ROOF
CONC. JOIST
HANGER ROD
X
X
O R
M I N
CONCRETE
JOIST CLAMP
(TYP.)
SCALE : NO SCALE
TYPICAL PIPE/DUCT HANGER
TO CONCRETE JOIST
INSERT NUT
HANGER ROD
CONC. STRUCTURE
INSERT W/ ELONGATED
SLOT (TYP.)
DO NOT DISPLACE
BEAM REINF.
SCALE : NO SCALE
TYPICAL PIPE/DUCT
HANGER TO INSERT
ELEVATION
PLAN
PIPE
L 5x3 1/2 (MIN.)
L 5x3 1/2 (MIN.)
L 4x3 (MIN.) x 0'-4" LG.
WELD TO L 5
1000# MAX.
FORCE
5/8" DIA. (MIN.)
EXP. BOLTS
5/8" DIA. (MIN.)
EXP. BOLTS
L 4x3 (MIN.) x 0'-4" LG.
WELD TO L 5
EXTRA HEAVY RISER CLAMP
BOLT TO L 4 & WELD
TO PIPE (TYP.)
SCALE : NO SCALE
TYPICAL PIPE ANCHORAGE
TO VERTICAL WALL
EXTRA HEAVY
RISER CLAMP
5/8" DIA. (MIN.) ADHESIVE
ANCHORS
INTO SLAB (TYP.)
SEE PLANS
CONCRETE SLAB
L 3x3 (MIN.) TYP.
L 2x2 (MIN.) TYP.
PIPE
1000# MAX.
FORCE
SCALE : NO SCALE
TYPICAL PIPE ANCHORAGE
TO CONCRETE SLAB
3/8" PL (MIN.)
CONC. BEAM
M
I N
A B
O V
E
P
I P
E
S U
1000# MAX.
FORCE
L 3x3 (MIN.)
5/8" DIA. (MIN.) ADHESIVE
ANCHORS INTO
BEAM (TYP.)
LOCATE LOWEST
ANCHOR ABOVE
BEAM BOTT.
REINF.
BEAM BOTT. REINF.
DO NOT CUT
BEAM REINF.
PIPE (W/ OR W/O
INSULATION, SEE MECH,)
3/8" PL (TYP)
SCALE : NO SCALE
TYPICAL PIPE ANCHORAGE
TO CONCRETE BEAM
USE ONLY FOR SINGLE 3"
OR LESS PIPE/CONDUIT.
PC WT (SKEWED AS REQD
FOR ANGLE OF DIAGONAL
48"
32" 2L1-1/2x1-1/2x3/16
2L2-1/2x2-1/2x3/16
NOTE:
1. REINF. NOT REQ'D. @ ROOF DRAIN FRAMES.
2. REINF. NOT REQ'D. IF LOAD IS 0'-3" OR LESS
FROM CENTER OF PANEL POINT.
LOAD ON BOTT. CHORD
GREATER THAN 250 POUNDS, BUT LESS
THAN 1000 POUNDS. LOADS OVER 1000 POUNDS
NOT PERMITTED
MAX JOIST
DEPTH
DOUBLE ANGLE
REINFORCING SIZE
LOAD ON TOP CHORD
GREATER THAN
250 POUNDS
NOTE #1
3"3"
NOTE #2
3" 3"NOTE #2
BOTT CHORD
DOUBLE ANGLE REINFORCING
FROM POINT OF LOAD TO
NEAREST PANEL POINT
HANGER
OR CURB
DO NOT WELD
ALONG LENGTH
OF REINF ANGLE
CUT REINF PARALLEL
TO BOTTOM CHORD
AND GRIND
3" PL
P
R
O
H
I
B
I
T
E
D
P
R
O
H
I
B
I
T
E
D
P
R
O
H
I
B
I
T
E
D
HANGER ROD
(LOAD LIMITATIONS APPLY.
SHOWN ELSEWHERE.)
FOR USE ONLY WITH SINGLE
3" OR LESS PIPE/CONDUIT.
FOR MULTIPLE PIPES/CONDUIT
PROVIDE SUPPLEMENTAL
FRAMING.
SUPPLEMENTAL FRAMING
TYPICAL HANGER TO STEEL BEAM
1000# MAX LOAD
ECCENTRIC
HANGER
1000# MAX
REINF STRAP
REINF STRAP
RESTRICTED USE FOR
LOADS OF
REINF STRAP
VERTICAL REINF STRAP
TO PANEL POINT
PROVIDE VERTICAL REINF
STRAP SHOWN ELSEWHERE
ON THIS DRAWING IF NOT AT
PANEL POINT
1000# OR LESS
RESTRICTED USE FOR
LOADS OF 1000# OR LESS
RESTRICTED USE FOR
LOADS OF 1000# OR LESS
RESTRICTED USE FOR
LOADS OF 1000# OR LESS
RESTRICTED USE FOR
LOADS OF 1000# OR LESS
TYP. JOIST REINFORCING STRAP DETAIL
SCALE : NO SCALE
3" MIN EMBED
3/4" CLR
DRILL & EPOXY #4
HOOKED DOWELS @ 24" OC
3" MIN EMBED
6"
(LOADS GREATER
THAN 2000#)
10/11/16 Preliminary (35%) Submittal
11/15/16 CD (65%) Submittal
01/13/17 Pre-Final (95%) Submittal
02/08/17 Final (100%) Submittal
2/7/2017 10:03:45 AM
| M-G1 |
| M-G2 |