Specifications_Volume_4_-_BTC4_Phase_2.PDF

PDF 2 MB Posted

Attached to
BTC4 Phase 2 Federal contract opportunity
Solicitation number
W912HP19R2001
Issued by
Department of the Army Corps of Engineers Engineering District Charleston

About this file

This document is a solicitation for the BCT4 Phase 2 project at Fort Jackson. The U.S. Army Corps of Engineers is seeking proposals to complete construction of barracks and training facilities. Proposals are due by 10 September 2019 and must include a data sheet, descriptive summary, past performance questionnaire, and small business participation plan. Drawings and specifications for the project are provided in four volumes. Site visits will be held on 10 September to review project details. The solicitation includes construction of new barracks to house and train soldiers according to TRADOC requirements.

Specifications Volume 4

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort Jackson, South Carolina

Solicitation Number

W912HP-19-R-2001

BCT4, Phase 2 Volume 4 of 4: Specification Divisions 28 - 33

PN 76218

July 2019

U.S. ARMY ENGINEER DISTRICT, SAVANNAH

CORPS OF ENGINEERS

100 WEST OGLETHORPE AVENUE

SAVANNAH, GEORGIA 31401-3640

US Army Corps of Engineers

BCT 4 Phase 2 JA76218 Ft . Jackson, SC

PROJECT TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

01 11 00 SUMMARY OF WORK

01 30 00 ADMI NI STRATI VE REQUI REMENTS

01 32 01 PROJECT SCHEDULE

01 33 00 SUBMI TTAL PROCEDURES

01 33 29 SUSTAI NABI LI TY REPORTI NG

01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS

01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS

01 45 00 QUALI TY CONTROL

01 45 00. 15 RESI DENT MANAGEMENT SYSTEM CONTRACTOR MODE ( RMS CM)

01 45 35 SPECI AL I NSPECTI ONS

01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS

01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS

01 57 19. 37 I NDOOR AI R QUALI TY ( I AQ) MANAGEMENT

01 74 19. 37 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMI TTALS

01 78 23 OPERATI ON AND MAI NTENANCE DATA

01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG

DI VI SI ON 03 - CONCRETE

03 11 13 STRUCTURAL CAST- I N- PLACE CONCRETE FORMI NG

03 15 00 CONCRETE ACCESSORI ES

03 20 00 CONCRETE REI NFORCI NG

03 30 00 CAST- I N- PLACE CONCRETE

03 35 00 CONCRETE FI NI SHI NG

03 39 00 CONCRETE CURI NG

DI VI SI ON 04 - MASONRY

04 20 00 MASONRY

DI VI SI ON 05 - METALS

05 05 23. 16 STRUCTURAL WELDI NG

05 12 00 STRUCTURAL STEEL

05 21 00 STEEL JOI ST FRAMI NG

05 30 00 STEEL DECKS

05 40 00 COLD- FORMED METAL FRAMI NG

05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS

05 51 00 METAL STAI RS

05 51 33 METAL LADDERS

05 52 00 METAL RAI LI NGS

DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES

06 10 00 ROUGH CARPENTRY

06 20 00 FI NI SH CARPENTRY

06 41 16 LAMI NATE CLAD ARCHI TECTURAL CASEWORK

06 61 16 SOLI D POLYMER ( SOLI D SURFACI NG) FABRI CATI ONS

DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON

07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS

07 21 13 BOARD AND BLOCK I NSULATI ON

07 21 16 MI NERAL FI BER BLANKET I NSULATI ON

PROJECT TABLE OF CONTENTS Page 1

07 22 00 ROOF AND DECK I NSULATI ON

07 27 10 BUI LDI NG AI R BARRI ER SYSTEM

07 41 00 METAL SOFFI T PANELS

07 41 13 METAL ROOF PANELS

07 42 13 METAL WALL PANELS

07 53 23 ETHYLENE- PROPYLENE- DI ENE- MONOMER ROOFI NG

07 60 00 FLASHI NG AND SHEET METAL

07 84 00 FIRESTOPPING

07 92 00 JOI NT SEALANTS

DI VI SI ON 08 - OPENI NGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMI NUM DOORS AND FRAMES

08 14 00 WOOD DOORS

08 34 59 VAULT DOORS AND DAY GATES

08 34 73 SOUND CONTROL DOOR ASSEMBLI ES

08 44 00 CURTAI N WALL AND GLAZED ASSEMBLI ES

08 51 13 ALUMI NUM WI NDOWS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL WALL LOUVERS

DI VI SI ON 09 - FI NI SHES

09 06 00 SCHEDULES FOR FI NI SHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG

09 51 00 ACOUSTI CAL CEI LI NGS

09 65 00 RESI LI ENT FLOORI NG

09 67 23. 13 STANDARD RESI NOUS FLOORI NG

09 90 00 PAI NTS AND COATI NGS

DI VI SI ON 10 - SPECI ALTI ES

10 09 00 MI SCELLANEOUS I TEMS

10 10 00 VI SUAL COMMUNI CATI ONS SPECI ALTI ES

10 14 00. 20 I NTERI OR SI GNAGE

10 21 13 TOI LET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTI ON

10 28 13 TOI LET ACCESSORI ES

DI VI SI ON 11 - EQUI PMENT

11 06 40. 13 FOODSERVI CE EQUI PMENT SCHEDULE

DI VI SI ON 12 - FURNI SHI NGS

12 21 00 WI NDOW BLI NDS

12 24 13 ROLLER WI NDOW SHADES

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

12 93 00 SI TE FURNI SHI NGS

DI VI SI ON 13 - SPECI AL CONSTRUCTI ON

13 34 19 METAL BUI LDI NG SYSTEMS ( COVERED TRAI NI NG CANOPY)

13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT

13 48 00. 22 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT

PROJECT TABLE OF CONTENTS Page 2

DI VI SI ON 21 - FI RE SUPPRESSI ON

21 13 13 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON

DI VI SI ON 22 - PLUMBI NG

22 00 00 PLUMBI NG, GENERAL PURPOSE

DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

23 05 48 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND

EQUIPMENT

23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC

23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS

23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC

23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC

23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER

BUI LDI NG CONTROL SYSTEMS

23 11 25 FACI LI TY GAS PI PI NG

23 23 00 REFRI GERANT PI PI NG

23 25 00 CHEMI CAL TREATMENT OF WATER FOR MECHANI CAL SYSTEMS

23 52 00 HEATI NG BOI LERS

23 57 10 FORCED HOT WATER HEATI NG SYSTEMS USI NG WATER HEAT

EXCHANGERS

23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE

23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS

23 82 02 UNI TARY HEATI NG AND COOLI NG EQUI PMENT

DI VI SI ON 25 - I NTEGRATED AUTOMATI ON

25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS ( HVAC)

25 05 12 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS ( DMS)

25 05 13 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

(FA/MNS)

25 08 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM TESTI NG

25 10 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM ( UMCS) FRONT END

AND I NTEGRATI ON

DI VI SI ON 26 - ELECTRI CAL

26 00 00 BASI C ELECTRI CAL MATERI ALS AND METHODS

26 05 48 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT

26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM

26 23 00 SWITCHBOARDS

26 28 01 COORDI NATED POWER SYSTEM PROTECTI ON

26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS

26 41 00 LI GHTNI NG PROTECTI ON SYSTEM

26 51 00 I NTERI OR LI GHTI NG

26 56 00 EXTERI OR LI GHTI NG

DI VI SI ON 27 - COMMUNI CATI ONS

27 05 14 CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM

27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM

DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

PROJECT TABLE OF CONTENTS Page 3

28 16 01 SMALL I NTRUSI ON DETECTI ON SYSTEM

28 20 01 DOOR MONI TORI NG SYSTEM

28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEMS

DI VI SI ON 31 - EARTHWORK

31 00 00 EARTHWORK

31 05 19 GEOTEXTILE

31 11 00 CLEARI NG AND GRUBBI NG

31 31 16. 13 CHEMI CAL TERMI TE CONTROL

31 32 11 SOI L SURFACE EROSI ON CONTROL

DI VI SI ON 32 - EXTERI OR I MPROVEMENTS

32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D

PAVEMENTS

32 05 33 LANDSCAPE ESTABLI SHMENT

32 11 16 BASE COURSE FOR RI GI D PAVI NG

32 11 23 AGGREGATE AND/ OR GRADED- CRUSHED AGGREGATE BASE COURSE

32 12 10 BI TUMI NOUS TACK AND PRI ME COATS

32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS

32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE

FACILITIES

32 16 19 CONCRETE CURBS, GUTTERS AND SI DEWALKS

32 17 23 PAVEMENT MARKI NGS

32 18 23. 39 SYNTHETI C RUNNI NG TRACK SURFACI NG

32 31 13 CHAI N LI NK FENCES AND GATES

32 32 23 SEGMENTAL CONCRETE BLOCK RETAI NI NG WALL

32 92 19 SEEDING

32 92 23 SODDING

32 93 00 EXTERI OR PLANTS

DI VI SI ON 33 - UTI LI TI ES

33 40 00 STORM DRAI NAGE UTI LI TI ES

33 46 16 SUBDRAI NAGE PI PI NG

33 51 15 NATURAL- GAS DI STRI BUTI ON

33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON

33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON

33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)

- - End of Pr oj ect Tabl e of Cont ent s - -

PROJECT TABLE OF CONTENTS Page 4

SECTI ON TABLE OF CONTENTS

DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

SECTI ON 28 16 01

SMALL I NTRUSI ON DETECTI ON SYSTEM

11/08

PART 1 GENERAL

1. 1 REFERENCES

1. 2 DEFI NI TI ONS

1. 2. 1 I nt r usi on Al ar m

1. 2. 2 Nui sance Al ar m

1. 2. 3 Envi r onment al Al ar m

1. 2. 4 Fal se Al ar m

1. 2. 5 Dur ess Al ar m

1. 2. 6 St andar d I nt r uder

1. 3 SYSTEM DESCRI PTI ON

1. 3. 1 Gener al

1. 3. 2 Over al l Syst em Rel i abi l i t y Requi r ement

1. 3. 3 Pr obabi l i t y of Det ect i on

1. 3. 4 El ect r i cal Requi r ement s

1. 3. 5 Power Li ne Sur ge Pr ot ect i on

1. 3. 6 Sensor Wi r i ng and Communi cat i on Ci r cui t Sur ge Pr ot ect i on

1. 3. 7 Syst em React i on

1. 3. 8 Syst em Capaci t y

1. 4 SUBMI TTALS

1. 5 QUALI TY ASSURANCE

1. 5. 1 Har dwar e Manuf act ur er

1. 5. 2 Sof t war e Manuf act ur er

1. 5. 3 Syst em I nst al l er

1. 5. 4 Li ne Super vi s i on

1. 5. 4. 1 Si gnal and Dat a Tr ansmi ssi on Syst em ( DTS) Li ne Super vi s i on

1. 5. 4. 2 Dat a Encr ypt i on

1. 5. 5 Dat a Tr ansmi ssi on Syst em ( DTS)

1. 6 ENVI RONMENTAL REQUI REMENTS

1. 6. 1 I nt er i or , Cont r ol l ed Envi r onment

1. 6. 2 I nt er i or , Uncont r ol l ed Envi r onment

1. 6. 3 Ext er i or Envi r onment

1. 6. 4 Hazar dous Envi r onment

1. 6. 5 Cent r al St at i on

1. 7 EXTRA MATERI ALS

PART 2 PRODUCTS

2. 1 MATERI ALS AND EQUI PMENT

2. 1. 1 Gener al

2. 1. 2 Encl osur es

2. 1. 2. 1 I nt er i or Sensor

2. 1. 2. 2 I nt er i or El ect r oni cs

2. 1. 2. 3 Ext er i or El ect r oni cs

2. 1. 3 Tamper Pr ovi s i ons

2. 1. 3. 1 Tamper Swi t ches

SECTI ON 28 16 01 Page 1

2. 1. 3. 1. 1 Nonsensor Encl osur es

2. 1. 3. 1. 2 Sensor Encl osur es

2. 1. 3. 2 Encl osur e Cover s

2. 1. 4 Locks and Key- Lock Swi t ches

2. 1. 4. 1 Locks

2. 1. 4. 2 Key- Lock- Oper at ed Swi t ches

2. 1. 4. 3 Const r uct i on Locks

2. 1. 5 Appl i cat i on of Syst em Component

2. 1. 5. 1 Mai nt ai nabi l i t y

2. 1. 5. 2 I nt er changeabi l i t y

2. 1. 5. 3 El ect r omagnet i c and Radi o Fr equency I nt er f er ence ( EMI / RFI )

2. 1. 5. 4 Pr oduct Saf et y

2. 1. 6 Cont r ol s and Desi gnat i ons

2. 1. 7 Speci al Test Equi pment

2. 1. 8 Al ar m Out put

2. 1. 9 Al ar m I ndi cat or Li ght s

2. 1. 10 Access/ Secur e Devi ces

2. 1. 10. 1 Swi t ches

2. 1. 10. 2 Key Pads

2. 2 I NTERI OR SENSORS

2. 2. 1 Bal anced Magnet i c Swi t ch ( BMS)

2. 2. 1. 1 BMS Subassembl i es

2. 2. 1. 2 Remot e Test

2. 2. 2 Dur ess Al ar m Swi t ches

2. 2. 2. 1 Pushbut t on

2. 2. 3 Secur i t y Scr een

2. 2. 4 Passi ve I nf r ar ed Mot i on Sensor

2. 2. 4. 1 Test I ndi cat or , I nf r ar ed Emi ssi ons

2. 2. 4. 2 Remot e Test , I nf r ar ed Emi ssi ons

2. 3 SOFTWARE

2. 3. 1 Syst em Sof t war e

2. 3. 2 Appl i cat i ons Sof t war e

2. 3. 2. 1 Oper at or Commands

2. 3. 2. 2 Command I nput

2. 3. 2. 3 Command I nput Er r or s

2. 3. 2. 4 Enhancement s

2. 3. 2. 4. 1 Hel p

2. 3. 2. 4. 2 Acknowl edge Al ar ms

2. 3. 2. 4. 3 Pl ace Zone i n Access

2. 3. 2. 4. 4 Pl ace Zone i n Secur e

2. 3. 2. 4. 5 Syst em Test

2. 3. 2. 4. 6 Zone Test

2. 3. 2. 4. 7 Change Oper at or

2. 3. 2. 4. 8 Secur i t y Li ght i ng Cont r ol s

2. 3. 2. 4. 9 Di spl ay Gr aphi cs

2. 3. 3 Si t e Speci f i c Dat abase Sof t war e

2. 3. 3. 1 Dat abase Def i ni t i on Pr ocess

2. 3. 3. 2 Syst em Access Cont r ol

2. 3. 3. 3 Al ar m Moni t or i ng Sof t war e

2. 4 FI ELD PROCESSI NG HARDWARE

2. 4. 1 Al ar m Annunci at i on Local Pr ocessor

2. 4. 1. 1 I nput s

2. 4. 1. 2 Out put s

2. 4. 2 Pr ocessor Power Suppl y

2. 4. 3 Auxi l i ar y Equi pment Power

2. 5 FI ELD PROCESSI NG SOFTWARE

2. 5. 1 Oper at i ng Syst em

2. 5. 1. 1 St ar t up

2. 5. 1. 2 Oper at i ng Mode

SECTI ON 28 16 01 Page 2

2. 5. 1. 3 Fai l ur e Mode

2. 5. 2 Funct i ons

2. 6 WI RE AND CABLE

2. 6. 1 Gener al

2. 6. 2 Above Gr ound Sensor Wi r i ng

2. 6. 3 Cl ass 2 Low Ener gy Conduct or s

PART 3 EXECUTI ON

3. 1 I NSTALLATI ON

3. 1. 1 Encl osur e Penet r at i ons

3. 1. 2 Col d Gal vani z i ng

3. 2 SYSTEM STARTUP

3. 3 SI TE TESTI NG

3. 3. 1 Test i ng

3. 3. 2 Per f or mance Ver i f i cat i on Test

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 28 16 01 Page 3

SECTI ON 28 16 01

SMALL I NTRUSI ON DETECTI ON SYSTEM

11/08

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE 142 ( 2007; Er r at a 2014) Recommended Pr act i ce f or Gr oundi ng of I ndust r i al and Commer ci al Power Syst ems - I EEE Gr een Book

I EEE C2 ( 2017; Er r at a 1- 2 2017; I NT 1 2017) Nat i onal El ect r i cal Saf et y Code

I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA 250 ( 2018) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NEMA I CS 1 ( 2000; R 2015) St andar d f or I ndust r i al Cont r ol and Syst ems: Gener al Requi r ement s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2017; ERTA 1- 2 2017; TI A 17- 1; TI A 17- 2;

TI A 17- 3; TI A 17- 4; TI A 17- 5; TI A 17- 6;

TI A 17- 7; TI A 17- 8; TI A 17- 9; TI A 17- 10;

TI A 17- 11; TI A 17- 12; TI A 17- 13; TI A

17- 14; TI A 17- 15; TI A 17- 16; TI A 17- 17)

Nat i onal El ect r i cal Code

NATI ONAL I NSTI TUTE OF STANDARDS AND TECHNOLOGY ( NI ST)

NI ST FI PS 140- 2 ( 2001) Secur i t y Requi r ement s f or Cr ypt ogr aphi c Modul es

NI ST FI PS 197 ( 2001) Advance Encr ypt i on St andar d

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

47 CFR 15 Radi o Fr equency Devi ces

SECTI ON 28 16 01 Page 4

UNDERWRI TERS LABORATORI ES ( UL)

UL 1037 ( 2016; Repr i nt Sep 2017) UL St andar d f or Saf et y Ant i t hef t Al ar ms and Devi ces

UL 1076 ( 2018) UL St andar d f or Saf et y Pr opr i et ar y Bur gl ar Al ar m Uni t s and Syst ems

UL 294 ( 2018; Repr i nt Oct 2018) UL St andar d f or Saf et y Access Cont r ol Syst em Uni t s

UL 639 ( 2007; Repr i nt May 2012) St andar d f or I nt r usi on Det ect i on Uni t s

UL 681 ( 2014) I nst al l at i on and Cl assi f i cat i on of Bur gl ar and Hol dup Al ar m Syst ems

UL 796 ( 2016) UL St andar d f or Saf et y Pr i nt ed- Wi r i ng Boar ds

1. 2 DEFINITIONS

1. 2. 1 I nt r usi on Al ar m

An al ar m r esul t i ng f r om t he det ect i on of a speci f i ed t ar get and whi ch r esul t s i n an at t empt t o i nt r ude i nt o t he pr ot ect ed ar ea or when ent r y i nt o an ent r y cont r ol l ed ar ea i s at t empt ed wi t hout successf ul l y usi ng ent r y cont r ol pr ocedur es.

1. 2. 2 Nui sance Al ar m

An al ar m r esul t i ng f r om t he det ect i on of an al ar m st i mul i , but whi ch does not r epr esent an at t empt t o i nt r ude i nt o t he pr ot ect ed ar ea.

1. 2. 3 Envi r onment al Al ar m

An al ar m dur i ng envi r onment al condi t i ons whi ch exceed t hose speci f i ed.

1. 2. 4 Fal se Al ar m

An al ar m when t her e i s no al ar m st i mul us.

1. 2. 5 Dur ess Al ar m

An al ar m condi t i on whi ch r esul t s f r om a set of pr e- est abl i shed condi t i ons such as ent er i ng a speci al code i nt o a keypad or by act i vat i ng a swi t ch.

Thi s al ar m cat egor y shal l t ake pr ecedence over ot her al ar m cat egor i es.

1. 2. 6 St andar d I nt r uder

I ndi v i dual t hat wei ghs 100 pounds or l ess and i s 5 f eet t al l or l ess, dr essed i n a l ong- sl eeved shi r t , s l acks and shoes, unl ess envi r onment al condi t i ons at t he s i t e r equi r e pr ot ect i ve c l ot hi ng. St andar d i nt r uder movement i s def i ned as any movement such as wal k i ng, r unni ng, cr awl i ng, r ol l i ng, or j umpi ng t hr ough a pr ot ect ed zone i n t he most advant ageous manner f or t he i nt r uder .

SECTI ON 28 16 01 Page 5

1. 3 SYSTEM DESCRI PTI ON

1. 3. 1 General

Pr ovi de a new I CI DS I V I nt r usi on Det ect i on Syst em i n t he Ar ms Vaul t . The I DS shal l be i nst al l ed i n accor dance wi t h I CI DS I V t echni cal manual TM 5- 6350- 297- 12&P. The I DS shal l be manuf act ur ed by DAQ El ect r oni cs, I nc.

The I DS shal l be t est ed by a Level 1 & Level 3 DAQ El ect r oni cs, I nc.

Cer t i f i ed Techni c i an.

Conf i gur e t he I nt r usi on Det ect i on Syst em ( I DS) as descr i bed and shown, i ncl udi ng Gover nment Fur ni shed Equi pment ( GFE) . Comput i ng devi ces, as def i ned i n 47 CFR 15, shal l be cer t i f i ed t o compl y wi t h t he r equi r ement s f or Cl ass A comput i ng devi ces and l abel ed as set f or t h i n 47 CFR 15.

Submi t t he f ol l owi ng:

a. Syst em bl ock di agr am.

b. Consol e i nst al l at i on, bl ock di agr ams, and wi r i ng di agr ams.

c. Pr ocessor i nst al l at i on, t ypi cal bl ock, and wi r i ng di agr ams.

d. Det ai l s of connect i ons t o power sour ces, i ncl udi ng power suppl i es and grounding.

e. Det ai l s of sur ge pr ot ect i on devi ce i nst al l at i on.

f . Sensor det ect i on pat t er ns.

g. The qual i f i cat i ons of t he Manuf act ur er , Cont r act or , and I nst al l er t o per f or m t he wor k speci f i ed her ei n.

1. 3. 2 Over al l Syst em Rel i abi l i t y Requi r ement

The syst em, i ncl udi ng al l component s and appur t enances, shal l be conf i gur ed and i nst al l ed t o y i el d a mean t i me bet ween f ai l ur e ( MTBF) of at l east 10, 000 hour s cont i nuous oper at i on.

1. 3. 3 Pr obabi l i t y of Det ect i on

Each zone shal l have a cont i nuous pr obabi l i t y of det ect i on gr eat er t han 90 per cent and shal l be demonst r at ed wi t h a conf i dence l evel of 95 per cent .

Thi s pr obabi l i t y of det ect i ng a st andar d i nt r uder equat es t o 49 successf ul det ect i ons out of 50 t est s or 98 successf ul det ect i ons out of 100 t est s.

1. 3. 4 El ect r i cal Requi r ement s

El ect r i cal l y power ed I DS equi pment shal l oper at e on 120 or 240 vol t 60 Hz AC sour ces as shown. Equi pment shal l be abl e t o t ol er at e var i at i ons i n t he vol t age sour ce of pl us or mi nus 10 per cent , and var i at i ons i n t he l i ne f r equency of pl us or mi nus 2 per cent wi t h no degr adat i on of per f or mance.

1. 3. 5 Power Li ne Sur ge Pr ot ect i on

Pr ot ect equi pment connect ed t o al t er nat i ng cur r ent c i r cui t s f r om power l i ne sur ges. Equi pment pr ot ect i on shal l wi t hst and sur ge t est wavef or ms descr i bed i n I EEE C62. 41. 1 and I EEE C62. 41. 2. Fuses shal l not be used f or sur ge pr ot ect i on.

1. 3. 6 Sensor Wi r i ng and Communi cat i on Ci r cui t Sur ge Pr ot ect i on

Pr ot ect i nput s agai nst sur ges i nduced on sensor wi r i ng. Out put s shal l be pr ot ect ed agai nst sur ges i nduced on cont r ol and sensor wi r i ng i nst al l ed out door s and as shown. Al l communi cat i ons equi pment shal l be pr ot ect ed agai nst sur ges i nduced on any communi cat i ons c i r cui t . Al l cabl es and

SECTI ON 28 16 01 Page 6 conduct or s, except f i ber opt i cs, whi ch ser ve as communi cat i ons c i r cui t s f r om t he consol e t o f i el d equi pment , and bet ween f i el d equi pment , shal l have sur ge pr ot ect i on c i r cui t s i nst al l ed at each end. Pr ot ect i on shal l be f ur ni shed at equi pment , and addi t i onal t r i pl e el ect r ode gas sur ge pr ot ect or s r at ed f or t he appl i cat i on on each wi r el i ne c i r cui t shal l be i nst al l ed wi t hi n 3 f eet of t he bui l di ng cabl e ent r ance. Fuses shal l not be used f or sur ge pr ot ect i on. The i nput s and out put s shal l be t est ed i n bot h nor mal mode and common mode usi ng t he f ol l owi ng t wo wavef or ms:

a. A 10 mi cr osecond r i se t i me by 1000 mi cr osecond pul se wi dt h wavef or m wi t h a peak vol t age of 1500 vol t s and a peak cur r ent of 60 amper es.

b. An 8 mi cr osecond r i se t i me by 20 mi cr osecond pul se wi dt h wavef or m wi t h a peak vol t age of 1000 vol t s and a peak cur r ent of 500 amper es.

1. 3. 7 Syst em React i on

Al l al ar ms shal l be annunci at ed on t he di spl ays wi t hi n 1 second of t hei r occur r i ng at a l ocal pr ocessor .

1. 3. 8 Syst em Capaci t y

The syst em shal l moni t or and cont r ol t he number of i nput s and out put s shown and shal l i ncl ude an expansi on capabi l i t y of a mi ni mum of 25 per cent .

1. 4 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 03 Pr oduct Dat a

I nt r usi on Det ect i on Syst em; G, RO Key Cont r ol Pl an Spar e Par t s Manuf act ur er ' s I nst r uct i ons Testing ; G, RO Experience

SD- 06 Test Repor t s

Per f or mance Ver i f i cat i on Test

SD- 07 Cer t i f i cat es

Mat er i al s and Equi pment

1. 5 QUALI TY ASSURANCE

Submi t wr i t t en pr oof t hat t he f ol l owi ng experience r equi r ement s ar e bei ng met.

1. 5. 1 Har dwar e Manuf act ur er

Al l syst em component s shal l be pr oduced by manuf act ur er s who have been r egul ar l y engaged i n t he pr oduct i on of i nt r usi on det ect i on syst em

SECTI ON 28 16 01 Page 7 component s of t he t ypes t o be i nst al l ed f or at l east 3 year s.

1. 5. 2 Sof t war e Manuf act ur er

Al l syst em and appl i cat i on sof t war e shal l be pr oduced by manuf act ur er s who have been r egul ar l y engaged i n t he pr oduct i on of i nt r usi on det ect i on syst em and appl i cat i on sof t war e of s i mi l ar t ype and compl exi t y as t he speci f i ed syst em f or at l east 2 year s.

1. 5. 3 Syst em I nst al l er

The syst em shal l be i nst al l ed by a Cont r act or who has been r egul ar l y engaged i n t he i nst al l at i on of i nt r usi on det ect i on syst ems of s i mi l ar t ype and compl exi t y as t he speci f i ed syst em f or at l east 2 year s.

1. 5. 4 Li ne Super vi s i on

1. 5. 4. 1 Si gnal and Dat a Tr ansmi ssi on Syst em ( DTS) Li ne Super vi s i on

Al l s i gnal or DTS l i nes bet ween sensor s and t he al ar m annunci at i on consol e shal l be super vi sed by t he syst em. The syst em shal l super vi se t he s i gnal l i nes by moni t or i ng changes i n t he di r ect cur r ent t hat f l ows t hr ough t he s i gnal l i nes and a t er mi nat i ng r esi st or . The syst em shal l i ni t i at e an al ar m i n r esponse t o a cur r ent change of 5 per cent or gr eat er . The syst em shal l al so i ni t i at e an al ar m i n r esponse t o openi ng, c l osi ng, shor t i ng, or gr oundi ng of t he s i gnal and DTS l i nes.

1. 5. 4. 2 Dat a Encr ypt i on

The i nt r usi on det ect i on syst em shal l i ncor por at e dat a encr ypt i on equi pment on dat a t r ansmi ssi on medi a l i nks as shown. The al gor i t hm used f or encr ypt i on shal l be t he Dat a Encr ypt i on St andar d ( DES) al gor i t hm descr i bed in NI ST FI PS 140- 2 and NI ST FI PS 197.

1. 5. 5 Dat a Tr ansmi ssi on Syst em ( DTS)

Pr ovi de dat a t r ansmi ssi on syst ems as speci f i ed i n Sect i on 27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM and as shown.

1. 6 ENVI RONMENTAL REQUI REMENTS

1. 6. 1 I nt er i or , Cont r ol l ed Envi r onment

Al l syst em component s, except t he consol e, i nst al l ed i n i nt er i or l ocat i ons havi ng cont r ol l ed envi r onment s shal l be r at ed f or cont i nuous oper at i on under ambi ent envi r onment al condi t i ons of 36 t o 122 degr ees F dr y bul b and 20 t o 90 per cent r el at i ve humi di t y, noncondensi ng.

1. 6. 2 I nt er i or , Uncont r ol l ed Envi r onment

Al l syst em component s i nst al l ed i n i nt er i or l ocat i ons havi ng uncont r ol l ed envi r onment s shal l be r at ed f or cont i nuous oper at i on under ambi ent envi r onment al condi t i ons of 0 t o 122 degr ees F dr y bul b and 10 t o 95 per cent r el at i ve humi di t y, noncondensi ng.

1. 6. 3 Ext er i or Envi r onment

Syst em component s t hat ar e i nst al l ed i n l ocat i ons exposed t o weat her shal l be r at ed f or cont i nuous oper at i on under ambi ent envi r onment al condi t i ons of

SECTI ON 28 16 01 Page 8 mi nus 30 t o 122 degr ees F dr y bul b and 10 t o 95 per cent r el at i ve humi di t y, condensi ng. I n addi t i on, t he syst em component s shal l be r at ed f or cont i nuous oper at i on when exposed t o per f or mance condi t i ons as speci f i ed i n UL 294 and UL 639 f or out door use equi pment . I n addi t i on, component s shal l be r at ed f or cont i nuous oper at i on when exposed t o r ai n as speci f i ed i n NEMA 250, wi nds up t o 85 mph and snow cover up t o 2 f eet t hi ck, measur ed vertically.

1. 6. 4 Hazar dous Envi r onment

Syst em component s l ocat ed i n ar eas wher e f i r e or expl osi on hazar ds may exi st because of f l ammabl e gases or vapor s, f l ammabl e l i qui ds, combust i bl e dust , or i gni t abl e f i ber s or f l y i ngs, shal l be r at ed and i nst al l ed accor di ng t o Chapt er 5 of NFPA 70 and as shown.

1. 6. 5 Cent r al St at i on

Al l cent r al st at i on equi pment shal l , unl ess desi gnat ed ot her wi se, be r at ed f or cont i nuous oper at i on under ambi ent envi r onment al condi t i ons of 60 t o 85 degr ees F and a r el at i ve humi di t y of 20 t o 80 per cent .

1. 7 EXTRA MATERI ALS

Submit spar e par t s dat a f or each di f f er ent i t em of equi pment and mat er i al speci f i ed, af t er appr oval of det ai l dr awi ngs and not l at er t han 2 mont hs pr i or t o t he dat e of benef i c i al occupancy. The dat a shal l i ncl ude a compl et e l i s t of par t s, t ool s and suppl i es, wi t h cur r ent uni t pr i ces and sour ce of suppl y, and a l i s t of t he par t s r ecommended f or st ocki ng.

PART 2 PRODUCTS

2. 1 MATERI ALS AND EQUI PMENT

Wher e mat er i al s or equi pment ar e speci f i ed t o conf or m, be const r uct ed or t est ed t o meet speci f i c r equi r ement s, submi t cer t i f i cat i on t hat t he i t ems pr ovi ded conf or m t o such r equi r ement s. Cer t i f i cat i on by a nat i onal l y r ecogni zed t est i ng l abor at or y t hat a r epr esent at i ve sampl e has been t est ed t o meet t he r equi r ement s, or a publ i shed cat al og speci f i cat i on st at ement t o t he ef f ect t hat t he i t em meet s t he r ef er enced st andar d, wi l l be accept abl e as evi dence t hat t he i t em conf or ms. Compl i ance wi t h t hese r equi r ement s does not r el i eve t he Cont r act or f r om compl i ance wi t h ot her r equi r ement s of t he speci f i cat i ons

2. 1. 1 General

Uni t s of t he same t ype of equi pment shal l be pr oduct s of a s i ngl e manuf act ur er . Al l mat er i al and equi pment shal l be new and cur r ent l y i n pr oduct i on. Each maj or component of equi pment shal l have t he manuf act ur er ' s model and ser i al number i n a conspi cuous pl ace. Pr ovi de l ami nat ed pl ast i c namepl at es f or l ocal pr ocessor s. Each namepl at e shal l i dent i f y t he l ocal pr ocessor and i t s l ocat i on wi t hi n t he syst em. Lami nat ed pl ast i c shal l be 1/ 8 i nch t hi ck, whi t e wi t h bl ack cent er cor e. Namepl at es shal l be a mi ni mum of 1 by 3 i nches, wi t h mi ni mum 1/ 4 i nch hi gh engr aved bl ock l et t er i ng. At t ach namepl at es t o t he i nsi de of t he encl osur e housi ng t he l ocal pr ocessor . Ot her maj or component s of t he syst em shal l have t he manuf act ur er ' s name, addr ess, t ype or st y l e, model or ser i al number , and cat al og number on a cor r osi on r esi st ant pl at e secur ed t o t he i t em of equi pment . Namepl at es wi l l not be r equi r ed f or devi ces smal l er t han 1 by 3 inches .

SECTI ON 28 16 01 Page 9

2. 1. 2 Enclosures

Syst em encl osur es shal l be as shown.

2. 1. 2. 1 I nt er i or Sensor

Sensor s t o be used i n an i nt er i or envi r onment shal l be housed i n an encl osur e t hat pr ovi des pr ot ect i on agai nst dust , f al l i ng di r t , and dr i ppi ng noncor r osi ve l i qui ds.

2. 1. 2. 2 I nt er i or El ect r oni cs

Syst em el ect r oni cs t o be used i n an i nt er i or envi r onment shal l be housed i n encl osur es whi ch meet t he r equi r ement s of NEMA 250 Type 12.

2. 1. 2. 3 Ext er i or El ect r oni cs

Syst em el ect r oni cs t o be used i n an ext er i or envi r onment shal l be housed i n encl osur es whi ch meet t he r equi r ement s of NEMA 250 Type 4X.

2. 1. 3 Tamper Pr ovi s i ons

2. 1. 3. 1 Tamper Swi t ches

Encl osur es, cabi net s, housi ngs, boxes, and f i t t i ngs of ever y descr i pt i on havi ng hi nged door s or r emovabl e cover s and whi ch cont ai n c i r cui t s or connect i ons of t he i nt r usi on det ect i on syst em and i t s power suppl i es, shal l be pr ovi ded wi t h cover oper at ed, cor r osi on- r esi st ant t amper swi t ches, ar r anged t o i ni t i at e an al ar m si gnal when t he door or cover i s moved. The encl osur e and t he t amper swi t ch shal l f unct i on t oget her i n such a manner as t o not al l ow di r ect l i ne of s i ght t o any i nt er nal component s bef or e t he swi t ch act i vat es. Make t amper swi t ches i naccessi bl e unt i l t he swi t ch i s act i vat ed; have mount i ng har dwar e so conceal ed t hat t he l ocat i on of t he swi t ch cannot be obser ved f r om t he ext er i or of t he encl osur e; be connect ed t o c i r cui t s whi ch ar e under el ect r i cal super vi s i on at al l t i mes, i r r espect i ve of t he pr ot ect i on mode i n whi ch t he c i r cui t i s oper at i ng;

shal l be spr i ng- l oaded and hel d i n t he c l osed posi t i on by t he door or cover ; and shal l be wi r ed so t hat t hey br eak t he c i r cui t when t he door or cover i s di st ur bed.

2. 1. 3. 1. 1 Nonsensor Encl osur es

Tamper swi t ches on nonsensor encl osur es, whi ch must be opened t o make r out i ne mai nt enance adj ust ment s t o t he syst em and t o ser vi ce t he power suppl i es, shal l be push/ pul l - set , aut omat i c r eset t ype.

2. 1. 3. 1. 2 Sensor Encl osur es

Tamper swi t ches on sensor encl osur es, whi ch must be opened t o make r out i ne mai nt enance adj ust ment s t o t he sensor , shal l be s i ngl e pol e s i ngl e t hr ow type.

2. 1. 3. 2 Encl osur e Cover s

Cover s of pul l and j unct i on boxes pr ovi ded t o f aci l i t at e i ni t i al i nst al l at i on of t he syst em need not be pr ovi ded wi t h t amper swi t ches i f t hey cont ai n no spl i ces or connect i ons, but shal l be pr ot ect ed by t ack wel di ng or br azi ng t he cover s i n pl ace or by t amper r esi st ant secur i t y

SECTI ON 28 16 01 Page 10 f ast ener s. Label s shal l be af f i xed t o such boxes i ndi cat i ng t hey cont ai n no connect i ons.

2. 1. 4 Locks and Key- Lock Swi t ches

2. 1. 4. 1 Locks

I nst al l l ocks on syst em encl osur es f or mai nt enance pur poses. Locks shal l be UL l i s t ed, convent i onal key t ype l ock havi ng a combi nat i on of f i ve cyl i nder pi n and f i ve- poi nt t hr ee posi t i on s i de bar . Keys shal l be st amped " U. S. GOVT. DO NOT DUP" . The l ocks shal l be so ar r anged t hat t he key can onl y be wi t hdr awn when i n t he l ocked posi t i on. Al l mai nt enance l ocks shal l be keyed al i ke and onl y t wo keys shal l be f ur ni shed f or al l of t hese l ocks. These keys shal l be cont r ol l ed i n accor dance wi t h t he key cont r ol plan . Submi t a Key cont r ol pl an i ncl udi ng t he f ol l owi ng:

a. Pr ocedur es t hat wi l l be used t o l og and posi t i vel y cont r ol al l keys dur i ng i nst al l at i on.

b. A l i s t i ng of al l keys and wher e t hey ar e used.

c. A l i s t i ng of al l per sons al l owed ent r y t o t he keys.

2. 1. 4. 2 Key- Lock- Oper at ed Swi t ches

Al l key- l ock- oper at ed swi t ches r equi r ed t o be i nst al l ed on syst em component s shal l be UL l i s t ed, convent i onal key t ype l ock havi ng a combi nat i on of f i ve cyl i nder pi n and f i ve- poi nt t hr ee posi t i on s i de bar .

Keys shal l be st amped " U. S. GOVT. DO NOT DUP" . Key- l ock- oper at ed swi t ches shal l be t wo posi t i on, wi t h t he key r emovabl e i n ei t her posi t i on. Al l key- l ock- oper at ed swi t ches shal l be keyed di f f er ent l y and onl y t wo keys shal l be f ur ni shed f or each key- l ock- oper at ed- swi t ch. These keys shal l be cont r ol l ed i n accor dance wi t h t he key cont r ol pl an.

2. 1. 4. 3 Const r uct i on Locks

I f t he Cont r act or r equi r es l ocks dur i ng i nst al l at i on and const r uct i on, a set of t empor ar y l ocks shal l be used. The f i nal set of l ocks i nst al l ed and del i ver ed t o t he Gover nment shal l not i ncl ude any of t he t empor ar y l ocks.

2. 1. 5 Appl i cat i on of Syst em Component

Syst em component s shal l be desi gned f or cont i nuous oper at i on. El ect r oni c component s shal l be sol i d st at e t ype, mount ed on pr i nt ed c i r cui t boar ds conf or mi ng t o UL 796. Pr i nt ed c i r cui t boar d connect or s shal l be pl ug- i n, qui ck- di sconnect t ype. Power di ssi pat i ng component s shal l i ncor por at e saf et y mar gi ns of not l ess t hat 25 per cent wi t h r espect t o di ssi pat i on r at i ngs, maxi mum vol t ages, and cur r ent car r y i ng capaci t y. Li ght dut y r el ays and si mi l ar swi t chi ng devi ces shal l be sol i d st at e t ype or seal ed electro-mechanical.

2. 1. 5. 1 Maintainability

Component s shal l be desi gned t o be mai nt ai ned usi ng commer ci al l y avai l abl e t ool s and equi pment . Component s shal l be ar r anged and assembl ed so t hey ar e accessi bl e t o mai nt enance per sonnel . Ther e shal l be no degr adat i on i n t amper pr ot ect i on, st r uct ur al i nt egr i t y, EMI / RFI at t enuat i on, or l i ne super vi s i on af t er mai nt enance when i t i s per f or med i n accor dance wi t h manuf act ur er ' s i nst r uct i ons. The syst em shal l be conf i gur ed and i nst al l ed

SECTI ON 28 16 01 Page 11 t o y i el d a mean t i me t o r epai r ( MTTR) of not mor e t han 8 hour s. Repai r t i me i s t he c l ock t i me f r om t he t i me mai nt enance per sonnel ar e gi ven ent r ance t o t he syst em and begi n wor k, unt i l t he syst em i s f ul l y f unct i onal .

2. 1. 5. 2 Interchangeability

Const r uct t he syst em wi t h of f - t he- shel f component s whi ch ar e physi cal l y , el ect r i cal l y and f unct i onal l y i nt er changeabl e wi t h equi val ent component s as compl et e i t ems. Repl acement of equi val ent component s shal l not r equi r e modi f i cat i on of ei t her t he new component or of ot her component s wi t h whi ch t he r epl acement i t ems ar e used. Cust om desi gned or one- of - a- k i nd i t ems shal l not be used. I nt er changeabl e component s or modul es shal l not r equi r e t r i al and er r or mat chi ng i n or der t o meet i nt egr at ed syst em r equi r ement s, syst em accur acy, or r est or e compl et e syst em f unct i onal i t y .

2. 1. 5. 3 El ect r omagnet i c and Radi o Fr equency I nt er f er ence ( EMI / RFI )

Syst em component s gener at i ng EMI / RFI shal l be desi gned and const r uct ed i n accor dance wi t h 47 CFR 15.

2. 1. 5. 4 Pr oduct Saf et y

Syst em component s shal l conf or m t o appl i cabl e r ul es and r equi r ement s of NFPA 70. Syst em component s shal l be equi pped wi t h i nst r uct i on pl at es, i ncl udi ng war ni ngs and caut i ons, descr i bi ng physi cal saf et y, and speci al or i mpor t ant pr ocedur es t o be f ol l owed i n oper at i ng and ser vi c i ng syst em equipment.

2. 1. 6 Cont r ol s and Desi gnat i ons

Pr ovi de cont r ol s and desi gnat i ons as speci f i ed i n NEMA I CS 1.

2. 1. 7 Speci al Test Equi pment

Pr ovi de al l speci al t est equi pment , speci al har dwar e, sof t war e, t ool s, and pr ogr ammi ng or i ni t i al i zat i on equi pment needed t o st ar t or mai nt ai n any par t of t he syst em and i t s component s. Speci al t est equi pment i s def i ned as any t est equi pment not nor mal l y used i n an el ect r oni cs mai nt enance facility.

2. 1. 8 Al ar m Out put

The al ar m out put of each sensor shal l be a s i ngl e pol e doubl e t hr ow ( SPDT) cont act r at ed f or a mi ni mum of 0. 25 A at 24 vol t s DC.

2. 1. 9 Al ar m I ndi cat or Li ght s

I ndi cat or l i ght s used t hr oughout t he syst em shal l be l i ght emi t t i ng di odes ( LED) or l ong l i f e i ncandescent l amps. The i ndi cat or l i ght s used shal l be v i s i bl e f r om a di st ance of 30 f eet i n an ar ea i l l umi nat ed t o 75 f oot candl es.

The i ndi cat or l i ght s shal l conf or m t o t he f ol l owi ng col or codi ng:

a. FLASHI NG RED t o al er t an oper at or t hat a zone has gone i nt o an unacknowl edged al ar m or t hat pr i mar y power has f ai l ed.

b. RED t o al er t an oper at or t hat a zone i s i n al ar m and t hat t he al ar m has been acknowl edged.

c. YELLOW t o advi se an oper at or t hat a zone i s i n access.

SECTI ON 28 16 01 Page 12

d. GREEN t o i ndi cat e t hat a zone i s secur e or t hat power i s on.

2. 1. 10 Access/ Secur e Devi ces

Access/ secur e devi ces shal l be used t o pl ace a pr ot ect ed zone i n ACCESS.

The devi ce shal l di sabl e al l sensor al ar m out put s, wi t h t he except i on of t amper al ar m out put s wi t hi n t he pr ot ect ed zone, and sensor s i n zones above f al se cei l i ngs or ot her i naccessi bl e l ocat i ons as shown.

2. 1. 10. 1 Switches

The swi t ch shal l consi st of a doubl e pul l key- oper at ed swi t ch housed i n a NEMA 12 equi val ent encl osur e.

2. 1. 10. 2 Key Pads

Secur e/ Access keypads shal l use a uni que combi nat i on of al phanumer i c and ot her symbol s as an i dent i f i er . Keypads shal l cont ai n an i nt egr al al phanumer i c/ speci al symbol s keyboar d wi t h symbol s ar r anged i n ascendi ng ASCI I code or di nal sequence. The keypad shal l have a cont act out put .

2. 2 I NTERI OR SENSORS

2. 2. 1 Bal anced Magnet i c Swi t ch ( BMS)

The BMS shal l det ect 1/ 4 i nch of separ at i ng r el at i ve movement bet ween t he magnet and t he swi t ch housi ng. Upon det ect i ng such movement , i t shal l t r ansmi t an al ar m si gnal t o t he al ar m annunci at i on syst em.

2. 2. 1. 1 BMS Subassembl i es

The BMS shal l consi st of a swi t ch assembl y and an act uat i ng magnet i c assembl y. The swi t ch mechani sm shal l be of t he bal anced magnet i c t ype.

Each swi t ch shal l be pr ovi ded wi t h an over cur r ent pr ot ect i ve devi ce, r at ed t o l i mi t cur r ent t o 80 per cent of t he swi t ch capaci t y. Swi t ches shal l be r at ed f or a mi ni mum l i f et i me of one mi l l i on oper at i ons. The housi ngs of sur f ace mount ed swi t ches and magnet s shal l be made of nonf er r ous met al and shal l be weat her pr oof . The housi ngs of r ecess mount ed swi t ches and magnet s shal l be made of nonf er r ous met al or pl ast i c.

2. 2. 1. 2 Remot e Test

Pr ovi de a r emot e t est capabi l i t y . The r emot e t est shal l be i ni t i at ed when commanded by t he al ar m annunci at i on syst em. The r emot e t est shal l act i vat e t he sensor ' s swi t ch mechani sm causi ng an al ar m si gnal t o be t r ansmi t t ed t o t he al ar m annunci at i on syst em. The r emot e t est shal l s i mul at e t he movement of t he act uat i ng magnet r el at i ve t o t he swi t ch subassembl y.

2. 2. 2 Dur ess Al ar m Swi t ches

Dur ess al ar m swi t ches shal l pr ovi de t he means f or an i ndi v i dual t o cover t l y not i f y t he al ar m annunci at i on syst em t hat a dur ess s i t uat i on exi st s.

2. 2. 2. 1 Pushbutton

Lat chi ng pushbut t on dur ess al ar ms shal l be desi gned t o be act i vat ed by depr essi ng a pushbut t on l ocat ed on t he dur ess swi t ch housi ng. No v i s i bl e or audi bl e al ar m or noi se shal l emanat e f r om t he swi t ch. The swi t ch shal l

SECTI ON 28 16 01 Page 13 l ock i n t he act i vat ed posi t i on unt i l manual l y r eset wi t h a key. The swi t ch housi ng shal l shr oud t he act i vat i ng but t on t o pr event acci dent al act i vat i on. Swi t ches shal l be r at ed f or a mi ni mum l i f et i me of 50, 000 operations.

2. 2. 3 Secur i t y Scr een

Secur i t y scr eens shal l det ect an st andar d i nt r uder when t he sensor wi r e i s di sconnect ed, cut , or br oken. An al ar m si gnal shal l be t r ansmi t t ed t o t he al ar m annunci at i on syst em. The sensor shal l be const r uct ed f r om 26 gauge i nsul at ed har d- dr awn copper wi r e i nst al l ed i n a gr i d pat t er n on a wooden f r ame or as shown. The sensor gr i d wi r es connect i on t o t he al ar m annunci at i on syst em shal l be housed wi t hi n a j unct i on box as shown. A t amper swi t ch shal l be pr ovi ded t o det ect at t empt s t o r emove t he scr een and t o det ect at t empt s t o t amper wi t h connect i ons and end of l i ne r esi st or .

2. 2. 4 Passi ve I nf r ar ed Mot i on Sensor

The passi ve i nf r ar ed mot i on sensor shal l det ect changes i n t he ambi ent l evel of i nf r ar ed emi ssi ons caused by t he movement of a st andar d i nt r uder wi t hi n t he sensor ' s f i el d of v i ew. Upon det ect i ng such changes, t he sensor shal l t r ansmi t an al ar m si gnal t o t he al ar m annunci at i on syst em. The sensor shal l det ect a change i n t emper at ur e of no mor e t han 2 degr ees F, and shal l det ect a st andar d i nt r uder t r avel i ng wi t hi n t he sensor ' s det ect i on pat t er n at a speed of 0. 3 t o 7. 5 f eet per second acr oss t wo adj acent segment s of t he f i el d of v i ew. Emi ssi ons moni t or ed by t he sensor shal l be i n t he 8 t o 14 mi cr on r ange. The sensor shal l be adj ust abl e t o obt ai n t he cover age pat t er n shown. The sensor shal l be equi pped wi t h a t emper at ur e compensat i on c i r cui t .

2. 2. 4. 1 Test I ndi cat or , I nf r ar ed Emi ssi ons

The passi ve i nf r ar ed mot i on sensor shal l be equi pped wi t h an LED wal k t est i ndi cat or . The wal k t est i ndi cat or shal l not be v i s i bl e dur i ng nor mal oper at i ons. When vi s i bl e, t he wal k t est i ndi cat or shal l l i ght when t he sensor det ect s an i nt r uder . The sensor shal l ei t her be equi pped wi t h a manual cont r ol , l ocat ed wi t hi n t he sensor ' s housi ng, t o enabl e/ di sabl e t he t est i ndi cat or or t he t est i ndi cat or shal l be l ocat ed wi t hi n t he sensor such t hat i t can onl y be seen when t he housi ng i s open/ r emoved.

2. 2. 4. 2 Remot e Test , I nf r ar ed Emi ssi ons

Pr ovi de a r emot e t est capabi l i t y . The r emot e t est har dwar e may be i nt egr al t o t he sensor or a separ at e pi ece of equi pment . The r emot e t est shal l be i ni t i at ed when commanded by t he al ar m annunci at i on syst em. The r emot e t est shal l exci t e t he sensi ng el ement and associ at ed el ect r oni cs causi ng an al ar m si gnal t o be t r ansmi t t ed t o t he al ar m annunci at i on syst em. The sensor st i mul at i on gener at ed by t he r emot e t est har dwar e shal l s i mul at e a st andar d i nt r uder movi ng wi t hi n t he sensor ' s det ect i on pat t er n.

2. 3 SOFTWARE

The sof t war e shal l suppor t al l speci f i ed f unct i ons. The cent r al st at i on shal l be onl i ne at al l t i mes and shal l per f or m al l r equi r ed f unct i ons as speci f i ed. Sof t war e shal l be r esi dent at t he cent r al st at i on and/ or t he l ocal pr ocessor as r equi r ed t o per f or m al l speci f i ed f unct i ons.

SECTI ON 28 16 01 Page 14

2. 3. 1 Syst em Sof t war e

The oper at i ng syst em shal l per f or m t he f ol l owi ng f unct i ons:

a. Suppor t mul t i user oper at or wi t h mul t i pl e t asks f or each user .

b. Suppor t oper at i on and management of al l per i pher al devi ces.

c. Pr ovi de f i l e management f unct i ons f or di sk I / O, i ncl udi ng cr eat i on and del et i on of f i l es, copyi ng of f i l es, a di r ect or y of al l f i l es i ncl udi ng s i ze and l ocat i on of each sequent i al and r andom or der ed r ecor ds.

2. 3. 2 Appl i cat i ons Sof t war e

2. 3. 2. 1 Oper at or Commands

The oper at or ' s commands shal l pr ovi de t he means f or ent r y of moni t or i ng and cont r ol commands, and f or r et r i eval of syst em i nf or mat i on. Pr ocessi ng of oper at or commands shal l commence wi t hi n 1 second of ent r y, wi t h some f or m of acknowl edgment pr ovi ded at t hat t i me. The oper at or ' s commands shal l per f or m t asks i ncl udi ng:

a. Request hel p wi t h t he syst em oper at i on.

b. Acknowl edge al ar ms.

c. Pl ace zone i n access.

d. Pl ace zone i n secur e.

e. Test t he syst em.

f . Change oper at or .

2. 3. 2. 2 Command I nput

Oper at or ' s commands shal l be f ul l Engl i sh l anguage wor ds and acr onyms sel ect ed t o al l ow oper at or s t o use t he syst em wi t hout ext ensi ve t r ai ni ng or dat a pr ocessi ng backgr ounds. The syst em shal l pr ompt t he oper at or i n Engl i sh wor d, phr ase, or acr onym. Commands shal l be avai l abl e i n an abbr evi at ed mode, i n addi t i on t o t he f ul l Engl i sh l anguage ( wor ds and acr onyms) commands, al l owi ng an exper i enced oper at or t o di sr egar d por t i ons, or al l , of t he pr ompt - r esponse r equi r ement s.

2. 3. 2. 3 Command I nput Er r or s

The syst em shal l super vi se oper at or i nput s t o ensur e t hey ar e cor r ect f or pr oper execut i on. Oper at or i nput assi st ance shal l be pr ovi ded whenever a command cannot be execut ed because of oper at or i nput er r or s. The syst em shal l expl ai n t o t he oper at or , i n Engl i sh wor ds and phr ases, why t he command cannot be execut ed. The er r or r esponses r equi r i ng an oper at or t o l ook up a code i n a manual or ot her document ar e not accept abl e.

Condi t i ons f or whi ch oper at or er r or assi st messages shal l be gener at ed include:

a. The command used i s i ncor r ect or i ncompl et e.

b. The oper at or i s r est r i c t ed f r om usi ng t hat command.

c. The command addr esses a poi nt whi ch i s di sabl ed or out of ser vi ce.

d. The command addr esses a poi nt whi ch does not exi st .

e. The command woul d v i ol at e const r ai nt s.

2. 3. 2. 4 Enhancements

The syst em shal l i mpl ement t he f ol l owi ng enhancement s by use of speci al

SECTI ON 28 16 01 Page 15 f unct i on keys, t ouch scr een, or mouse, i n addi t i on t o al l ot her command i nput s speci f i ed:

2. 3. 2. 4. 1 Help

Used t o pr oduce a di spl ay f or al l commands avai l abl e t o t he oper at or . The hel p command, f ol l owed by a speci f i c command shal l pr oduce a shor t expl anat i on of t he pur pose, use, and syst em r eact i on t o t hat command.

2. 3. 2. 4. 2 Acknowl edge Al ar ms

Used t o acknowl edge t hat t he al ar m message has been obser ved by t he operator.

2. 3. 2. 4. 3 Pl ace Zone i n Access

Used t o r emot el y di sabl e al l i nt r usi on al ar m ci r cui t s emanat i ng f r om a speci f i c zone. The syst em shal l be st r uct ur ed so t hat t amper c i r cui t s cannot be di sabl ed by t he consol e oper at or .

2. 3. 2. 4. 4 Pl ace Zone i n Secur e

Used t o r emot el y act i vat e al l i nt r usi on al ar m ci r cui t s emanat i ng f r om a speci f i c zone.

2. 3. 2. 4. 5 Syst em Test

Al l ows t he oper at or t o i ni t i at e a syst em wi de oper at i onal t est .

2. 3. 2. 4. 6 Zone Test

Al l ows t he oper at or t o i ni t i at e an oper at i onal t est f or a speci f i c zone.

2. 3. 2. 4. 7 Change Oper at or

Used f or changi ng oper at or s.

2. 3. 2. 4. 8 Secur i t y Li ght i ng Cont r ol s

Al l ows t he oper at or t o r emot el y t ur n on/ of f secur i t y l i ght s.

2. 3. 2. 4. 9 Di spl ay Gr aphi cs

Used t o di spl ay any gr aphi c di spl ays i mpl ement ed i n t he syst em.

2. 3. 3 Si t e Speci f i c Dat abase Sof t war e

2. 3. 3. 1 Dat abase Def i ni t i on Pr ocess

Sof t war e shal l be pr ovi ded t o def i ne and modi f y each poi nt i n t he dat abase usi ng oper at or commands. The def i ni t i on shal l i nc l ude al l physi cal par amet er s and const r ai nt s associ at ed wi t h each sensor , commandabl e out put , zone, et c. Each dat abase i t em shal l be cal l abl e f or di spl ay, i ncl udi ng EEPROM, ROM and RAM r esi dent dat a. Def i ne and ent er t he dat abase i nt o t he cent r al st at i on based upon i nput f r om t he Gover nment .

2. 3. 3. 2 Syst em Access Cont r ol

The syst em shal l pr ovi de a means t o def i ne syst em oper at or capabi l i t y and

SECTI ON 28 16 01 Page 16 f unct i ons t hr ough mul t i pl e, passwor d oper at ed pr ot ect ed oper at or l evel s.

At l east 3 oper at or l evel s shal l be pr ovi ded. Syst em oper at or s and manager s wi t h appr opr i at e passwor d c l ear ances shal l be abl e t o change oper at or l evel s f or al l oper at or s. Thr ee successi ve at t empt s by an oper at or t o execut e f unct i ons beyond t hei r def i ned l evel dur i ng a 24- hour per i od shal l i ni t i at e a sof t war e t amper al ar m. A mi ni mum of 32 passwor ds shal l be usabl e wi t h t he i nt r usi on det ect i on syst em sof t war e. The syst em shal l di spl ay t he oper at or ' s name or i ni t i al s i n t he consol e' s f i r s t f i el d. The passwor d shal l not be di spl ayed. Each passwor d shal l be def i nabl e and assi gnabl e f or t he f ol l owi ng:

a. Commands usabl e.

b. Access t o syst em sof t war e.

c. Access t o appl i cat i on sof t war e.

d. I ndi v i dual zones whi ch ar e t o be accessed.

e. Access t o dat abase.

2. 3. 3. 3 Al ar m Moni t or i ng Sof t war e

Thi s pr ogr am shal l moni t or al l sensor s, l ocal pr ocessor s and DTS ci r cui t s and not i f y t he oper at or of an al ar m condi t i on. Hi gher pr i or i t y al ar ms shal l be di spl ayed f i r st and wi t hi n al ar m pr i or i t i es. The ol dest unacknowl edged al ar m shal l be di spl ayed f i r st . Oper at or acknowl edgment of one al ar m shal l not be consi der ed as acknowl edgment of any ot her al ar m nor shal l i t i nhi bi t r epor t i ng of subsequent al ar ms. Al ar m dat a t o be di spl ayed shal l i ncl ude t ype of al ar m, and l ocat i on of al ar m, and secondar y al ar m messages. A uni que message f i el d wi t h a wi dt h of 60 char act er s shal l be pr ovi ded f or each al ar m. Assi gnment of messages t o a zone or sensor shal l be an oper at or edi t abl e f unct i on. The syst em shal l pr ovi de f or 25 secondar y messages wi t h a f i el d of 4 l i nes of 60 char act er s each. The most r ecent 1000 al ar ms shal l be st or ed and shal l be r ecal l abl e by t he oper at or usi ng t he r epor t gener at or .

2. 4 FI ELD PROCESSI NG HARDWARE

2. 4. 1 Al ar m Annunci at i on Local Pr ocessor

The al ar m annunci at i on l ocal pr ocessor shal l r espond t o i nt er r ogat i ons f r om t he f i el d devi ce net wor k, r ecogni ze and st or e al ar m st at us i nput s unt i l t hey ar e t r ansmi t t ed t o t he cent r al st at i on and change out…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .