This document provides specifications for the BTC4 Phase 2 federal contract opportunity at Fort Jackson. The solicitation package includes proposal, summary, past performance, and small business participation plan attachments. It also includes four volumes of drawings and specifications. A site visit is scheduled for September 10, 2019 to review the project requirements. Questions must be submitted through the projnet system. The Army Corps of Engineers Engineering District Charleston is the issuing agency. The response due date and award date are not specified. The solicitation appears to be for construction services at Fort Jackson but does not include pricing or set-aside terms.

Specifications Volume 3

View the file

Other files for this federal contract opportunity

Show all 21

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fort Jackson, South Carolina

Solicitation Number

W912HP-19-R-2001

BCT4, Phase 2 Volume 3 of 4: Specification Divisions 23 - 27

PN 76218

July 2019

U.S. ARMY ENGINEER DISTRICT, SAVANNAH

CORPS OF ENGINEERS

100 WEST OGLETHORPE AVENUE

SAVANNAH, GEORGIA 31401-3640

US Army Corps of Engineers

BCT 4 Phase 2 JA76218 Ft . Jackson, SC

PROJECT TABLE OF CONTENTS

DI VI SI ON 01 - GENERAL REQUI REMENTS

01 11 00 SUMMARY OF WORK

01 30 00 ADMI NI STRATI VE REQUI REMENTS

01 32 01 PROJECT SCHEDULE

01 33 00 SUBMI TTAL PROCEDURES

01 33 29 SUSTAI NABI LI TY REPORTI NG

01 35 26 GOVERNMENTAL SAFETY REQUI REMENTS

01 42 00 SOURCES FOR REFERENCE PUBLI CATI ONS

01 45 00 QUALI TY CONTROL

01 45 00. 15 RESI DENT MANAGEMENT SYSTEM CONTRACTOR MODE ( RMS CM)

01 45 35 SPECI AL I NSPECTI ONS

01 50 00 TEMPORARY CONSTRUCTI ON FACI LI TI ES AND CONTROLS

01 57 19 TEMPORARY ENVI RONMENTAL CONTROLS

01 57 19. 37 I NDOOR AI R QUALI TY ( I AQ) MANAGEMENT

01 74 19. 37 CONSTRUCTI ON AND DEMOLI TI ON WASTE MANAGEMENT

01 78 00 CLOSEOUT SUBMI TTALS

01 78 23 OPERATI ON AND MAI NTENANCE DATA

01 91 00. 15 TOTAL BUI LDI NG COMMI SSI ONI NG

DI VI SI ON 03 - CONCRETE

03 11 13 STRUCTURAL CAST- I N- PLACE CONCRETE FORMI NG

03 15 00 CONCRETE ACCESSORI ES

03 20 00 CONCRETE REI NFORCI NG

03 30 00 CAST- I N- PLACE CONCRETE

03 35 00 CONCRETE FI NI SHI NG

03 39 00 CONCRETE CURI NG

DI VI SI ON 04 - MASONRY

04 20 00 MASONRY

DI VI SI ON 05 - METALS

05 05 23. 16 STRUCTURAL WELDI NG

05 12 00 STRUCTURAL STEEL

05 21 00 STEEL JOI ST FRAMI NG

05 30 00 STEEL DECKS

05 40 00 COLD- FORMED METAL FRAMI NG

05 50 13 MI SCELLANEOUS METAL FABRI CATI ONS

05 51 00 METAL STAI RS

05 51 33 METAL LADDERS

05 52 00 METAL RAI LI NGS

DI VI SI ON 06 - WOOD, PLASTI CS, AND COMPOSI TES

06 10 00 ROUGH CARPENTRY

06 20 00 FI NI SH CARPENTRY

06 41 16 LAMI NATE CLAD ARCHI TECTURAL CASEWORK

06 61 16 SOLI D POLYMER ( SOLI D SURFACI NG) FABRI CATI ONS

DI VI SI ON 07 - THERMAL AND MOI STURE PROTECTI ON

07 05 23 PRESSURE TESTI NG AN AI R BARRI ER SYSTEM FOR AI R TI GHTNESS

07 21 13 BOARD AND BLOCK I NSULATI ON

07 21 16 MI NERAL FI BER BLANKET I NSULATI ON

PROJECT TABLE OF CONTENTS Page 1

07 22 00 ROOF AND DECK I NSULATI ON

07 27 10 BUI LDI NG AI R BARRI ER SYSTEM

07 41 00 METAL SOFFI T PANELS

07 41 13 METAL ROOF PANELS

07 42 13 METAL WALL PANELS

07 53 23 ETHYLENE- PROPYLENE- DI ENE- MONOMER ROOFI NG

07 60 00 FLASHI NG AND SHEET METAL

07 84 00 FIRESTOPPING

07 92 00 JOI NT SEALANTS

DI VI SI ON 08 - OPENI NGS

08 11 13 STEEL DOORS AND FRAMES

08 11 16 ALUMI NUM DOORS AND FRAMES

08 14 00 WOOD DOORS

08 34 59 VAULT DOORS AND DAY GATES

08 34 73 SOUND CONTROL DOOR ASSEMBLI ES

08 44 00 CURTAI N WALL AND GLAZED ASSEMBLI ES

08 51 13 ALUMI NUM WI NDOWS

08 71 00 DOOR HARDWARE

08 81 00 GLAZING

08 91 00 METAL WALL LOUVERS

DI VI SI ON 09 - FI NI SHES

09 06 00 SCHEDULES FOR FI NI SHES

09 22 00 SUPPORTS FOR PLASTER AND GYPSUM BOARD

09 29 00 GYPSUM BOARD

09 30 10 CERAMI C, QUARRY, AND GLASS TI LI NG

09 51 00 ACOUSTI CAL CEI LI NGS

09 65 00 RESI LI ENT FLOORI NG

09 67 23. 13 STANDARD RESI NOUS FLOORI NG

09 90 00 PAI NTS AND COATI NGS

DI VI SI ON 10 - SPECI ALTI ES

10 09 00 MI SCELLANEOUS I TEMS

10 10 00 VI SUAL COMMUNI CATI ONS SPECI ALTI ES

10 14 00. 20 I NTERI OR SI GNAGE

10 21 13 TOI LET COMPARTMENTS

10 26 00 WALL AND DOOR PROTECTI ON

10 28 13 TOI LET ACCESSORI ES

DI VI SI ON 11 - EQUI PMENT

11 06 40. 13 FOODSERVI CE EQUI PMENT SCHEDULE

DI VI SI ON 12 - FURNI SHI NGS

12 21 00 WI NDOW BLI NDS

12 24 13 ROLLER WI NDOW SHADES

12 48 13 ENTRANCE FLOOR MATS AND FRAMES

12 93 00 SI TE FURNI SHI NGS

DI VI SI ON 13 - SPECI AL CONSTRUCTI ON

13 34 19 METAL BUI LDI NG SYSTEMS ( COVERED TRAI NI NG CANOPY)

13 48 00 SEI SMI C PROTECTI ON FOR MI SCELLANEOUS EQUI PMENT

13 48 00. 22 SEI SMI C PROTECTI ON FOR MECHANI CAL EQUI PMENT

PROJECT TABLE OF CONTENTS Page 2

DI VI SI ON 21 - FI RE SUPPRESSI ON

21 13 13 WET PI PE SPRI NKLER SYSTEM, FI RE PROTECTI ON

DI VI SI ON 22 - PLUMBI NG

22 00 00 PLUMBI NG, GENERAL PURPOSE

DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

23 05 48 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND

EQUIPMENT

23 05 93 TESTI NG, ADJUSTI NG, AND BALANCI NG FOR HVAC

23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS

23 09 00 I NSTRUMENTATI ON AND CONTROL FOR HVAC

23 09 13 I NSTRUMENTATI ON AND CONTROL DEVI CES FOR HVAC

23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER

BUI LDI NG CONTROL SYSTEMS

23 11 25 FACI LI TY GAS PI PI NG

23 23 00 REFRI GERANT PI PI NG

23 25 00 CHEMI CAL TREATMENT OF WATER FOR MECHANI CAL SYSTEMS

23 52 00 HEATI NG BOI LERS

23 57 10 FORCED HOT WATER HEATI NG SYSTEMS USI NG WATER HEAT

EXCHANGERS

23 64 10 WATER CHI LLERS, VAPOR COMPRESSI ON TYPE

23 64 26 CHI LLED, CHI LLED- HOT, AND CONDENSER WATER PI PI NG SYSTEMS

23 82 02 UNI TARY HEATI NG AND COOLI NG EQUI PMENT

DI VI SI ON 25 - I NTEGRATED AUTOMATI ON

25 05 11 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS ( HVAC)

25 05 12 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS ( DMS)

25 05 13 CYBERSECURI TY FOR FACI LI TY- RELATED CONTROL SYSTEMS

(FA/MNS)

25 08 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM TESTI NG

25 10 10 UTI LI TY MONI TORI NG AND CONTROL SYSTEM ( UMCS) FRONT END

AND I NTEGRATI ON

DI VI SI ON 26 - ELECTRI CAL

26 00 00 BASI C ELECTRI CAL MATERI ALS AND METHODS

26 05 48 SEI SMI C PROTECTI ON FOR ELECTRI CAL EQUI PMENT

26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM

26 23 00 SWITCHBOARDS

26 28 01 COORDI NATED POWER SYSTEM PROTECTI ON

26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS

26 41 00 LI GHTNI NG PROTECTI ON SYSTEM

26 51 00 I NTERI OR LI GHTI NG

26 56 00 EXTERI OR LI GHTI NG

DI VI SI ON 27 - COMMUNI CATI ONS

27 05 14 CABLE TELEVI SI ON PREMI SES DI STRI BUTI ON SYSTEM

27 10 00 BUI LDI NG TELECOMMUNI CATI ONS CABLI NG SYSTEM

DI VI SI ON 28 - ELECTRONI C SAFETY AND SECURI TY

PROJECT TABLE OF CONTENTS Page 3

28 16 01 SMALL I NTRUSI ON DETECTI ON SYSTEM

28 20 01 DOOR MONI TORI NG SYSTEM

28 31 76 I NTERI OR FI RE ALARM AND MASS NOTI FI CATI ON SYSTEMS

DI VI SI ON 31 - EARTHWORK

31 00 00 EARTHWORK

31 05 19 GEOTEXTILE

31 11 00 CLEARI NG AND GRUBBI NG

31 31 16. 13 CHEMI CAL TERMI TE CONTROL

31 32 11 SOI L SURFACE EROSI ON CONTROL

DI VI SI ON 32 - EXTERI OR I MPROVEMENTS

32 01 19 FI ELD MOLDED SEALANTS FOR SEALI NG JOI NTS I N RI GI D

PAVEMENTS

32 05 33 LANDSCAPE ESTABLI SHMENT

32 11 16 BASE COURSE FOR RI GI D PAVI NG

32 11 23 AGGREGATE AND/ OR GRADED- CRUSHED AGGREGATE BASE COURSE

32 12 10 BI TUMI NOUS TACK AND PRI ME COATS

32 12 16 HOT- MI X ASPHALT ( HMA) FOR ROADS

32 13 13. 06 PORTLAND CEMENT CONCRETE PAVEMENT FOR ROADS AND SI TE

FACILITIES

32 16 19 CONCRETE CURBS, GUTTERS AND SI DEWALKS

32 17 23 PAVEMENT MARKI NGS

32 18 23. 39 SYNTHETI C RUNNI NG TRACK SURFACI NG

32 31 13 CHAI N LI NK FENCES AND GATES

32 32 23 SEGMENTAL CONCRETE BLOCK RETAI NI NG WALL

32 92 19 SEEDING

32 92 23 SODDING

32 93 00 EXTERI OR PLANTS

DI VI SI ON 33 - UTI LI TI ES

33 40 00 STORM DRAI NAGE UTI LI TI ES

33 46 16 SUBDRAI NAGE PI PI NG

33 51 15 NATURAL- GAS DI STRI BUTI ON

33 61 13. 13 PREFABRI CATED UNDERGROUND HYDRONI C ENERGY DI STRI BUTI ON

33 71 02 UNDERGROUND ELECTRI CAL DI STRI BUTI ON

33 82 00 TELECOMMUNI CATI ONS OUTSI DE PLANT ( OSP)

- - End of Pr oj ect Tabl e of Cont ent s - -

PROJECT TABLE OF CONTENTS Page 4

SECTI ON TABLE OF CONTENTS

DI VI SI ON 23 - HEATI NG, VENTI LATI NG, AND AI R CONDI TI ONI NG ( HVAC)

SECTI ON 23 00 00

AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

08/10

PART 1 GENERAL

1. 1 REFERENCES

1. 2 SYSTEM DESCRI PTI ON

1. 2. 1 Mechani cal Equi pment I dent i f i cat i on

1. 2. 2 Ser v i ce Label i ng

1. 2. 3 Col or Codi ng

1. 3 SUBMI TTALS

1. 4 QUALI TY ASSURANCE

1. 4. 1 Pr event i on of Cor r osi on

1. 4. 2 Asbest os Pr ohi bi t i on

1. 4. 3 Ozone Depl et i ng Subst ances Used as Ref r i ger ant s

1. 4. 4 Use of Ozone Depl et i ng Subst ances, Ot her t han Ref r i ger ant s

1. 4. 5 Det ai l Dr awi ngs

1. 4. 6 Test Pr ocedur es

1. 4. 7 Sust ai nabl e Desi gn Cer t i f i cat i on

1. 5 DELI VERY, STORAGE, AND HANDLI NG

PART 2 PRODUCTS

2. 1 STANDARD PRODUCTS

2. 2 I DENTI FI CATI ON PLATES

2. 3 EQUI PMENT GUARDS AND ACCESS

2. 4 ELECTRI CAL WORK

2. 5 ANCHOR BOLTS

2. 6 SEI SMI C ANCHORAGE

2. 7 PAI NTI NG

2. 8 I NDOOR AI R QUALI TY

2. 9 DUCT SYSTEMS

2. 9. 1 Met al Duct wor k

2. 9. 1. 1 I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s

2. 9. 1. 2 Gener al Ser vi ce Duct Connect or s

2. 9. 1. 3 Hi gh Temper at ur e Ser vi ce Duct Connect i ons

2. 9. 1. 4 Copper Sheet s

2. 9. 1. 5 Cor r osi on Resi st i ng ( St ai nl ess) St eel Sheet s

2. 9. 2 Duct Access Door s

2. 9. 3 Fi r e Damper s

2. 9. 4 Manual Bal anci ng Damper s

2. 9. 5 Ai r Suppl y And Exhaust Ai r Damper s

2. 9. 6 Ai r Def l ect or s and Br anch Connect i ons

2. 9. 7 Di f f user s, Regi st er s, and Gr i l l es

2. 9. 7. 1 Di f f user s

2. 9. 7. 2 Regi st er s and Gr i l l es

2. 9. 8 Louver s

2. 9. 9 Bi r d Scr eens and Fr ames

2. 10 AI R SYSTEMS EQUI PMENT

SECTI ON 23 00 00 Page 1

2. 10. 1 Fans

2. 10. 1. 1 Cent r i f ugal Fans

2. 10. 1. 2 I n- Li ne Cent r i f ugal Fans

2. 10. 2 Coi l s

2. 10. 3 Ai r Fi l t er s

2. 10. 3. 1 Ext ended Sur f ace Pl eat ed Panel Fi l t er s

2. 10. 3. 2 Car t r i dge Type Fi l t er s

2. 10. 3. 3 Hol di ng Fr ames

2. 10. 3. 4 Fi l t er Gauges

2. 11 AI R HANDLI NG UNI TS

2. 11. 1 Casi ngs

2. 11. 2 Fans

2. 11. 3 Access Sect i ons and Fi l t er / Mi x i ng Boxes

2. 12 TERMI NAL UNI TS

2. 12. 1 Room Fan- Coi l Uni t s

2. 12. 1. 1 Encl osur es

2. 12. 1. 2 Fans

2. 12. 1. 3 Coi l s

2. 12. 1. 4 Dr ai n Pans

2. 12. 1. 5 Manual l y Oper at ed Out si de Ai r Damper s

2. 12. 1. 6 Fi l t er s

2. 12. 1. 7 Mot or s

2. 12. 2 Var i abl e Ai r Vol ume ( VAV)

2. 12. 2. 1 Var i abl e Vol ume, Si ngl e Duct Ter mi nal Uni t s

2. 12. 2. 2 Reheat Uni t s

2. 13 DESI CCANT WHEEL

2. 14 FACTORY PAI NTI NG

2. 15 SUPPLEMENTAL COMPONENTS/ SERVI CES

2. 15. 1 Chi l l ed, Condenser , or Dual Ser vi ce Wat er Pi pi ng

2. 15. 2 Ref r i ger ant Pi pi ng

2. 15. 3 Wat er Heat i ng Syst em Accessor i es

2. 15. 4 Condensat e Dr ai n Li nes

2. 15. 5 Backf l ow Pr event er s

2. 15. 6 I nsul at i on

2. 15. 7 Cont r ol s

PART 3 EXECUTI ON

3. 1 EXAMI NATI ON

3. 2 I NSTALLATI ON

3. 2. 1 Condensat e Dr ai n Li nes

3. 2. 2 Equi pment and I nst al l at i on

3. 2. 3 Access Panel s

3. 2. 4 Fl exi bl e Duct

3. 2. 5 Met al Duct wor k

3. 2. 6 Dust Cont r ol

3. 2. 7 I nsul at i on

3. 2. 8 Duct Test Hol es

3. 2. 9 Power Tr ansmi ssi on Component s Adj ust ment

3. 3 EQUI PMENT PADS

3. 4 CUTTI NG AND PATCHI NG

3. 5 CLEANI NG

3. 6 PENETRATI ONS

3. 6. 1 Sl eeves

3. 6. 2 Fr amed Pr epar ed Openi ngs

3. 6. 3 I nsul at i on

3. 6. 4 Cl osur e Col l ar s

3. 6. 5 Fi r est oppi ng

3. 7 FI ELD PAI NTI NG OF MECHANI CAL EQUI PMENT

SECTI ON 23 00 00 Page 2

3. 7. 1 Temper at ur es l ess t han 120 degr ees F

3. 7. 2 Temper at ur es bet ween 120 and 400 degr ees F

3. 7. 3 Temper at ur es gr eat er t han 400 degr ees F

3. 7. 4 Fi ni sh Pai nt i ng

3. 7. 5 Col or Codi ng Scheme f or Locat i ng Hi dden Ut i l i t y Component s

3. 8 I DENTI FI CATI ON SYSTEMS

3. 9 DUCTWORK LEAK TEST

3. 10 DAMPER ACCEPTANCE TEST

3. 11 TESTI NG, ADJUSTI NG, AND BALANCI NG

3. 12 PERFORMANCE TESTS

3. 13 CLEANI NG AND ADJUSTI NG

3. 14 OPERATI ON AND MAI NTENANCE

3. 14. 1 Oper at i on and Mai nt enance Manual s

3. 14. 2 Oper at i on And Mai nt enance Tr ai ni ng

- - End of Sect i on Tabl e of Cont ent s - -

SECTI ON 23 00 00 Page 3

SECTI ON 23 00 00

AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS

08/10

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AI R MOVEMENT AND CONTROL ASSOCI ATI ON I NTERNATI ONAL, I NC. ( AMCA)

AMCA 201 ( 2002; R 2011) Fans and Syst ems

AMCA 210 ( 2016) Labor at or y Met hods of Test i ng Fans f or Aer odynami c Per f or mance Rat i ng

AMCA 300 ( 2014) Rever ber ant Room Met hod f or Sound Test i ng of Fans

AMCA 301 ( 2014) Met hods f or Cal cul at i ng Fan Sound Rat i ngs f r om Labor at or y Test Dat a

AI R- CONDI TI ONI NG, HEATI NG AND REFRI GERATI ON I NSTI TUTE ( AHRI )

AHRI 260 I - P ( 2012) Sound Rat i ng of Duct ed Ai r Movi ng and Condi t i oni ng Equi pment

AHRI 350 ( 2015) Sound Rat i ng of Non- Duct ed I ndoor Ai r - Condi t i oni ng Equi pment

AHRI 410 ( 2001; Addendum 1 2002; Addendum 2 2005;

Addendum 3 2011) For ced- Ci r cul at i on Ai r - Cool i ng and Ai r - Heat i ng Coi l s

AHRI 430 ( 2009) Cent r al - St at i on Ai r - Handl i ng Uni t s

AHRI 440 ( 2008) Per f or mance Rat i ng of Room Fan- Coi l s

AHRI 880 I - P ( 2011) Per f or mance Rat i ng of Ai r Ter mi nal s

AHRI 885 ( 2008; Addendum 2011) Pr ocedur e f or Est i mat i ng Occupi ed Space Sound Level s i n t he Appl i cat i on of Ai r Ter mi nal s and Ai r Outlets

AHRI Gui del i ne D ( 1996) Appl i cat i on and I nst al l at i on of Cent r al St at i on Ai r - Handl i ng Uni t s

AMERI CAN BEARI NG MANUFACTURERS ASSOCI ATI ON ( ABMA)

ABMA 11 ( 2014) Load Rat i ngs and Fat i gue Li f e f or Rol l er Bear i ngs

ABMA 9 ( 2015) Load Rat i ngs and Fat i gue Li f e f or

SECTI ON 23 00 00 Page 4

Bal l Bear i ngs

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 189. 1 ( 2014) St andar d f or t he Desi gn of Hi gh- Per f or mance Gr een Bui l di ngs Except Low- Ri se Resi dent i al Bui l di ngs

ASHRAE 52. 2 ( 2012) Met hod of Test i ng Gener al Vent i l at i on Ai r - Cl eani ng Devi ces f or Removal Ef f i c i ency by Par t i c l e Si ze

ASHRAE 62. 1 ( 2010) Vent i l at i on f or Accept abl e I ndoor Ai r Qual i t y

ASHRAE 68 ( 1997) Labor at or y Met hod of Test i ng t o Det er mi ne t he Sound Power I n a Duct

ASHRAE 70 ( 2006; R 2011) Met hod of Test i ng f or Rat i ng t he Per f or mance of Ai r Out l et s and Inlets

ASME I NTERNATI ONAL ( ASME)

ASME A13. 1 ( 2015) Scheme f or t he I dent i f i cat i on of Pi pi ng Syst ems

ASTM I NTERNATI ONAL ( ASTM)

ASTM A123/ A123M ( 2017) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s

ASTM A167 ( 2011) St andar d Speci f i cat i on f or St ai nl ess and Heat - Resi st i ng Chr omi um- Ni ckel St eel Pl at e, Sheet , and Strip

ASTM A53/ A53M ( 2018) St andar d Speci f i cat i on f or Pi pe, St eel , Bl ack and Hot - Di pped, Zi nc- Coat ed, Wel ded and Seaml ess

ASTM A924/ A924M ( 2018) St andar d Speci f i cat i on f or Gener al Requi r ement s f or St eel Sheet , Met al l i c- Coat ed by t he Hot - Di p Pr ocess

ASTM B117 ( 2016) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us

ASTM B152/ B152M ( 2013) St andar d Speci f i cat i on f or Copper Sheet , St r i p, Pl at e, and Rol l ed Bar

ASTM B766 ( 1986; R 2015) St andar d Speci f i cat i on f or El ect r odeposi t ed Coat i ngs of Cadmi um

ASTM C1071 ( 2016) St andar d Speci f i cat i on f or Fi br ous Gl ass Duct Li ni ng I nsul at i on ( Ther mal and Sound Absor bi ng Mat er i al )

SECTI ON 23 00 00 Page 5

ASTM C553 ( 2013) St andar d Speci f i cat i on f or Mi ner al Fi ber Bl anket Ther mal I nsul at i on f or Commer ci al and I ndust r i al Appl i cat i ons

ASTM D1654 ( 2008; R 2016; E 2017) St andar d Test Met hod f or Eval uat i on of Pai nt ed or Coat ed Speci mens Subj ect ed t o Cor r osi ve Environments

ASTM D3359 ( 2017) St andar d Test Met hods f or Rat i ng Adhesi on by Tape Test

ASTM D520 ( 2000; R 2011) Zi nc Dust Pi gment

ASTM E2016 ( 2015) St andar d Speci f i cat i on f or I ndust r i al Woven Wi r e Cl ot h

ASTM F1040 ( 1987; R 2007) St andar d Speci f i cat i on f or Fi l t er Uni t s, Ai r Condi t i oni ng, Vi scous - I mpi ngement and Dr y Types, Repl aceabl e

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

NEMA MG 1 ( 2016; SUPP 2016) Mot or s and Gener at or s

NEMA MG 10 ( 2017) Ener gy Management Gui de f or Sel ect i on and Use of Fi xed Fr equency Medi um AC Squi r r el - Cage Pol yphase I nduct i on Mot or s

NEMA MG 11 ( 1977; R 2012) Ener gy Management Gui de f or Sel ect i on and Use of Si ngl e Phase Mot or s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 701 ( 2015) St andar d Met hods of Fi r e Test s f or Fl ame Pr opagat i on of Text i l es and Fi l ms

NFPA 90A ( 2018) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems

SCI ENTI FI C CERTI FI CATI ON SYSTEMS ( SCS)

SCS SCS Gl obal Ser vi ces ( SCS) I ndoor Advant age

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1819 ( 2002) Fi r e, Smoke and Radi at i on Damper I nst al l at i on Gui de f or HVAC Syst ems, 5t h Edition

SMACNA 1966 ( 2005) HVAC Duct Const r uct i on St andar ds Met al and Fl exi bl e, 3r d Edi t i on

SMACNA 1972 CD ( 2012) HVAC Ai r Duct Leakage Test Manual - 2nd Edi t i on

SECTI ON 23 00 00 Page 6

SMACNA 1981 ( 2008) Sei smi c Rest r ai nt Manual Gui del i nes f or Mechani cal Syst ems, 3r d Edi t i on

U. S. DEPARTMENT OF DEFENSE ( DOD)

MIL-STD-101 ( 2014; Rev C) Col or Code f or Pi pel i nes and f or Compr essed Gas Cyl i nder s

U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)

40 CFR 82 Pr ot ect i on of St r at ospher i c Ozone

UL ENVI RONMENT ( ULE)

ULE Gr eenguar d UL Gr eenguar d Cer t i f i cat i on Pr ogr am

UNDERWRI TERS LABORATORI ES ( UL)

UL 181 ( 2013; Repr i nt Apr 2017) UL St andar d f or Saf et y Fact or y- Made Ai r Duct s and Ai r Connectors

UL 1995 ( 2015) UL St andar d f or Saf et y Heat i ng and Cool i ng Equi pment

UL 555 ( 2006; Repr i nt Aug 2016) UL St andar d f or Saf et y Fi r e Damper s

UL 586 ( 2009; Repr i nt Dec 2017) St andar d f or Hi gh- Ef f i c i ency Par t i cul at e, Ai r Fi l t er Units

UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel

UL 705 ( 2017; Repr i nt Feb 2018) UL St andar d f or Saf et y Power Vent i l at or s

UL 900 ( 2015) St andar d f or Ai r Fi l t er Uni t s

UL 94 ( 2013; Repr i nt Sep 2017) UL St andar d f or Saf et y Test s f or Fl ammabi l i t y of Pl ast i c Mat er i al s f or Par t s i n Devi ces and Appliances

UL Bl d Mat Di r ( updat ed cont i nuousl y onl i ne) Bui l di ng Mat er i al s Di r ect or y

UL El ect r i cal Const r uct n ( 2012) El ect r i cal Const r uct i on Equi pment Directory

UL Fi r e Resi st ance ( 2014) Fi r e Resi st ance Di r ect or y

1. 2 SYSTEM DESCRI PTI ON

Fur ni sh duct wor k, pi pi ng of f set s, f i t t i ngs, and accessor i es as r equi r ed t o pr ovi de a compl et e i nst al l at i on. Coor di nat e t he wor k of t he di f f er ent t r ades t o avoi d i nt er f er ence bet ween pi pi ng, equi pment , st r uct ur al , and el ect r i cal wor k. Pr ovi de compl et e, i n pl ace, al l necessar y of f set s i n

SECTI ON 23 00 00 Page 7 pi pi ng and duct wor k, and al l f i t t i ngs, and ot her component s, r equi r ed t o i nst al l t he wor k as i ndi cat ed and speci f i ed.

1. 2. 1 Mechani cal Equi pment I dent i f i cat i on

The number of char t s and di agr ams shal l be equal t o or gr eat er t han t he number of mechani cal equi pment r ooms. Wher e mor e t han one char t or di agr am per space i s r equi r ed, mount t hese i n edge pi vot ed, swi ngi ng l eaf , ext r uded al umi num f r ame hol der s whi ch open t o 170 degr ees.

Pr ovi de char t l i s t i ng of equi pment by desi gnat i on number s and capaci t i es such as f l ow r at es, pr essur e and t emper at ur e di f f er ences, heat i ng and cool i ng capaci t i es, hor sepower , pi pe s i zes, and vol t age and cur r ent characteristics.

1. 2. 2 Ser vi ce Label i ng

Label equi pment , i ncl udi ng f ans, ai r handl er s, t er mi nal uni t s, et c. wi t h l abel s made of sel f - st i ck i ng, pl ast i c f i l m desi gned f or per manent i nst al l at i on. Label s shal l be i n accor dance wi t h t he equi pment schedul es on t he cont r act dr awi ngs.

I dent i f y s i mi l ar ser vi ces wi t h di f f er ent t emper at ur es or pr essur es. Wher e pr essur es coul d exceed 125 pounds per squar e i nch, gage, i ncl ude t he maxi mum syst em pr essur e i n t he l abel . Label and ar r ow pi pi ng i n accor dance wi t h t he f ol l owi ng:

a. Each poi nt of ent r y and exi t of pi pe passi ng t hr ough wal l s.

b. Each change i n di r ect i on, i . e. , el bows, t ees.

c. I n congest ed or hi dden ar eas and at al l access panel s at each poi nt r equi r ed t o c l ar i f y ser vi ce or i ndi cat ed hazar d.

d. I n l ong st r ai ght r uns, l ocat e l abel s at di st ances wi t hi n eyesi ght of each ot her not t o exceed 75 f eet . Al l l abel s shal l be v i s i bl e and l egi bl e f r om t he pr i mar y ser vi ce and oper at i ng ar ea.

For Bar e or I nsul at ed Pi pes f or Out si de Di amet er s of Lettering

1/ 2 t hr u 1- 3/ 8 i nch 1/ 2 i nch

1- 1/ 2 t hr u 2- 3/ 8 i nch 3/ 4 i nch

2- 1/ 2 i nch and l ar ger 1- 1/ 4 i nch

1. 2. 3 Col or Codi ng

Col or codi ng of al l pi pi ng syst ems shal l be i n accor dance wi t h ASME A13. 1 or MIL-STD-101 .

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce

SECTI ON 23 00 00 Page 8 t hat wi l l r evi ew t he submi t t al f or t he Gover nment . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Det ai l Dr awi ngs; G, RO

SD- 03 Pr oduct Dat a

I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s Duct Connect or s Duct Access Door s Fi r e Damper s Manual Bal anci ng Damper s Diffusers Regi st er s and Gr i l l es Louvers Cent r i f ugal Fans; G, RO I n- Li ne Cent r i f ugal Fans; G, RO Ai r Handl i ng Uni t s; G, RO Room Fan- Coi l Uni t s; G, RO Var i abl e Vol ume, Si ngl e Duct Ter mi nal Uni t s; G, RO Reheat Uni t s; G, RO Desi ccant Wheel ; G, RO

SD- 06 Test Repor t s

Certification Test Pr ocedur es Per f or mance Test s; G, RO Damper Accept ance Test

SD- 08 Manuf act ur er ' s I nst r uct i ons

Manuf act ur er ' s I nst al l at i on I nst r uct i ons; G, RO Oper at i on and Mai nt enance Tr ai ni ng; G, RO

SD- 10 Oper at i on and Mai nt enance Dat a

Oper at i on and Mai nt enance Manual s; G, RO Fi r e Damper s Manual Bal anci ng Damper s Cent r i f ugal Fans; G, RO I n- Li ne Cent r i f ugal Fans; G, RO Ai r Handl i ng Uni t s; G, RO Room Fan- Coi l Uni t s; G, RO Var i abl e Vol ume, Si ngl e Duct Ter mi nal Uni t s; G, RO Desi ccant Wheel ; G, RO

1. 4 QUALI TY ASSURANCE

Except as ot her wi se speci f i ed, appr oval of mat er i al s and equi pment i s based on manuf act ur er ' s publ i shed dat a.

a. Wher e mat er i al s and equi pment ar e speci f i ed t o conf or m t o t he st andar ds of t he Under wr i t er s Labor at or i es, t he l abel of or l i s t i ng wi t h r eexami nat i on i n UL Bl d Mat Di r , and UL 6 i s accept abl e as suf f i c i ent evi dence t hat t he i t ems conf or m t o Under wr i t er s Labor at or i es r equi r ement s. I n l i eu of such l abel or l i s t i ng, submi t a wr i t t en

SECTI ON 23 00 00 Page 9 cer t i f i cat e f r om any nat i onal l y r ecogni zed t est i ng agency, adequat el y equi pped and compet ent t o per f or m such ser vi ces, s t at i ng t hat t he i t ems have been t est ed and t hat t he uni t s conf or m t o t he speci f i ed r equi r ement s. Out l i ne met hods of t est i ng used by t he speci f i ed agencies.

b. Wher e mat er i al s or equi pment ar e speci f i ed t o be const r uct ed or t est ed, or bot h, i n accor dance wi t h t he st andar ds of t he ASTM I nt er nat i onal ( ASTM) , t he ASME I nt er nat i onal ( ASME) , or ot her st andar ds, a manuf act ur er ' s cer t i f i cat e of compl i ance of each i t em i s accept abl e as pr oof of compl i ance.

c. Conf or mance t o such agency r equi r ement s does not r el i eve t he i t em f r om compl i ance wi t h ot her r equi r ement s of t hese speci f i cat i ons.

1. 4. 1 Pr event i on of Cor r osi on

Pr ot ect met al l i c mat er i al s agai nst cor r osi on. Manuf act ur er shal l pr ovi de r ust - i nhi bi t i ng t r eat ment and st andar d f i ni sh f or t he equi pment encl osur es. Do not use al umi num i n cont act wi t h ear t h, and wher e connect ed t o di ssi mi l ar met al . Pr ot ect al umi num by appr oved f i t t i ngs, bar r i er mat er i al , or t r eat ment . Fer r ous par t s such as anchor s, bol t s, br aces, boxes, bodi es, c l amps, f i t t i ngs, guar ds, nut s, pi ns, r ods, shi ms, t hi mbl es, washer s, and mi scel l aneous par t s not of cor r osi on- r esi st ant st eel or nonf er r ous mat er i al s shal l be hot - di p gal vani zed i n accor dance wi t h ASTM A123/ A123M f or ext er i or l ocat i ons and cadmi um- pl at ed i n conf or mance with ASTM B766 f or i nt er i or l ocat i ons.

1. 4. 2 Asbest os Pr ohi bi t i on

Do not use asbest os and asbest os- cont ai ni ng pr oduct s.

1. 4. 3 Ozone Depl et i ng Subst ances Used as Ref r i ger ant s

Mi ni mi ze r el eases of Ozone Depl et i ng Subst ances ( ODS) dur i ng r epai r , mai nt enance, ser vi c i ng or di sposal of appl i ances cont ai ni ng ODS' s by compl yi ng wi t h al l appl i cabl e sect i ons of 40 CFR 82 Par t 82 Subpar t F. Any per son conduct i ng r epai r , mai nt enance, ser vi c i ng or di sposal of appl i ances owned by NASA shal l compl y wi t h t he f ol l owi ng:

a. Do not knowi ngl y vent or ot her wi se r el ease i nt o t he envi r onment , Cl ass I or Cl ass I I subst ances used as a r ef r i ger ant .

b. Do not open appl i ances wi t hout meet i ng t he r equi r ement s of 40 CFR 82 Par t 82. 156 Subpar t F, r egar di ng r equi r ed pr act i ces f or evacuat i on and col l ect i on of r ef r i ger ant , and 40 CFR 82 Par t 82. 158 Subpar t F, r egar di ng st andar ds of r ecycl i ng and r ecover y equi pment .

c. Onl y per sons who compl y wi t h 40 CFR 82 Par t 82. 161 Subpar t F, r egar di ng t echni c i an cer t i f i cat i on, can conduct wor k on appl i ances cont ai ni ng refrigerant.

I n addi t i on, pr ovi de copi es of al l appl i cabl e cer t i f i cat i ons t o t he Cont r act i ng Of f i cer at l east 14 cal endar days pr i or t o i ni t i at i ng mai nt enance, r epai r , ser vi c i ng, di smant l i ng or di sposal of appl i ances, including:

a. Pr oof of Techni c i an Cer t i f i cat i on

SECTI ON 23 00 00 Page 10

b. Pr oof of Equi pment Cer t i f i cat i on f or r ecover y or r ecycl i ng equi pment .

c. Pr oof of avai l abi l i t y of cer t i f i ed r ecover y or r ecycl i ng equi pment .

1. 4. 4 Use of Ozone Depl et i ng Subst ances, Ot her t han Ref r i ger ant s

The use of Cl ass I or Cl ass I I ODS' s l i s t ed as nonessent i al i n 40 CFR 82 Par t 82. 66 Subpar t C i s pr ohi bi t ed. These pr ohi bi t ed mat er i al s and uses include:

a. Any pl ast i c par t y spr ay st r eamer or noi se hor n whi ch i s pr opel l ed by a chlorofluorocarbon

b. Any c l eani ng f l ui d f or el ect r oni c and phot ogr aphi c equi pment whi ch cont ai ns a chl or of l uor ocar bon; i ncl udi ng l i qui d packagi ng, sol vent wi pes, sol vent spr ays, and gas spr ays.

c. Any pl ast i c f l exi bl e or packagi ng f oam pr oduct whi ch i s manuf act ur ed wi t h or cont ai ns a chl or of l uor ocar bon, i ncl udi ng, open cel l f oam, open cel l r i gi d pol yur et hane pour ed f oam, c l osed cel l ext r uded pol yst yr ene sheet f oam, c l osed cel l pol yet hyl ene f oam and cl osed cel l pol ypr opyl ene f oam except f or f l exi bl e or packagi ng f oam used i n coaxi al cabl i ng.

d. Any aer osol pr oduct or ot her pr essur i zed di spenser whi ch cont ai ns a chl or of l uor ocar bon, except f or t hose l i s t ed i n 40 CFR 82 Par t 82. 66 Subpar t C.

Request a wai ver i f a f aci l i t y r equi r ement di ct at es t hat a pr ohi bi t ed mat er i al i s necessar y t o achi eve pr oj ect goal s. Submi t t he wai ver r equest i n wr i t i ng t o t he Cont r act i ng Of f i cer . The wai ver wi l l be eval uat ed and dispositioned.

1. 4. 5 Det ai l Dr awi ngs

Submi t det ai l dr awi ngs showi ng equi pment l ayout , i ncl udi ng assembl y and i nst al l at i on det ai l s and el ect r i cal connect i on di agr ams; duct wor k l ayout showi ng t he l ocat i on of al l suppor t s and hanger s, t ypi cal hanger det ai l s , gauge r ei nf or cement , r ei nf or cement spaci ng r i gi di t y c l assi f i cat i on, and st at i c pr essur e and seal c l assi f i cat i ons. I ncl ude any i nf or mat i on r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and f unct i ons pr oper l y as a uni t on t he dr awi ngs and show equi pment r el at i onshi p t o ot her par t s of t he wor k, i ncl udi ng c l ear ances r equi r ed f or oper at i on and mai nt enance.

Submi t dr awi ngs showi ng bol t - set t i ng i nf or mat i on, and f oundat i on bol t s pr i or t o concr et e f oundat i on const r uct i on f or al l equi pment i ndi cat ed or r equi r ed t o have concr et e f oundat i ons. Submi t f unct i on desi gnat i on of t he equi pment and any ot her r equi r ement s speci f i ed t hr oughout t hi s Sect i on wi t h t he shop dr awi ngs.

1. 4. 6 Test Pr ocedur es

Submi t pr oposed t est pr ocedur es and t est schedul es f or t he per f or mance t est s of syst ems, at l east 2 weeks pr i or t o t he st ar t of r el at ed t est i ng.

1. 4. 7 Sust ai nabl e Desi gn Certification

Pr oduct shal l be t hi r d par t y cer t i f i ed i n accor dance wi t h ULE Gr eenguar d, SCS, or equal .

SECTI ON 23 00 00 Page 11

1. 5 DELI VERY, STORAGE, AND HANDLI NG

Pr ot ect st or ed equi pment at t he j obsi t e f r om t he weat her , humi di t y and t emper at ur e var i at i ons, di r t and dust , or ot her cont ami nant s.

Addi t i onal l y, cap or pl ug al l pi pes unt i l i nst al l ed.

PART 2 PRODUCTS

2. 1 STANDARD PRODUCTS

Pr ovi de component s and equi pment t hat ar e " st andar d pr oduct s" of a manuf act ur er r egul ar l y engaged i n t he manuf act ur i ng of pr oduct s t hat ar e of a s i mi l ar mat er i al , desi gn and wor kmanshi p. " St andar d pr oduct s" i s def i ned as bei ng i n sat i sf act or y commer ci al or i ndust r i al use f or 2 year s bef or e bi d openi ng, i nc l udi ng appl i cat i ons of component s and equi pment under s i mi l ar c i r cumst ances and of s i mi l ar s i ze, sat i sf act or i l y compl et ed by a pr oduct t hat i s sol d on t he commer ci al mar ket t hr ough adver t i sement s, manuf act ur er s ' cat al ogs, or br ochur es. Pr oduct s havi ng l ess t han a 2- year f i el d ser vi ce r ecor d ar e accept abl e i f a cer t i f i ed r ecor d of sat i sf act or y f i el d oper at i on, f or not l ess t han 6000 hour s excl usi ve of t he manuf act ur er ' s f act or y t est s, can be shown. Pr ovi de equi pment i t ems t hat ar e suppor t ed by a ser vi ce or gani zat i on. Wher e appl i cabl e, pr ovi de equi pment t hat i s an ENERGY STAR Qual i f i ed pr oduct or a Feder al Ener gy Management Pr ogr am ( FEMP) desi gnat ed pr oduct .

2. 2 I DENTI FI CATI ON PLATES

I n addi t i on t o st andar d manuf act ur er ' s i dent i f i cat i on pl at es, pr ovi de engr aved l ami nat ed phenol i c i dent i f i cat i on pl at es f or each pi ece of mechani cal equi pment . I dent i f i cat i on pl at es ar e t o desi gnat e t he f unct i on of t he equi pment . Submi t desi gnat i on wi t h t he shop dr awi ngs.

I dent i f i cat i on pl at es shal l be t hr ee l ayer s, bl ack- whi t e- bl ack, engr aved t o show whi t e l et t er s on bl ack backgr ound. Let t er s shal l be upper case.

I dent i f i cat i on pl at es 1- 1/ 2- i nches hi gh and smal l er shal l be 1/ 16- i nch t hi ck, wi t h engr aved l et t er i ng 1/ 8- i nch hi gh; i dent i f i cat i on pl at es l ar ger than 1- 1/ 2- i nches hi gh shal l be 1/ 8- i nch t hi ck, wi t h engr aved l et t er i ng of sui t abl e hei ght . I dent i f i cat i on pl at es 1- 1/ 2- i nches hi gh and l ar ger shal l have bevel ed edges. I nst al l i dent i f i cat i on pl at es usi ng a compat i bl e adhesive.

2. 3 EQUI PMENT GUARDS AND ACCESS

Ful l y encl ose or guar d bel t s, pul l eys, chai ns, gear s, coupl i ngs, pr oj ect i ng set scr ews, keys, and ot her r ot at i ng par t s exposed t o per sonnel cont act accor di ng t o OSHA r equi r ement s. Pr oper l y guar d or cover wi t h i nsul at i on of a t ype speci f i ed, hi gh t emper at ur e equi pment and pi pi ng exposed t o cont act by per sonnel or wher e i t cr eat es a pot ent i al f i r e hazar d. The r equi r ement s f or l adder s, and guar dr ai l s ar e speci f i ed i n Sect i on 05 50 13 MI SCELLANEOUS

METAL FABRI CATI ONS.

2. 4 ELECTRI CAL WORK

a. Pr ovi de mot or s, cont r ol l er s, i nt egr al di sconnect s, cont act or s, and cont r ol s wi t h t hei r r espect i ve pi eces of equi pment , except cont r ol l er s i ndi cat ed as par t of mot or cont r ol cent er s. Pr ovi de el ect r i cal equi pment , i ncl udi ng mot or s and wi r i ng, as speci f i ed i n Sect i on 26 20 00 I NTERI OR DI STRI BUTI ON SYSTEM. Pr ovi de manual or aut omat i c cont r ol and pr ot ect i ve or s i gnal devi ces r equi r ed f or t he oper at i on speci f i ed and cont r ol wi r i ng r equi r ed f or cont r ol s and devi ces speci f i ed, but not

SECTI ON 23 00 00 Page 12 shown. For packaged equi pment , i ncl ude manuf act ur er pr ovi ded cont r ol l er s wi t h t he r equi r ed moni t or s and t i med r est ar t .

b. For s i ngl e- phase mot or s, pr ovi de hi gh- ef f i c i ency t ype, f r act i onal - hor sepower al t er nat i ng- cur r ent mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em, i n accor dance wi t h NEMA MG 11. I nt egr al s i ze mot or s shal l be t he pr emi um ef f i c i ency t ype i n accor dance wi t h NEMA MG 1.

c. For pol yphase mot or s, pr ovi de squi r r el - cage medi um i nduct i on mot or s, i ncl udi ng mot or s t hat ar e par t of a syst em , and t hat meet t he ef f i c i ency r at i ngs f or pr emi um ef f i c i ency mot or s i n accor dance wi t h NEMA MG 1. Sel ect pr emi um ef f i c i ency pol yphase mot or s i n accor dance with NEMA MG 10.

d. Pr ovi de mot or s i n accor dance wi t h NEMA MG 1 and of suf f i c i ent s i ze t o dr i ve t he l oad at t he speci f i ed capaci t y wi t hout exceedi ng t he namepl at e r at i ng of t he mot or . Pr ovi de mot or s r at ed f or cont i nuous dut y wi t h t he encl osur e speci f i ed. Pr ovi de mot or dut y t hat al l ows f or maxi mum f r equency st ar t - st op oper at i on and mi ni mum encount er ed i nt er val bet ween st ar t and st op. Pr ovi de mot or t or que capabl e of accel er at i ng t he connect ed l oad wi t hi n 20 seconds wi t h 80 per cent of t he r at ed vol t age mai nt ai ned at mot or t er mi nal s dur i ng one st ar t i ng per i od.

Pr ovi de mot or st ar t er s compl et e wi t h t her mal over l oad pr ot ect i on and ot her necessar y appur t enances. Fi t mot or bear i ngs wi t h gr ease suppl y f i t t i ngs and gr ease r el i ef t o out s i de of t he encl osur e.

e. Wher e t wo- speed or var i abl e- speed mot or s ar e i ndi cat ed, sol i d- st at e var i abl e- speed cont r ol l er s ar e al l owed t o accompl i sh t he same f unct i on. Use sol i d- st at e var i abl e- speed cont r ol l er s f or mot or s r at ed 10 hp or l ess and adj ust abl e f r equency dr i ves f or l ar ger mot or s.

Pr ovi de var i abl e f r equency dr i ves f or mot or s as speci f i ed i n Sect i on

26 29 23 VARI ABLE FREQUENCY DRI VE SYSTEMS UNDER 600 VOLTS.

2. 5 ANCHOR BOLTS

Pr ovi de anchor bol t s f or equi pment pl aced on concr et e equi pment pads or on concr et e s l abs. Bol t s t o be of t he s i ze and number r ecommended by t he equi pment manuf act ur er and l ocat ed by means of sui t abl e t empl at es.

I nst al l at i on of anchor bol t s shal l not degr ade t he sur r oundi ng concr et e.

2. 6 SEI SMI C ANCHORAGE

Anchor equi pment i n accor dance wi t h appl i cabl e sei smi c cr i t er i a f or t he ar ea and as def i ned i n SMACNA 1981

2. 7 PAINTING

Pai nt equi pment uni t s i n accor dance wi t h appr oved equi pment manuf act ur er ' s st andar ds unl ess speci f i ed ot her wi se. Fi el d r et ouch onl y i f appr oved.

Ot her wi se, r et ur n equi pment t o t he f act or y f or r ef i ni shi ng.

2. 8 I NDOOR AI R QUALI TY

Pr ovi de equi pment and component s t hat compl y wi t h t he r equi r ement s of ASHRAE 62. 1 unl ess mor e st r i ngent r equi r ement s ar e speci f i ed her ei n.

SECTI ON 23 00 00 Page 13

2. 9 DUCT SYSTEMS

2. 9. 1 Met al Duct wor k

Pr ovi de met al duct wor k const r uct i on, i ncl udi ng al l f i t t i ngs and component s, t hat compl i es wi t h SMACNA 1966, as suppl ement ed and modi f i ed by t hi s specification.

a. Pr ovi de r adi us t ype el bows wi t h a cent er l i ne r adi us of 1. 5 t i mes t he wi dt h or di amet er of t he duct wher e space per mi t s. Ot her wi se, el bows havi ng a mi ni mum r adi us equal t o t he wi dt h or di amet er of t he duct or squar e el bows wi t h f act or y f abr i cat ed t ur ni ng vanes ar e al l owed.

b. Pr ovi de duct wor k t hat meet s t he r equi r ement s of Seal Cl ass A. Pr ovi de duct wor k i n VAV syst ems upst r eam of t he VAV boxes t hat meet s t he r equi r ement s of Seal Cl ass A.

c. Pr ovi de seal ant s t hat conf or m t o f i r e hazar d c l assi f i cat i on speci f i ed i n Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS and ar e sui t abl e f or t he r ange of ai r di s t r i but i on and ambi ent t emper at ur es t o whi ch i t i s exposed. Do not use pr essur e sensi t i ve t ape as a seal ant .

d. Make spi r al l ock seam duct , and f l at oval wi t h duct seal ant and l ock wi t h not l ess t han 3 equal l y spaced dr i ve scr ews or ot her appr oved met hods i ndi cat ed i n SMACNA 1966. Appl y t he seal ant t o t he exposed mal e par t of t he f i t t i ng col l ar so t hat t he seal er i s on t he i nsi de of t he j oi nt and f ul l y pr ot ect ed by t he met al of t he duct f i t t i ng. Appl y one br ush coat of t he seal ant over t he out s i de of t he j oi nt t o at l east 2 i nch band wi dt h cover i ng al l scr ew heads and j oi nt gap. Dent s i n t he mal e por t i on of t he s l i p f i t t i ng col l ar ar e not accept abl e. Fabr i cat e out door ai r i nt ake duct s and pl enums wi t h wat er t i ght sol der ed or br azed j oi nt s and seams.

2. 9. 1. 1 I nsul at ed Nonmet al l i c Fl exi bl e Duct Runout s

Use f l exi bl e duct r unout s onl y wher e i ndi cat ed. Runout l engt h i s i ndi cat ed on t he dr awi ngs, and i s not t o exceed 5 f eet . Pr ovi de r unout s t hat ar e pr ei nsul at ed, f act or y f abr i cat ed, and t hat compl y wi t h NFPA 90A and UL 181.

Pr ovi de ei t her f i el d or f act or y appl i ed vapor bar r i er . Pr ovi de not l ess than 20 ounce gl ass f abr i c duct connect or s coat ed on bot h s i des wi t h neopr ene. Wher e coi l i nduct i on or hi gh vel oci t y uni t s ar e suppl i ed wi t h ver t i cal ai r i nl et s, use a st r eaml i ned, vaned and mi t er ed el bow t r ansi t i on pi ece f or connect i on t o t he f l exi bl e duct or hose. Pr ovi de a di e- st amped el bow and not a f l exi bl e connect or as t he l ast el bow t o t hese uni t s ot her t han t he ver t i cal ai r i nl et t ype. I nsul at ed f l exi bl e connect or s ar e al l owed as r unout s. Pr ovi de i nsul at ed mat er i al and vapor bar r i er t hat conf or m t o t he r equi r ement s of Sect i on 23 07 00 THERMAL I NSULATI ON FOR MECHANI CAL SYSTEMS. Do not expose t he i nsul at i on mat er i al sur f ace t o t he ai r st r eam.

2. 9. 1. 2 Gener al Ser vi ce Duct Connect or s

Pr ovi de a f l exi bl e duct connect or appr oxi mat el y 6 i nches i n wi dt h wher e sheet met al connect i ons ar e made t o f ans or wher e duct s of di ssi mi l ar met al s ar e connect ed. For r ound/ oval duct s, secur e t he f l exi bl e mat er i al by st ai nl ess st eel or z i nc- coat ed, i r on c l i nch- t ype dr aw bands. For r ect angul ar duct s, i nst al l t he f l exi bl e mat er i al l ocked t o met al col l ar s usi ng nor mal duct const r uct i on met hods. Pr ovi de a composi t e connect or syst em t hat compl i es wi t h NFPA 701 and i s c l assi f i ed as " f l ame- r et ar dent

SECTI ON 23 00 00 Page 14 f abr i cs" i n UL Bl d Mat Di r .

2. 9. 1. 3 Hi gh Temper at ur e Ser vi ce Duct Connect i ons

Pr ovi de mat er i al t hat i s appr oxi mat el y 3/ 32 i nch t hi ck, 35 t o 40- ounce per squar e yar d wei ght , pl ai n weave f i br ous gl ass c l ot h wi t h, ni ckel / chr ome wi r e r ei nf or cement f or ser vi ce i n excess of 1200 degr ees F.

2. 9. 1. 4 Copper Sheet s

ASTM B152/ B152M, l i ght col d r ol l ed t emper .

2. 9. 1. 5 Cor r osi on Resi st i ng ( St ai nl ess) St eel Sheet s

ASTM A167

2. 9. 2 Duct Access Door s

Pr ovi de hi nged access door s conf or mi ng t o SMACNA 1966 i n duct wor k and pl enums wher e i ndi cat ed and at al l ai r f l ow measur i ng pr i mar i es, aut omat i c damper s, f i r e damper s, coi l s , t her most at s, and ot her appar at us r equi r i ng ser vi ce and i nspect i on i n t he duct syst em. Pr ovi de access door s upst r eam and downst r eam of ai r f l ow measur i ng pr i mar i es and heat i ng and cool i ng coi l s. Pr ovi de door s t hat ar e a mi ni mum 15 by 18 i nches, unl ess ot her wi se shown. Wher e duct s i ze does not accommodat e t hi s s i ze door , make t he door s as l ar ge as pr act i cabl e. Equi p door s 24 by 24 i nches or l ar ger wi t h f ast ener s oper abl e f r om i nsi de and out s i de t he duct . Use i nsul at ed t ype door s i n i nsul at ed duct s.

2. 9. 3 Fi r e Damper s

Use 1. 5 hour r at ed f i r e damper s unl ess ot her wi se i ndi cat ed. Pr ovi de f i r e damper s t hat conf or m t o t he r equi r ement s of NFPA 90A and UL 555. Per f or m t he f i r e damper t est as out l i ned i n NFPA 90A. Pr ovi de a pr essur e r el i ef door upst r eam of t he f i r e damper . I f t he duct wor k connect ed t o t he f i r e damper i s t o be i nsul at ed t hen pr ovi de a f act or y i nst al l ed pr essur e r el i ef damper . Pr ovi de aut omat i c oper at i ng f i r e damper s wi t h a dynami c r at i ng sui t abl e f or t he maxi mum ai r vel oci t y and pr essur e di f f er ent i al t o whi ch i t i s subj ect ed. Pr ovi de f i r e damper s appr oved f or t he speci f i c appl i cat i on, and i nst al l accor di ng t o t hei r l i s t i ng. Equi p f i r e damper s wi t h a st eel s l eeve or adequat el y s i zed f r ame i nst al l ed i n such a manner t hat di sr upt i on of t he at t ached duct wor k, i f any, does not i mpai r t he oper at i on of t he damper . Equi p s l eeves or f r ames wi t h per i met er mount i ng angl es at t ached on bot h s i des of t he wal l or f l oor openi ng. Const r uct duct wor k i n f i r e- r at ed f l oor - cei l i ng or r oof - cei l i ng assembl y syst ems wi t h ai r duct s t hat pi er ce t he cei l i ng of t he assembl i es i n conf or mance wi t h UL Fi r e Resi st ance.

Pr ovi de cur t ai n t ype wi t h damper bl ades out of t he ai r st r eam or s i ngl e bl ade t ype f i r e damper s. I nst al l damper s t hat do not r educe t he duct or t he ai r t r ansf er openi ng cr oss- sect i onal ar ea. I nst al l damper s so t hat t he cent er l i ne of t he damper dept h or t hi ckness i s l ocat ed i n t he cent er l i ne of t he wal l , par t i t i on or f l oor s l ab dept h or t hi ckness. Unl ess ot her wi se i ndi cat ed, compl y wi t h t he i nst al l at i on det ai l s gi ven i n SMACNA 1819 and i n manuf act ur er ' s i nst r uct i ons f or f i r e damper s. Per f or m accept ance t est i ng of f i r e damper s accor di ng t o par agr aph Fi r e Damper Accept ance Test and

NFPA 90A.

2. 9. 4 Manual Bal anci ng Damper s

Fur ni sh manual bal anci ng damper s wi t h accessi bl e oper at i ng mechani sms. Use

SECTI ON 23 00 00 Page 15 chr omi um pl at ed oper at or s ( wi t h al l exposed edges r ounded) i n f i ni shed por t i ons of t he bui l di ng. Pr ovi de manual vol ume cont r ol damper s t hat ar e oper at ed by l ocki ng- t ype quadr ant oper at or s. I nst al l damper s t hat ar e 2 gauges heavi er t han t he duct i n whi ch i nst al l ed. Unl ess ot her wi se i ndi cat ed, pr ovi de opposed bl ade t ype mul t i l eaf damper s wi t h maxi mum bl ade wi dt h of 12 i nches. Pr ovi de access door s or panel s f or al l conceal ed damper oper at or s and l ocki ng set scr ews. Pr ovi de st and- of f mount i ng br acket s, bases, or adapt er s not l ess t han t he t hi ckness of t he i nsul at i on when t he l ocki ng- t ype quadr ant oper at or s f or damper s ar e i nst al l ed on duct s t o be t her mal l y i nsul at ed, t o pr ovi de c l ear ance bet ween t he duct sur f ace and t he oper at or . St and- of f mount i ng i t ems shal l be i nt egr al wi t h t he oper at or or st andar d accessor y of t he damper manuf act ur er .

2. 9. 5 Ai r Suppl y And Exhaust Ai r Damper s Pr ovi de out door ai r suppl y and exhaust ai r damper s t hat have a maxi mum l eakage r at e when t est ed i n accor dance wi t h AMCA 500- D as r equi r ed by ASHRAE 90. 1 - SI ASHRAE 90. 1 - I P, i ncl udi ng maxi mum Damper Leakage f or :

a. Cl i mat e Zones 1, 2, 6, 7, 8 t he maxi mum damper l eakage at 250 Pa 1. 0 i nch

w. g. f or mot or i zed damper s i s 20 L/ s per squar e m 4 cf m per squar e f oot of damper ar ea and non- mot or i zed damper s ar e not al l owed.

b. Al l ot her Cl i mat e Zones t he maxi mum damper l eakage at 250 Pa 1. 0 i nch

w. g. i s 50 L/ s per squar e m 10 cf m per squar e f oot and f or non- mot or i zed damper s i s 100 L/ s per squar e m 20 cf m per squar e f oot of damper ar ea.

Damper s smal l er t han 600 mm 24 i nches i n ei t her di r ect i on may have l eakage of 200 L/ s per squar e m 40 cf m per squar e f oot .

2. 9. 6 Ai r Def l ect or s and Br anch Connect i ons

Pr ovi de ai r def l ect or s at al l duct mount ed suppl y out l et s, at t akeof f or ext ensi on col l ar s t o suppl y out l et s, at duct br anch t akeof f connect i ons, and at 90 degr ee el bows, as wel l as at l ocat i ons as i ndi cat ed on t he dr awi ngs or ot her wi se speci f i ed. Coni cal br anch connect i ons or 45 degr ee ent r y connect i ons ar e al l owed i n l i eu of def l ect or s f or br anch connect i ons. Fur ni sh al l ai r def l ect or s, except t hose i nst al l ed i n 90 degr ee el bows, wi t h an appr oved means of adj ust ment . Pr ovi de easi l y accessi bl e means f or adj ust ment i nsi de t he duct or f r om an adj ust ment wi t h st ur dy l ock on t he f ace of t he duct . When i nst al l ed on duct s t o be t her mal l y i nsul at ed, pr ovi de ext er nal adj ust ment s wi t h st and- of f mount i ng br acket s, i nt egr al wi t h t he adj ust ment devi ce, t o pr ovi de c l ear ance bet ween t he duct sur f ace and t he adj ust ment devi ce not l ess t han t he t hi ckness of t he t her mal i nsul at i on. Pr ovi de f act or y- f abr i cat ed ai r def l ect or s consi st i ng of cur ved t ur ni ng vanes or l ouver bl ades desi gned t o pr ovi de uni f or m ai r di st r i but i on and change of di r ect i on wi t h mi ni mum t ur bul ence or pr essur e l oss. Pr ovi de f act or y or f i el d assembl ed ai r def l ect or s. Make adj ust ment f r om t he f ace of t he di f f user or by posi t i on adj ust ment and l ock ext er nal t o t he duct . Pr ovi de st and- of f br acket s on i nsul at ed duct s as descr i bed her ei n. Pr ovi de f i xed ai r def l ect or s, al so cal l ed t ur ni ng vanes, i n 90 degr ee el bows.

2. 9. 7 Di f f user s, Regi st er s, and Gr i l l es

Pr ovi de f act or y- f abr i cat ed uni t s of cor r osi on- r esi st ant st eel or al umi num t hat di st r i but e t he speci f i ed quant i t y of ai r evenl y over space i nt ended wi t hout causi ng not i ceabl e dr af t s , ai r movement f ast er t han 50 f pm i n occupi ed zone, or dead spot s anywher e i n t he condi t i oned ar ea. Pr ovi de out l et s f or di f f usi on, spr ead, t hr ow, and noi se l evel as r equi r ed f or speci f i ed per f or mance. Cer t i f y per f or mance accor di ng t o ASHRAE 70.

SECTI ON 23 00 00 Page 16

Pr ovi de sound r at ed and cer t i f i ed i nl et s and out l et s accor di ng t o ASHRAE 70.

Pr ovi de sound power l evel as i ndi cat ed. Pr ovi de di f f user s and r egi st er s wi t h vol ume damper wi t h accessi bl e oper at or , unl ess ot her wi se i ndi cat ed; or i f s t andar d wi t h t he manuf act ur er , an aut omat i cal l y cont r ol l ed devi ce i s accept abl e. Pr ovi de opposed bl ade t ype vol ume damper s f or al l di f f user s and r egi st er s, except l i near s l ot di f f user s. Pr ovi de l i near s l ot di f f user s wi t h r ound or el l i pt i cal bal anci ng damper s. Wher e t he i nl et and out l et openi ngs ar e l ocat ed l ess t han 7 f eet above t he f l oor , pr ot ect t hem by a gr i l l e or scr een accor di ng t o NFPA 90A.

2. 9. 7. 1 Diffusers

Pr ovi de di f f user t ypes i ndi cat ed. Fur ni sh cei l i ng mount ed uni t s wi t h ant i - smudge devi ces, unl ess t he di f f user uni t mi ni mi zes cei l i ng smudgi ng t hr ough desi gn f eat ur es. Pr ovi de di f f user s wi t h ai r def l ect or s of t he t ype i ndi cat ed. Pr ovi de ai r handl i ng t r of f er s or combi nat i on l i ght and cei l i ng di f f user s conf or mi ng t o t he r equi r ement s of UL El ect r i cal Const r uct n f or t he i nt er changeabl e use as cool ed or heat ed ai r suppl y di f f user s or r et ur n ai r uni t s. I nst al l cei l i ng mount ed uni t s wi t h r i ms t i ght agai nst cei l i ng.

Pr ovi de sponge r ubber gasket s bet ween cei l i ng and sur f ace mount ed di f f user s f or ai r l eakage cont r ol . Pr ovi de sui t abl e t r i m f or f l ush mount ed di f f user s. For connect i ng t he duct t o di f f user , pr ovi de duct col l ar t hat i s ai r t i ght and does not i nt er f er e wi t h vol ume cont r ol l er . Pr ovi de r et ur n or exhaust uni t s t hat ar e s i mi l ar t o suppl y di f f user s.

2. 9. 7. 2 Regi st er s and Gr i l l es

Pr ovi de uni t s t hat ar e f our - way di r ect i onal - cont r ol t ype, except pr ovi de r et ur n and exhaust r egi st er s t hat ar e f i xed hor i zont al or ver t i cal l ouver t ype s i mi l ar i n…