HAZARDOUS MATERIAL SURVEY
U.S. ARMY RESERVE CENTER – FL103
RATTLESNAKE POINT USARC
5201 WEST TYSON AVENUE
TAMPA FL 33611
PRIME CONTRACT # W912HP18D6000
TASK ORDER – W912HP18F1203
PROJECT NUMBER - F5Y67384
SUBCONSULTING F5Y67384-S19-0001
Prepared for:
JACOBS GOVERNMENT SERVICE COMPANY
1100 North Glebe Road, Suite 500 Arlington, VA 22201
Submitted by:
6401 Golden Triangle Drive, #304
Greenbelt, MD 20770
March 12, 2019
ARCHITECTURAL AND ENGINEERING SERVICES CONTRACT
U.S. Army Corps of Engineers, Charleston
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC 5201 West Tyson Avenue
Tampa FL 33611 i
Table of Contents
EXECUTIVE SUMMARY .................................................................................................i
1.0 INTRODUCTION
2.0 ASBESTOS SURVEY REPORT
2.1 Survey Methodology
2.2 Analytical Procedures
2.3 Inaccessible and Limited-Access Spaces
2.4 Survey Limitations
2.5 Asbestos Survey Results
2.6 Asbestos Conclusions and Recommendations
3.0 LEAD-BASED PAINT SURVEY REPORT
3.1 LBP Survey Methodology
3.2 LBP Survey Results
3.3 LBP Conclusions and Recommendations
4.0 OTHER POTENTIAL HAZARDOUS AND REGULATED MATERIALS
5.0 DISCLAIMER
Appendices:
Appendix 1 – ACM Analytical Results Appendix 2 – Lead Paint Chip Results Appendix 3 – Drawings of Sample Locations Appendix 4 – Inspector Certification(s)/License(s)
Carlk323 Text Box
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC 5201 West Tyson Avenue
Tampa, FL 33611 i
EXECUTIVE SUMMARY
The U.S. Army Corps of Engineers, Charleston District, retained Jacobs Government Service Company (Jacobs) to provide Architect-Engineering Services for the 81st Readiness Division (RD) Reset Design Project, for the U.S. Army Reserve Center (USARC), U.S.
Army Reserve Center – FL103, Rattlesnake Point USARC, 5201 West Tyson Avenue, Tampa FL 33611. Jacobs retained Global Consulting, Inc. (GCI) to perform an environmental and hazardous material survey for this project. This report documents the survey of the Facility by GCI’s certified inspector for Asbestos-Containing Material (ACM), Lead-Based Paint (LBP), other hazardous materials, and Universal Waste (UW).
The Facility is scheduled for a partial HVAC renovation (Reset), and this survey was limited to identifying the potentially hazardous materials and conditions that may be impacted by the renovation.
Asbestos:
On February 20, 2019, GCI’s EPA-accredited and licensed Asbestos Inspector assessed the existing building materials suspected to contain asbestos and likely to be impacted during renovation. GCI identified twenty-three (23) specific suspect homogenous building materials, from which a total of seventy-three (73) suspected asbestos-containing samples were collected and submitted for laboratory analysis.
Samples FL103-10.1 to 10.3 was collected from the black mastic on the fiberglass insulated ductwork and was found to contain 8% chrysotile and is classified as a Class II Non-friable ACM. This ductwork is located throughout the old office building and is above the drop ceilings. In the event this material is disturbed during the HVAC Reset this will require the development of abatement specification and drawings.
Sample FL103-20.1 to 20.3 of the black roof flashing on the roof of the old office building and was not found to have asbestos concentration above 1% by weight. FL103-20.4-QC was found to contain 2.7% chrysotile. This material is classified as a Class II Non-friable ACM and if disturbed during the renovation of the HVAC system will require the development of abatement specification and drawings.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC ii
The black vinyl vibration damper gasket located in the duct work for the HVAC system in Assembly Room 140 could not be sampled without compromising the equipment and is assumed to be ACM. While the vibration damper is considered to have a low potential to be ACM, we recommend this material be sampled and analyzed for asbestos prior to renovation to confirm the classification.
The other twenty-one (21) suspect materials identified, sampled, and analyzed were not found to be asbestos-containing. Remedial action or specification development is not indicated for these building materials.
Details of the survey are presented in Section 2.0 – Asbestos Survey Report, Analytical results are presented in Appendix 1 – ACM Analytical Results and ACM and LBP Sample Locations are presented in Appendix 3 – Sample Location Drawings. The development of asbestos abatement drawings and specifications is indicated for the black mastic on insulated ductwork throughout the old office building.
Lead-Based Paint:
GCI’s Industrial Hygienist (IH), an EPA and certified LBP Inspector, performed a survey of the Facility for Lead-Based Paint (LBP) and Lead-Containing Paint (LCP) painted surfaces that have an elevated potential to be impacted during renovation.
The building components that were sampled and analyzed were not found to be LBP. The following components were sampled, analyzed and did contain lead above the detection limit for the analytical method and are considered to be LCP:
• Tan Paint Exterior Office Walls
• Grey Paint on Concrete Block Walls and Stairs
The other painted building components were not found to have lead (Pb) above the detection limit for the method and are not considered to be LBP or LCP and no special requirements apply. Details of the survey are presented in Section 3.0 – Lead-Based Paint Survey Report.
Analytical results are presented in Appendix 2 – Lead Paint Chip Results. OSHA lead safe work practices should be used if the LCP painted surfaces are disturbed.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC iii
Other Potential Hazardous Materials:
The Facility was surveyed for other potentially hazardous materials that may be impacted by the HVAC renovation. The existing original lighting systems have an elevated potential to contain mercury-containing florescent light bulbs which should be disposed of in accordance with the Environmental Protection Agency (EPA) Universal Waste (UW) Regulations 40 CFR 273. The original fluorescent lighting system in the building has an elevated potential to be equipped with potentially PCB-containing electrical light ballasts that require management as a PCB-containing waste unless specifically marked as non-PCB containing ballasts. Should the lighting system be impacted by the HVAC system renovation, specifications should be developed to address these materials. UW Waste storage issues were not observed.
The fire protection system has an elevated potential to contain ionization-type smoke and fire detectors that are typically constructed with an Americium-241 radioactive source. If impacted by the renovation, these detectors should be segregated and disposed of properly in accordance with Federal, state, and local regulations.
The existing heating and cooling system consists of several air-conditioning systems that contain a significant quantity of potentially regulated refrigerants that may be classified as Ozone Depleting Substances (ODS). Section 608 of the Clean Air Act prohibits the known release of refrigerants and ODS during the maintenance, service, repair, or disposal of air-conditioning and refrigeration equipment. The EPA requires proper refrigerant management practices by owners and operators of refrigeration and air-conditioning systems, technicians, and others. The refrigerants should be managed and disposed of in accordance with 40 CFR 82 and applicable Federal, state, and local regulations.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC iv
ACRONYMS
ACM Asbestos-Containing Material
AHERA Asbestos Hazard Emergency Response Act
CFR Code of Federal Regulations
EPA Environmental Protection Agency
FDEP Florida Department of Environmental Protection
IH Industrial Hygienist
LBP Lead-Based Paint
LCP Lead-Containing Paint
NESHAP National Emission Standards for Hazardous Air Pollution
NIOSH National Institute of Occupational Safety and Health
NVLAP National Voluntary Laboratory Accreditation Program
OSHA Occupational Safety & Health Administration
ODS Ozone-Depleting Substances
PCB Polychlorinated Biphenyl
PLM Polarized Light Microscopy
PACM Presumed Asbestos-Containing Material
RACM Regulated Asbestos-Containing Material
UW Universal Waste
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
Tampa FL 33611
1.0 INTRODUCTION
The U.S. Army Corps of Engineers, Charleston District, retained Jacobs Government Service Company (Jacobs) to provide Architect-Engineering Services for the 81st Readiness Division (RD) Reset Design Project, for the U.S. Army Reserve Center (USARC), U.S.
Army Reserve Center – FL103, Rattlesnake Point USARC, 5201 West Tyson Avenue, Tampa FL 33611. Jacobs retained Global Consulting, Inc. (GCI) to perform the limited environmental and hazardous material survey associated with this project. This report documents the limited survey of the Facility by a certified inspector for Asbestos- Containing Material (ACM), Lead-Based Paint (LBP), other hazardous materials, and Universal Waste (UW). The Facility is scheduled for a HVAC renovation and this survey was limited to identifying the potentially hazardous materials and conditions likely to be impacted by the proposed project. The mutual goal of the contractor and the government is to safely achieve a quality product within the expected timeframe and budget.
The scope of work for this survey consisted of the following tasks:
1. Review of available records for identified and suspect ACM, LBP, and other hazardous and regulated materials that may be impacted by the scope of work;
2. Conduct a visual survey of the project area to identify potential location(s) of hazardous materials that may be affected by the scope of work.
3. Collect bulk samples of suspect ACMs and assess painted surfaces for LBP using paint chip analysis.
4. Submit the bulk samples to a certified laboratory to positively identify ACM via Polarized Light Microscopy (PLM) using EPA Method 600/R-93/116 and to identify LBP/LCP using Atomic Absorption Analysis for Lead method SW846 – 3050B/7000B.
5. Prepare a report summarizing data, collection techniques, analysis procedures, location and quantity of ACM, LBP/LCP and other hazardous and regulated materials observed and detailed recommendations for any indicated response actions.
6. Abatement specification(s) will be prepared separately, if required.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
2.0 ASBESTOS SURVEY REPORT
This section describes the site survey and sample collection of suspect ACMs. The site survey was conducted on January 17, 2019, by EPA Asbestos Hazard Emergency Response Act (AHERA) and State of Florida, Department of Environmental Protection accredited Asbestos Inspector, Mr. William Zukauskas. A copy of Mr. Zukauskas’s credentials are presented in Appendix 4.
The Environmental Protection Agency (EPA) and the Florida Department of Environmental Protection (FDEP), are the authorities that regulate activities related to Asbestos-Containing Materials (ACM) in Florida. The EPA regulations enforce four asbestos activities; (1) removal, repair, or encapsulation of ACM, (2) approval of asbestos training providers, (3) regulation of professionals accredited to perform asbestos-related activities, and (4) asbestos in schools. The GPED regulates the enforcement of the EPA’s National Emission Standards for Hazardous Air Pollutants (NESHAP), and enforcement of the asbestos notification regulations.
2.1 Survey Methodology
The asbestos survey was divided into two distinct phases: pre-survey planning and field survey.
2.1.1 Pre-Survey Planning
The pre-survey planning phase included reviewing previous survey reports, drawings, management plans, and abatement reports, if available. Jacobs provided GCI with information regarding the planned HVAC Reset of the Facility. GCI planned a survey strategy and scheduled the survey work. It was determined that this survey should include all applicable and accessible areas of the Facility to ensure that intended renovation, can be conducted in an efficient and safe manner compliant with applicable Federal, state, and local regulations.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
2.1.2 Field Survey
The field survey was conducted for the areas affected by the HVAC renovation as determined in the planning phase, and suspect asbestos-containing building materials were identified. Suspect materials that were homogeneous in nature (i.e., uniform in color and texture, installation date) were identified, touched to determine friability, and sampled by removing a small amount of material. Extreme care was taken to avoid potential fiber release during the sampling process. Before sample collection, a fine mist of water was typically applied to the sampling location. Samples were collected using sharpened core samplers and/or utility knives, where necessary, and immediately placed in labeled containers and sealed. Any dust generated was wet-wiped to minimize the potential fiber release. All sampling locations were promptly patched and repaired. The location and condition of each homogeneous material were recorded.
2.2 Analytical Procedures
The samples of suspect ACMs were packaged and delivered under strict chain of custody procedures to EMSL Analytical, Inc. of Tampa, FL, a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory. Quality control samples were duplicated in the field and submitted to ATL International Asbestos Testing Laboratories in Mt. Laurel, NJ.
Quantification of asbestos content in bulk samples was performed via EPA 600/R-93/116 Method using Polarized Light Microscopy (PLM). This method of analysis involves the dispersion staining of a suspect material in a solution of known refractive index and then subjected to illumination by polarized light. The resulting color contrast enables fiber and mineral identification. The Occupational Health and Safety Administration (OSHA) and the State of Georgia define an ACM as any material containing greater than 1% asbestos.
A summary of field data including the sample designations, gross descriptions, and analytical results are provided in Table 2. The analytical results of all bulk samples and chain of custody documents are provided in Appendix 1.
2.3 Inaccessible and Limited-Access Spaces
Every reasonable effort was made to locate suspect ACM at elevated potential to be
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC impacted by this project. All rooms were made accessible for the survey. Other inaccessible areas might include, but are not limited to, those listed in Table 1: Description of Potential Inaccessible Locations.
Table 1: Description of Potential Inaccessible Locations
Mechanical and plumbing system above the reach of readily accessible ladders
Concealed by roofing and building waterproofing systems
Enclosed pipe/duct chases/floor penetrations Inside mechanical equipment/ductwork
Above hard plaster ceilings Inside fire doors
2.4 Survey Limitations
This survey was limited to areas and building systems scheduled for HVAC replacement, upgrade, or renovation as part of the scope of this project. Other suspect materials uncovered during renovation and/or demolition activities not identified within this report should be considered presumed asbestos-containing material (PACM) and should be treated as ACM until sampling and laboratory analysis confirm otherwise.
2.5 Asbestos Survey Results
A total of seventy-three (73) bulk samples were collected from thirteen (23) homogeneous suspect materials during the survey. The suspect ACM and asbestos laboratory analytical results are summarized in Table 2: Description of Homogeneous Areas and Sampling Results.
Table 2: Description of Homogeneous Areas and Sampling Results
HA
# Description Sample # Location Asbestos
Content Friable
(Yes/No)
1 Concrete Slab FL103-1.1 Office 108 ND
No FL103-1.2 Office 108 ND FL103-1.3 Office 108 ND
2 Exterior Tan Brick Wall
FL103-2.1 Bathroom 111 ND No
FL103-2.2 Server 103 ND
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
# Description Sample # Location Asbestos
Content Friable
(Yes/No) FL103-2.3 Office 101 ND
3 Grey Exterior Brick Mortar
FL103-3.1 Bathroom 111 ND No FL103-3.2 Server 103 ND
FL103-3.3 Office 101 ND
4 Exterior Soffit FL103-4.1 Outside Breakroom 114 ND
No FL103-4.2 Outside Server 103 ND FL103-4.3 Outside Office 101 ND
5 Concrete Block Walls
FL103-5.1 Reception 110 ND Yes FL103-5.2 Office 108 ND
FL103-5.3 Office 108 ND
6 Concrete Block Wall Mortar
FL103-6.1 Reception 110 ND No FL103-6.2 Office 108 ND
FL103-6.3 Office 108 ND
7 Drywall Board
FL103-7.1 Reception 110 ND
No FL103-7.2 Reception 110 ND
FL103-7.3 Reception 110 ND
8 White Joint Compound
FL103-8.1 Reception 110 ND
No
FL103-8.2 Reception 110 ND FL103-8.3 Office 108 ND
FL103-8.4 - QC
Office 108 – QC Sample Result Confirms Prime
Sample Results
ND
9 2’ x 2’ White Ceiling Tiles
FL103-9.1 Reception 110 ND
No FL103-9.2 Hallway Outside Office
106 ND
FL103-9.3 Hallway Outside Office
104 ND
10 Black Duct Mastic
FL103-10.1 8%
No FL103-10.2 PS
FL103-10.3 Hallway Outside Office
108 PS
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
# Description Sample # Location Asbestos
Content Friable
(Yes/No)
FL103-10.4 - QC
Hallway Outside Office 108 - QC Sample Result Confirms Prime Sample
Results
5.7%
11 Concrete Slab Main Building
FL103-11.1 High Bay 121 Near Conference Room 134 ND
No FL103-11.2 High Bay 121 Near Breakroom 114 ND
FL103-11.3 High Bay 121 – Southwest Corner ND
12 2’ x 4’ White Ceiling Tiles
FL103-12.1 Conference Room 134 ND
No FL103-12.2 Conference Room 134 ND
FL103-12.3 Administration 122 ND
13 Drywall Board Panels
FL103-13.1 Conference Room 134 ND
No FL103-13.2 Conference Room 134 ND
FL103-13.3 Administration 122 ND
Grey Duct Mastic
FL103-14.1
Conference Room 134
ND
No FL103-14.2 Administration 123 ND
FL103-14.3 Office 124 ND
15 Drywall Board
FL103-15.1 Office 200 ND
No FL103-15.2 Office 200 ND
FL103-15.3 Office 200 ND
16 White Joint Compound FL103-16.1 Office 200 ND No
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
# Description Sample # Location Asbestos
Content Friable
(Yes/No)
FL103-16.2 Office 200 ND
FL103-16.3 Office 200 ND
FL103-16.4
Office 200 - QC Sample Result Confirms Prime
Sample Results
ND
17 Grey Duct Mastic
FL103-17.1 Mechanical 201 ND
No FL103-17.2 Mechanical 201 ND
FL103-17.3 Mechanical 201 ND
18 Roof Shingle
FL103-18.1 Roof ND
No FL103-18.2 Roof ND
FL103-18.3 Roof ND
19 Black Roof Tar
FL103-19.1 Roof ND
No FL103-19.2 Roof ND
FL103-19.3 Roof ND
20 Black Flashing Material
FL103-20.1 Roof of Old Office Building ND
No
FL103-20.2 Roof of Old Office Building ND
FL103-20.3 Roof of Old Office Building ND
FL103-20.4
Roof - QC Sample Result does not Confirm Prime Sample Results and this material is classified as an
ACM
2.7%
21 FL103-21.1 Office 108 ND No
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
# Description Sample # Location Asbestos
Content Friable
(Yes/No)
Compressed Fiber Roof Boards -
Tectum
FL103-21.2 Office 108 ND
FL103-21.3 Office 108 Hallway ND
Plaster Applied directly to Concrete Block
FL103-22.1 Office 108 Hallway ND
No FL103-22.2 Office 108 ND
FL103-22.3 Office 108 ND
Black Vinyl
Vibration Damper Gasket
Samples not collected due to concerns about compromising integrity of gasket.
HVAC Ductwork in Room
Assumed ACM No
ND – Not Detected PS – Positive Stop
2.6 Asbestos Conclusions and Recommendations
Regulated asbestos-containing material (RACM) is defined as friable ACM or non-friable ACM with an asbestos fiber content greater than 1% that will be, or has been, subjected to sanding, grinding, cutting, or abrading or has crumbled, pulverized, or reduced to powder during demolition or renovation operations.
Sample FL103-10.1 to 10.3 was collected from the black mastic on the fiberglass insulated ductwork was found to contain 8% Chrysotile and is considered a Class II Non-friable ACM. This ductwork is located throughout the old office building and is above the drop ceilings. In the event this material is disturbed during the HVAC Reset this will require the development of abatement specification and drawings.
Sample FL103-20.1 to 20.3 of the black roof flashing on the roof of the old office building and was not found to have asbestos concentration above 1% by weight. FL103-20.4-QC was found to contain 2.7% chrysotile. This material is classified as a Class II Non-friable
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
ACM and if disturbed during the renovation of the HVAC system will require the development of abatement specification and drawings.
The black vinyl vibration damper gasket located in the duct work for the HVAC system in Assembly room 140 could not be sampled without compromising the equipment and is assumed to be ACM. While the vibration damper is considered to have a low potential to be ACM, we recommend this material be sampled and analyzed for asbestos prior to renovation to confirm the classification.
The other twenty-one (21) suspect materials identified, sampled, and analyzed as part of the survey were not found to be asbestos-containing. Remedial action or specification development is not indicated for these materials.
If additional suspect materials are identified during renovation/demolition and have not been tested to determine the presence of asbestos, those materials should be protected from impact until further investigated and the asbestos content is determined.
All quantities must be field-verified by a licensed asbestos abatement contractor(s) prior to demolition or renovation.
Sampling locations and positively-identified materials are identified on drawings presented in Appendix 3.
3.0 LEAD-BASED PAINT SURVEY REPORT
This section describes data collection activities including the site survey and sample collection for Lead-Based Paint (LBP) that will be affected by the HVAC renovation. The site survey was completed on February 20, 2019, by EPA-accredited and Lead-Safe State Program Inspector, Mr. William Zukauskas.
3.1 LBP Survey Methodology
Testing for LBP was conducted using paint chips sampling techniques. LBP is defined as a paint containing greater than 0.5% lead by weight according to the FDEP. Samples were delivered to EMSL of Orlando, FL for analysis using Atomic Absorption Analysis for Lead in accordance with method SW846 – 3050B/7000B.
The analytical results are presented in Appendix 2 – Lead Paint Chip Results.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
3.2 LBP Survey Results
A total of seven (7) components were assessed using paint chip sampling. These painted surfaces included the components with an elevated potential to be impacted by the planned HVAC renovation. The summary of the paint chip sampled and analyzed are presented in Table 3.
Table 3 – Paint Chip Sample Results
Sample Number Description Location LBP/LCP Classification
FL103-PS-01 Beige Paint Interior Office Walls NA
FL103-PS-02 Tan Paint Exterior Walls LCP
FL103-PS-03 White Paint High Bay NA
FL103-PS-04 Grey Paint Concrete and Stairs LCP
FL103-PS-05 Tan Paint Administration Walls NA
FL103-PS-06 Beige Paint West Office and Classrooms NA
FL103-PS-07 Grey Paint HVAC NA
LBP – Lead Based Paint, LCP – Lead Containing Paint, ND – Not Detected
The analytical results for samples FL103-PS-01, 3, 5, 6 and 7 were not found to have detectable levels of lead and no special consideration is required if these painted surfaces are disturbed. Sample FL103-PS-02 and FL103-PS-04 were found to be below the standard for LBP and above the detection limit for the analytical method and are classified as LCP.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
3.3 LBP Conclusions and Recommendations
The tan exterior walls and the grey painted surfaces inspected and sampled were found to be LCP and are classified as lead containing paint. The development of LBP abatement specifications is not indicated. Should these painted surfaces be impacted by the planned HVAC Reset we recommend that OSHA Lead Safe Construction practices be used.
4.0 OTHER POTENTIAL HAZARDOUS AND REGULATED MATERIALS
The Facility was surveyed for other potentially hazardous materials that may be impacted by the planned renovation. The existing original lighting systems have an elevated potential to contain mercury-containing florescent light bulbs and should be disposed of in accordance with the Environmental Protection Agency (EPA) Universal Waste (UW) Regulations 40 CFR 273. The original fluorescent lighting fixtures in the building have an elevated potential to be equipped with potentially PCB-containing electrical light ballasts.
These ballasts require management as a PCB-containing waste unless specifically marked as non-PCB containing ballasts. The development of specifications for Universal Waste (UW) and PCB light ballasts is indicated if the lighting system is impacted by the planned HVAC renovation.
The fire protection system has an elevated potential to contain ionization-type smoke and fire detectors that are constructed with an Americium-241 radioactive source. If they do, they should be segregated and disposed of properly in accordance with Federal, state and local regulations.
The existing heating and cooling system consist of several air-conditioning systems that contain a significant quantity of potentially regulated refrigerants that may be classified as Ozone Depleting Substances (ODS). Section 608 of the Clean Air Act prohibits the known release of refrigerants and ODS during the maintenance, service, repair, or disposal of air-conditioning and refrigeration equipment. The EPA requires proper refrigerant management practices by owners and operators of refrigeration and air-conditioning systems, technicians, and others. The refrigerants should be managed and disposed of in accordance with 40 CFR 82 and applicable Federal, state, and local regulations.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
5.0 DISCLAIMER
Information in this limited survey report relating to hazardous materials (i.e., asbestos and lead), although believed to be inclusive and accurate, was based on visual observations and field sampling of accessible areas at the time of survey. Global Consulting, Inc. reserves the right to revise any recommendations and conclusions based on new information that may become available and does not guarantee or accept any liability that encompasses this limited survey of hazardous or regulated materials located within this Facility. This report should not be used as a comprehensive hazardous material survey of the whole facility.
Hazardous Material Survey U.S. Army Reserve Center – FL103
Rattlesnake Point USARC
Appendix 1 – ACM Analytical Results
EMSL Analytical, Inc.
3303 PARKWAY CENTER COURT Orlando, FL 32808
Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com
341903353EMSL Order:
Customer ID: SHAE77
Customer PO:
Project ID:
Attention: Phone:Bill Zukauskas (904) 636-9360
Fax:APTIM Environmental & Infrastructure (904) 636-9356
Received Date:9143 Phillips Highway 02/22/2019 9:40 AM
Analysis Date:Suite 400 02/28/2019
Collected Date:Jacksonville, FL 32256 02/21/2019
Project: FL103-Rattlesnake Point-USARC
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
FL103-1.1
341903353-0001
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
White
Non-Fibrous
Homogeneous
Concrete Slab
FL103-1.2
341903353-0002
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Slab
FL103-1.3
341903353-0003
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Slab
FL103-2.1
341903353-0004
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Beige
Non-Fibrous
Homogeneous
Tan Brick
FL103-2.2
341903353-0005
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Beige
Non-Fibrous
Homogeneous
Tan Brick
FL103-2.3
341903353-0006
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Beige
Non-Fibrous
Homogeneous
Tan Brick
FL103-3.1
341903353-0007
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Gray Brick Mortar
FL103-3.2
341903353-0008
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Gray Brick Mortar
FL103-3.3
341903353-0009
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Gray Brick Mortar
FL103-4.1
341903353-0010
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
20%
15%
65%
Gray
Non-Fibrous
Homogeneous
Exterior Stucco-Soffit
FL103-4.2
341903353-0011
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Exterior Stucco-Soffit
FL103-4.3
341903353-0012
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Exterior Stucco-Soffit
FL103-5.1
341903353-0013
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
FL103-5.2
341903353-0014
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
FL103-5.3
341903353-0015
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
FL103-6.1
341903353-0016
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
Mortar
Initial report from: 03/01/2019 09:01:10
Page 1 of 5ASB_PLM_0008_0001 - 1.78 Printed: 3/1/2019 9:01 AM
Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com
341903353EMSL Order:
Customer ID: SHAE77
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
FL103-6.2
341903353-0017
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
Mortar
FL103-6.3
341903353-0018
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Block
Mortar
FL103-7.1
341903353-0019
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose
Glass
10%
<1%
Brown/White
Fibrous
Heterogeneous
Drywall Board
FL103-7.2
341903353-0020
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose
Glass
10%
<1%
Brown/White
Fibrous
Heterogeneous
Drywall Board
FL103-7.3
341903353-0021
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose
Glass
10%
<1%
Brown/White
Fibrous
Heterogeneous
Drywall Board
FL103-8.1
341903353-0022
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-8.2
341903353-0023
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-8.3
341903353-0024
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-9.1
341903353-0025
None DetectedPerlite
Non-fibrous (Other)
10%
20%
Cellulose
Min. Wool
40%
30%
Tan/White
Fibrous
Heterogeneous
2x2 White Ceiling
Tiles
FL103-9.2
341903353-0026
None DetectedPerlite
Non-fibrous (Other)
10%
20%
Cellulose
Min. Wool
40%
30%
Tan/White
Fibrous
Heterogeneous
2x2 White Ceiling
Tiles
FL103-9.3
341903353-0027
None DetectedPerlite
Non-fibrous (Other)
10%
20%
Cellulose
Min. Wool
40%
30%
Tan/White
Fibrous
Heterogeneous
2x2 White Ceiling
Tiles
FL103-10.1
341903353-0028
8% ChrysotileNon-fibrous (Other)92%Black
Non-Fibrous
Homogeneous
Blk Duct Mastic
FL103-10.2
341903353-0029
Positive Stop (Not Analyzed)Blk Duct Mastic
FL103-10.3
341903353-0030
Positive Stop (Not Analyzed)Blk Duct Mastic
FL103-11.1
341903353-0031
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Slab
FL103-11.2
341903353-0032
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Slab
FL103-11.3
341903353-0033
None DetectedQuartz
Ca Carbonate
Non-fibrous (Other)
30%
15%
55%
Gray
Non-Fibrous
Homogeneous
Concrete Slab
FL103-12.1
341903353-0034
None DetectedPerlite
Non-fibrous (Other)
20%
10%
Cellulose
Min. Wool
40%
30%
Gray/White
Fibrous
Heterogeneous
2x4 White Ceiling
Tiles
FL103-12.2
341903353-0035
None DetectedPerlite
Non-fibrous (Other)
20%
10%
Cellulose
Min. Wool
40%
30%
Gray/White
Fibrous
Homogeneous
2x4 White Ceiling
Tiles
Page 2 of 5ASB_PLM_0008_0001 - 1.78 Printed: 3/1/2019 9:01 AM
Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com
341903353EMSL Order:
Customer ID: SHAE77
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
FL103-12.3
341903353-0036
None DetectedPerlite
Non-fibrous (Other)
20%
10%
Cellulose
Min. Wool
40%
30%
Gray/White
Fibrous
Homogeneous
2x4 White Ceiling
Tiles
FL103-13.1
341903353-0037
None DetectedGypsum
Mica
Non-fibrous (Other)
65%
3%
22%
Cellulose
Glass
10%
<1%
Brown/Gray
Fibrous
Heterogeneous
Drywall Board
FL103-13.2
341903353-0038
None DetectedGypsum
Mica
Non-fibrous (Other)
65%
3%
22%
Cellulose
Glass
10%
<1%
Brown/Gray
Fibrous
Heterogeneous
Drywall Board
FL103-13.3
341903353-0039
None DetectedGypsum
Mica
Non-fibrous (Other)
65%
3%
22%
Cellulose
Glass
10%
<1%
Brown/Gray
Non-Fibrous
Homogeneous
Drywall Board
FL103-14.1-Gray Mastic
341903353-0040
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-14.1-Tan Mastic
341903353-0040A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-14.2-Gray Mastic
341903353-0041
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-14.2-Tan Mastic
341903353-0041A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-14.3-Gray Mastic
341903353-0042
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-14.3-Tan Mastic
341903353-0042A
None DetectedNon-fibrous (Other)100%Tan
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-15.1
341903353-0043
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose
Glass
10%
<1%
Brown/Gray
Fibrous
Heterogeneous
Drywall Board
FL103-15.2
341903353-0044
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose
Glass
10%
<1%
Brown/Tan
Fibrous
Heterogeneous
Drywall Board
FL103-15.3
341903353-0045
None DetectedGypsum
Non-fibrous (Other)
65%
25%
Cellulose10%Brown/Tan
Fibrous
Heterogeneous
Drywall Board
FL103-16.1
341903353-0046
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-16.2
341903353-0047
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-16.3
341903353-0048
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
White Joint
Compound
FL103-17.1-Gray Mastic
341903353-0049
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-17.1-White
Mastic
341903353-0049A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Gray Duct Mastic
Page 3 of 5ASB_PLM_0008_0001 - 1.78 Printed: 3/1/2019 9:01 AM
Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com
341903353EMSL Order:
Customer ID: SHAE77
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
FL103-17.2-Gray Mastic
341903353-0050
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-17.2-White
Mastic
341903353-0050A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-17.3-Gray Mastic
341903353-0051
None DetectedNon-fibrous (Other)100%Gray
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-17.3-White
Mastic
341903353-0051A
None DetectedNon-fibrous (Other)100%White
Non-Fibrous
Homogeneous
Gray Duct Mastic
FL103-18.1
341903353-0052
None DetectedNon-fibrous (Other)90%Glass10%White/Black
Fibrous
Homogeneous
White/Blk Rolled
Asphalt Shingle
FL103-18.2
341903353-0053
None DetectedNon-fibrous (Other)90%Glass10%White
Non-Fibrous
Homogeneous
White/Blk Rolled
Asphalt Shingle
FL103-18.3
341903353-0054
None DetectedNon-fibrous (Other)90%Glass10%White
Non-Fibrous
Homogeneous
White/Blk Rolled
Asphalt Shingle
FL103-19.1
341903353-0055
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Blk Roof Tar
FL103-19.2
341903353-0056
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Blk Roof Tar
FL103-19.3
341903353-0057
None DetectedNon-fibrous (Other)100%Black
Non-Fibrous
Homogeneous
Blk Roof Tar
FL103-20.1
341903353-0058
None DetectedNon-fibrous (Other)65%Cellulose35%Black
Fibrous
Homogeneous
Blk Flashing
FL103-20.2
341903353-0059
None DetectedNon-fibrous (Other)65%Cellulose35%Black
Fibrous
Homogeneous
Blk Flashing
FL103-20.3
341903353-0060
None DetectedNon-fibrous (Other)65%Cellulose
Synthetic
20%
15%
Black
Fibrous
Homogeneous
Blk Flashing
FL103-21.1
341903353-0061
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Compound Fiber Roof
Deck
FL103-21.2
341903353-0062
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Compound Fiber Roof
Deck
FL103-21.3
341903353-0063
None DetectedNon-fibrous (Other)5%Cellulose95%Tan
Fibrous
Homogeneous
Compound Fiber Roof
Deck
FL103-22.1-Skim Coat
341903353-0064
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
Plaster Wall
FL103-22.1-Base Coat
341903353-0064A
None DetectedCa Carbonate
Perlite
Non-fibrous (Other)
15%
20%
65%
Gray
Non-Fibrous
Homogeneous
Plaster Wall
Page 4 of 5ASB_PLM_0008_0001 - 1.78 Printed: 3/1/2019 9:01 AM
Tel/Fax: (407) 599-5887 / (407) 599-9063 http://www.EMSL.com / orlandolab@emsl.com
341903353EMSL Order:
Customer ID: SHAE77
Customer PO:
Project ID:
Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized
Light Microscopy
Sample Description Appearance % Fibrous % Non-Fibrous
Non-Asbestos Asbestos
% Type
FL103-22.2-Skim Coat
341903353-0065
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
Plaster Wall
FL103-22.2-Base Coat
341903353-0065A
None DetectedCa Carbonate
Perlite
Non-fibrous (Other)
15%
20%
65%
Brown
Non-Fibrous
Homogeneous
Plaster Wall
FL103-22.3-Skim Coat
341903353-0066
None DetectedCa Carbonate
Non-fibrous (Other)
15%
85%
White
Non-Fibrous
Homogeneous
Plaster Wall
FL103-22.3-Base Coat
341903353-0066A
None DetectedCa Carbonate
Perlite
Non-fibrous (Other)
15%
20%
65%
Gray
Non-Fibrous
Homogeneous
Plaster Wall
Analyst(s)
Jessicka Lopez (31)
Jhon Rosario (42)
Carlos Rivadeneyra, Laboratory Director or Other Approved Signatory
EMSL maintains liability limited to cost of analysis . The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 "Interim
Method"), but augmented with procedures outlined in the 1993 ("final") version of the method. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . Interpretation and use of test results are the responsibility of the client. All samples received in acceptable condition unless otherwise noted. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. EMSL recommends gravimetric reduction for all non -friable organically bound materials prior to analysis. Estimation of uncertainty is available on request.
Samples analyzed by EMSL Analytical, Inc. Orlando, FL NVLAP Lab Code 101151-0
Page 5 of 5ASB_PLM_0008_0001 - 1.78 Printed: 3/1/2019 9:01 AM
OrderID: 341903353
Lab No.: 6723731 Client No.: FL103-8.4QA
Analyst Observation: White Joint Compound Client Description: White Joint Compound
Location:
Facility:
Percent Asbestos:
None Detected
Percent Non-Asbestos Fibrous Material:
Percent Non-Fibrous Material:
Lab No.: 6723732 Client No.: FL103-10.4QA
Analyst Observation: Black Mastic Client Description: Blk Duct Mastic
PC 5.7 Chrysotile
7 Cellulose
87.3
Lab No.: 6723733 Client No.: FL103-16.4QA
Analyst Observation: White Joint Compound Client Description: White Joint Compound
Lab No.: 6723734 Client No.: FL103-20.4QA
Analyst Observation: Black Flashing Client Description: Blk Flashing
PC 2.7 Chrysotile
10 Cellulose 3 Fibrous Glass
84.3
Laboratory Director
Approved By:
Date Analyzed:
2/22/2019Date Received:
Analyst:
Please refer to the Appendix of this report for further information regarding your analysis.
Signature:
Ellen Smith
02/28/2019 Frank E. Ehrenfeld, III
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Aptim
9143 Phillips Highway, Suite 400 Jacksonville FL 32256
2/28/2019Report Date:
Report No.: 584163 - PLM Project: FL103-Rattlesnake Point - USARC Project No.: 631004314
PLM BULK SAMPLE ANALYSIS SUMMARY
Client: SHA873
Dated : 3/1/2019 3:33:11 Page 1 of 4
Appendix to Analytical Report Customer Contact: Dave Mosher Method: US EPA 600, R93-116
This appendix seeks to promote greater understanding of any observations, exceptions, special instructions, or circumstances that the laboratory needs to communicate to the client concerning the above samples. The information below is used to help promote your ability to make the most informed decisions for you and your customers.
Please note the following points of contact for any questions you may have.
iATL Customer Service: customerservice@iatl.com iATL Office Manager: cdavis@iatl.com iATL Account Representative: Kelly Klippel Sample Login Notes: See Batch Sheet Attached Sample Matrix: Bulk Building Materials Exceptions Noted: See Following Pages
General Terms, Warrants, Limits, Qualifiers:
General information about iATL capabilities and client/laboratory relationships and responsibilities are spelled out in iATL policies that are listed at www.iATL.com and in our Quality Assurance Manual per ISO 17025 standard requirements. The information therein is a representation of iATL definitions and policies for turnaround times, sample submittal, collection media, blank definitions, quantification issues and limit of detection, analytical methods and procedures, sub-contracting policies, results reporting options, fees, terms, and discounts, confidentiality, sample archival and disposal, and data interpretation.
iATL warrants the test results to be of a precision normal for the type and methodology employed for each sample submitted. iATL disclaims any other warrants, expressed or implied, including warranty of fitness for a particular purpose and warranty of merchantability. iATL accepts no legal responsibility for the purpose for which the client uses test results. Any analytical work performed must be governed by our Standard Terms and Conditions. Prices, methods and detection limits may be changed without notification. Please contact your Customer Service Representative for the most current information.
This confidential report relates only to those item(s) tested and does not represent an endorsement by NIST-NVLAP, AIHA LAP LLC, or any agency of local, state or province governments nor of any agency of the U.S. government.
This report shall not be reproduced except in full, without written approval of the laboratory.
Information Pertinent to this Report:
Analysis by US EPA 600 93-116: Determination of Asbestos in Bulk Building Materials by Polarized Light Microscopy (PLM).
Certifications:
NIST-NVLAP No. 101165-0• NYSDOH-ELAP No. 11021• AIHA-LAP, LLC No. 100188•
Quantification at <0.25% by volume is possible with this method. (PC) Indicates Stratified Point Count Method performed. (PC-Trace) means that asbestos was detected but is not quantifiable under the Point Counting regimen. PC Trace represents a <0.25% amount. Analysis includes all distinct separable layers in accordance with EPA 600 Method. If not reported or otherwise noted, layer is either not present or the client has specifically requested that it not be analyzed (ex. analyze until positive instructions). Small asbestos fibers may be missed by PLM due to resolution limitations of the optical microscope. Therefore, PLM is not consistently reliable in detecting asbestos in non-friable organically bound (NOB) materials. Quantitative transmission electron microscopy (TEM) is currently the only method that can pronounce materials as non-asbestos containing.
Analytical Methodology Alternatives: Your initial request for analysis may not have accounted for recent advances in regulatory requirements or advances in technology that are routinely used in similar situations for other qualified projects. You may have the option to explore additional analysis for further information. Below are a few options, listed as the matrix followed by the appropriate methodology. Also included are links to more information on our website.
Bulk Building Materials that are Non-Friable Organically Bound (NOB) by Gravimetric Reduction techniques employing PLM and TEM: ELAP 198.6 (PLM-NOB), ELAP 198.4 (TEM-NOB)
Loose Fill Vermiculite Insulation, Attic Insulation, Zonolite (copyright), etc.: US EPA 600 R-4/004 (multi-tiered analytical process)
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Aptim 9143 Phillips Highway, Suite 400 Jacksonville FL 32256
2/28/2019Report Date:
Report No.: 584163 - PLM Project: FL103-Rattlesnake Point - USARC Project No.: 631004314
Page 2 of 4Dated : 3/1/2019 3:33:11
Sprayed On Insulation/Fireproofing with Vermiculite (SOF-V): ELAP 198.8 (PLM-SOF-V)
Soil, sludge, sediment, aggregate, and like materials analyzed for asbestos or other elongated mineral particles (ex. erionite, etc.): ASTM D7521, CARB 435, and other options available
Asbestos in Surface Dust according to one of ASTM's Methods (very dependent on sampling collection technique – by TEM): ASTM D 5755, D5756, or D6480
Various other asbestos matrices (air, water, etc.) and analytical methods are available.
Disclaimers / Qualifiers:
There may be some samples in this project that have a "NOTE:" associated with a sample result. We use added disclaimers or qualifiers to inform the client about something that requires further explanation. Here is a list with highlighted disclaimers that may be pertinent to this project. For a full explanation of these and other disclaimers, please inquire at customerservice@iatl.com.
1) Note: No mastic provided for analysis.
2) Note: Insufficient mastic provided for analysis.
3) Note: Insufficient material provided for analysis.
4) Note: Insufficient sample provided for QC reanalysis.
5) Note: Different material than indicated on Sample Log / Description.
6) Note: Sample not submitted.
7) Note: Attached to asbestos containing material.
8) Note: Received wet.
9) Note: Possible surface contamination.
10) Note: Not building material. 1% threshold may not apply.
11) Note: Recommend TEM-NOB analysis as per EPA recommendations.
12) Note: Asbestos detected but not quantifiable.
13) Note: Multiple identical samples submitted, only one analyzed.
14) Note: Analyzed by EPA 600/R-93/116. Point Counting detection limit at 0.080%.
15) Note: Analyzed by EPA 600/R-93/116. Point Counting detection limit at 0.125%.
16) Note: This sample contains >10% vermiculite mineral. See Appendix for Recommendations for Vermiculite Analysis.
Recommendations for Vermiculite Analysis:
Several analytical protocols exist for the analysis of asbestos in vermiculite. These analytical approaches vary depending upon the nature of the vermiculite mineral being tested (e.g. un-processed gange, homogeneous exfoliated books of mica, or mixed mineral composites).Please contact your client representative for pricing and turnaround time options available.
iATL recommends initial testing using the EPA 600/R-93/116 method. This method is specifically designed for the analysis of asbestos in bulk building materials. It provides an acceptable starting point for primary screening of vermiculite for possible asbestos.
Results from this testing may be inconclusive. EPA suggests proceeding to a multi-tiered analysis involving wet separation techniques in conjunction with PLM and TEM gravimetric analysis (EPA 600/R-04/004).
For New York State customers, NYSDOH requires disclaimers and qualifiers for various vermiculite containing samples that direct analysis via ELAP198.6 and ELAP198.8 for samples that contain >10% vermiculite mineral where ELAP198.6 may be used to evaluate the asbestos content of the material. However, any test result using ELAP198.6 will be reported with the following disclaimer: “ELAP198.6 method does not remove vermiculite and may underestimate the level of asbestos present in a sample containing >10% vermiculite.”
Further information on this method and other vermiculite and asbestos issues can be found at the following: Agency for Toxic Substances and Disease Registry (ATSDR) www.atsdr.cdc.gov, United States Geological Survey (USGS) www.minerals.usgs.gov/minerals/, US EPA www.epa.gov/asbestos. The USEPA also has an informative brochure "Current Best Practices for Vermiculite Attic Insulation" EPA 747F03001 May 2003, that may assist the health and remediation professional.
The following is a summary of the analytical process outlines in the EPA 600/R-04/004 Method:
1)Analytical Step/Method: Initial Screening by PLM, EPA 600R-93/116 Requirements/Comments: Minimum of 0.1 g of sample. ~0.25% LOQ for most samples.
2)Analytical Step/Method:Wet Separation by PLM Gravimetric Technique, EPA R-04/004 Requirements/Comments: Minimum 50g** of dry sample. Analysis of "Sinks" only.
9000 Commerce Parkway Suite B Mt. Laurel, New Jersey 08054
Telephone: 856-231-9449 Email: customerservice@iatl.com
CERTIFICATE OF ANALYSIS
Client: Aptim 9143 Phillips Highway, Suite 400 Jacksonville FL 32256
2/28/2019Report Date:
Report No.: 584163 - PLM Project: FL103-Rattlesnake Point - USARC Project No.: 631004314
Page 3 of 4Dated : 3/1/2019 3:33:11
3)Analytical Step/Method:Wet Separation by PLM Gravimetric Technique, EPA R-04/004 Requirements/Comments: Minimum 50g** of dry sample.