Savannah, Georgia
Solicitation Number
W912HN-13-R-0018
SHEP Dissolved Oxygen Injection System Volume 2 of 3: Technical Divisions 05 through 28 October 2014
U.S. ARMY ENGINEER DISTRICT, SAVANNAH
CORPS OF ENGINEERS
100 WEST OGLETHORPE AVENUE
SAVANNAH, GEORGIA 31401-3640
US Army Corps of Engineers Savannah District
Dissolved Oxygen Injection Systems 13R18 Savannah, GA
(Revised by Amendment 0002)
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 SUMMARY OF WORK
01 22 00 *1 DELETED MEASUREMENT AND PAYMENT
01 30 00 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 PROJECT SCHEDULE
01 32 17.00 NETWORK ANALYSIS SCHEDULES (NAS)
01 33 00 SUBMITTAL PROCEDURES
01 42 00 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00.00 10 QUALITY CONTROL
01 45 00.10 10 QUALITY CONTROL SYSTEM (QCS)
01 45 35 SPECIAL INSPECTIONS
01 50 00 TEMPORARY CONSTRUCTION FACILITIES AND CONTROLS
01 57 20.00 10 ENVIRONMENTAL PROTECTION
01 57 16 *1 TEMPORARY PEST CONTROL
01 57 23 TEMPORARY STORM WATER POLLUTION CONTROL
01 78 00 CLOSEOUT SUBMITTALS
01 78 23 OPERATION AND MAINTENANCE DATA
01 86 26 RELIABILITY CENTERED ACCEPTANCE FOR ELECTRICAL SYSTEMS
01 91 00 COMMISSIONING
DIVISION 03 - CONCRETE
03 30 00 CAST-IN-PLACE CONCRETE
03 45 33 PRECAST STRUCTURAL CONCRETE
DIVISION 04 - MASONRY
04 20 00 MASONRY
DIVISION 05 - METALS
05 12 00 STRUCTURAL STEEL
05 21 19 OPEN WEB STEEL JOIST FRAMING
05 40 00 COLD-FORMED METAL FRAMING
05 51 00 METAL STAIRS
05 51 33 METAL LADDERS
05 52 00 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 10 00 ROUGH CARPENTRY
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
07 14 00 FLUID-APPLIED WATERPROOFING
07 21 13 BOARD AND BLOCK INSULATION
07 22 00 ROOF AND DECK INSULATION
07 60 00 FLASHING AND SHEET METAL
07 61 14.00 20 STEEL STANDING SEAM ROOFING
07 72 00 ROOF VENTILATORS, GRAVITY-TYPE
07 92 00 JOINT SEALANTS
(Revised by Amendment 0002)
DIVISION 08 - OPENINGS
08 11 13 STEEL DOORS AND FRAMES
08 33 23 OVERHEAD COILING DOORS
08 51 13 ALUMINUM WINDOWS
08 71 00 DOOR HARDWARE
08 81 00 GLAZING
08 91 00 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 51 00 ACOUSTICAL CEILINGS
09 90 00 PAINTS AND COATINGS
09 97 13.26 COATING OF STEEL WATERFRONT STRUCTURES
09 97 23 *2 DELETEDMETALLIC TYPE CONDUCTIVE/SPARK RESISTANT CONCRETE
FLOOR FINISH
DIVISION 10 - SPECIALTIES
10 14 01 EXTERIOR SIGNAGE
10 14 02 INTERIOR SIGNAGE
10 44 16 FIRE EXTINGUISHERS
10 56 13 STEEL SHELVING
DIVISION 12 - FURNISHINGS
12 31 00 MANUFACTURED METAL CASEWORK
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING
23 00 00 AIR SUPPLY AND DISTRIBUTION
23 03 00.00 BASIC MECHANICAL MATERIALS AND METHODS
23 05 48.00 VIBRATION AND SEISMIC CONTROLS FOR HVAC PIPING AND
EQUIPMENT
23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC
23 07 00 THERMAL INSULATION FOR MECHANICAL SYSTEMS
23 08 00.00 10 COMMISSIONING OF HVAC SYSTEMS
23 09 53 SPACE TEMPERATURE CONTROL SYSTEMS
23 31 13.00 METAL DUCTS
23 37 13.00 DIFFUSERS, REGISTERS, AND GRILLS
23 82 02.00 10 UNITARY HEATING AND COOLING EQUIPMENT
DIVISION 26 - ELECTRICAL
26 00 00 BASIC ELECTRICAL MATERIALS AND METHODS
26 05 13.00 MEDIUM-VOLTAGE CABLES (5KV)
26 05 19.00 10 INSULATED WIRE AND CABLE
26 08 00 APPARATUS INSPECTION AND TESTING
26 09 23.00 LIGHTING CONTROL DEVICES
26 11 13.00 MEDIUM VOLTAGE SWITCHGEAR (5 KV)
26 18 23.00 MEDIUM-VOLTAGE SURGE ARRESTERS (5KV)
26 20 00 INTERIOR DISTRIBUTION SYSTEM
26 23 00.00 LOW VOLTAGE SWITCHGEAR (600V)
26 24 16.00 PANELBOARDS
26 24 19.00 MOTOR CONTROL CENTERS
26 28 01.00 10 COORDINATED POWER SYSTEM PROTECTION
26 29 23 VARIABLE FREQUENCY DRIVE SYSTEMS UNDER 600 VOLTS
(Revised by Amendment 0002)
26 29 24 MEDIUM VOLTAGE VARIABLE FREQUENCY DRIVE SYSTEMS
26 41 00.00 LIGHTNING PROTECTION SYSTEM
26 42 13.00 CATHODIC PROTECTION BY GALVANIC ANODES
26 51 00.00 INTERIOR LIGHTING
26 52 00.00 EMERGENCY LIGHTING
26 56 00.00 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 15 19 WIRE LINE DATA TRANSMISSION SYSTEM
27 21 10 FIBER OPTIC DATA TRANSMISSION SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 05 26.00 GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND SECURITY
28 23 23 NETWORK VIDEO SECURITY
28 31 74.00 INTERIOR FIRE DETECTION AND ALARM SYSTEM
DIVISION 31 - EARTHWORK
31 00 00 EARTHWORK
31 05 19 GEOTEXTILE
31 11 00 CLEARING AND GRUBBING
31 32 11 SOIL SURFACE EROSION CONTROL
31 32 39 BIOENGINEERING PRACTICES FOR STREAM BANK AND SHORELINE
STABILIZATION
31 41 16 STEEL SHEET PILING
31 62 16.16 STEEL H-PILES
31 62 19.13 WOOD MARINE PILES
31 63 36 HELICAL PILES
31 68 13 SOIL AND ROCK ANCHORS
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 24 GRADED CRUSHED AGGREGATE BASE COURSE
32 15 00 AGGREGATE SURFACE COURSE
32 16 13 CONCRETE DITCHES AND CURBS AND GUTTERS
32 32 23 SEGMENTAL CONCRETE BLOCK RETAINING WALL
DIVISION 33 - UTILITIES
33 40 00 STORM DRAINAGE UTILITIES
33 71 02 UNDERGROUND ELECTRICAL DISTRIBUTION
DIVISION 35 - WATERWAY AND MARINE CONSTRUCTION
35 20 23 DREDGING
DIVISION 4 - PROCESS INTEGRATION
40 05 13 PIPELINES, LIQUID PROCESS PIPING
40 17 26.00 WELDING PRESSURE PIPING
40 95 00 PROCESS CONTROL
DIVISION 41 - MATERIAL PROCESSING AND HANDLING EQUIPMENT
41 22 13.13 JIB CRANE SYSTEM
(Revised by Amendment 0002)
DIVISION 43 - PROCESS GAS AND LIQUID HANDLING, PURIFICATION, AND STORAGE
EQUIPMENT
43 00 01 TESTING, ADJUSTING, AND BALANCING FOR PROCESS
43 08 00.00 10 COMMISSIONING OF PROCESS SYSTEMS
43 13 10 OXYGEN GENERATION SYSTEMS
43 16 00 SPEECE CONES
43 21 30 SUMP PUMPS
43 21 39 PUMPS: WATER, VERTICAL TURBINE
DIVISION 46 - WATER AND WASTEWATER EQUIPMENT
46 21 12 STOP GATES, GUIDES, LIFTING BEAMS, AND STORAGE RACKS
46 21 51 TRAVELING WATER SCREENS & RETURN TROUGHS (FISH HANDLING
DUAL FLOW SCREEN)
46 21 71 TRASH RAKE SYSTEMS
APPENDICES
Appendix A *2 Speece Cone Scope of Supply and Price Appendix B *2 GA DNR Letter Of Authorization
-- End of Project Table of Contents --
SECTION TABLE OF CONTENTS
DIVISION 05 - METALS
SECTION 05 12 00
STRUCTURAL STEEL
11/11
PART 1 GENERAL
1.1 REFERENCES
1.2 SYSTEM DESCRIPTION
1.3 SUBMITTALS
1.4 AISC QUALITY CERTIFICATION
1.5 SEISMIC PROVISIONS
1.6 QUALITY ASSURANCE
1.6.1 Drawing Requirements
1.6.2 Certifications
1.6.2.1 Overhead, Top Running Crane Rail Beam
1.6.2.2 Erection Plan
1.6.2.3 Welding Procedures and Qualifications
PART 2 PRODUCTS
2.1 STEEL
2.1.1 Structural Shapes for Use in Building Framing
2.1.2 Structural Steel Tubing
2.1.3 Steel Pipe
2.2 BOLTS, NUTS, AND WASHERS
2.2.1 Structural Steel, Structural Steel Tubing and Steel Pipe
2.2.1.1 Bolts
2.2.1.2 Nuts
2.2.1.3 Washers
2.2.2 Foundation Anchorage
2.2.2.1 Anchor Bolts
2.2.2.2 Anchor Nuts
2.2.2.3 Anchor Washers
2.2.2.4 Anchor Plate Washers
2.2.3 Load Indicator Washers
2.2.4 Load Indicator Bolts
2.3 STRUCTURAL STEEL ACCESSORIES
2.3.1 Welding Electrodes and Rods
2.3.2 Non-Shrink Grout
2.3.3 Welded Shear Stud Connectors
2.4 SHOP PRIMER
2.5 GALVANIZING
2.6 GALVNIZED TOUCHUP COATING
2.7 FABRICATION
2.7.1 Markings
2.7.2 Shop Primer
2.7.2.1 Cleaning
2.7.2.2 Primer
2.7.3 Epoxy Coated Surfaces
2.8 DRAINAGE HOLES
SECTION 05 12 00 Page 1
PART 3 EXECUTION
3.1 FABRICATION
3.2 ERECTION
3.2.1 STORAGE
3.3 CONNECTIONS
3.3.1 Common Grade Bolts
3.3.2 High-Strength Bolts
3.3.2.1 Installation of Load Indicator Washers (LIW)
3.4 GAS CUTTING
3.5 WELDING
3.6 SHOP PRIMER REPAIR
3.6.1 Field Priming
3.7 GALVANIZING REPAIR
3.8 FIELD QUALITY CONTROL
3.8.1 Welds
3.8.1.1 Visual Inspection
3.8.1.2 Nondestructive Testing
3.8.2 Load Indicator Washers
3.8.2.1 Load Indicator Washer Compression
3.8.2.2 Load Indicator Gaps
3.8.3 High-Strength Bolts
3.8.3.1 Testing Bolt, Nut, and Washer Assemblies
3.8.3.2 Inspection
3.8.3.3 Testing
3.8.4 Testing for Embrittlement
3.9 SPECIAL INSPECTION AND TESTING FOR SEISMIC-RESISTING SYSTEMS
-- End of Section Table of Contents --
SECTION 05 12 00 Page 2
SECTION 05 12 00
STRUCTURAL STEEL
11/11
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 201 (2006) AISC Certification Program for Structural Steel Fabricators
AISC 325 (2011) Steel Construction Manual
AISC 326 (2009) Detailing for Steel Construction
AISC 341 (2010) Seismic Provisions for Structural Steel Buildings
AISC 360 (2010) Specification for Structural Steel Buildings
AMERICAN WELDING SOCIETY (AWS)
AWS A2.4 (2012) Standard Symbols for Welding, Brazing and Nondestructive Examination
AWS D1.1/D1.1M (2010; Errata 2010) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME B46.1 (2009) Surface Texture, Surface Roughness, Waviness and Lay
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2013) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A143/A143M (2007) Standard Practice for Safeguarding Against Embrittlement of Hot-Dip Galvanized Structural Steel Products and Procedure for Detecting Embrittlement
ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A307 (2012) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile
SECTION 05 12 00 Page 3
Strength
ASTM A325 (2010; E 2013) Standard Specification for Structural Bolts, Steel, Heat Treated, 120/105 ksi Minimum Tensile Strength
ASTM A36/A36M (2012) Standard Specification for Carbon Structural Steel
ASTM A490 (2012) Standard Specification for Structural Bolts, Alloy Steel, Heat Treated, 150 ksi Minimum Tensile Strength
ASTM A500/A500M (2013) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A501 (2007) Standard Specification for Hot-Formed Welded and Seamless Carbon Steel Structural Tubing
ASTM A514/A514M (2005; R 2009) Standard Specification for High-Yield-Strength, Quenched and Tempered Alloy Steel Plate, Suitable for Welding
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A563 (2007a) Standard Specification for Carbon and Alloy Steel Nuts
ASTM A6/A6M (2013a) Standard Specification for General Requirements for Rolled Structural Steel Bars, Plates, Shapes, and Sheet Piling
ASTM A780/A780M (2009) Standard Practice for Repair of Damaged and Uncoated Areas of Hot-Dip Galvanized Coatings
ASTM A992/A992M (2011) Standard Specification for Structural Steel Shapes
ASTM B695 (2004; R 2009) Standard Specification for Coatings of Zinc Mechanically Deposited on Iron and Steel
ASTM C1107/C1107M (2013) Standard Specification for Packaged Dry, Hydraulic-Cement Grout (Nonshrink)
ASTM C827/C827M (2010) Change in Height at Early Ages of Cylindrical Specimens from Cementitious Mixtures
ASTM F1554 (2007a; E 2011) Standard Specification for Anchor Bolts, Steel, 36, 55, and 105-ksi Yield Strength
SECTION 05 12 00 Page 4
ASTM F436 (2011) Hardened Steel Washers
ASTM F844 (2007a; R 2013) Washers, Steel, Plain (Flat), Unhardened for General Use
ASTM F959 (2013) Compressible-Washer-Type Direct Tension Indicators for Use with Structural Fasteners
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC PA 1 (2000; E 2004) Shop, Field, and Maintenance Painting of Steel
SSPC PS 13.01 (1982; E 2004) Epoxy Polyamide Painting System
SSPC Paint 25 (1997; E 2004) Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel, Type I and Type II
SSPC SP 3 (1982; E 2004) Power Tool Cleaning
SSPC SP 6/NACE No.3 (2007) Commercial Blast Cleaning
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1926.756 Steel Erection; Beams and Columns
1.2 SYSTEM DESCRIPTION
Provide the structural steel system, including shop primer or as indicated on the drawings to be galvanizing, complete and ready for use. Structural steel systems including design, materials, installation, workmanship, fabrication, assembly, erection, inspection, quality control, and testing shall be provided in accordance with AISC 360 and AISC 341 except as modified in this contract.
1.3 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Erection Plan; G, RO Fabrication Drawings; G, RO
SD-03 Product Data
Shop Primer Welding Electrodes And Rods Load Indicator Washers Non-Shrink Grout Load Indicator Bolts
SECTION 05 12 00 Page 5
SD-06 Test Reports
Bolts, Nuts, And Washers
SD-07 Certificates
Steel Bolts, Nuts, And Washers Galvanizing Aisc Quality Certification Overhead, Top Running Crane Rail Beam Welding Procedures And Qualifications
1.4 AISC QUALITY CERTIFICATION
Work shall be fabricated in an AISC certified Category Std fabrication plant.
1.5 SEISMIC PROVISIONS
The structural steel system shall be provided in accordance with AISC 341.
1.6 QUALITY ASSURANCE
1.6.1 Drawing Requirements
Submit fabrication drawings for approval prior to fabrication. Prepare in accordance with AISC 326 and AISC 325. Fabrication drawings shall not be reproductions of contract drawings. Include complete information for the fabrication and erection of the structure's components, including the location, type, and size of bolts, welds, member sizes and lengths, connection details, blocks, copes, and cuts. Double connections that require an erection seat to comply with OSHA 29 CFR 1926.756(c)(1) shall be shown on the shop drawings, reviewed and approved by the structural engineer of record. Use AWS A2.4 standard welding symbols. Shoring and temporary bracing shall be designed and sealed by a registered professional engineer and submitted for record purposes, with calculations, as part of the drawings. Member substitutions of details shown on the Contract Drawings shall be clearly highlighted on the fabrication drawings. Explain the reasons for deviations from the Contract Drawings.
1.6.2 Certifications
1.6.2.1 Overhead, Top Running Crane Rail Beam
Submit written field survey results for overhead, top running crane rail beam verifying tolerance alignment requirements, areas out of tolerance and proposed corrective measures.
1.6.2.2 Erection Plan
Submit for record purposes. Indicate the sequence of erection, temporary shoring, and bracing and description of temporary supports.
1.6.2.3 Welding Procedures and Qualifications
Prior to welding, submit certification for each welder stating the type of welding and positions qualified for, the code and procedure qualified under, date qualified, and the firm and individual certifying the
SECTION 05 12 00 Page 6 qualification tests. If the qualification date of the welding operator is more than one-year old, the welding operator's qualification certificate shall be accompanied by a current certificate by the welder attesting to the fact that he has been engaged in welding since the date of certification, with no break in welding service greater than 6 months.
Conform to requirements specified in AWS D1.1/D1.1M.
PART 2 PRODUCTS
2.1 STEEL
2.1.1 Structural Shapes for Use in Building Framing
Wide flange shapes, ASTM A992/A992M.
2.1.2 Structural Steel Tubing
ASTM A500/A500M, Grade B; ASTM A501.
2.1.3 Steel Pipe
ASTM A53/A53M, Type E or S, Grade B, weight class STD (Standard).
2.2 BOLTS, NUTS, AND WASHERS
Submit the certified manufacturer's mill reports which clearly show the applicable ASTM mechanical and chemical requirements together with the actual test results for the supplied fasteners. Provide the following unless indicated otherwise.
2.2.1 Structural Steel, Structural Steel Tubing and Steel Pipe
2.2.1.1 Bolts
ASTM A307, Grade A (unless noted otherwise); ASTM A325, Type 1 where high strength bolts are indicated on the drawings. The bolt heads and the nuts of the supplied fasteners must be marked with the manufacturer's identification mark, the strength grade and type specified by ASTM specifications.
2.2.1.2 Nuts
ASTM A563, Grade and Style for applicable ASTM bolt standard recommended.
2.2.1.3 Washers
ASTM F844 washers for ASTM A307 bolts, and ASTM F436 washers for ASTM A325 bolts.
2.2.2 Foundation Anchorage
2.2.2.1 Anchor Bolts
ASTM F1554 Gr 55, Class 1A.
2.2.2.2 Anchor Nuts
ASTM A563, Grade A, hex style.
SECTION 05 12 00 Page 7
2.2.2.3 Anchor Washers
ASTM F844.
2.2.2.4 Anchor Plate Washers
ASTM A36/A36M.
2.2.3 Load Indicator Washers
ASTM F959. Provide ASTM B695, Class 50, Type 1 galvanizing.
2.2.4 Load Indicator Bolts
ASTM A325, Type 1; ASTM A490, Type 1, with a manufactured notch between the bolt tip and threads. The bolt shall be designed to react to the opposing rotational torques applied by the installation wrench, with the bolt tip automatically shearing off when the proper tension is obtained.
2.3 STRUCTURAL STEEL ACCESSORIES
2.3.1 Welding Electrodes and Rods
AWS D1.1/D1.1M.
2.3.2 Non-Shrink Grout
ASTM C1107/C1107M, with no ASTM C827/C827M shrinkage. Grout shall be nonmetallic.
2.3.3 Welded Shear Stud Connectors
AWS D1.1/D1.1M.
2.4 SHOP PRIMER
SSPC Paint 25, (alkyd primer) or SSPC PS 13.01 epoxy-polyamide, green primer (Form 150) type 1, except provide a Class B coating in accordance with AISC 325 for slip critical joints. Primer shall conform to Federal, State, and local VOC regulations. If flash rusting occurs, re-clean the surface prior to application of primer.
2.5 GALVANIZING
ASTM A123/A123M or ASTM A153/A153M, as applicable, unless specified otherwise galvanize after fabrication where practicable.
2.6 GALVNIZED TOUCHUP COATING
Use zinc-rich coating, manufactured in accordance with ASTM A780/A780M, to repair damaged galvanized steel.
2.7 FABRICATION
2.7.1 Markings
Prior to erection, members shall be identified by a painted erection mark.
Connecting parts assembled in the shop for reaming holes in field
SECTION 05 12 00 Page 8 connections shall be match marked with scratch and notch marks. Do not locate erection markings on areas to be welded. Do not locate match markings in areas that will decrease member strength or cause stress concentrations. Affix embossed tags to hot-dipped galvanized members.
2.7.2 Shop Primer
Shop prime structural steel, except as modified herein, in accordance with SSPC PA 1. Do not prime steel surfaces embedded in concrete, galvanized surfaces, surfaces to receive epoxy coatings, surfaces designed as part of a composite steel concrete section, or surfaces within 0.5 inch of the toe of the welds prior to welding except surfaces on which metal decking is to be welded. Slip critical surfaces shall be primed with a Class B coating.
Prior to assembly, prime surfaces which will be concealed or inaccessible after assembly. Do not apply primer in foggy or rainy weather; when the ambient temperature is below 45 degrees F or over 95 degrees F; or when the primer may be exposed to temperatures below 40 degrees F within 48 hours after application, unless approved otherwise by the Contracting Officer.
2.7.2.1 Cleaning
SSPC SP 6/NACE No.3, except steel exposed in spaces above ceilings, attic spaces, furred spaces, and chases that will be hidden to view in finished construction may be cleaned to SSPC SP 3 when recommended by the shop primer manufacturer. Maintain steel surfaces free from rust, dirt, oil, grease, and other contaminants through final assembly.
2.7.2.2 Primer
Apply primer to a minimum dry film thickness of 2.0 mil except provide the Class B coating for slip critical joints in accordance with the coating manufacturer's recommendations. Repair damaged primed surfaces with an additional coat of primer.
2.7.3 Epoxy Coated Surfaces
Surfaces to receive epoxy coatings shall be cleaned and prepared in accordance with the manufacturer's recommendations.
2.8 DRAINAGE HOLES
Adequate drainage holes shall be drilled to eliminate water traps. Hole diameter shall be 1/2 inch and location shall be indicated on the detail drawings. Hole size and location shall not affect the structural integrity.
PART 3 EXECUTION
3.1 FABRICATION
Fabrication shall be in accordance with the applicable provisions of AISC 325. Fabrication and assembly shall be done in the shop to the greatest extent possible. The fabricating plant shall be certified under the AISC 201 for Category Conventional Steel Building Structures (SBD) Supplement structural steelwork.
Compression joints depending on contact bearing shall have a surface roughness not in excess of 500 micro inch as determined by ASME B46.1, and ends shall be square within the tolerances for milled ends specified in
ASTM A6/A6M.
SECTION 05 12 00 Page 9
Structural steelwork, except surfaces of steel to be encased in concrete, surfaces to be field welded, surfaces to be fireproofed, and contact surfaces of friction-type high-strength bolted connections shall be prepared for painting in accordance with endorsement "P" of AISC 201 and primed with the specified paint.
Shop splices of members between field splices will be permitted only where indicated on the Contract Drawings. Splices not indicated require the approval of the Contracting Officer.
3.2 ERECTION
a. Erection of structural steel, shall be in accordance with the applicable provisions of AISC 325. Erection plan shall be reviewed, stamped and sealed by a licensed structural engineer.
b. Do not splice truss top and bottom chords except as approved by the Contracting Officer. Chord splices shall occur at panel joints at approximately the third point of the span. The center of gravity lines of truss members shall intersect at panel points unless otherwise approved by the Contracting Officer. When the center of gravity lines do not intersect at a panel point, provisions shall be made for the stresses due to eccentricity. Cumber of trusses shall be 1/8 inch in 10 feet unless otherwise indicated.
Provide for drainage in structural steel. After final positioning of steel members, provide full bearing under base plates and bearing plates using nonshrink grout. Place nonshrink grout in accordance with the manufacturer's instructions.
3.2.1 STORAGE
Store material out of contact with the ground in a manner and location that will minimize deterioration.
3.3 CONNECTIONS
Except as modified in this Section, connections not detailed shall be designed in accordance with AISC 360. Build connections into existing work. Do not tighten anchor bolts set in concrete with impact torque wrenches. Punch, subpunch and ream, or drill bolt holes perpendicular to the surface of the member. Holes shall not be cut or enlarged by burning.
Bolts, nuts, and washers shall be clean of dirt and rust, and lubricated immediately prior to installation.
3.3.1 Common Grade Bolts
ASTM A307 bolts shall be tightened to a "snug tight" fit. "Snug tight" is the tightness that exists when plies in a joint are in firm contact. If firm contact of joint plies cannot be obtained with a few impacts of an impact wrench, or the full effort of a man using a spud wrench, contact the Contracting Officer for further instructions.
3.3.2 High-Strength Bolts
ASTM A325 bolts shall be fully tensioned to 70 percent of their minimum tensile strength. Provide load indicator bolts or washers in bolted connections, except provide only load indicator washers for slip critical
SECTION 05 12 00 Page 10 connections. Direct tension indicator tightening, or installation of alternate design fasteners, shall be the only acceptable tightening methods. Use only direct tension indicator tightening for slip critical connections. Bolts shall be installed in connection holes and initially brought to a snug tight fit. After the initial tightening procedure, bolts shall then be fully tensioned, progressing from the most rigid part of a connection to the free edges.
3.3.2.1 Installation of Load Indicator Washers (LIW)
ASTM F959. Where possible, the LIW shall be installed under the bolt head and the nut shall be tightened. If the LIW is installed adjacent to the turned element, provide a flat ASTM F436 washer between the LIW and nut when the nut is turned for tightening, and between the LIW and bolt head when the bolt head is turned for tightening. In addition to the LIW, provide flat ASTM F436 washers under both the bolt head and nut when ASTM A490 bolts are used.
3.4 GAS CUTTING
Use of gas-cutting torch in the field for correcting fabrication errors will not be permitted on major member in the structural framing. Use of a gas cutting torch will be permitted on minor members not under stress only after approval has been obtained from the Contracting Officer.
3.5 WELDING
AWS D1.1/D1.1M, except use only shielded metal arc welding and low hydrogen electrodes for ASTM A514/A514M steel. Do not stress relieve ASTM A514/A514M steel by heat treatment. Grind exposed welds smooth as indicated.
Provide AWS D1.1/D1.1M qualified welders, welding operators, and tackers.
The Contractor shall develop and submit the Welding Procedure Specifications (WPS) for welding, including welding done using prequalified procedures. Prequalified procedures may be submitted for information only;
however, procedures that are not prequalified shall be submitted for approval.
3.6 SHOP PRIMER REPAIR
Repair shop primer in accordance with the paint manufacturer's recommendation for surfaces damaged by handling, transporting, cutting, welding, or bolting.
3.6.1 Field Priming
Field priming of steel exposed to the weather, or located in building areas without HVAC for control of relative humidity. After erection, the field bolt heads and nuts, field welds, and abrasions in the shop coat shall be cleaned and primed with paint of the same quality as that used for the shop coat.
3.7 GALVANIZING REPAIR
Provide as indicated or specified. Galvanize after fabrication where practicable. Repair damage to galvanized coatings using ASTM A780/A780M zinc rich paint for galvanizing damaged by handling, transporting, cutting, welding, or bolting. Do not heat surfaces to which repair paint has been applied.
SECTION 05 12 00 Page 11
3.8 FIELD QUALITY CONTROL
Perform field tests, and provide labor, equipment, and incidentals required for testing. The Contracting Officer shall be notified in writing of defective welds, bolts, nuts, and washers within 7 working days of the date of weld inspection.
3.8.1 Welds
3.8.1.1 Visual Inspection
Inspection by the Government will include proper preparation, size, gaging location, and acceptability of welds; identification marking; operation and current characteristics of welding sets in use.
3.8.1.2 Nondestructive Testing
AWS D1.1/D1.1M. Test locations shall be selected by the Contracting Officer. If more than 20 percent of welds made by a welder contain defects identified by testing, then welds made by that welder shall be tested by radiographic or ultrasonic testing, as approved by the Contracting Officer. When welds made by an individual welder are required to be tested, magnetic particle testing shall be used only in areas inaccessible to either radiographic or ultrasonic testing. Retest defective areas after repair.
3.8.2 Load Indicator Washers
3.8.2.1 Load Indicator Washer Compression
Load indicator washers shall be tested in place to verify that they have been compressed sufficiently to provide the 0.015 inch gap when the load indicator washer is placed under the bolt head and the nut is tightened, and to provide the 0.005 inch gap when the load indicator washer is placed under the turned element, as required by ASTM F959.
3.8.2.2 Load Indicator Gaps
In addition to the above testing, an independent testing agency as approved by the Contracting Officer, shall test in place the load indicator gapson 20 percent of the installed load indicator washers to verify that the ASTM F959 load indicator gaps have been achieved. If more than 10 percent of the load indicators tested have not been compressed sufficiently to provide the average gaps required by ASTM F959, then in place load indicator washers shall be tested to verify that the ASTM F959 load indicator gaps have been achieved. Test locations shall be selected by the Contracting Officer.
3.8.3 High-Strength Bolts
3.8.3.1 Testing Bolt, Nut, and Washer Assemblies
Test a minimum of 3 bolt, nut, and washer assemblies from each mill certificate batch in a tension measuring device at the job site prior to the beginning of bolting start-up. Demonstrate that the bolts and nuts, when used together, can develop tension not less than the provisions specified in AISC 360, depending on bolt size and grade. The bolt tension shall be developed by tightening the nut. A representative of the
SECTION 05 12 00 Page 12 manufacturer or supplier shall be present to ensure that the fasteners are properly used, and to demonstrate that the fastener assemblies supplied satisfy the specified requirements.
3.8.3.2 Inspection
Inspection procedures shall be in accordance with AISC 360. Confirm and report to the Contracting Officer that the materials meet the project specification and that they are properly stored. Confirm that the faying surfaces have been properly prepared before the connections are assembled.
Observe the specified job site testing and calibration, and confirm that the procedure to be used provides the required tension. Monitor the work to ensure the testing procedures are routinely followed on joints that are specified to be fully tensioned.
Inspection by the Government will include calibration of torque wrenches for high-strength bolts. The Contractor shall inspect calibration of torque wrenches for high-strength bolts.
3.8.3.3 Testing
The Government has the option to perform nondestructive tests on 5 percent of the installed bolts to verify compliance with pre-load bolt tension requirements. The Contractor shall allow access for the Government to perform the tests. The nondestructive testing will be done in-place using an ultrasonic measuring device or other device capable of determining in-place pre-load bolt tension. The test locations shall be selected by the Contracting Officer. If more than 10 percent of the bolts tested contain defects identified by testing, then bolts used from the batch from which the tested bolts were taken, shall be tested at the Contractor's expense. Retest new bolts after installation at the Contractor's expense.
3.8.4 Testing for Embrittlement
ASTM A143/A143M for steel products hot-dip galvanized after fabrication.
3.9 SPECIAL INSPECTION AND TESTING FOR SEISMIC-RESISTING SYSTEMS
Special inspections and testing for seismic-resisting systems and components shall be done in accordance with Section 01 45 35 SPECIAL
INSPECTIONS.
-- End of Section --
SECTION 05 12 00 Page 13
SECTION TABLE OF CONTENTS
DIVISION 05 - METALS
SECTION 05 21 19
OPEN WEB STEEL JOIST FRAMING
07/07
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 REGULATORY REQUIREMENT
1.4 DELIVERY AND STORAGE
1.5 QUALITY ASSURANCE
1.5.1 Drawing Requirements
1.5.2 Certification of Compliance
PART 2 PRODUCTS
2.1 JOISTS AND ACCESSORIES
2.2 PAINTING
2.2.1 Shop Painting
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Handling and Erection
3.1.2 Welding
3.2 PAINTING
3.2.1 Touch-Up Painting
3.2.2 Field Painting
3.3 VISUAL INSPECTIONS
3.3.1 Erection Inspection
SECTION 05 21 19 Page 1
SECTION 05 21 19
OPEN WEB STEEL JOIST FRAMING
07/07
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN WELDING SOCIETY (AWS)
AWS B2.1/B2.1M (2009) Specification for Welding Procedure and Performance Qualification
AWS D1.1/D1.1M (2010; Errata 2011) Structural Welding Code - Steel
STEEL JOIST INSTITUTE (SJI)
SJI LOAD TABLES (2005; Errata 1 2006; Errata 2 2007;
Errata 3 2007) 42nd Edition Catalog of Standard Specifications Load Tables and Weight Tables for Steel Joists and Joist Girders
SJI MANUAL (2009) 80 Years of Open Web Steel Joist Construction
SJI TD 10 (2003) Technical Digest No. 10 - Design of Fire Resistive Assemblies with Steel Joists
SJI TD 8 (2008) Technical Digest No. 8 - Welding Of Open-Web Steel Joists And Joist Girders;
2nd Edition
SJI TD 9 (2008) Technical Digest No. 9 - Handling and Erection of Steel Joists and Joist Girders; 3rd Edition
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 15 (1999; E 2004) Steel Joist Shop Primer
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
29 CFR 1910.1200 Hazard Communication
29 CFR 1926 Safety and Health Regulations for Construction
29 CFR 1926.757 Steel Erection; Open Web Steel Joists
SECTION 05 21 19 Page 2
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
Submit the following in accordance with Section 01 33 00 SUBMITTAL
PROCEDURES:
SD-01 Preconstruction Submittals
Welder Qualification Material Safety Data Sheet
SD-02 Shop Drawings
Steel Joist Framing; G, RO
SD-06 Test Reports
Erection Inspection Welding Inspections
SD-07 Certificates
Accessories Certification of Compliance
1.3 REGULATORY REQUIREMENT
All joist girder framing must conform to 29 CFR 1926.757. Secure all joist bridging and anchoring in place prior to the application of any construction loads. Distribute temporary loads so that joist capacity is not exceeded. Do not apply loads to bridging.
1.4 DELIVERY AND STORAGE
Handle, transport, and store joists in a manner to prevent damage affecting their structural integrity. Store all items off the ground in a well drained location protected from the weather and easily accessible for inspection and handling.
1.5 QUALITY ASSURANCE
All work must comply with the requirements set forth in 29 CFR 1926.
1.5.1 Drawing Requirements
Submit steel joist framing drawings. Show joist type and size, layout in plan, and erection details including methods of anchoring, framing at openings, type and spacing of bridging, requirements for field welding, and details of accessories as applicable.
1.5.2 Certification of Compliance
Prior to construction commencement, submit Material Safety Data Sheetper 29 CFR 1910.1200 for steel joists , and certification for welder qualification, compliance with AWS B2.1/B2.1M, welding operation, and tacker, stating the type of welding and positions qualified for, the code
SECTION 05 21 19 Page 3 and procedure qualified under, date qualified, and the firm and individual certifying the qualification tests.
Submit certification of compliance for the following:
SJI MANUAL
SJI TD 8
SJI TD 9
SJI TD 10
29 CFR 1926
29 CFR 1926.757
PART 2 PRODUCTS
2.1 JOISTS AND ACCESSORIES
Provide design data from SJI LOAD TABLES for the joist series indicated.
2.2 PAINTING
2.2.1 Shop Painting
Clean and prime joists in accordance with SSPC Paint 15, using only Type I, "Red Oxide Paint." Finish coat of paint is specified in Section 09 90 00
PAINTING AND COATING.
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Handling and Erection
Conform to SJI LOAD TABLES for the joist series indicated.
3.1.2 Welding
All welding must conform to AWS B2.1/B2.1M and AWS D1.1/D1.1M.
3.2 PAINTING
3.2.1 Touch-Up Painting
After erection of joists, touch-up connections and areas of abraded shop coat with paint of the same type used for the shop coat.
3.2.2 Field Painting
Paint joists requiring a finish coat in conformance with the requirements of Section 09 90 00 PAINTING AND COATING.
3.3 VISUAL INSPECTIONS
3.3.1 Erection Inspection
AWS D1.1/D1.1M, Section 6. Perform erection inspection and field welding inspections with AWS certified welding inspectors. Welding inspectors must visually inspect and mark welds.
SECTION 05 21 19 Page 4
SECTION 05 21 19 Page 5
SECTION TABLE OF CONTENTS
DIVISION 05 - METALS
SECTION 05 40 00
COLD-FORMED METAL FRAMING
04/06
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 DELIVERY, STORAGE, AND HANDLING
1.4 MAXIMUM DEFLECTION
1.5 QUALITY ASSURANCE
1.5.1 Drawing Requirements
1.5.2 Design Data Required
PART 2 PRODUCTS
2.1 STEEL ACCESSORIES
2.1.1 Studs of 18 Gage (0.0478 Inch) and Lighter
2.1.2 Roof Truss Members
2.1.3 Sizes, Gages, Section Modulus, and Other Structural Properties
2.2 MARKINGS
2.3 CONNECTIONS
2.4 PLASTIC GROMMETS
PART 3 EXECUTION
3.1 FASTENING
3.1.1 Screws
3.1.2 Anchors
3.2 INSTALLATION
3.2.1 Tracks
3.2.2 Trusses
3.2.3 Erection Tolerances
SECTION 05 40 00 Page 1
SECTION 05 40 00
COLD-FORMED METAL FRAMING
04/06
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI SG02-1 (2001) North American Specification for the Design of Cold-Formed Steel Structural Members
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2008) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A153/A153M (2005) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A1008/A1008M (2013) Standard Specification for Steel, Sheet, Cold-Rolled, Carbon, Structural, High-Strength Low-Alloy and High-Strength Low-Alloy with Improved Formability, Solution Hardened, and Bake Hardened
ASTM A653/A653M (2013) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B633 (2007) Standard Specification for Electrodeposited Coatings of Zinc on Iron and Steel
ASTM C955 (2011c) Load-Bearing (Transverse and Axial) Steel Studs, Runners (Tracks), and Bracing or Bridging for Screw Application of Gypsum Panel Products and Metal Plaster Bases
SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)
SAE J78 (1998) Steel Self Drilling Tapping Screws
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control
SECTION 05 40 00 Page 2 approval. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government.
The following shall be submitted in accordance with Section 01 33 00
SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Framing Components; G, RO
SD-03 Product Data
Accessories; G, RO
SD-05 Design Data
Metal Framing Calculations; G, RO
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to job site and store in adequately ventilated, dry locations. Storage area shall permit easy access for inspection and handling. If necessary to store materials outside, stack off the ground, support on a level platform, and protect from the weather as approved.
Handle materials to prevent damage. Finish of the framing members shall be maintained at all times, using an approved high zinc dust content, galvanizing repair paint whenever necessary to prevent the formation of rust. Replace damaged items with new, as directed by the Contracting Officer.
1.4 MAXIMUM DEFLECTION
Maximum deflectionf or roof rafters shall be L/240 - live load only.
1.5 QUALITY ASSURANCE
1.5.1 Drawing Requirements
Submit framing components to show sizes, thicknesses, layout, material designations, methods of installation, and accessories. Shop drawings shall indicate:
a. Cross sections, plans, and/or elevations showing component types and locations for each framing application; including shop coatings and material thicknesses for each framing component.
b. Connection details showing fastener type, quantity, location, and other information to ensure proper installation.
c. Drawings depicting panel configuration, dimensions, components, locations, and construction sequence if the Contractor elects to install prefabricated/prefinished frames.
d. For Steel accessories, include layout, spacings, sizes, thicknesses, and types of cold-formed metal framing; fabrication; and fastening and anchorage details, including mechanical fasteners.
e. Include structural analysis data, signed and sealed by the qualified professional engineer responsible for their preparation.
SECTION 05 40 00 Page 3
1.5.2 Design Data Required
Submit metal framing calculations to verify sizes, gages, and spacing of members and connections. Show methods and practices used in installation.
PART 2 PRODUCTS
2.1 STEEL ACCESSORIES
Framing components (studs, trusses, tracks, bracing, bridging, etc.) shall comply with ASTM C955 and the following.
2.1.1 Studs of 18 Gage (0.0478 Inch) and Lighter
Studs and Joists of 18 Gage (0.0478 Inch) and Lighter, Track, and Accessories (All Gages): Galvanized steel, ASTM A653/A653M, SS, Grade 50 33,000 psi G60; or carbon steel, ASTM A1008/A1008M, Grade C, painted.
2.1.2 Roof Truss Members
Manufacturer's standard C-shaped steel sections, of web depths indicated, unpunched, with stiffened flanges, complying with ASTM C955, of minimum uncoated-steel thickness and flange width indicated on Shop Drawings.
2.1.3 Sizes, Gages, Section Modulus, and Other Structural Properties
Size and gage as indicated.
2.2 MARKINGS
Studs and track shall have product markings stamped on the web of the section. The markings shall be repeated throughout the length of the member at a maximum spacing of 4 feet on center and shall be legible and easily read. The product marking shall include the following:
a. An ICBO number.
b. Manufacturer's identification.
c. Minimum delivered uncoated steel thickness.
d. Protective coating designator.
e. Minimum yield strength.
2.3 CONNECTIONS
Screws for steel-to-steel connections shall be self-drilling tapping in compliance with SAE J78 of the type, size, and location as shown on the drawings. Electroplated screws shall have a Type II coating in accordance with ASTM B633. Screws, bolts, and anchors shall be hot-dipped galvanized in accordance with ASTM A123/A123M or ASTM A153/A153M as appropriate.
Screws bolts, and anchors shall be hot dipped galvanized in accordance with ASTM A123/A123M or ASTM A153/A153M as appropriate.
2.4 PLASTIC GROMMETS
Supply plastic grommets, recommended by stud manufacturer, to protect electrical wires. Prevent metal to metal contact for plumbing pipes.
SECTION 05 40 00 Page 4
PART 3 EXECUTION
3.1 FASTENING
Fasten framing members together by using self-drilling or self-tapping screws. Screw connections shall be as required and indicated in the design calculations.
3.1.1 Screws
Screws shall be self-drilling self-tapping type, size, and location shown on the drawings. Screw penetration through joined materials shall not be less than three exposed threads. Minimum spacings and edge distances for screws shall be as specified in AISI SG02-1. Screws covered by sheathing materials shall have low profile heads.
3.1.2 Anchors
Anchors shall be of the type, size, and location shown on the drawings.
3.2 INSTALLATION
3.2.1 Tracks
Provide accurately aligned runners at top and bottom of partitions. Anchor tracks as indicated in design calculations. Butt weld joints in tracks or splice with stud inserts. Fasteners shall be at least 3 inches from the edge of concrete slabs.
3.2.2 Trusses
Install, bridge, and brace trusses according to shop drawings. Do not alter, cut, or remove framing members or connections of trusses.
a. Erect trusses with plane of truss webs plumb and parallel to each other, align, and accurately position at spacings indicated.
b. Erect trusses without damaging framing members or connections.
c. Anchor trusses securely at all bearing points.
d. Install continuous bridging and permanently brace trusses as indicated.
CLEAR SPAN BRIDGING
Up to 14 feet One row near center 14 to 20 feet Two rows at 1/3 points 20 to 26 feet Three rows at 1/4 points 26 to 32 feet Four rows at 1/5 points
Temporary bracing shall be provided and remain in place until work is permanently stabilized.
3.2.3 Erection Tolerances
a. Framing members which shall be covered by finishes such as wallboard, plaster, or ceramic tile set in a mortar setting bed, shall be within the following limits:
SECTION 05 40 00 Page 5
(1) Layout of walls and partitions: 1/4 inch from intended position;
(2) Plates and runners: 1/4 inch in 8 feet from a straight line;
(3) Studs: 1/4 inch in 8 feet out of plumb, not cumulative; and
(4) Face of framing members: 1/4 inch in 8 feet from a true plane.
b. Framing members which shall be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive shall be within the following limits:
(1) Layout of walls and partitions: 1/4 inch from intended position;
(2) Plates and runners: 1/8 inch in 8 feet from a straight line;
(3) Studs: 1/8 inch in 8 feet out of plumb, not cumulative; and
(4) Face of framing members: 1/8 inch in 8 feet from a true plane.
SECTION 05 40 00 Page 6
SECTION TABLE OF CONTENTS
DIVISION 05 - METALS
SECTION 05 51 00
METAL STAIRS
02/12
PART 1 GENERAL
1.1 REFERENCES
1.2 SUBMITTALS
1.3 QUALIFICATIONS FOR WELDING WORK
PART 2 PRODUCTS
2.1 GENERAL REQUIREMENTS
2.2 STRUCTURAL STEEL PLATES, SHAPES AND BARS
2.3 STRUCTURAL STEEL TUBING
2.4 STEEL PIPE
2.5 FASTENERS
2.6 GENERAL FABRICATION
2.7 PROTECTIVE COATING
2.8 STEEL PAN STAIRS
2.8.1 General
2.8.2 Stair Framing
2.8.3 Riser, Subtread, And Subplatform Metal Pans
2.8.4 Safety Nosings For Concrete Treads
2.8.5 Steel Stairs
2.8.5.1 Design Loads
2.8.5.2 Materials
PART 3 EXECUTION
3.1 STEEL STAIRS
3.2 INSTALLATION OF SAFETY NOSINGS
3.3 FIELD WELDING
3.4 TOUCHUP PAINTING
SECTION 05 51 00 Page 1
SECTION 05 51 00
METAL STAIRS
02/12
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 360 (2010) Specification for Structural Steel Buildings
AMERICAN WELDING SOCIETY (AWS)
AWS D1.1/D1.1M (2010; Errata 2011) Structural Welding Code - Steel
ASME INTERNATIONAL (ASME)
ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and Screws (Inch Series)
ASME B18.6.1 (1981; R 2008) Wood Screws (Inch Series)
ASME B18.6.3 (2013) Machine Screws, Tapping Screws, and Machine Drive Screws (Inch Series)
ASTM INTERNATIONAL (ASTM)
ASTM A153/A153M (2009) Standard Specification for Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A283/A283M (2013) Standard Specification for Low and Intermediate Tensile Strength Carbon Steel Plates
ASTM A307 (2012) Standard Specification for Carbon Steel Bolts and Studs, 60 000 PSI Tensile Strength
ASTM A36/A36M (2012) Standard Specification for Carbon Structural Steel
ASTM A500/A500M (2013) Standard Specification for Cold-Formed Welded and Seamless Carbon Steel Structural Tubing in Rounds and Shapes
ASTM A53/A53M (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
SECTION 05 51 00 Page 2
ASTM A653/A653M (2013) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B209 (2010) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 101 (2012; Amendment 1 2012) Life Safety Code
THE SOCIETY FOR PROTECTIVE COATINGS (SSPC)
SSPC Paint 25 (1997; E 2004) Zinc Oxide, Alkyd, Linseed Oil Primer for Use Over Hand Cleaned Steel, Type I and Type II
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for information only. When used, a designation following the "G" designation identifies the office that will review the submittal for the Government. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Iron and Steel Hardware; G, RO Steel Shapes, Plates, Bars and Strips; G, RO Metal Stair System; G, RO
SD-03 Product Data
Structural Steel Plates, Shapes, and Bars; G, RO Structural Steel Tubing; G, RO Protective Coating; G, RO Steel Pan Stairs; G, RO Steel Stairs; G, RO
SD-08 Manufacturer's Instructions
Structural Steel Plates, Shapes, and Bars; G, RO Structural Steel Tubing; G, RO
1.3 QUALIFICATIONS FOR WELDING WORK
Section 05 12 00 STRUCTURAL STEEL applies to work specified in this section.
PART 2 PRODUCTS
2.1 GENERAL REQUIREMENTS
Submit complete and detailed fabrication drawings for iron and steel hardware, and for steel shapes, plates, bars and strips used in accordance with the design specifications referenced in this section.
Pre-assemble items in the shop to the greatest extent possible.
SECTION 05 51 00 Page 3
Disassemble units only to the extent necessary for shipping and handling.
Clearly mark units for reassembly and coordinated installation.
For the fabrication of work exposed to view, use only materials that are smooth and free of surface blemishes, including pitting, seam marks, roller marks, rolled trade names, and roughness. Remove blemishes by grinding, or by welding and grinding, prior to cleaning, treating, and application of surface finishes, including zinc coatings.
2.2 STRUCTURAL STEEL PLATES, SHAPES AND BARS
Structural-size shapes and plates, conforming to ASTM A36/A36M, unless otherwise noted, except bent or cold-formed plates.
Steel plates - bent or cold-formed, conforming to ASTM A283/A283M, Grade C.
Steel bars and bar-size shapes, conforming to ASTM A36/A36M, unless otherwise noted for steel bars and bar-size shapes.
2.3 STRUCTURAL STEEL TUBING
Structural steel tubing, hot-formed, welded or seamless, conforming to ASTM A500/A500M, Grade B, unless otherwise noted.
2.4 STEEL PIPE
Steel pipe conforming to ASTM A53/A53M, type as selected, Grade B; primed finish, unless galvanizing is required; standard weight (Schedule 40).
2.5 FASTENERS
Galvanized zinc-coated fasteners in accordance with ASTM A153/A153M and used for exterior applications or where built into exterior walls or floor systems. Select fasteners for the type, grade, and class required for the installation of steel stair items.
Standard/regular hexagon-head bolts and nuts be conforming to ASTM A307, Grade A.
Square-head lag bolts conforming to ASME B18.2.1.
Machine screws cadmium-plated steel conforming to ASME B18.6.3.
Wood screws, flat-head carbon steel conforming to ASME B18.6.1.
Lockwashers helical spring, carbon steel conforming to.
2.6 GENERAL FABRICATION
Prepare and submit metal stair system shop drawings with detailed plans and elevations at not less than 1 inch to 1 foot with details of sections and connections at not less than 3 inches to 1 foot. Also detail placement drawings, diagrams, templates for installation of anchorage, including but not limited to, concrete inserts, anchor bolts, and miscellaneous metal items having integral anchorage devices.
Use materials of size and thicknesses indicated or, if not indicated, of
SECTION 05 51 00 Page 4 required size and thickness to produce adequate strength and durability in finished product for intended…