Fire Hydrant Flow
Test Report
We Deliver May 25, 2018
Page | 1
Fire Hydrant Flow Test Report | FOR OFFICIAL USE ONLY | May 25, 2018
Code of Business Conduct 2015 KBR Fire Hydrant Flow Test Report
1. The first test was performed on May 24, 2018 during off-peak hours. The test started at 1:30 PM and had the following results:
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant # 2):
Static pressure: 85 psi;
Residual pressure (with one flow hydrant #1 fully open): 70 psi.
Flow hydrant result (hydrant # 1):
Pitot pressure: 28 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 28
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√28 = 888.18 𝑔𝑝𝑚
𝑄𝑓 = 𝑄 [ 𝑃𝑠 − 20
𝑃𝑠 − 𝑃𝑟
0.54
𝑄𝑓 = 888.178 [ 85 − 20
85 − 70
= 1960.577 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 2
2. The second test was performed on June 29, 2017 during peak hours. The test started at 2:00 PM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #6):
Static pressure: 75 psi;
Residual pressure (with one flow hydrant #5 fully open): 70 psi.
Flow hydrant result (hydrant #5):
Pitot pressure: 22 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 22
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√22 = 787.28 𝑔𝑝𝑚
𝑃𝑠 − 𝑃𝑟
𝑄𝑓 = 787.28 [ 75 − 20
75 − 70
= 2873.963 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 3
3. The third test was performed on May 24, 2018 during peak hours. The test started at 2:15 PM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #7):
Static pressure: 65 psi;
Residual pressure (with one flow hydrant #8 fully open): 60 psi.
Flow hydrant result (hydrant #8):
Pitot pressure: 24 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 24
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√24 = 822.293 𝑔𝑝𝑚
𝑃𝑠 − 𝑃𝑟
𝑄𝑓 = 822.293 [ 65 − 20
65 − 60
= 2693.503 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 4
4. The fourth test was performed on May 24, 2018 during peak hours. The test started at 2:30 PM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #12):
Static pressure: 60 psi;
Residual pressure (with one flow hydrant #11 fully open): 55 psi.
Flow hydrant result (hydrant #11):
Pitot pressure: 24 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5
𝑃𝑠 − 𝑃𝑟
60 − 20
60 − 55
= 2527.523 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 5
5. The fourth test was performed on May 25, 2018 during peak hours. The test started at 6:00 AM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #15):
Static pressure: 60 psi;
Residual pressure (with one flow hydrant #16 fully open): 55 psi.
Flow hydrant result (hydrant #16):
Pitot pressure: 24 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5
𝑃𝑠 − 𝑃𝑟
60 − 20
60 − 55
= 2527.523 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 6
6. The fourth test was performed on May 25, 2018 during peak hours. The test started at 6:15 AM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #26):
Static pressure: 70 psi;
Residual pressure (with one flow hydrant #27 fully open): 65 psi.
Flow hydrant result (hydrant #27):
Pitot pressure: 27 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 27
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√27 = 872.174 𝑔𝑝𝑚
𝑃𝑠 − 𝑃𝑟
𝑄𝑓 = 872.174 [ 70 − 20
70 − 65
= 3024.148 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 7
7. The fourth test was performed on May 25, 2018 during peak hours. The test started at 6:30 AM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #41):
Static pressure: 70 psi;
Residual pressure (with one flow hydrant #40 fully open): 60 psi.
Flow hydrant result (hydrant #40):
Pitot pressure: 25 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 25
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√25 = 839.25 𝑔𝑝𝑚
𝑃𝑠 − 𝑃𝑟
𝑄𝑓 = 839.25 [ 70 − 20
70 − 60
= 2001.405 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖
Page | 8
8. The fourth test was performed on May 25, 2018 during peak hours. The test started at 6:45 AM
Water main diameter: ∅250 𝑚𝑚 (9.84 𝑖𝑛𝑐ℎ) Residual hydrant results (hydrant #47):
Static pressure: 80 psi;
Residual pressure (with one flow hydrant #46 fully open): 75 psi.
Flow hydrant result (hydrant #46):
Pitot pressure: 28 psi.
Discharge: 𝑄 = 29.84𝑐𝑑2√𝑝 c = 0.90 d = 2.5 p = 28
𝑄 = 29.84 ∗ 0.9 ∗ 2.52√28 = 888.18 𝑔𝑝𝑚
𝑃𝑠 − 𝑃𝑟
𝑄𝑓 = 888.18 [ 80 − 20
80 − 75
= 3398.277 𝑔𝑝𝑚 𝑎𝑡 20 𝑝𝑠𝑖