DRAWN:
DATE:
DRAWING
NUMBER
REV.
TITLE
SCALE: APPROVED:DRAWN APPR. DATENO. REVISION
BRL
EI-1
NONE
U.S. Army Corps of Engineers
Dredge Goetz Fountain City, WI
DRAWING NUMBER
9300 EVERGREEN BOULEVARD NW
MINNEAPOLIS, MN 554335815
US Army Corps of Engineers - Dredge Goetz Variable Frequency Drives Replacement Electrical Drawing List, Sheet 1 of 3
ELECTRICAL DRAWING INDEX
DREDGE GOETZ VFD REPLACEMENT
SHEET 1 OF 3
EI-1
01-25-21
ISSUED FOR CONSTRUCTION0 BRL 1-25-21
DRAWING NO. REVISION DESCRIPTION USACE ORIGINAL DRAWING NUMBERS
EI-1 TO 3 0 ELECTRICAL DRAWING INDEX
DEL-1 TO 4 0 ELECTRICAL DEMOLITION - ELEVATION, 600V AND 480V SWITCHGEAR 659D-740-01 SHT 1, 2; 659D740-02 SHT 1, 3
EEL-1 TO 4 0 ELECTRICAL CONSTRUCTION - ELEVATION, 600V AND 480V SWITCHGEAR 659D-740-01 SHT 1, 2; 659D740-02 SHT 1, 3
D0L-1 TO 2 0 ELECTRICAL DEMOLITION - ONELINE, 600V AND 480V SWITCHGEAR 659D-720-01 SHT 1, 3
EOL-1 TO 2 0 ELECTRICAL CONSTRUCTION - ONELINE, 600V AND 480V SWITCHGEAR 659D-720-01 SHT 1, 3
DS-1.1 TO DS-1.3 0 ELECTRICAL DEMOLITION - SCHEMATIC - CENTER SPUD HOIST WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-09 SHT. 2; 659-D750-10 SHT. 1; 659-D750-10 SHT. 2
ES-1.1 TO ES-1.3 0 ELECTRICAL CONSTRUCTION - SCHEMATIC - CENTER SPUD HOIST WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-09 SHT. 2; 659-D750-10 SHT. 1; 659-D750-10 SHT. 2
DS-2.1 TO DS-2.3 0 ELECTRICAL DEMOLITION - SCHEMATIC - STARBOARD SPUD HOIST WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-12 SHT. 2; 659-D750-13 SHT. 1; 659-D750-13 SHT. 2
ES-2.1 TO ES-2.3 0 ELECTRICAL CONSTRUCTION - STARBOARD SPUD HOIST WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-12 SHT. 2; 659-D750-13 SHT. 1; 659-D750-13 SHT. 2
DS-3.1 TO DS-3.3 0 ELECTRICAL DEMOLITION - WALKING SPUD CARRIAGE WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-24 SHT. 2; 659-D750-25 SHT. 1; 659-D750-25 SHT. 2
ES-3.1 TO ES-3.3 0 ELECTRICAL CONSTRUCTION - WALKING SPUD CARRIAGE WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-24 SHT. 2; 659-D750-25 SHT. 1; 659-D750-25 SHT. 2
DS-4.1 TO DS-4.3 0 ELECTRICAL DEMOLITION - STARBOARD SWING WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-21 SHT. 2; 659-D750-10 SHT. 1; 659-D750-10 SHT. 2
ES-4.1 TO ES-4.3 0 ELECTRICAL CONSTRUCTION - STARBOARD SWING WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-21 SHT. 2; 659-D750-10 SHT. 1; 659-D750-10 SHT. 2
DS-5.1 TO DS-5.3 0 ELECTRICAL DEMOLITION - PORT SWING WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-18 SHT. 2; 659-D750-19 SHT. 1; 659-D750-19 SHT. 2
ES-5.1 TO ES-5.3 0 ELECTRICAL CONSTRUCTION - PORT SWING WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-18 SHT. 2; 659-D750-19 SHT. 1; 659-D750-19 SHT. 2
DS-6.1 TO DS-6.3 0 ELECTRICAL DEMOLITION - LADDER WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-15 SHT. 2; 659-D750-16 SHT. 1; 659-D750-16 SHT. 2
ES-6.1 TO ES-6.3 0 ELECTRICAL CONSTRUCTION - LADDER WINCH AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-15 SHT. 2; 659-D750-16 SHT. 1; 659-D750-16 SHT. 2
DS-7.1 TO DS-7.5 0 ELECTRICAL DEMOLITION - CUTTER DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-06 SHT. 2; 659-D750-07 SHT. 1 TO 4
ES-7.1 TO ES-7.3 0 ELECTRICAL CONSTRUCTION - CUTTER DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-06 SHT. 2; 659-D750-07 SHT. 1, 3
DS-8.1 TO DS-8.8 0 ELECTRICAL DEMOLITION - SCHEMATIC - DREDGE PUMP MASTER DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-01 SHT. 1 TO 2; 659-D750-02 SHT. 1 TO 6
ES-8.1 TO ES-8.6 0 ELECTRICAL CONSTRUCTION - SCHEMATIC - DREDGE PUMP MASTER AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-01 SHT. 1 TO 2; 659-D750-02 SHT. 1, 3, 4, 6
DS-9.1 TO DS-9.8 0 ELECTRICAL DEMOLITION - SCHEMATIC - DREDGE PUMP SLAVE DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-03 SHT. 1 TO 2; 659-D750-04 SHT. 1 TO 6
ES-9.1 TO ES-9.6 0 ELECTRICAL CONSTRUCTION - SCHEMATIC - DREDGE PUMP SLAVE AC DRIVE THREE LINE & SCHEMATIC DIAGRAMS 659-D750-03 SHT. 1 TO 2; 659-D750-04 SHT. 1, 3, 4, 6
DAN-1 0 ELECTRICAL DEMOLITION - DREDGE AUTOMATION NETWORK DA-1005-01
EAN-1 0 ELECTRICAL CONSTRUCTION - DREDGE AUTOMATION NETWORK DA-1005-01
DWG. DEL-1 REV. 0, 1-25-21
600V & 480V SWITCHGEAR ELEVATION
DEMOLITION, SHEET 1 OF 4
GENERAL NOTES
1. THIS DRAWING PROVIDED
FOR REFERENCE.
2. SEE DEMOLITION
SCHEMATIC DRAWINGS
DS-X.X FOR DETAILS OF
DEMOLITION WORK TO BE
PERFORMED IN DRIVE
CUBICLES.
DWG. DEL-2 REV. 0, 1-25-21
DEMOLITION, SHEET 2 OF 4
REMOVE KEYPAD
FROM DOOR (3
PLACES). PROTECT
AND SAVE KEYPAD.
TURN KEYPAD OVER
TO L&S ELECTRIC.
SEE DWG. EDD-5.
DWG. DEL-3 REV. 0, 1-25-21
DEMOLITION, SHEET 3 OF 4
GENERAL NOTES
1. THIS DRAWING PROVIDED
FOR REFERENCE.
2. SEE DEMOLITION
SCHEMATIC DRAWINGS
DS-X.X FOR DETAILS OF
DEMOLITION WORK TO BE
PERFORMED IN DRIVE
CUBICLES.
DWG. DEL-4 REV. 0, 1-25-21
DEMOLITION, SHEET 4 OF 4
REMOVE KEYPAD
FROM DOOR (6
PLACES). PROTECT
AND SAVE KEYPAD.
TURN KEYPAD OVER
TO L&S ELECTRIC.
SEE DWG. EDD-5.
DWG. EEL-1 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION,
SHEET 1 OF 4
GENERAL NOTES
1. RED COLORED TEXT AND
LINES REPRESENT NEW
CONSTRUCTION.
2. BLACK COLORED TEXT
AND LINES REPRESENT
EXISTING CONSTRUCTION.
DWG. EEL-2 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION, SHEET 2 OF 4
Key-Pad / Control Panel
GENERAL NOTES
1. RED COLORED TEXT AND LINES REPRESENT
NEW CONSTRUCTION.
2. BLACK COLORED TEXT AND LINES
REPRESENT EXISTING CONSTRUCTION.
DWG. EEL-3 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION, SHEET 3 OF 4
GENERAL NOTES
1. RED COLORED TEXT AND LINES REPRESENT
NEW CONSTRUCTION.
DWG. EEL-4 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION, SHEET 4 OF 4
Key-Pad / Control Panel
GENERAL NOTES
1. RED COLORED TEXT AND LINES REPRESENT
NEW CONSTRUCTION.
DWG. D0L-1 REV. 0, 1-25-21
600V & 480V SWITCHGEAR ONELINE
DEMOLITION, SHEET 1 OF 2
KEY NOTES
ELECTRICAL DEMOLITION, THIS AREA
SEE ELECTRICAL SCHEMATIC DEMOLITION DRAWINGS:
CUTTER MOTOR DRIVE: DS-7.1 TO DS-7.5
DREDGE PUMP MOTOR #1 (MASTER) DRIVE: DS-8.1 TO DS-8.8
DREDGE PUMP MOTOR #2 (SLAVE) DRIVE: DS-9.1 TO DS-9.8
11 11 11
KEY NOTES
ELECTRICAL DEMOLITION, THIS AREA
SEE ELECTRICAL SCHEMATIC DEMOLITION DRAWINGS:
CENTER SPUD WINCH: DS-1.1 TO DS-1.3
STARBOARD SPUD WINCH DRIVE: DS-2.1 TO DS-2.3
SPUD CARRIAGE WINCH DRIVE: DS-3.1 TO DS-3.3
STARBOARD SWING WINCH DRIVE: DS-4.1 TO DS-4.3
PORT SWING WINCH DRIVE: DS-5.1 TO DS-5.3
LADDER WINCH DRIVE: DS-6.1 TO DS-6.3
DWG. D0L-2 REV. 0, 1-25-21
600V & 480V SWITCHGEAR ONELINE
DEMOLITION, SHEET 2 OF 2
11 11 11 11 11
350A
DWG. E0L-1 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION, SHEET 1 OF 2
AC VARIABLE
SPEED DRIVE
450 HP
600VAC
AC VARIABLE
SPEED DRIVE
1250 HP
600VAC
DU/DT DRIVE
OUTPUT FILTER
(2) 725A
AC VARIABLE
SPEED DRIVE
1250 HP
600VAC
DU/DT DRIVE
OUTPUT FILTER
(2) 725A
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION,
THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING
CONSTRUCTION.
FU
800A
600VAC
(TYP. 6)
FU
800A
600VAC
(TYP. 6)
DWG. E0L-2 REV. 0, 1-25-21
ELECTRICAL CONSTRUCTION, SHEET 2 OF 2
AC VARIABLE
SPEED DRIVE
250 HP
600VAC
AC VARIABLE
SPEED DRIVE
250 HP
600VAC
AC VARIABLE
SPEED DRIVE
250 HP
600VAC
AC VARIABLE
SPEED DRIVE
250 HP
600VAC
AC VARIABLE
SPEED DRIVE
250 HP
600VAC
AC VARIABLE
SPEED DRIVE
100 HP
600VAC
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT
NEW CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT
EXISTING CONSTRUCTION.
FU
150A
600VAC
(TYP. 3)
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE. LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
12 12
DWG. DS-1.1 REV. 0, 1-25-21
CENTER SPUD WINCH DRIVE
DEMOLITION, SHEET 1 OF 3
K
EY
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
1 1 D
W G
. D S-
1.
R
EV
. 0
, 1 -2
5-
C
EN
TE
R
S
PU
D W
IN
C
H D
R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
1 1
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-1.3 REV. 0, 1-25-21
CENTER SPUD WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #2 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-302A-5+C131+
D150+E208+P444+R700
DWG. ES-1.1 REV. 0, 1-25-21
CENTER SPUD WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E C
E N
T E
R S
P U
D W
IN
C
H D
R
IV
E N
E W
C O
N S
T R
U C
T
IO
N S
H E
E T
O
F
F O
R W
IR
IN
G D
E T
A
IL
S
D W
G . E
S- 1.
. 0
, 1 -2
5-
C
EN
TE
R
S
PU
D W
IN
C
H D
R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B V
FD
13416
XR01
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-10
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-09
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-10
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-302A-5+C131+D150
+E208+P444+R700
DWG. ES-1.3 REV. 0, 1-25-21
CENTER SPUD WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
12FROM STARBOARD SPUD DRIVE FDNA-01 (CAN_H) DWG # 659-D750-13 SHT 2 OF 2
FROM STARBOARD SPUD DRIVE FDNA-01 (CAN_L) DWG # 659-D750-13 SHT 2 OF 2
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_H) DWG # 659-D750-04 SHT. 4 OF 6
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_L) DWG # 659-D750-04 SHT. 4 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE.LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
12 12
DWG. DS-2.1 REV. 0, 1-25-21
STARBOARD SPUD WINCH DRIVE
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
1 1 D
W G
. D S-
2.
. 0 , 1
-2 5-
ST
A
R B
O A
R D
S
PU
D W
IN
C
H D
R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-2.3 REV. 0, 1-25-21
STARBOARD SPUD WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #2 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-302A-5+C131+
D150+E208+P444+R700
DWG. ES-2.1 REV. 0, 1-25-21
STARBOARD SPUD WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E S
T A
R B
O A
R D
S P
U D
W
IN
C H
D R
IV
E
N E
W C
O N
S T
R U
C T
IO
N
S H
E E
T
O F
F
O R
W
IR
IN
G
D E
T A
IL
S
D W
G . E
S- 2.
. 0
, 1 -2
5-
ST
A
R B
O A
R D
S
PU
D W
IN
C
H D
R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-13
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-12
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-13
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-302A-5+C131+D150
+E208+P444+R700
DWG. ES-2.3 REV. 0, 1-25-21
STARBOARD SPUD WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
12FROM SPUD CARRIAGE DRIVE FDNA-01 (CAN_H) DWG # 659-D750-25 SHT 2 OF 2
FROM SPUD CARRIAGE DRIVE FDNA-01 (CAN_L) DWG # 659-D750-25 SHT 2 OF 2
TO CENTER SPUD DRIVE FDNA-01 (CAN_H) DWG # 659-D750-10 SHT. 2 OF 2
TO CENTER SPUD DRIVE FDNA-01 (CAN_L) DWG # 659-D750-10 SHT. 2 OF 2
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
DWG. DS-3.1 REV. 0, 1-25-21
WALKING SPUD CARRIAGE WINCH DRIVE
DEMOLITION, SHEET 1 OF 3
TRANSFORMER
480V:240V
250VA
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
1 1 D
W G
. D S-
3.
. 0 , 1
-2 5-
SP
U
D C
A R
R
IA
G E
W
IN
C H
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
1 1
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-3.3 REV. 0, 1-25-21
SPUD CARRIAGE WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE SHIELDED MULTI-PAIR CABLE
ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED PAIRS & OVERALL SHIELD.
INSTALL (3) NEW 150A FUSES, MERSEN A60X150-4TA. RE-USE THE EXISTING BLOWN-FUSE STATUS SWITCHES.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #4 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-124A-5+C131+
D150+E208+P444+R700
DWG. ES-3.1 REV. 0, 1-25-21
SPUD CARRIAGE WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
U
V
W
U
V
W
1 - # 8 AWG PER PHASE,
RE-CONNECT 8GNDA
1 - # 8 AWG PER PHASE,
RE-CONNECT 8GND
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01 ADAPTER
BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE
THAT EXISTING CONDUCTOR MAY
BE RE-USED WHERE INSTALLATION
CAN BE MADE NEAT, AND
CONDUCTOR IS IN GOOD
CONDITION.
(FA)
1 2
150A, 600V
(FB)
1 2 150A, 600V
(FC)
1 2
150A, 600V
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E S
P U
D C
A R
R
IA
G E
W
IN
C H
D R
IV
E
N E
W C
O N
S T
R U
C T
IO
N
S H
E E
T
O F
F
O R
W
IR
IN
G
D E
T A
IL
S
D W
G . E
S- 3.
. 0
, 1 -2
5-
SP
U
D C
A R
R
IA
G E
W
IN
C H
D R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-25
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-24
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-25
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-124A-5+C131+D150
+E208+P444+R700
DWG. ES-3.3 REV. 0, 1-25-21
SPUD CARRIAGE WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
12FROM STARBOARD SWING WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-22 SHT 2 OF 2
FROM STARBOARD SWING WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-22 SHT 2 OF 2
TO STARBOARD SPUD WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-13 SHT. 2 OF 2
TO STARBOARD SPUD WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-13 SHT. 2 OF 2
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE. LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
12 12
DWG. DS-4.1 REV. 0, 1-25-21
STARBOARD SWING WINCH DRIVE
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
TA
KI
N
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D T
U R
N O
VE
R
T O
L &S
E
LE
C
TR
IC
F
O R
T H
EI
R
U
SE
SE
E D
EM
O
LI
TI
O N
D R
AW
IN
G
-D
0-
S
H
EE
T
O F
FO
R A
D D
IT
IO
N
AL
IN
FO
R M
AT
IO
N
1 1 D
W G
. D S-
4.
. 0 , 1
-2 5-
ST
A
R B
O A
R D
S W
IN
G
W
IN
C H
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-4.3 REV. 0, 1-25-21
STARBOARD SWING WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #1/0 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-302A-5+C131+
D150+E208+P444+R700
DWG. ES-4.1 REV. 0, 1-25-21
STARBOARD SWING WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
UDC-
DC6
DC5
DC6
DC5
TO PORT SWING WINCH DRIVE
(SEE DRAWING 659-D750-18
SHEET 2 OF 2, COOR R26)
DC5 & DC6 = (1) # 1/0 AWG XHHW OR XHHW-214
S E
E S
T A
R B
O A
R D
S W
IN
G
W
IN
C H
D R
IV
E
N E
W C
O N
S T
R U
C T
IO
N
S H
E E
T
O F
F
O R
W
IR
IN
G
D E
T A
IL
S
D W
G . E
S- 4.
. 0
, 1 -2
5-
ST
A
R B
O A
R D
S W
IN
G
W
IN
C H
D R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
A B
B V
FD
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-22
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-21
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-22
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-302A-5+C131+D150
+E208+P444+R700
DWG. ES-4.3 REV. 0, 1-25-21
STARBOARD SWING WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
12FROM PORT SWING WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-19 SHT 2 OF 2
FROM PORT SWING WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-19 SHT 2 OF 2
TO SPUD CARRIAGE DRIVE FDNA-01 (CAN_H) DWG # 659-D750-25 SHT. 2 OF 2
TO SPUD CARRIAGE DRIVE FDNA-01 (CAN_L) DWG # 659-D750-25 SHT. 2 OF 2
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE. LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
12 12
DWG. DS-5.1 REV. 0, 1-25-21
PORT SWING WINCH DRIVE
DEMOLITION, SHEET 1 OF 3
NOTE: BUS TIE
CONTACTOR LOCATED
IN STARBOARD SWING
CABINET
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
1 1
D W
G . D
S- 5.
. 0 , 1
-2 5-
PO
R
T
SW
IN
G
W
IN
C H
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-5.3 REV. 0, 1-25-21
PORT SWING WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #1/0 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-302A-5+C131+
D150+E208+P444+R700
DWG. ES-5.1 REV. 0, 1-25-21
PORT SWING WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
UDC -
DC1 & DC2 = (1) # 1/0 AWG XHHW OR XHHW-2
DC1
DC2
DC6
DC5
TO STARBOARD
SWING WINCH DRIVE (SEE
DRAWING 659-D750-18 SHEET 2
OF 2, COOR R26)
DC5 & DC6 = (1) # 1/0 AWG XHHW OR XHHW-2 14
NOTE: BUS TIE
CONTACTOR LOCATED
IN STARBOARD SWING
CABINET
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E P
O R
T S
W
IN
G W
IN
C
H D
R
IV
E N
E W
C O
N S
T R
U C
T
IO
N S
H E
E T
O
F
F O
R W
IR
IN
G D
E T
A
IL
S
D W
G . E
S- 5.
. 0
, 1 -2
5-
PO
R
T
SW
IN
G
W
IN
C H
D R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B V
FD
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-19
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-18
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-19
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-302A-5+C131+D150
+E208+P444+R700
DWG. ES-5.3 REV. 0, 1-25-21
PORT SWING WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#4 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
12FROM LADDER WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-16 SHT 2 OF 2
FROM LADDER WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-16 SHT 2 OF 2
TO STARBOARD SWING WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-22 SHT. 2 OF 2
TO STARBOARD SWING WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-22 SHT. 2 OF 2
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE. LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
12 12
DWG. DS-6.1 REV. 0, 1-25-21
LADDER WINCH DRIVE
DEMOLITION, SHEET 1 OF 3
350A
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
1 1 D
W G
. D S-
6.
. 0
, 1 -2
5-
LA
D
D
ER
W
IN
C H
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
PROTECT AND SAVE THE DEVICENET TERMINATION
RESISTOR FOR RE-USE.
DWG. DS-6.3 REV. 0, 1-25-21
LADDER WINCH DRIVE
DEMOLITION, SHEET 3 OF 3
DEVICENET
TERMINATION
RESISTOR
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#4 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
INSTALL (3) NEW 250A FUSES, MERSEN A60X250-4TA. RE-USE THE EXISTING
BLOWN-FUSE STATUS SWITCHES.
T1/U
T2/V
T3/W
R +
R -
L1
L2
L3
PE
L12
L22
L32
1 - #1/0 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
G3
ABB VFD PART NO.
ACS880-01-302A-5+C131+
D150+E208+P444+R700
DWG. ES-6.1 REV. 0, 1-25-21
LADDER WINCH DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
(FA)
1 2
250A, 600V
(FB)
1 2 250A, 600V
(FC)
1 2
250A, 600V
D R
IV
E
O K
D R
IV
E
R U
N
B R
A K
E C
O N
TR
O
L
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E L
A D
D E
R W
IN
C
H D
R
IV
E N
E W
C O
N S
T R
U C
T
IO
N S
H E
E T
O
F
F O
R W
IR
IN
G D
E T
A
IL
S
D W
G . E
S- 6.
. 0
, 1 -2
5-
LA
D
D
ER
W
IN
C H
D R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-16
SHEET 1 OF 2 (B04)
TB4
611C 611C 611C
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-15
SHT. 1 OF 2
COOR. L10)
(CN1)
611617
(B1X)(B1Y) (659-D750-16
SHT. 1 OF 2
COOR. Q07)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-01-302A-5+C131+D150
+E208+P444+R700
DWG. ES-6.3 REV. 0, 1-25-21
LADDER WINCH DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
DEVICENET TERMINATION RESISTOR. RE-USE EXISTING RESISTOR IF
ABLE, OTHERWISE INSTALL NEW 121 OHM, 1/4 WATT 1% METAL FILM
RESISTOR.
TO PORT SWING WINCH DRIVE FDNA-01 (CAN_H) DWG # 659-D750-19 SHT. 2 OF 2
TO PORT SWING WINCH DRIVE FDNA-01 (CAN_L) DWG # 659-D750-19 SHT. 2 OF 2
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE
CONDUCTOR.
DEVICENET
TERMINATION
RESISTOR
(121 OHM,
1/4W, 1%)
KEY NOTES
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION
TO THE NEW DRIVE. LABEL EACH CONDUCTOR (XT1, ETC.) FOR
RE-CONNECTION.
ABANDON COMPONENT IN PLACE. (FUTURE SPARE FOR
CUSTOMER).
FIELD DETERMINE THE EXISTING WIRE SIZE AND INCLUDE IN
AS-BUILT DRAWING COMMENTS SENT TO ENGINEER.
DWG. DS-7.1 REV. 0, 1-25-21
CUTTER DRIVE
DEMOLITION, SHEET 1 OF 5
2 # ? AWG PER PHASE 2 # ? AWG PER PHASE
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
D W
G . D
S- 7.
. 0 , 1
-2 5-
C U
TT
ER
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
DWG. DS-7.3 REV. 0, 1-25-21
CUTTER DRIVE
DEMOLITION, SHEET 3 OF 5
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-7.4 REV. 0, 1-25-21
CUTTER DRIVE
DEMOLITION, SHEET 4 OF 5
501A
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
DWG. DS-7.5 REV. 0, 1-25-21
CUTTER DRIVE
DEMOLITION, SHEET 5 OF 5
CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS
INDICATING THE WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES
#1 AWG COPPER MINIMUM. NOTE THAT EXISTING CONDUCTOR MAY BE RE-USED
WHERE INSTALLATION CAN BE MADE NEAT, AND CONDUCTOR IS IN GOOD
CONDITION.
ABB PART NO. FEN-01 PULSE ENCODER INTERFACE MODULE WITH FETA-01
ADAPTER BOARD. MODULE INSTALLED INTO OPTION SLOT 2 (X203) ON THE DRIVE.
RE-CONNECT EXISTING CABLES, PROVIDE AS-BUILT DRAWING MARK-UP TO
DOCUMENT THE EXISTING CONDUCTOR SIZE.
NEW CABLES AND TERMINATIONS.
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED SHIELDED PAIR.
T1/U2
T2/V2
T3/W2
R +
R -
L1/U1
L2/V1
L3/W1
PE
L12
L22
L32
1 - #4/0 AWG PER PHASE,
XHHW OR XHHW-2
A
A
- B + B
TT
L_
VC
C
TT
L_
C O
M
SH
IE
LD
1 2 3 4 7 8
503 502
G3
ABB VFD PART NO.
ACS880-04-430A-7+C131+
D150+E208+H356+R700
DWG. ES-7.1 REV. 0, 1-25-21
CUTTER DRIVE
NEW CONSTRUCTION, SHEET 1 OF 3
L12
L22
L32
X5
X4
5VDC TO MOTOR SPEED ENCODER.
SEE DWG. 659-D750-07 SHEET 3 OF 4
TEMPERATURE SWITCH DIGITAL INPUT
SEE DWG. 659-D750-07 SHEET 3 OF 4
UDC +
UDC -
2 # ? AWG PER PHASE 2 # ? AWG PER PHASE
D R
IV
E
O K
D R
IV
E
R U
N
SP
A
R E
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E C
U T
T E
R D
R
IV
E N
E W
C O
N S
T R
U C
T
IO
N S
H E
E T
O
F
F O
R W
IR
IN
G D
E T
A
IL
S
D W
G . E
S- 7.
. 0
, 1 -2
5-
C U
TT
ER
D R
IV
E
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
619 618
SEE DWG. 659-D750-07
SHEET 1 OF 4 (B04)
TB4
809 810 811
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-06
SHT. 1 OF 2
COOR. L10)
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLUE
BLUE
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
ABB VFD. PART NO.
ACS880-04-430A-7+C131+D150
+E208+H356+R700
DWG. ES-7.3 REV. 0, 1-25-21
CUTTER DRIVE
NEW CONSTRUCTION, SHEET 3 OF 3
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET ADAPTER MODULE. MODULE
INSTALLED INTO OPTION SLOT 3 (X204) ON THE DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR ENGINEER APPROVED EQUAL.
EPR/CPE SHIELDED PAIR CABLE ASSEMBLY WITH (1) #16 AWG TWISTED
SHIELDED PAIR.
TO PLC CABINET, SEE DACS DWG # 659-D598-05-100
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_H) DWG # 659-D750-04 SHT. 4 OF 6
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_L) DWG # 659-D750-04 SHT. 4 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW
CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT
EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE
INK WIRE MARKERS INDICATING THE WIRE NUMER (L12,
503, ETC.) ON EACH END OF THE CONDUCTOR.
4. SET JUMPERS J3, J6 TO "OFF"
TB4
CUTTER MOTOR
AMMETER
0-600AAC
(4-20mA)
TB5
(COM) (NC) (COM) (NC) (COM) (NC)
506TO MOTOR TEMPERATURE
SWITCHES. SEE DWG.
659-D750-06 SHEET 2 OF 2 2
5VDC
POWER SUPPLY
AC1
AC2
TO 120VAC CONTROL
POWER SEE DWG.
659-D750-07
SHT. 1 OF 4 (H17)
5VDC TO MOTOR SPEED
ENCODER. SEE DWG.
659-D750-06 SHEET 2 OF 2
MOTOR SPEED ENCODER TERMINATIONS.
SEE DWG. 659-D750-06 SHEET 2 OF 2
J6
GROUND
SELECTION
ON
OFF
DICOM = DIOGND
DICOM = DIOGND
TO PLC CABINET, SEE DACS DWG # 659-D598-05-100
DRAWINGS ARE NOT
AVAILABLE / MISSING
DISCONNECT CABLE OR BUS, THIS LOCATION. TURN OVER SCRAP
BUS TO L&S ELECTRIC.
DWG. DS-8.1 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 1 OF 8
KEY NOTES
DISCONNECT CABLE OR BUS, THIS LOCATION. TURN OVER SCRAP BUS TO L&S ELECTRIC.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER TO L&S ELECTRIC FOR THEIR USE. SEE
DEMOLITION DRAWING 659-D750-10 SHEET 2 OF 2 FOR ADDITIONAL INFORMATION.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION TO THE NEW DRIVE. LABEL EACH
CONDUCTOR (XT1, ETC.) FOR RE-CONNECTION. FIELD DETERMINE THE EXISTING WIRE SIZE
AND INCLUDE IN AS-BUILT DRAWING COMMENTS SENT TO ENGINEER.
DWG. DS-8.2 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 2 OF 8
4-# ? MCM
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
D W
G . D
S- 8.
. 0
, 1 -2
5-
D R
ED
G
E
PU
M P
M A
ST
ER
D R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
DWG. DS-8.4 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 4 OF 8
DISCONNECTED ON EACH END, REMOVE AND
DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE
ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER
TO L&S ELECTRIC FOR THEIR USE.
NOTE THAT THE RELAY IN CR1 SOCKET LOCATION IS
LABELLED "CR4" AND THE RELAY IN SOCKET
LOCATION CR4 IS LABELLED "CR1". RE-LABEL THE
RELAYS TO CORRECT THIS, OR SWAP THE TWO
RELAYS IF THEY ARE THE SAME MODEL NUMBER.
MARK "406" CONDUCTORS AS NEEDED AND
TERMINATE IN THE SAME MANNER ON THE NEW
DRIVE.
DWG. DS-8.5 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 5 OF 8
13 13
KEY NOTES
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
DWG. DS-8.6 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 6 OF 8
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO DAMAGE THE COMPONENT. SAVE COMPONENT
AND TURN OVER TO L&S ELECTRIC FOR THEIR USE.
DWG. DS-8.7 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 7 OF 8
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
DWG. DS-8.8 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE
DEMOLITION, SHEET 8 OF 8
DWG. ES-8.1 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE A & B
NEW CONSTRUCTION, SHEET 1 OF 6
TO DREDGE PUMP MASTER
FUSES A / B / C
(SEE DWG. # 659-D750-01
SHT 2 OF 2, COOR. T04)
2 - 535 MCM
PER PHASE
L11
L21
L31
L11
L21
L31
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS INDICATING THE WIRE
NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES:
ANIXTER CABLE NO. 5N-5351-CPE OR ENGINEER APPROVED EQUAL. EPR INSULATION WITH CPE
JACKET, EXTRA FLEXIBLE CONDUCTOR, (2KV DLO TYPE SINGLE CONDUCTOR CABLE).
FIELD DETERMINE BREAKER LOAD LUG CAPABILITY TO ACCEPT (2) 535 MCM CONDUCTORS AND
ADVISE ENGINEER.
T1/U2
T2/V2
T3/W2
R +
R -
L1/U1
L2/V1
L3/W1
PE
L11
L21
L31
UDC +
UDC -
U2
V2
W2
U1
V1
W1
(4) 4T1 4T1
(4) 4T2 4T2
(4) 4T3 4T3
4GND 4GND
PO2
4 # ? MCM
PER PHASE
DREDGE PUMP
MASTER MOTOR
1500 HP, 575V, 3-PHASE,
40 HZ, 788 RPM,
1300 FLA
T1/U2
T2/V2
T3/W2
R +
R -
L1/U1
L2/V1
L3/W1
PE
DREDGE MASTER DRIVE A
ABB VFD PART NO.
ACS880-04XT-1320A-7+R700
UDC +
UDC -
U2
V2
W2
U1
V1
W1
TO DREDGE PUMP
MASTER CIRCUIT BREAKER
(SEE DWG. # 659-D750-01
SHT 1 OF 2, COOR. R26)
1 - 535 MCM
PER PHASE
1 - 535 MCM
PER PHASE
1 - 535 MCM
PER PHASE
1 - 535 MCM
PER PHASE
ABB du/dt FILTER.
FOCH0875-70 du/dt
ABB du/dt FILTER.
FOCH0875-70 du/dt
DWG. ES-8.2 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE A & B
NEW CONSTRUCTION, SHEET 2 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS INDICATING THE
WIRE NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
4. SEE DRAWINGS ECD-14 TO ECD-20 FOR ADDITIONAL INFORMATION.
5. FIELD DETERMINE CONDUCTOR SIZES FROM THE DU/DT FILTER TO THE MOTOR AND
INCLUDE IN AS-BUILT DRAWING COMMENTS SENT TO ENGINEER.
KEY NOTES
ANIXTER CABLE NO. 5N-5351-CPE OR ENGINEER APPROVED EQUAL. EPR INSULATION WITH CPE JACKET, EXTRA FLEXIBLE CONDUCTOR, (2KV DLO TYPE SINGLE CONDUCTOR CABLE).
1/0, 600V, COPPER MINIMUM, BOND TO GROUND BUSBAR IN SWITCHGEAR.
NEW CABLES AND TERMINATIONS
(6) FUSES (FA, FB, FC) ARE MERSEN / FERRAZ TYPE A4BY800TA WITH ADD ON SWITCH AOS-S & (6) 1SC375 800A FUSE BLOCKS.
2 - 535 MCM
PER PHASE
L12
L22
L32
L13
L23
L33
L12, L13
L22, L23
L32, L33
2 - 535 MCM
PER PHASE
12 12
13 13
13 13 13
13 13 13
T13
T23
T33
T12
T22
T32
(2) 4T1
(2) 4T2
(2) 4T3
DREDGE MASTER DRIVE B
ABB VFD PART NO.
ACS880-04XT-1320A-7+R700
1 2 800A, 600V
(FC)
1 2 800A, 600V
(FA)
1 2 800A, 600V
(FB)
L14
L24
L34
1 - 535 MCM
PER PHASE
11 13
1 2 800A, 600V
(FC)
1 2 800A, 600V
(FA)
1 2 800A, 600V
(FB)
L15
L25
L35
1 - 535 MCM
PER PHASE
11 13
(2) 4T1
(2) 4T2
(2) 4T3
D R
IV
E
O K
D R
IV
E
R U
N
SP
A
R E
XR
XR
XR
XR
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
RE
LA
Y
OU
TP
UT
XR
XR
S E
E D
R E
D G
E P
U M
P M
A S
T E
R D
R
IV
E N
E W
C O
N S
T R
U C
T
IO
N S
H E
E T
O
F
F O
R W
IR
IN
G D
E T
A
IL
S
D W
G . E
S- 8.
. 0
, 1 -2
5-
D R
ED
G
E
PU
M P
M A
ST
ER
D R
IV
E
A
B
N
EW
C O
N
ST
R U
C
TI
O N
, S H
EE
T
O
F
A B
B
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01, XR02, XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
SEE DWG. 659-D750-02
SHEET 1 OF 6 (B04)
TB4
809 810 811
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(CR1)
(5) (9) (659-D750-01
SHT. 1 OF 2
COOR. L10)
617 611
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
X1
FDNA-01
DEVICENET
ADAPTER
MODULE
V+
CAN_H
SHLD
CAN_L
V-
WHITE
WHITE
BLACK
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
DREDGE PUMP MASTER A
ABB VFD. PART NO.
ACS880-04XT-1320A-7+R700
DWG. ES-8.4 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE A & B
NEW CONSTRUCTION, SHEET 4 OF 6
KEY NOTES
#14 AWG GRAY SIS WIRE.
ABB PART NO. FDNA-01 DEVICENET
ADAPTER MODULE. MODULE INSTALLED
INTO OPTION SLOT 3 (X204) ON THE
DRIVE.
ANIXTER CABLE NO. 2MR-1601POS OR
ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED PAIR CABLE ASSEMBLY WITH
(1) #16 AWG TWISTED SHIELDED PAIR.
ANIXTER CABLE NO. 2MR-1603SPOS OR
ENGINEER APPROVED EQUAL. EPR/CPE
SHIELDED MULTI-PAIR CABLE ASSEMBLY
WITH (3) #16 AWG TWISTED SHIELDED
PAIRS & OVERALL SHIELD.
INSTALL JUMPER J3 IN THE "ON"
POSITION.
ABB PART NO. FEN-01 PULSE ENCODER
INTERFACE MODULE WITH FETA-01
ADAPTER BOARD MODULE INSTALLED
INTO OPTION SLOT 2 (X203) ON THE
DRIVE
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_H) DWG # 659-D750-04 SHT. 3 OF 6
TO DREDGE PUMP SLAVE DRIVE FDNA-01 (CAN_L) DWG # 659-D750-04 SHT. 3 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW
CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT
EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE
INK WIRE MARKERS INDICATING THE WIRE NUMER (L12,
503, ETC.) ON EACH END OF THE CONDUCTOR.
4. SET JUMPER J6 TO "OFF"
TB5
(COM) (NC) (COM) (NC) (COM) (NC)
506TO MOTOR THERMAL
SWITCHES. SEE DWG.
659-D750-02 SHEET 6 OF 6 2
5VDC
POWER SUPPLY
AC1
AC2
TO 120VAC CONTROL
POWER SEE DWG.
659-D750-02
SHT. 1 OF 6 (H17)
J6
GROUND
SELECTION
ON
OFF
DICOM = DIOGND
DICOM = DIOGND
TO CUTTER DRIVE FDNA-01 (CAN_H) DWG # 659-D750-07 SHT 4 OF 4
TO CUTTER DRIVE FDNA-01 (CAN_L) DWG # 659-D750-07 SHT 4 OF 4
TB4
PUMP MASTER
MOTOR AMMETER
0-1500AAC
(4-20mA)
■ The XD2D connector The XD2D connector provides an RS-485 connection that can be used for
• basic master/follower communication with one master drive and multiple followers,
• fieldbus control through the embedded fieldbus interface (EFB), or
• drive-to-drive (D2D) communication implemented by application programming.
See the firmware manual of the drive for the related parameter settings.
Enable bus termination on the units at the ends of the drive-to-drive link. Disable bus termination on the intermediate units.
Use shielded twisted-pair cable with a twisted pair for data and a wire or another pair for signal ground (nominal impedance 100 to 165 ohm, for example Belden 9842) for the wiring.
For best immunity, ABB recommends high quality cable. Keep the cable as short as possible.
Avoid unnecessary loops and parallel runs near power cables such as motor cables.
The following diagram shows the wiring between control units.
ZCU-14
X D
2D
X D
2D
X D
2D1 2 3 4
B A
BG
N
D
S H
IE
LD
1 2 3 4
B A
BG
N
D
S H
IE
LD
1 2 3 4
B A
BG
N
D
S H
IE
LD
Termination ON Termination ONTermination OFF
WHITE
BLACK
WHITE
BLACK
WHITE (SPARE)
BLACK (SPARE)
TO DREDGE PUMP MASTER B DRIVE
XD2D (DRIVE TO DRIVE LINK)
DWG # 659-D750-02 SHT. 4 OF 6
BLACK
B1
B2
B3
W1
W2
W3
B1
B2
B3
W1
W2
W3
807 806
A
FUSE SWITCH
B
FUSE SWITCH
C
FUSE SWITCH
(COM) (NC) (COM) (NC) (COM) (NC)
MASTER DRIVE A FUSES
MASTER DRIVE B FUSES
X41, X51
B- Z+ Z-
TTL_VCC
FEN-01 PULSE
ENCODER
INTERFACE WITH
FETA-01 ADAPTOR
BOARD
X51
TTL_COM
SHIELD
501A
TO SPEED ENCODER
TTL_COM
NO
NC
COM
NO
NC
COM
NO
NC
COM
XR02
32 XR03
RELAY
OUTPUTS
XR01,
XR02,
XR03
XPOW
EXTERNAL
POWER
INPUT
+24VI
GND4
XD24
AULILIARY
VOLTAGE
OUTPUT;
DIGITAL
INPUT
INTERLOCK
DIOGND
+24VD
DICOM
+24VD
DIIL
XDI
DI6
DI5
DI4
DI3
DI2
DI1
DIGITAL
INPUTS
XDIO
DIGITAL
INPUTS /
OUTPUTS
DIO2
DIO1
AGND
AO2
AGND
AO1
XAO
ANALOG
OUTPUTS
7AI2 -
AI1 -
AI2+
AI1+
- VREF
AGND
J1, J2, XAI
+ VREF
REFERENCE
VOLTAGE
AND ANALOG
INPUTS
AI1:U AI1:I
AI2:U AI2:I
J3, XD2D
DRIVE TO
DRIVE LINK
ON
SHIELD
A B
OFF
BGND
IN2
IN1
SGND
OUT
XSTO
SAFE
TORQUE
OFF
DREDGE PUMP MASTER B
ABB VFD. PART NO.
ACS880-04XT-1320A-7+R700
DWG. ES-8.5 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE A & B
NEW CONSTRUCTION, SHEET 5 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS INDICATING THE WIRE
NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
4. SET JUMPER J6 TO "OFF"
KEY NOTES:
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE SHIELDED
MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED PAIRS & OVERALL SHIELD.
INSTALL JUMPER J3 IN THE "ON" POSITION.
J6
GROUND
SELECTION
ON
OFF
DICOM = DIOGND
DICOM = DIOGND
WHITE
BLACK
WHITE
BLACK
WHITE (SPARE)
BLACK (SPARE)
TO DREDGE PUMP MASTER A DRIVE
XD2D (DRIVE TO DRIVE LINK)
DWG # 659-D750-02 SHT. 3 OF 6
B1
B2
B3
W1
W2
W3
B1
B2
B3
W1
W2
W3
WHITE
BLACK
WHITE
BLACK
WHITE (SPARE)
BLACK (SPARE)
TO DREDGE PUMP SLAVE A DRIVE
XD2D (DRIVE TO DRIVE LINK)
DWG # 659-D750-02 SHT. 3 OF 6
B1
B2
B3
W1
W2
W3
B1
B2
B3
W1
W2
W3
506TO DREDGE PUMP MASTER
DRIVE A DIGITAL INPUTS. SEE
DWG. 659-D750-02 SHEET 3 OF 6
DWG. ES-8.6 REV. 0, 1-25-21
DREDGE PUMP MASTER DRIVE A & B
NEW CONSTRUCTION, SHEET 6 OF 6
GENERAL NOTES:
1. RED COLORED TEXT AND LINES REPRESENT NEW CONSTRUCTION, THIS CONTRACT.
2. BLACK COLORED TEXT AND LINES REPRESENT EXISTING CONSTRUCTION.
3. NEW CONDUCTORS TO BE LABELLED WITH INDELIBLE INK WIRE MARKERS INDICATING THE WIRE
NUMER (L12, 503, ETC.) ON EACH END OF THE CONDUCTOR.
KEY NOTES:
ANIXTER CABLE NO. 2MR-1603SPOS OR ENGINEER APPROVED EQUAL. EPR/CPE SHIELDED
MULTI-PAIR CABLE ASSEMBLY WITH (3) #16 AWG TWISTED SHIELDED PAIRS & OVERALL SHIELD.
DWG. DS-9.1 REV. 0, 1-25-21
DREDGE PUMP SLAVE DRIVE
DEMOLITION, SHEET 1 OF 8
KEY NOTES
DISCONNECT CABLE OR BUS, THIS LOCATION. TURN OVER SCRAP
BUS TO L&S ELECTRIC.
KEY NOTES
DISCONNECT CABLE OR BUS CONNECTION, THIS LOCATION. TURN OVER SCRAP BUS TO L&S
ELECTRIC.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING CARE NOT TO DAMAGE THE
COMPONENT. SAVE COMPONENT AND TURN OVER TO L&S ELECTRIC FOR THEIR USE. SEE
DEMOLITION DRAWING 659-D750-10 SHEET 2 OF 2 FOR ADDITIONAL INFORMATION.
PROTECT CABLES AND TERMINATIONS FOR RE-CONNECTION TO THE NEW DRIVE. LABEL EACH
CONDUCTOR (XT1, ETC.) FOR RE-CONNECTION. FIELD DETERMINE THE EXISTING WIRE SIZE AND
INCLUDE IN AS-BUILT DRAWING COMMENTS SENT TO ENGINEER.
DWG. DS-9.2 REV. 0, 1-25-21
DREDGE PUMP SLAVE DRIVE
DEMOLITION, SHEET 2 OF 8
4-# ? MCM
N O
TE
S
D
IS
C O
N N
EC
T
C
AB
LE
, T
H
IS
L O
C
AT
IO
N
D
IS
C
AR
D
C
AB
LE
R
EM
O
VE
C O
M
PO
N
EN
T
FR
O M
T H
E D
R
IV
E
EN
C
LO
SU
R
ES
T
AK
IN
G C
AR
E
N O
T
TO
D
AM
AG
E
TH
E
C O
M
PO
N
EN
T.
S
AV
E
C O
M
PO
N
EN
T
AN
D
TU
R N
O
VE
R T
O L
&S E
LE
C
TR
IC
F O
R T
H
EI
R U
SE
SE
E
D
EM
O
LI
TI
O
N D
R
AW
IN
G
-D
0-
S H
EE
T
O
F
FO
R
A D
D
IT
IO
N
AL
IN
FO
R
M
AT
IO
N
D W
G . D
S- 9.
. 0
, 1 -2
5-
D R
ED
G
E
PU
M P
SL
A
VE
D
R
IV
E
D
EM
O
LI
TI
O
N , S
H
EE
T
O F
DISCONNECT CABLE, THIS LOCATION. IF CABLE IS
DISCONNECTED ON EACH END, REMOVE AND DISCARD CABLE.
REMOVE COMPONENT FROM THE DRIVE ENCLOSURES TAKING
CARE NOT TO…