Addtional Inquiries with Government Responses - Barracks.pdf
PDF 468 KB Posted
- Attached to
- Three Story Barracks Federal contract opportunity
- Solicitation number
- W912DW23R2001
About this file
This document contains inquiries and responses regarding a solicitation for construction of three story barracks at Joint Base Lewis McChord in Washington. Elastomeric cellular insulation is allowed on heating hot water supply and return pipes and domestic water pipes according to the government's response. The related federal contract opportunity is solicitation number W912DW23R2001 for the Three Story Barracks project, with a description and attachments provided. This is a construction project with a solicitation closing date of April 13, 2023. The soliciting agency is the Department of the Army Corps of Engineers Engineering District Seattle.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| Amendment 06_Three Story Barracks.pdf | ||
| Amendment 05 -Barracks.pdf | ||
| Specs- Amendment R0004.pdf | ||
| Attachment A - Index of Drawings- Amendment R0004.docx | DOCX document | |
| Amendment R0004 - Barracks.pdf | ||
| Plans- Amendment R0004.pdf | ||
| Summary of changes in Amendment 4 (R0004).docx | DOCX document | |
| Specs.pdf | ||
| 00 72 00-A.docx | DOCX document | |
| Drawings.pdf | ||
| Summary of Changes in Amendment 0003 - Drawings and Specs.pdf | ||
| Amendment 03- Barracks.pdf | ||
| signin sheet.pdf | ||
| Site Visit Slides - Barracks_sfn.pptx | PPTX presentation | |
| Amendment 0002 - Barracks.pdf | ||
| Amendment 0001 - Barracks.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Inquiries and Government Responses: Three Story Barracks, Joint Base Lewis McChord (JBLM), WA.
1) In the insulation spec 230700: 2.3.2.2 and 2.3.3.3 narratives both allow elastomeric rubber on both cold and hot piping. But 3.2.1.6 Table 1 does not show rubber on the heating hot water and domestic hot water. Table 2 does not show rubber on the heating hot and line 1 does not show the material type on the 1.5” and 2” wall thickness line item. And then table 2 shows rubber on the domestic hot contradicting table 1. How did you interpret when deciding on inserts on the heating hot?
Government Response:
Elastomeric cellular insulation is allowed on the Heating Hot Water Supply & return and Domestic Water pipes.
File details come from the government source that posted it. Updated .